Power Development Department has published Tender For Augmentation Of Receiving Station Budgam From 26.3 To 30 Mva. Submission Date for this Tender is 03-02-2024. Electrification Work Tenders in budgam Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 11-Jan-2024 | EXTENSION 1 | Date | 18-01-2024 |
2 | 18-Jan-2024 | EXTENSION2 | Date | 25-01-2024 |
3 | 25-Jan-2024 | EXTENSION3 | Date | 03-02-2024 |
Sl. No. | Item Description |
1 | A) SUB-STATION MAIN EQUIPMENT:- |
2 | Supply, Installation, Testing & Commissioning of 33 kV Current Transformer (33 kV, 1F, Multi Ratio Multi Core, Outdoor) (1 No. per F) |
3 | Supply, Installation, Testing & Commissioning of33kV Isolator without Earthing Blade(36kV,1250A, Outdoor,3 poles, 25 kA) |
4 | Supply, Installation, Testing & Commissioning of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m |
5 | Supply, Installation, Testing & Commissioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less (1set = 3 pieces) |
6 | Supply, Installation, Testing & Commissioning of 33 kV C&R Panelalong with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port |
7 | Supply, Installation, Testing & Commissioning of33KV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) |
8 | ii)Pipe Structures |
9 | Supply and erection of G.I Pipe of Dia 150mm, 5.9 mm Thick 3 m longwith G.I Base Plate 8 mm Thick (Design as per REC standard) |
10 | Supply and erection of Galvanised Steel Structures |
11 | Providing and fixing of Galvanised Nuts & Bolts |
12 | iii) Control Cables:- |
13 | Supply,Laying,Testing, and commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
14 | Supply,Laying,Testing, and commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
15 | Supply,Laying,Testing, and commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS |
16 | Providing and fixing of Lugs,Ferrules etc. |
17 | iv) Conductor and Hardware:- |
18 | Providing,Laying,stringing ,tensioning and binding of 0.2 ACSR Conductor (Panther) as per REC construction standards |
19 | Supply Installation Testing and Commissioning of 33kV Polymeric composite Disc Insulator (36KV, Lightening Impulse 170kV Positive and 180kV Negative, creepage distance 900mm,min failing load 70kN) with tension fittings |
20 | Providing and fixing of T- Clampsof standard make |
21 | B) Power Transformer for the 33/11KV Substation:- |
22 | Dismantling of existing 6.3MVA33/11kV,Power Transformer including itsloading, unloading etcand carriage to store |
23 | Installation, Testing and Commissioning, of 33/11kV, 10MVA Power Transformer including its carriage,loading, unloading etc(Power Transformerto be provided by the department and to be lifted from store) |
24 | Supply,Laying,Testing, and commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
25 | Supply,Laying,Testing, and commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
26 | Supply,Laying,Testing, and commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
27 | P/laying of HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room including excavation |
28 | C) 11KV Indoor Switchgear of 33/11sub station |
29 | Supply, Installation, Testing and commissioning of (1+3) 11kV VCB Panel with breaker complete Setof reputed make 2 O/C (overcurrent) and 1 E/F (earth fault) relay (IEC61850) ,Mimic Diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port complete(12 kV, 1250A, 25 kA, Outgoing) complete with copper bus and other allied accessories Note:-Outgoing 11KV Panel VCB panel should be having 11KV CT of Ratio 600-300/5-5-5A & Incomer 11KV VCB Panel CT Ratio:- 750-375/5-5-5A |
30 | Supply,Laying,Testing, and commissioning of 11 kV 630 mm² Single Core XLPE Cable (with one spare length) armoured, FRLS |
31 | Providing and fixing of Indoor Heat Shrinkable Cable Termination Kits suitable for 11 kV630 mm² Single Core XLPE Cable |
32 | Providing and fixing of outdoor Heat Shrinkable Cable Termination Kits suitable for 11 kV630 mm² Single Core XLPE Cable |
33 | Supply, Installation, Testing and commissioning of 11 kV Bus Coupler with Adaptor Panel |
34 | Providing and fixing of Galvanisedironof sorts |
35 | Supply, Installation, Testing and commissioning of 100 kVA,33/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound) |
36 | D) Common Miscellaneous Equipments in 33/11KV Receiving station |
37 | Supply, Installation, Testing & Commissioning of A) Battery Bank 30 Volt, 200AH, of 15 no cells of 2Volt each, sealed maintanance free VRLA type, high impact polyprophelene copolymer container, flame retardant. B) 30 Volt, 200AH, float cum bost charger with full wave rectification for 220Volt, 1 phase, 50 Hz, AC input supply |
38 | Supply, Installation, Testing & Commissioning of Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories |
39 | Supply, Installation, Testing & Commissioning of Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB"s (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
40 | Supply of Rubber Mat 1mx2m 19mm thick |
41 | Supply ofRubber Gloves for 11kV level |
42 | Supply and fixing of Recessed celing LED fixtures 18w each with complete all accessories |
43 | Supply and fixing ofLED 100W yard lights with complete all accessories |
44 | Dismantling of existing electrical equipments (11/0.433kV Auxillary Transformer, Battery Bank, 5 No 11kV VCB Panels, 300sqm power cable 70mtrs approxand allied accessories etc)including theirloading, unloading etcand carriage to store (complete job) |
45 | E) Substation Civil Works: Bidders shall quote the rates inclusive of carriage |
46 | Construction of foundation Blocks of various Equipments at Rec/stn Budgam |
47 | Earth work and excavation by manual means over areas (exceeding 30 Cmand upto depth 1.5 mtr in width as well as 10 Sq m on plan) including disposal of excavated earth upto 1 meter from cutting edge ,disposed earth to be levelled and neatly dressed inall kinds of soil. |
48 | Providing and laying of dry stone soling in the excavated trenches, duly hand packed on level including ramming with iron hand rammers, leveling,ramming etc |
49 | Providing and laying in positionof mud mat in 1:4:8 mix with 40 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8stone aggregate of 20mm nominal size) |
50 | Providing and laying in position specified grade of reinforcedcement conc. excluding the cost of centering, shuttering, finishing -and reinforcement All work upto plinth level, M20 gradeconcrete (1:1.5:3)for Transformer and VCB bed |
51 | Providing & laying in position cement conc. of specified grade excld. Cost of centering & shuttering- all work upto plinth level in 1:2:4 (1 cement :2 coarse sand :4 graded stone agg. 40 mm nominal size (Crushed) M-15 Grade PCC |
52 | Centering and shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases for columns etc |
53 | Providing 12 mm thick cement plaster on the block faces above ground level of mix:1:6 (1: cement :6 fine sand) |
54 | Providing and fixing of re-inforcements 10mm and 12mm forfoundationsincluding bending and cutting etc |
55 | F) Yard Earthing |
56 | P/F of earthng electrode40mm dia 3m long GI pipe through GI flat strip 50x 6mm in 33KV and 11KV yard |
57 | Providing and fixing ofGI flat for earthing 50x6 mm for earthing risers as per REC construction standards |