| 1 | Ductable AcSupply installation testing and commissioning of, air cooled ductable air conditioning unit of following capacity with scroll compressor of approved make suitable for operation on 3 phase 415 V, 50 Hz AC supply. Comprising of copper condenser, and aluminum fins, and first charge refrigerant. The indoor comprising of fan, fan motor, copper tube, aluminum finned cooling coil, drain pan, filter, controls, safety with ecofriendly gas R410/R410A excluding connection copper pipe of required size, insulation, stand for outdoor unit, connection copper lead wire, condensed water outlet pipe complete etc as required. Outdoor/indoor units should be of same make (brand).10.0-11.0 TR three phaseMPPWD SOR 2020 46.14.3 |
| 2 | AC installation :- Installation, air cooled ductable air conditioning unit of following capacity with scroll compressor suitable for operation on 3 phase 415 V, 50 Hz AC supply. The indoor/outdoor comprising of condenser, fan, fan motor, cooling coil, drain pan with filter and first charge refrigerant ecofriendly gas including connection of copper pipe and material supplied with complete unit etc as required.11.0 TRMPPWD SOR 2020 46.16.3 |
| 3 | Copper piping: - Supply, installation, testing and commissioning of interconnecting copper refrigerant pipe work (19mm/13mm thick) duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications. And exposed piping should be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as per specification.34.9 mm O.D. wall thickness = 1.4mm (insulation – 19 mm thick)MPPWD SOR 2020 46.30.4 |
| 4 | Drain piping :- Providing and fixing of CPVC, 6Kg/cm2 drain water piping with fittings, support and insulated with 6 mm thick closed cell elastomeric nitrile rubber insulation complete as per specification. 25 mm dia IDMPPWD SOR 2020 46.31.2 |
| 5 | Refrigerant:- Supply and additional refrigerant charge of refrigerant R410/410A to compensate the additional piping done at site for all systems including testing commissioning as required,MPPWD SOR 2020 46.34 |
| 6 | Ducting:- Supply and fixing of site fabricated GI sheet metal ducts in accordance with the approved shop drawings and as required as per specifications. GI sheet will be as per IS-277. All necessary GI /MS supports using thread rods (as directed). Angle, flat, and anchor bolts, food grade neoprene gaskets, food grade adhesive included in the scope24GMPPWD SOR 2020 46.36.1 |
| 7 | Ducting:- Supply and fixing of site fabricated GI sheet metal ducts in accordance with the approved shop drawings and as required as per specifications. GI sheet will be as per IS-277. All necessary GI /MS supports using thread rods (as directed). Angle, flat, and anchor bolts, food grade neoprene gaskets, food grade adhesive included in the scope 22GMPPWD SOR 2020 46.36.2 |
| 8 | Thermal insulation :- Supplying and fixing of following thickness of mat finish closed cell nitrile rubber (class “1”) insulation on existing duct after applying two coats of cold setting adhesive complete as per specifications and as required. 25 mm thick MPPWD SOR 2020 46.37.1 |
| 9 | Thermal insulation :- Supplying and fixing of following thickness of mat finish closed cell nitrile rubber (class “1”) insulation on existing duct after applying two coats of cold setting adhesive complete as per specifications and as required.19 mm thick MPPWD SOR 2020 46.37.2 |
| 10 | Internal duct acoustic insulation: - Supply, installation, testing and commissioning of internal duct acoustic insulation with open cell structured class \"O\" fire retardant nitrile rubber with density 140 - 180 kg/m³ and specs as per RISAC chart specification sheet inside of the AHU supply air ducting up to 4 mtr. length from AHU mouth as per the specifications, it should have antimicrobial properties.10 mm thick MPPWD SOR 2020 46.38.2 |
| 11 | Grills and diffusersSupplying & fixing of powder coated extruded aluminum air grills without volume control damper complete as required.MPPWD SOR 2020 46.39.1 |
| 12 | Grills and diffusersSupplying & fixing of coller damper complete as required.MPPWD SOR 2020 46.39.2 |
| 13 | Grills and diffusersSupplying & fixing of G.I duct volume control damperMPPWD SOR 2020 46.39.5 |
| 14 | Flexible connections :- Providing & fixing of flexible canvas connection between indoor unit and duct to avoid the vibration transferMPPWD SOR 2020 46.4 |
| 15 | Controlcable: - Supply and laying, testing & commissioning of following sizes of copper conductor control cables on existing tray including fixing clamps & proper connections to equipment etc. complete as required.4Cx1.5 sq.mm MPPWD SOR 2020 46.41.2 |
| 16 | Controlcable: - Supply and laying, testing & commissioning of following sizes of copper conductor control cables on existing tray including fixing clamps & proper connections to equipment etc. complete as required.4Cx2.5 sq.mmMPPWD SOR 2020 46.41.3 |
| 17 | Controlcable: - Supply and laying, testing & commissioning of following sizes of copper conductor control cables on existing tray including fixing clamps & proper connections to equipment etc. complete as required.4Cx 10 sq.mmMPPWD SOR 2020 46.41.6 |
| 18 | Outdoor stand fabrication :- Supply, fabrication and erection of angle/channel/flat iron stand, hanging arrangement for air conditioning machines & ducts etc, back /support clamps or other similar work etc. including nut bolts of required size, making holes, fabrication, welding, cutting, etc. and painting with one coat of red oxide paint & two coat of enamel paint as required as per specification.MPPWD SOR 2020 46.42 |
| 19 | External duct insulation :- Supplying & fixing of following thickness of mat finish closed cell nitrile rubber (class \"O\") insulation along with company fitted weather proof UV protected glass wool cloth for protection of weather conditions and mechanical damages to insulation on existing duct after applying two coats of cold setting adhesive complete as per the specifications as required.19 mm thickMPPWD SOR 2020 46.45.1 |
| 20 | Fire damper: - Supply, installation, testing and commissioning of fire dampers in supply air duct/return air duct/main branch of required size as and where required i/c control wiring. The motorized damper shall open/close on power failure and restore. The system shall also function on fire signals accordingly complete as required as per specification. MPPWD SOR 2020 46.46.1 |
| 21 | Actuators MPPWD SOR 2020 46.46.2 |
| 22 | Providing 10 mm thick Plaster of Paris (Gypsum Anhydrous) celling up to a height of 5 m above floor level over first classkail wood strips 25X6 mm with 10 mm gap in between and reinforcedwith rabbit wire mesh fixed to any frame (frame work to be paid separately) Flat surfaces (UADD Sor-2021 S.N.12.33.1) |
| 23 | Providing 10 mm thick Plaster of Paris (Gypsum Anhydrous) celling up to a height of 5 m above floor level over first classkail wood strips 25X6 mm with 10 mm gap in between and reinforcedwith rabbit wire mesh fixed to any frame (frame work to be paid separately) curved surfaces (UADD Sor-2021 S.N.12.33.2) |
| 24 | Point wiring including metallic switch box, sheet, switche, socket, lamp holders/ceiling roses etc with 1.5 Sq. mm. PVC insulated cable FR with copper multi strand conductor ISI marked in Concealed rigid steel conduit ISI Marked of suitable size and 1.5 Sq. mm. PVC insulated copper earth continuity conductor of green colour inside conduit including painting, etc. as required as per specification for : Light Point/Fan Points (UADD SOR-2021-2.4.1 P no. 22)A) short point |
| 25 | Point wiring including metallic switch box, sheet, switche, socket, lamp holders/ceiling roses etc with 1.5 Sq. mm. PVC insulated cable FR with copper multi strand conductor ISI marked in Concealed rigid steel conduit ISI Marked of suitable size and 1.5 Sq. mm. PVC insulated copper earth continuity conductor of green colour inside conduit including painting, etc. as required as per specification for : Light Point/Fan Points (UADD SOR-2021-2.4.1 P no. 22)B)midium point |
| 26 | Point wiring including metallic switch box, sheet, switche, socket, lamp holders/ceiling roses etc with 1.5 Sq. mm. PVC insulated cable FR with copper multi strand conductor ISI marked in Concealed rigid steel conduit ISI Marked of suitable size and 1.5 Sq. mm. PVC insulated copper earth continuity conductor of green colour inside conduit including painting, etc. as required as per specification for : Light Point/Fan Points (UADD SOR-2021-2.4.1 P no. 22)C)Long point |
| 27 | Supplying, fixing, testing & commissioning wall/floor mounted LT Panel primer coated with two coat of enamel paint & provided with required gasket for dust/vermin proof with degree of protection IP42 suitable for 415V 3 phase, 50Hz,4-wire system fabricated out of CRCA sheet upto 2mm thick (1.6mmfordoors) with frame work of angle iron/channel/bolted type construction duly compartment alised for incomer,bussection,outgoings ,cablealleys & C T,PT Ampere Meter ,VoltMeter,selector switches, Frequency Meter, phase indicating lamps,energy Meter complete including cost of busbar supports,detachable cable gland plates,2 earthing terminals,internal wiring & fixing of separately supplied MCBs, MCCBs ,panel mounted Change overs witch /SFUs,etc.as required but excluding cost of busbar strips,AmpereMeter,Volt Meter,Selector switch as perapproved design & specification(UADD SOR-2021-9.15 ) |
| 28 | Digital Ampere Meter with CTs with selector switch (UADD SOR-2021-9.16.1 ) |
| 29 | Digital Volt Meter with selector switch & HRC fuse (UADD SOR-2021-9.16.2 ) |
| 30 | Frequency Meter (UADD SOR-2021-9.16.3 ) |
| 31 | Copper Bus bar strips with PVC sleeves (UADD SOR-2021-9.16.4 ) |
| 32 | Aluminium bus bar strips with PVC sleeves (UADD SOR-2021-9.16.5 ) |
| 33 | LED lamps (UADD SOR-2021-9.16.6 ) |
| 34 | Dismantling &shifting, installation, testing & commissioning of split air conditioning unit 1.0TR/1.5TR/2TRcapacity including indoor / outdoor unit complete as required within town. (NON SOR) |
| 35 | Comprehensive maintenance and servicing of air-conditioners of following type and capacity including replacement with new compressor, and related parts such as capacitors, relay, electronic controls, PCB, display, thermostat, remote control, and related accessories, rewinding of fan/blower motor, flushing of cooling & condensing units with nitrogen gas, required refrigerant gas charging & rectification of leakage, replacement of filter, flair nut etc. if any All inclusive maintenance charges for the entire system after completion of guarantee period( Per Ton Per five year) (NON SOR |
| 36 | Supply and installation of 08-10 W Light LED fixtures with beam angle 90 Deg. and colourtemperature 3000K to 6000K outdoor type LED lighting fixtures with IP 65 ingress protection. ( Make : Philips / Bajaj / Wipro / Havells/ Disano /Crompton Greaves / Suryaor Equivalent approved by Engineer Incharge )Pop Roof led Light (Non Sor) |