All India Institute Of Medical Sciences-AIIMS has published Tender For Re- Insulation Of Hvac Pipeline And Duct In Various Ward, Corridorin Ipd At Aiims Patna.. Submission Date for this Tender is 19-01-2024. Pipe Laying Tenders in patna Bihar. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 12-Jan-2024 | Date | Date | 19-01-2024 |
Sl. No. | Item Description |
1 | Supplying, laying,fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of class ‘O’ applied by adhesive confirming to standard specifications, as per specifications and as required complete in all respect.(duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK)make- Armacell, k- Flex,and Adhesive - SR-998 Insulation with nitrile rubber of thickness 32mm on existing pipe |
2 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.25 mm nitrile insulation |
3 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.25 mm nominal outer dia Pipes |
4 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core |
5 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core |
6 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.63 mm thick |
7 | With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works |
8 | Painting on G.S. sheet with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : New work (two or more coats) including a coat of approved steel primer but excluding a coat of mordant solution |
9 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes inCement mortar 1:6 (1 cement : 6 coarse sand) |
10 | Cement Plaster(Fine sand) 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
11 | Cutting and welding of existing pipe line for shiting to provide space for installation of PUF i/c providing necessary arrangement asM S support, hangers, pipe,bendsetc as reqd. |
12 | SITC of0.63mm aluminium sheet cladding complete on existing all size HVAC PIPE Line etc as reqd (Pipe aluminium Cladding 0.63mm ) |
13 | SITC of fire redrant canvas cloth 2mm thick( including nut- bolts ,strip etc is required) |
14 | SITC of STAR BOND1mm thick cotton cloth on 2or more coat on existing HVACpipe line( including adhesive-star bond, colouretc required arrangement) |
15 | Removing of Insulation , and cleaning of rust etcin pipe line/Duct |
16 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd 25 mm dia (Thickness of PUF insulation 30mm) |
17 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd32 mm dia (Thickness of PUF insulation 30mm) |
18 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd 40 mm dia (Thickness of PUF insulation 30mm) |
19 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd50 mm dia (Thickness of PUF insulation 50mm) |
20 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd65 mm dia (Thickness of PUF insulation 50mm) |
21 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd80 mm dia (Thickness of PUF insulation 50mm) |
22 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd100 mm dia (Thickness of PUF insulation 50mm) |
23 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd125 mm dia (Thickness of PUF insulation 50mm) |
24 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd150 mm dia (Thickness of PUF insulation 75mm) |
25 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd 200 mm dia (Thickness of PUF insulation 75mm) |
26 | Supplying, laying/ fixing, testing and commissioning of following thickness insulation with fire retardant quality expandedpolyuthrane Foam (PUF) moulded pipe section of minimum density 36(+/-2) kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date in folowing pipe line section i/c necessary arrangemnet of scofolding/ladder etc as reqd250 mm dia (Thickness of PUF insulation 75mm) |