Tender For Special Repair To Air Conditioning And Power Supply Arrangements And Associated Works In The Ug Base Ops Complex And Addn/Altn Of Bldg No P-188 And P-190 At Af Stn Halwara, halwara-Punjab

Military Engineer Services-MES has published Tender For Special Repair To Air Conditioning And Power Supply Arrangements And Associated Works In The Ug Base Ops Complex And Addn/Altn Of Bldg No P-188 And P-190 At Af Stn Halwara. Submission Date for this Tender is 20-01-2024. Power Supply Unit Tenders in halwara Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

41262866
Corrigendum : Tender For Special Repair To Air Conditioning And Power Supply Arrangements And Associated Works In The Ug Base Ops Complex And Addn/Altn Of Bldg No P-188 And P-190 At Af Stn Halwara
Open Tender
Indian
Punjab
halwara
20-01-2024

Tender Details

Tender For Special Repair To Air Conditioning And Power Supply Arrangements And Associated Works In The Ug Base Ops Complex And Addn/Altn Of Bldg No P-188 And P-190 At Af Stn Halwara

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Jan-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-01-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 96780.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: SPL REPAIR TO AIR CONDITIONING AND POWER SUPPLY ARRANGEMENTS AND ASSOCIATED WORKS IN THE UG BASE OPS COMPLEX AND ADDN/ALTN OF BLDG NO P-188 & P-190 AT AF STN HALWARA
Sl. No. Item Description
1Taking down chowkhats or frame with shutter without taking off shutter from the frame areaexc 1.5 Sqm but n.exc4 sqm eachcomplete all as specified and directed.
2Taking down cement plaster of any description and thickness including raking out joints hacking for key scrubbing down with water etc complete all as specified and directed.
3M&L for 15 mm thick rendering in cement mortar 1:6 on brickor concrete surface finished even and smooth without using extra cement complete all as specified and directed.
4M&L for 5 mm thick rendering in cement mortar 1:3 on ceiling surface finished even and smooth without using extra cement complete all as specified and directed.
5Dismantling floor hearth or wall tiling including cement mortar bedding but not backing removing serviceable tiles to store and rubbish off the MoD premises complete all as specified and directed.
6M&L for 25mm thick cement concrete type B-0 using 12.5mm graded crushed stone aggregate as in sub base finished even and fair surfaces without using extra cement complete all as specified and directed.
7M&L for light shade vitrified ceramic coloured tiles 10 mm thick (Square/rectangular) area of each tile n.exc 0.36 Sqm set in neatcement slurry and pointed in white or coloured cementwith pigmentover and including 20mm thick screeding in CM 1:6 complete all as specified and directed.
8All as per Sl item No 7 above but as in skirting over and including 10mm thick rendering in CM 1:4
9M&L for glazed ceramic colouredtiles (300x450mm)x6-7mm thick on vertical surfaces as in skirting/dado, set and jointed with neat cement slurry and pointed in white/coloured cement to match the shade of tiles over and including 10mm thick rendering in cement mortar 1:4 complete all as specified and directed.
10Dismantling wall and ceiling boards (fibre, pulp, insulation, etc) or insulation boards/slabs/blankets, any thickness including cover fillets of any description complete all as specified and as directed
11S&F Anodised aluminium snap grid frame work for false ceiling, size of grid 605x605mm including hangers, cleats, fasteners complete all as specified and as directed
12S&F Gypsum Board 12mm thick in ceiling fixed with screw as per manufacturers instructions, 60x60cm in size complete all as specified and as directed
13All as per Sl item No 12 above but except material. Note :Sericeable material obtained from dismantling shall be re-used in the work after cleaning.
14S&F Powder Coating aluminium frame for doors, windows,(minimum thickness of powder coating 50 micron) ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed.
15S&FPowder coated (minimum thickness of powder coating 50 micron) aluminium door shutters, aluminium sectionweighing 0.55 Kg/ m including necessary joining cleats, zing clips, ruber neoprene packing, handles 2 Nos ineach door,tower bolt, hinges, anodised aluminium snap beading screwscomplete all as specified and directed.
16S&F 4.8 mm thick sheet glass selected quality plain/ tinted in squares exc 0.5 sqm each pane complete all as specified and directed.
17S&F 9mm thick block boards, grade 2 quality, interior grade, decorative type with decorative face veneer on both faces and fixed with screws to frame work complete all as specfied and directed.
18M&L for preparation of new plastered surface of wall and applying two coat of distemper oil emulsion overa coat primer over 1mm thick wall care putty complete all as specified and directed.
19Preparation of new wood or wooden surfaces of any description over 10 cm width or grith and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified and directed.
20M&L for prepration of new plastered surfaces of ceiling and applying two coat of white wash complete all as specified and directed.
21M&L for prepration of new plastered surfaces of walls and applying two coat of white wash complete all as specified and directed.
22S&F plates (Plain or chequered) channels, square cut or notched (ordinary or counter sunk), forming holes, without any attachement, conforming to Fe-410W (Gde E-250 quality -A) complete all as specified and directed.
23Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminium conductor of any Cross sectional areafrom trenches, from wall/poles/under floor etc,shifting serviceable cable for relaying or removing the unserviceable cable complete all as specified and directed. Note : (i)Excavation and earth work shall be measured and paid for separately (ii)Unit rate of this item is also includes the removal of brick/tile as cable protection, GI pipe and cable joint etc. and nothing extra shall be admissible on this account. (iii)After taking out the cables from the trench, serviceability of cable shall be checked by the contractor in presence of the Engr-in-Charge and nothing extra shall be paid on this account.
24M&L for excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exeeding 1.5 m deep, getting out the excavated earth and making bottom surface to required gradient complete all as specified and directed.
25M&L for returning filling in and including spreading and leveling in layers not exceeding 25 cm thick complete all as specified & directed.
26M&L for removal of excavated material such as soils n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed.
27M&L for sand cushioning using dry clean sand for protection of underground cable with a layer of 80mm thick before laying of cable and 150mm after laying of cable, consolidatedand compacted complete all as specified and as directed. Note : 180mm thick punned thickness of sand cushioning shall be measured for payment.
28Supplying and laying,factory made unreinforced precast concrete cable cover LV type-1, flat, of size 250x150x40mm, laid flat and dryin trenches over the cable for protection, length perpendicular to the direction of cable adjacent to each other, complete all as specified and directed.
29Supply and laying in tranches/floors or fixed on wall 35 sqmm 3.5 core aluninium conductor cable XLPE Insulated screenedPVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor including fixing materials like lugs,cable glands etcall as specified and directed.
30All as per Sl item No 29 above but 50 sqmm 3.5 core
31All as per Sl item No 29 above but 95 sqmm 3.5 core
32All as per Sl item No 29 above but 185 sqmm 3.5 core
33All as per Sl item No 29 above but 16 Sqmm 4 core
34M&L for GI pipe 40mm dia bore light gradewith all fittings for cable protection, and fixed complete to wall, panel, pole or laid in trenches and road crossing complete all as specified and directed.
35Supply and installation in replacement , commissioning and testing Polycarbonate ASTA CPRI approved OEM made main LT Panel. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel shall be anti-acid & anti corrosive. Degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262.The CPRI report shall have mention of following tests performed and passed out satisfactorily - Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer shall submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing] comprising the followings :- INCOMER:160Amp, 4 pole MCCB, 25 KA- 01 No, Digital VAF meter with inbuilt selector switch & CT Coil -01 No Set of LED type indicating lamps - 01 NoCopper Bus Bar 200Amp TPN OUTGOINGS: 63 Amp, MCCB TPN 25ka 415 V, -2Nos ( one Spare) 125 Amp, MCCB TPN 25ka 415 V, -2Nos ( one Spare)
36S&F 3 Pole MCCB 125 to160 Amp, 50 Hz, 415 V with rupturing capacity 25 KA complete all as specified and directed.
37Taking down copper/aluminium point wiring for (light, fan , socket or power and bell) complete including unserviceable fittings such as switches, ceiling rose, holders, sockets bell etc. and making good the distrubed surfaces on wall/floor etc complete all as specified and dirceted.
38Taking down MCB DB TPN/SPNof any make and type including dismantling all electrical connections from MCBs/MCCB/isolators and making good the distrubed surface complete all as specified and directed.
39Disconnecting and taking down old existing light fitting of any description from any position complete all as specified and directed.
40Disconnecting and taking down old existing electric ceiling fan/exhaust fan/wall fan of any description from any position and deposting to E/M Store Yard Halwara for safecustody, collection of the same after repair works in the buildingand refixing of the samecomplete all as specified and directed.
41Disconnecting and taking down old existing meter box carefully with meter and depositing the same to E/M Store Yard Halwara complete all as specified and directed
42Disconnecting and taking down existing electric geyserof any make and size including dismantling all electrical connections, safety valve, thermostate, NRV, connection piece and all accessories etc and depositing the same to E/M store yard Halwara complete all as specified and directed.
43Disconnecting and taking down old sub main wiring of any description carefully complete all as specified and directed
44Disconnecting and taking down old exising earthing of any description carefully complete all as specified and directed
45M&L for point wiring for one light point/fan point controlled by one switch using proper colour coding complete with 1100 Volts grade 1.5 Sq.mm, single core, PVC insulated,unsheathed cable with multistranded copper conductor with ISI mark FRLS grade, conforming to IS-694 in and including PVC medium grade conduit not less than 25mm dia. ISI marked with all accessories concealed in wall/ceiling/ floor /roof etc,including GI terminal boxes with 3 mm thick plastic laminated sheet cover having necessary cutting for fixing switches/ socketsincluding 1.5 Sq.mm PVC insulated, unsheathed, multistranded copper conductor, FRLS 1100 volts grade (green colour) as earth wire, connected to common earth dolly complete all as specified and directed.
46All as per Sl item No 45 above but for one three pin switch socket 5 amps outlet on same board.
47All as per Sl item No 45 above but for one three pin switch socket 5 amps outlet on Independent board.
48All as per Sl item No 45 above but for one bell point
49All as per Sl item No 45 above but point wiring with 2.5 Sqmm PVC insulated, FRLS, unsheathed, cable confirming to IS-694,PartII, ISI marked with Multistranded copper conductor cable in and including PVC conduit.
50S&FSwitch piano, flush type single pole, one way 5 Amp complete all as specified and directed.
51S&F Socket outlet 3 pin, 5A, flush type complete all as specified and directed.
52S&FSwitch piano, flush type single pole, one way 15 Amp complete all as specified and directed..
53S&F Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type complete all as specified and directed.
54S&F ceiling rose surface bakelite 65x50mm with three terminals complete all as specified and directed.
55S&F stepped type fan regulator flush type on the existing phenolic laminated sheet complete all as specified and directed.
56S&F Single pole and neutral enclosure for AC and Geyser with a two pin and earth plug and socket complete with one single pole MCB 20 Amps complete all as specified and directed.
57S&FPolycarbonate AC Box with Industrial Socket 16 Amp 3 Pin.The AC box shall be anti-acid & anti corrosive, degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262. The Box DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane.Lid fasteners shall not have screws but shall be with quarter turn locking knobswhich is well visible ( open – locked), and they will be sealable without any accessories. The panel shall pass glow wire test 960 degrees centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing]. Make-Hensel/Rittal/Emitter/Schneider
58S&F IP 65 Thermoplastic PS polystyrene weatherproof MCB Box suitable for any makes MCBs, for 12 Way ( 14 MCB"s SP Cut )with multi - level knockouts for cable glands in different sizes, double door with IP-65 protection single phase 240 volts including neutral link fixed flush concealed in wall including taking out old DB"s and chases wall for fixing DB and making good distributed wall/surfaces to match with existing specification. The MCB box shall fulfill the following technical features: • for the installation of DIN rail equipment up to 63 A, top hat profile 35 mm • with transparent lid, sealable • locking device for hinged lid and sealing facility see accessories • with cable entry cover • protective cover can be cut out • colour: grey, RAL 7035standards The MCB box shall fulfill the following standards:- Weatherproof : Rainwater proof, temperature resistant, IP65 IEC 60670-24 : Particular requirements for connecting boxes and enclosures. IEC 60695 – 2 – 11 : Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 750 deg C. IEC 60529 : IP 65 degree of protection.
59All as Per Item No 58 above butIP 65 Thermoplastic PS polystyrene weatherproof MCB Box suitable for any makes MCBs, for 8 Way ( 10 MCB"s SP Cut ).
60All as Per Item No 58 above but IP 65 Thermoplastic PS polystyrene weatherproof MCB Box suitable for any makes MCBs, for 6 Way ( 6 MCB"s SP Cut )
61All as Per Item No 58 above but IP 65 Thermoplastic PS polystyrene weatherproof MCB Box suitable for any makes MCBs, for 4 Way ( 6 MCB"s SP Cut )
62S&F MCBSPN,6 to 32 Amp,240V, 10KA"B" curve in the MCB DB complete with connection testing and commissioning. complete all as specified and directed.
63S&F MCB SP, 6 Amp to 32 Amp, 240 Volt, 50HZ, 10 KA, `B` Series, making electrical connection with the help of Lugs/thimbles complete all as specified and directed.
64S&F LED light fitting 4 feet Long1x 20W, 220V AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
65S&F LED ceiling light fitting 600mm x 600mm, 35/36W, 220V AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
66S&F LED round shape 6 watt 220 volts AC decorative box rtype with driver, holdering including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed
67M&L for sub main wiring with 2 x 4.00 sqmm (nominal area) PVC insulated FRLSH, unsheathed, multistrand, 1100 volts grade copper conductor cable single core drawn through in and including non metalic PVC concealed conduit not less than 20mm dia medium grade and its accessories including one run of 4 sqmm PVC insulated copper conductorfor earth wire complete all as specified and directed. Note:- (i) Surface conduit shall be laid in celing portion only. (ii)Two run of 4.00 Sqmm and one run of 4.00 Sqmm as earth wire shall be measured as one unit length ie 01 RM.
68S&F submain wiring with 2 x 6.00 sqmm (nominal area) PVC insulated FRLSH, unsheathed, multistrand, 1100 volts grade copper conductor cable single core. drawn through in and including non metalic PVC concealed conduit not less than 20mm dia medium grade and its accessories including one run of 6 sqmm PVC insulated copper conductorfor earth wire complete all as specified and directed . Note:- (i) Surface conduit shall be laid in celing portion only. (ii)Two run of 6.00 Sqmm and one run of 6.00 Sqmm as earth wire shall be measured as one unit length ie 01 RM.
69S&F building security light fitting 35 W LED New generation Energy Saving & Environment friendly long life versatile pressure die-cast aluminium IP-66 roadwayluminars with high power LEDs as light source and electronic drive including connecting complete all as specified and directed.
70S&F Angular lamp holder PVC / Polycarbonate type with back plate suitable for bulb fitting Including 9 watt LED Bulb complete all as specified and directed.
71S & F Bell, AC, 230 volts, single pole complete all as specified and directed.
72Supply and fixing , installation, commissioning and testing polycarbonate CPRI approved OEM made 1 No meter pannel. the panel shell be made of polycarbanate thermoplastic enclosers which should be uv resistance in accordance with IEC 61439-1, clause 10.2.4. The meter panel shall be anti acid, anti corrosive & fully transparent door for meter vision. Degree of protection against mechanical load should be IK08 ( 5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channelpartner or sister concerned assmbly will not be accepted. DEGREE OR INGRESS PROTECTION IP 65 IN ACCORANCE WITH IEC 60529. The gasket should be internally embedded made of ployurethane. The manufacturer of panel shall submit a copy of type test report of a board made out of plycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily :- tempreature rise, dielectric properties, short circuit withstand current- rated peak & short time withstand current and rated conditional short circuit current effectiveness of protective circuits. The board manufacturer must submit the copy of type test report for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960º C in accordance with 60685-2-11 (flame retardant and self-extinguishing). One main incomer MCCB 63A TPN 25KA Thermal/Magnetic release with spreader link. MCCB/MCB Nob operated by filp cover. Indicator provided on each phase, including ONETHREE phase sub-meters. Output supply by MCB40 Amp 8 Nos meter enclosures & enclosures accessories as per RAL 7035. Ten Nos terminal block provided for output supply complete all as specified and directed. Make- Hensel/Rittal/Emitter/Schneider.
73Supply and fixing , installation, commissioning and testing polycarbonate CPRI approved OEM made 1 No meter pannel. the panel shell be made of polycarbanate thermoplastic enclosers which should be uv resistance in accordance with IEC 61439-1, clause 10.2.4. The meter panel shall be anti acid, anti corrosive & fully transparent door for meter vision. Degree of protection against mechanical load should be IK08 ( 5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channelpartner or sister concerned assmbly will not be accepted. DEGREE OR INGRESS PROTECTION IP 65 IN ACCORANCE WITH IEC 60529. The gasket should be internally embedded made of ployurethane. The manufacturer of panel shall submit a copy of type test report of a board made out of plycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily :- tempreature rise, dielectric properties, short circuit withstand current- rated peak & short time withstand current and rated conditional short circuit current effectiveness of protective circuits. The board manufacturer must submit the copy of type test report for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960º C in accordance with 60685-2-11 (flame retardant and self-extinguishing). One main incomer MCCB 125A TPN 25KA Thermal/Magnetic release with spreader link. MCCB/MCB Nob operated by filp cover. Indicator provided on each phase, including ONETHREE phase sub-meters. Output supply by MCB32 Amp 6 Nos meter enclosures & enclosures accessories as per RAL 7035. Ten Nos terminal block provided for output supply complete all as specified and directed. Make- Hensel/Rittal/Emitter/Schneider.
74Supply and fixing , installation, commissioning and testing polycarbonate CPRI approved OEM made 1 No meter pannel. the panel shell be made of polycarbanate thermoplastic enclosers which should be uv resistance in accordance with IEC 61439-1, clause 10.2.4. The meter panel shall be anti acid, anti corrosive & fully transparent door for meter vision. Degree of protection against mechanical load should be IK08 ( 5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channelpartner or sister concerned assmbly will not be accepted. DEGREE OR INGRESS PROTECTION IP 65 IN ACCORANCE WITH IEC 60529. The gasket should be internally embedded made of ployurethane. The manufacturer of panel shall submit a copy of type test report of a board made out of plycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily :- tempreature rise, dielectric properties, short circuit withstand current- rated peak & short time withstand current and rated conditional short circuit current effectiveness of protective circuits. The board manufacturer must submit the copy of type test report for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960º C in accordance with 60685-2-11 (flame retardant and self-extinguishing). One main incomer MCCB 200A TPN 25KA Thermal/Magnetic release with spreader link. MCCB/MCB Nob operated by filp cover. Indicator provided on each phase, including ONETHREE phase sub-meters. Output supply by MCB32 Amp 8 Nos meter enclosures & enclosures accessories as per RAL 7035. Ten Nos terminal block provided for output supply complete all as specified and directed. Make- Hensel/Rittal/Emitter/Schneider.
75Supply and installation in repairs, commissioning and testing Polycarbonate ASTA CPRI approved OEM made main DB Panel wall Mounted . The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel shall be anti-acid & anti corrosive. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily - Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer shall submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Bus Bar Copper 1.5 times Main incomer.Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 flame retardant and self-extinguishing comprising the followings :-INCOMER:- 63 Amp, 4 pole MCCB, 25KA - 01 No Digital Volt meter 0-500V with iinbuilt selector switch - 01 No Digital Amp meter 0-200A with iinbuilt selector switch & CT Coils- 01 No Set of LED type indicating lamps - 01 No OUTGOINGS: 40 Amp, MCB DP 240 Volt- 01 Nos 6-40 Amps MCB SP 240 Volt -10 Nos Make-Hensel/Rittal/Emitter/Schneider
76S&F sheet metal enclosureDB SPN, 8 way with 200 Amp rated bus bar, 240 V, double doorfor fixing MCB’s, isolators etc., having IP-43 protection,flush mounting complete all as specified and directed.
77S&F 300mm sweep exhaust fan, steel body AC single Phase. 230Vwith blades,frame and louvers complete all as specified and directed.
78Supply , installation, fixing, testing and commisioning of AC split type, intellisense dual inverter technology compressor, five star energy saving unit, single phase, cooling capacity 1.5 TR, including Remote Control unit, Plasma filter for better indoor air quality with minimum 5 star rating electric driven and split AC copper condensing unit (Outdoor unit) fixed on suitable size perforated angle iron frame for mounting condensing unit as required and evaporator grouted in side room at suitable height with provision of outlet PVC pipe for draining out condensed water upto floor level and gas connection by soldering or brazing including extra copper pipe duly insulated by insulator material and filling of gas where as required and testing after installation complete all as specified and directed.
79S&F 4 KVA wall mounting type Electronic Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as specified and directed.
80S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 32 Amps rating10KA, "C" Curve, 230 Volts complete all as specified and directed.
81S&F TPN neutral vertical load line DB double door 4 way with 160 Amp bus bar 415 Volt sheet metal enclouser suitable for incomer MCCB 4 Pole including suitable dummy plate single pole complete all as specified and directed.
82S&F MCCB 4 pole, 415 Volt fixed thermal and fixed maganatic setting of cap 63 Amp 36KA of make Havells/L&T/Legrand/Standard or equivalent
83S & FMCBSingle Pole 240 volts of capacity 40 Amp complete all as specified and directed.
84Supply , install, testing and commissioning of LT Panel board as per IS-8632, made out of 3.15 mm CRCA Sheet,outdoor cubical type totally enclosedweather dust and vermin proof with front and rear opening of 415 Volts 3 phase 4 wire 50 Hzincluding internal wiring with copper conductor including two coats of synthetic enamel paint over one coat of red oxide primer including connecting all in coming and out going cable feeders with necessary cable glands, thimbles etc. The panel should have angle iron base frame made of 40 x 40 x 6 mm fixed / grouted,including suitable size PCC blocks with PCC 1:2:4 type B-1 using 20mm graded mechanically crushed stone aggregate foundation support , well finishing with cement mortar and comprising of the following switchgear and accessories :- (a) 04 strips of aluminium bus bar with insulation colour sleeves of capacity 200 Amp fixed on PVC heat shrinkable insulator heavy duty. (b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No. (c) Amp meter 0-500 Amps, digital type panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size of CTs-01 No. (d) Indicatorlamp LED type on all phases (R,Y,B) - 03 Nos (e)MCCB 160 Amps, 3 phase, 415 volt, 4 pole, breaking capacity 36 kA rating with adjustable thermal & Adjustable magnetic type - 01 Nos (Incoming) (f)MCCB 63 Amps, 3 phase, 415 volt, 4 pole, breaking capacity 25 kA rating with adjustable thermal & Adjustable magnetic type - 02 Nos (Outgoing) (g)Supply and fixing charge of LT Panel including making all connections etc
85M&L for 4mm dia galvanised iron or steel wire earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation of or loop earhting etc as required complete all as specified and directed.
86M & L for cleaning of filters of AHU & complete overhauling of the AHU of any size including removal of smoke residue and repair/maint of damaged parts complete all as specified and directed
87M&L for 24 gauge steel sheet for addition / alteration in the existing SA GI sheet metal ducts made of GI sheet of Class -VIII as per IS -277 for supply air ducting as per IS - 655 and as required complete all as specified and directed.
88M&L for 22 gauge steel sheet for addition / alteration in the existing SA GI sheet metal ducts made of GI sheet of Class -VIII as per IS -277 for supply air ducting as per IS - 655 and as required complete all as specified and directed.
89Supply, fabrication, installation and testing the flexible connections constructed of fire resistant double resinsleeve complete all as specified and directed.
90Supply, fabrication, installation and testing the grills / Diffusers for Supply Air made of etruded Aluminum section with powder coated paint and GI VCD complete all as specified and directed.
91Supply, fabrication, installation and testing the grills / Diffusers for Return Air made of etruded Aluminum section with powder coated paint complete all as specified and directed
92Supplying, fixing, testing and commissioning of power coated extruded aluminium section of 120 gauge thick for fresh air grill in weather maker room with volume control dampers, bird screen etc complete all as specified and directed
93Supply, installation, testing and commissioning of motorised combined fire damper made of 20 gauge GI sheet complete with control panel, inter connecting wiring at locations shown in approved shop drawings and as per specifications including followings :- (a)Fire damper - 01 Sqm (b)Actuators - 01 No (c)Control Panel - 01 No
94M&L for earthing with galavanised steel plate electrode 600x600x6.0mm thick burried directly in ground vertically (earth plate to a depth of not less than2.25 meter deep below ground level) with the top edge of earth plate at a depth of not less than 1.5 meter below normal ground level connected to GI earth lead wire 4mm by means of bolts, nuts, washers of galvanised iron and provision of earth wire, galvanised iron protection pipe 40mm bore, light grade up to and including test point including necessary earth work in any type of soild and PCC (1:3:6) type C1 (using 20mm graded stone aggregate) earth chamber, watering pipe 20mm dia galvanised iron light grade with funnel, RCC (1:2:4) type B1 precast cover 40mm thick with 6mm dia mild steel bars complete all as shown in electrical plate No 3 of SSR part-I connected to earthing test point all as specified or indicated and testing on completion complete all as specified and directed. Note:- Quoted rate deemed to include the cost of excavation and earth work, PCC pit, funnel and cover etc,
95M&L for earthing with galavanised steel plate electrode 600x600x6.0mm thick burried directly in ground vertically (earth plate to a depth of not less than2.25 meter deep below ground level) with the top edge of earth plate at a depth of not less than 1.5 meter below normal ground level connected to GI earth strip of size 32mmx6mm by means of bolts, nuts, washers of galvanised iron and provision of earth wire, galvanised iron protection pipe 40mm bore, light grade up to and including test point including necessary earth work in any type of soild and PCC (1:3:6) type C1 (using 20mm graded stone aggregate) earth chamber, watering pipe 20mm dia galvanised iron light grade with funnel, RCC (1:2:4) type B1 precast cover 40mm thick with 6mm dia mild steel bars complete all as shown in electrical plate No 3 of SSR part-I connected to earthing test point all as specified or indicated and testing on completion complete all as specified and directed. Note:- Quoted rate deemed to include the cost of excavation and earth work, PCC pit, funnel and cover etc,
96M&L for earthing with galavanised steel plate electrode 600x600x3.15mm thick burried directly in ground vertically (earth plate to a depth of not less than2.25 meter deep below ground level) with the top edge of earth plate at a depth of not less than 1.5 meter below normal ground level connected to GI earth lead wire 4mm by means of bolts, nuts, washers of galvanised iron and provision of earth wire, galvanised iron protection pipe 40mm bore, light grade up to and including test point including necessary earth work in any type of soild and PCC (1:3:6) type C1 (using 20mm graded stone aggregate) earth chamber, watering pipe 20mm dia galvanised iron light grade with funnel, RCC (1:2:4) type B1 precast cover 40mm thick with 6mm dia mild steel bars complete all as shown in electrical plate No 3 of SSR part-I connected to earthing test point all as specified or indicated and testing on completion complete all as specified and directed. Note for item no 94 to 96:-:- (i)Quoted rate deemed to include the cost of excavation and earth work, PCC pit, funnel and cover etc, (ii) Item of earthing includes cost of 15mm bore medium grade GI protection Pipe and 7.5 Meters long earth strip/lead upto test point. (iii) On testing after completion of earthing if the desired earth resistance is not obtated earthning will be re-done by the contractor at his own risk and cost to the entire satisfaction of Engr-in Charge.