Tender For Repair / Maintenance Of Dg Sets Amf Panels And Connected Items At Af Station Bhowali, bhowali-Uttarakhand

Military Engineer Services-MES has published Tender For Repair / Maintenance Of Dg Sets Amf Panels And Connected Items At Af Station Bhowali. Submission Date for this Tender is 27-01-2024. Diesel Generators Tenders in bhowali Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

41392763
Corrigendum : Tender For Repair / Maintenance Of Dg Sets Amf Panels And Connected Items At Af Station Bhowali
Open Tender
Indian
Uttarakhand
bhowali
27-01-2024

Tender Details

Tender For Repair / Maintenance Of Dg Sets Amf Panels And Connected Items At Af Station Bhowali

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Jan-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 27-01-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 19000.0 /-
Tender Value
INR 9.50 Lakhs /-

BOQ Items

Name of Work : REPAIR / MAINT OF DG SETS AMF PANELS AND CONNECTED ITEMS ATAF STATION BHOWALI
Sl. No. Item Description
1Material and labour for maintenance and servicing of DG Set of capacity 30 to 63 KVA, Kirlosker make, water cooled type with and including replacement of 02 Nos. fuel filters, 02 Nos. oil filters, 01 No. air filter etc. by carrying out "B" check as per manufacturer"s maintenance chart complete all as specified and directed.
2Material and labour for maintenance and servicing of DG Set of capacity 82.50 KVA, Kirlosker make, water cooled type with and including replacement of 02 Nos. fuel filters, 02 Nos. oil filters, 01 No. air filter etc. by carrying out "B" check as per manufacturer"s maintenance chart complete all as specified and directed.
3Material and labour for maintenance and servicing of DG Set of capacity 125 KVA, Kirlosker make, water cooled type with and including replacement of 02 Nos. fuel filters, 02 Nos. oil filters, 01 No. air filter etc. by carrying out "B" check as per manufacturer"s maintenance chart complete all as specified and directed. NOTE FOR ITEM NO. 1.00 TO 3.00: - ENGINE OIL AND COOLENT SHALL BE MEASURED AND PAID SEPARATELY AS "SUPPLY ONLY".
4Supply only coolant SK-802 complete all as specified. Make- IOC, Servo, Hindustan.
5Supply only Engine oil 15W40 of specified grade as required by OEM of DG set complete all as specified. Make- Castrol, Servo, Hindustan Oil.
6Supply and fixing in repairs digital type Ammeter 0-300 Ampere range 96 X 96 mm flush type 3 Phase 415 Volts AC with CTs Ratio 100/5-A in all three phases with 3P selector switch to read current in all three phases complete all as specified and directed. MAKE- L&T, AE, MECO.
7Supply and fixing in repairs digital type Voltmeter 0-500 Volts ACrange 96 X 96 mm flush type 3 Phase 415 Volts AC with 3P selector switch to read voltage in all three phases complete all as specified and directed. MAKE- L&T, AE, MECO.
8Supply and fixing in repairs three pole power contactors with standard coil voltage of 415 Volts 50 Hz and auxiliary of 02 Nos. of AC-3 Rating of 140 Ampere MCX 140 series as per Cat. part No. CS 94138 of L&T or having same specification in GE, Siemens or BCH complete all as specified and directed.
9Supply and fixing in repairs three pole power contactors with standard coil voltage of 415 Volts 50 Hz and auxiliary of 02 Nos. of AC-3, Rating of 95 Ampere MCX 95 series as per Cat. part No. CS 94136 of L&T or having same specification in GE, Siemens or BCH complete all as specified and directed.
10Supply and fixing in repairs four pole power contactors with standard coil voltage of 415 Volts 50 Hz and auxiliary of 03 Nos. of AC-3, Rating of 95 Ampere MCX 95 series as perL&T or having same specification in GE, Siemens or BCH complete all as specified and directed.
11Supply and fixing in repairs three pole power contactors with standard coil voltage of 415 Volts 50 Hz and auxiliary of 02 Nos. of AC-3, Rating of 50 Ampere MCX 50 series as per Cat. part No. CS 97075 of L&T or having same specification in GE, Siemens or BCH complete all as specified and directed.
12Supply and fixing in repairs AMF controller relay for Auto / Manual operation for protection of external fault, over speed, over and under voltage protection, fail to start, fail to stop, emergency stop with 1% accuracy as per Model No. DGC-7 of Procom or having same specifications in L&T, Schenider complete all as specified and directed.
13Supply and fixing in repairs supply monitoring phase and voltage control 3 phase, 4 watt, 240 volts AC, 47 to 63 Hz as per Cat Part No. MG73BH (SM series) of L&T or having same specifications in C&S, Siemens complete all as specified and directed.
14M & L for washing, cleaning and repairing of Radiator assembly of DG set of 30 KVA to 62.5 KVA by proper opening and re-fixing back after repair, washing, cleaning in same existing position properly complete all as specified and directed.
15M & L for washing, cleaning and repairing of radiator assembly of DG set of 82.5 KVA to 125 KVA by proper opening and re-fixing back after repair, washing, cleaning in same existing position properly complete all as specified and directed.
16M & L for rewinding of armature assembly of 62.5 KVA capacity DG set with super enamelled insulated copper wire of existing size and gauge, varnishing work, drying, refixing the same, testing, commissioning with and including dismantling of old coil, cleaning throughly complete all as specified and directed.
17S & F of AVR unit suitable for Kirlosker make DG set including dismantling of old unserviceable one complete all as specified and directed.
18S & F of new battery charger of Kirloskar make, suitable of 6 Ampere, 12 Volts suitable for charging of generator battery with and including taking out old unserviceable one complete all as speicified and directed.
19S & F in re-placement of LED type street light fitting 70/72 watt with IP 66 fixed to existing electric pole with all accessories duly pre-wired including taking down unserviceable one street light fitting complete all as specified and directed.
20S & F in re-placement of LED type street light fitting 45 watt with IP 66 fixed to existing electric pole with all accessories duly pre-wired including taking down unserviceable one street light fitting complete all as specified and directed.
21Supply and fixing or laying or passing through pipe 1100 volts grade weather proof flat twin core aluminium stranded conductor cable of size 6 Sqmm complete all as specified and directed.
22S & F in re-placement of LED flood light fitting200 watt with IP 66 to befixed on high mast light complete with all accessories duly pre-wired including taking down unserviceable one street light fitting complete all as specified and directed.
23S & F in re-placement of LED flood light fitting50 watt with IP 66 to befixed on high mast light complete with all accessories duly pre-wired including taking down unserviceable one street light fitting complete all as specified and directed.
24S & F of storage type lead acid battery 150 AH 12/24 volts fully charged suitable for generators with and including taking down old unserviceable battery complete all as specified and directed.
25M & L for copper pipe of 10 to 15 mm dia as required at site for split type AC any capacity complete all as specified and directed.
26M & L for flushing of condenser and evaporator coil of split type AC by using carbon-di-oxide / Nitrogen gas including checking of leakage in the system, brazing the leakage part of oil gas tubing as required and charging with required quantity of appropriate refrigerant gas complete all as specified and directed.
27Taking down carefully defective split type AC including transporation of the same from MES store yard or site to the workshop and back, refixing / reinstalling, connecting and testing the same after replacement of defective / burnt compresssor sealed unit by providing new compressor suitable for 2.00 TR capacity AC purchased directly from the authorised dealer, flushing of condenser and charging with required quantity of appropriate refrigerant gas complete all as specified and directed.
28Supply and fixing in repairs Fuse Base for din type HN Fuse links for current rating 160 Ampere make L&T, Havells or C&S complete all as specified and directed.
29Supply and fixing in repairs timer relay of 240 volts, 50 Hz make L&T, Havells or C&S complete all as specified and directed.
30Supply and fixing in repairs start / stop relay of 12 Volts, 50 Hz make L&T, Havells or C&S complete all as specified and directed.
31S&F in repair voltage stabilizers 4/5 KVA capacity installed for all split type AC"s single phase 230 volts 50 Hz with copper wound bulk and boost type with high and low voltage cut off 2-3 minute time delay relay with input voltage range of 140-280 volts and output voltage of 200V-240V with 95% efficiency.Make-V-Guard or equivalent
32S&F (in replacemement) following items in the existing out door/indoor LT panels/AMF panels and connetion with using aluminum lugs/ferruls incl disconnection & connection of cable and making necessary alteration in panel/door using welding wk and cutting as required for proper fixing & connection complete all as specified and directed as below :- (Note :- Make of MCCB/MCB : Schneider/L&T/ABB)
33MCCB 4 pole 100 amps rating, 16 KA breaking capacity, with separator at both side
34MCCB 4 pole 125 amps rating, 16 KA breaking capacity, with separator at both side
35MCCB 4 pole 63 amps rating, 16 KA breaking capacity, with separator at both side
36MCCB 4 pole 40 amps rating, 16 KA breaking capacity, with separator at both side
37MCCB 4 pole 160 amps rating, 16 KA breaking capacity, with separator at both side
38M & L for applying two coats of aluminium paint over acoat ofred oxide on Steel tubular pole of following lengthincluding cross arms and clamps except embedded portion of pole in ground and concrete after removing old painted surfaces by scraping of poles complete and making colour band with synthetic enamel paint of approved colour up to 1.2 mtr from coping level including numbering of poles in red colour paint complete all as specified and directed for LT pole 9 mtr long straight /single/double swan neck.
39M&L for repairing of unserviceable LED street light any make /model of 70-90 watt cap by replacing compact LED electronic driver suitable to operate on 120 to 277 Volt 50/60 Hz AC supply complete all as specified and directed.Driver makePhillips/
40M&L for repairing of unserviceable LED street/flood light any make /model of 100-150 watt cap by replacing compact LED electronic driver suitable to operate on 120 to 277 Volt 50/60 Hz AC supply complete all as specified and directed. Driver makePhillips/ havells/wipro/CG or as approved.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail