| Sl. No. | Item Description |
| 1 | SITC of Distribution Transformer. |
| 2 | Supply Installation Testing Commissioning of \"33/0.433 KV Distribution Transformerrating of 1000 KVA,Outdoor type ,3 phase ,50 HZ, Oil filled ONAN, Copper Wound core type ,step down ,Delta/Star ,Dyn-11 with on load tap changer. The transformer shall be designed and manufacturedas perIS 2026-1977 with upto date Amendments and shall be as per technical specifications avaliable in this tender document complete as required. |
| 3 | 33 KV HIGH VOLTAGE PANELSupply, Installation, Testing & Commissioning of indoor type (IP 4X) floor mounted metal clad, 33KVSwitch Board VCB panel with06 Nos. VCBs, totally enclosed & fully interlocked, truck mounting, horizontal draw out, horizontal isolation type vacuum breaker as perIS / IEC 62271- 100 (2007) for breakers & 200 (2003),for panels / IS3247 as amended up to date, having capacities as mentioned below, free standing extensible on both sides, single break, trip free mechanism, motorised charged and auto/ manually closing breaker suitable for use on (33KV ), 3 Phase,50Hz A.C. supply with short circuit fault level of 1500 MVA,complete with self contained shorttimecurrent26.3kAfor3sec,InternalArcTestforAFLR26.3kAfor1secatindividual compartmentsi.ebusbar,VCB,andcablecompartment,rackinandrackoutmechanism,air insulatedbutencapsulatedcopperbusbarscapacitymeetingfaultlevelcurrent,DCpowerpack, breakerfeaturedwithmechanicalON/OFFindicatorwithhandtripdevice, BreakercontrolTNC switch and all accessoriessuch as shunt trip coil, and auxiliary switch of 4NO+4NC, motorised and manually operated spring assisted closing mechanism, emergency trip push button, interconnections, space heaters, earthing, etc.and equipped with following switchgears and accessories, connections suitable for cable upto 3C x 300 sqmmXLPE cable of (33KV ) grade (cable entry from bottom), Separate earthing switch shall be provided forCable earthing . The earthing truck shall be so designed that it is impossible to earth alive. cable terminations suitable for 3C x 300 sq.mm. XLPE (33KV ) cable. |
| 4 | 33 KV HIGH VOLTAGE PANEL AT OTB A.Incomer 1 No. consisting of following;1 No. of800 Amp , 33KV , 3 Ph, 3P VCB1 No - Multifunction Meter withaccuracy class 0.5 LED display of I ,V, Hz, Active, Reactive , Apparent Power & Energy, Power factor,%THD , Maximum demand load,(complying with IEC61557-12)with RS 485 & Ethernet port andprotection MCB and required accessories to complete the system3No.Castresindrawout typePTs33KV/3/1103,class0.5,100VAburden including HT HRC fuse on 33KV Side and MCBs on secondary side protction.3 No. Cast resin insulated Dual core 3 CTs 30 / 5-5A of 15VAburden and accuracy Class-0.5 for metering and class 5P10 for protection.Aux. relays for Anti Pumping & indication. Trip Circuit supervision relay, Master Trip Circuit Relay1 No. Micro processor based over current, short circuit 50,50 N & earth fault numerical IDMT relay with having RS485 modbus communicationfacilityconsisting3 elementfor over current relay and one earth fault capable of storing last 10 trip history.1 No. Over & under voltage protection relay, 1 No. Over & under frequency relay1No.Alarmannunciatorwithminimum8windowsandbuzzer,ACK,rest,testpushbuttonfor transformer faults and electrical faults in respective window.B. Busbar800 Amps TP, 36KV Copper Bus bar with heat shrinkable insulated sleeves with cast epoxy insulator to withstand full short circuit currents upto 26.3 kA for 1 second.C. BUS COUPLER800 Amps.,33KV horizontal draw out type VCB with motorized spring charge mechanism, T/N/C switch and required safety switchgears complete.1 Set of LED indication lamp protected by MCB for ON & OFF and spring charge of breaker complete Electrical inter locking with both incomers & bus couplerD. Outgoings 02 Nos each consisting of following;01 No. 800Amp, 33KVVCBhorizontaldrawouttypeVCBwithmotorized spring charge mechanism, T/N/C switch and required safety switchgears completeAux. relays for Anti Pumping & indication. Trip Circuit supervision relay, Master Trip Circuit Relay1 No. Micro processor based over current, short circuit 50,50 N & earth fault numericalIDMT relay with having RS 485modbus communicationfacility consisting3 element for over current relay and one earth fault capable of storing last 10 trip history.1 No - Multifunction Meter withLED display of I ,V, Hz, Active, Reactive , Apparent Power & Energy, Power factor, %%THD , Maximum demand,(complying with IEC61557-12)with RS 485 & Ethernet port andprotection MCB and required accessories to complete the system.3No.CastresininsulatedDualcore3CTs30/5-5Aof15VAburdenandaccuracyClass-0.5for metering and class 5P10 for protection.1 No. Auxiliary relays for transformer faults WTI with alarm, trip and hooter, 1No. Alarmannunciatorwithminimum8windowsandbuzzer,ACK,rest,testpushbuttonfor transformer faults and electrical faults in respective window.E. All I/C & O/GBreaker have followingAccessories & indication6AMCB for spring charge, DC Control Supply healthy & fails, Surge Arrestor of type 1, 33KV grade shall be provided for all phases of each incomer AC Supplycontrol ON/OFF Switch, Circuit breaker failure Alarm indication, VCB spring charge indication, LED Illumination lamp ON / OFFwith limit Switch, T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. All control wiring with protection & test terminal block as required.Emergency trip push button, 2A MCB for lamp, 60 watts space heater with thermostat, 16 Amp MCB for space heater and plug point, 6/16 Amps 5 Pin with piano type switch socket outlet. Supply, fixing, testing and commissioning of automatic linear pneumatic tube Detection basedClean agent System for Electrical Panels (Linear Pnuematic Heat Detection tube Panel Protection System), consisting of the Mentioned compenents.Suitablecapacity , Direct Low Pressure (DLP) Assembly with automatic valve, push in connector for tube, Cleanagent,mountingbracket,EndofLineadopterandlowpressureswitchformonitoring system activation.i) Linear Pneumatic Heat detection tube with all necessary & supportsii)MasterControlUnitforcontrollingeachsystem,completewithpressureswitches,buzzersand electronic hooters, including all necessary accessories + electrical wiring to make each entire system functional. |
| 5 | EXTENSION OF EXISTING 33 KV HIGH VOLTAGEINDOORPANEL AT NEW POWER HOUSE.Extension of existing 33 KV indoor typeHT panel bySupplying, Installing, Configuring, Testing & Commissioning of indoor type (IP 4X) floor mounted metal clad, 33KVSwitch Board VCB panel with02 Nos. VCBs, totally enclosed & fully interlocked, truck mounting, horizontal draw out, horizontal isolation type vacuum breaker as perIS / IEC 62271- 100 (2007) for breakers & 200 (2003),for panels / IS3247 as amended up to date, having capacities as mentioned below, free standing extensible on oneside, single break, trip free mechanism, motorised charged and auto/ manually closing breaker suitable for use on 33KV , 3 Phase, 50Hz A.C. supply with short circuit fault level of 1500MVA,complete with self contained shorttimecurrent26.3kAfor3sec,InternalArcTestforAFLR26.3kAfor1secatindividual compartmentsi.ebusbar,VCB,andcablecompartment,rackinandrackoutmechanism,air insulatedbutencapsulatedcopperbusbarscapacitymeetingfaultlevelcurrent,DCpowerpack, breakerfeaturedwithmechanicalON/OFFindicatorwithhandtripdevice, BreakercontrolTNC switch and all accessoriessuch as shunt trip coil, and auxiliary switch of 4NO+4NC, motorised and manually operated spring assisted closing mechanism, emergency trip push button, interconnections, space heaters, earthing, etc.and equipped with following switchgears and accessories, connections suitable for cable upto 3C x 300 sqmmXLPE cable of (33KV ) grade (cable entry from bottom), Separate earthing switch shall be provided forCable earthing .The earthing truck shall be so designed that it is impossible to earth a live. cable terminations suitable for 3C x 300 sq.mm. XLPE (33KV ) cable.A. Busbar1250 Amps TP, 36KV Copper Bus bar with heat shrinkable insulated sleeves with cast epoxy insulator to withstand full short circuit currents upto 26.3 kA for 1 second.Busbar of size 2//50x10mm(Double Run),VCB Module and integration of the panel with existing 33 KV VCB panelwith all controls, protection indication, other accessories & fitting.B. Outgoings 02 Nos each consisting of following;01 No. 800Amp, 33KVVCBhorizontaldrawouttypeVCBwithmotorized spring charge mechanism, T/N/C switch and required safety switchgears completeAux. relays for Anti Pumping & indication. Trip Circuit supervision relay, Master Trip Circuit Relay1 No. Micro processor based over current, short circuit 50,50 N & earth fault numericalIDMT relay with having RS 485modbus communicationfacility consisting3 element for over current relay and one earth fault capable of storing last 10 trip history.1 No - Multifunction Meter withLED display of I ,V, Hz, Active, Reactive , Apparent Power & Energy, Power factor, %%THD , Maximum demand,(complying with IEC61557-12)with RS 485 & Ethernet port andprotection MCB and required accessories to complete the system.3No.CastresininsulatedDualcore3CTs30/5-5Aof15VAburdenandaccuracyClass-0.5for metering and class 5P10 for protection.1 No. Auxiliary relays for transformer faults WTI with alarm, trip and hooter, 1No. Alarmannunciatorwithminimum8windowsandbuzzer,ACK,rest,testpushbuttonfor transformer faults and electrical faults in respective window.C. All I/C & O/GBreaker have followingAccessories & indication6AMCB for spring charge, DC Control Supply healthy & fails, Surge Arrestor of type 1, 33KV grade shall be provided for all phases of each incomer, AC Supplycontrol ON/OFF Switch, Circuit breaker failure Alarm indication, VCB spring charge indication, LED Illumination lamp ON / OFFwith limit Switch, T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. All control wiring with protection & test terminal block as required.Emergency trip push button, 2A MCB for lamp, 60 watts space heater with thermostat, 16 Amp MCB for space heater and plug point, 6/16 Amps 5 Pin with piano type switch socket outlet. Supply, fixing, testing and commissioning of automatic linear pneumatic tube Detection basedClean agent System for Electrical Panels (Linear Pnuematic Heat Detection tube Panel Protection System), consisting of the Mentioned compenents.Suitablecapacity , Direct Low Pressure (DLP) Assembly with automatic valve, push in connector for tube, Cleanagent,mountingbracket,EndofLineadopterandlowpressureswitchformonitoring system activation.i) Linear Pneumatic Heat detection tube with all necessary & supportsii)MasterControlUnitforcontrollingeachsystem,completewithpressureswitches,buzzersand electronic hooters, including all necessary accessories + electrical wiring to make each entire system functional. |
| 6 | LT PanelsSupply, Installation, Testing and Commissioning of cubicle typeLT panel , as per 61439-1 & 61439-2, suitable for 415V+/-10%, 3 Phase, 4 wire 50 HzAC supply system,fabricated in compartmentalized 4b bolted modular design IP 42 from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade, having TPN Aluminium alloy bus bars for high conductivity, SMC bus bar supports,with short circuit withstand capacity of 50 KA for 1 sec &Internal arc withstand of 50kA for 0.3 second ,bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections,entire panel shall have a common GI earth bar of size 50 mm x 6 mm at the rear with 2 Nos. earth stud, solid / flexible connections from main bus bar to switchgears and from switchgear output to cable termination in cable alley with required size of AL conductors / bus bars and control wiring with 2.5 sqmm PVC insulated copper conductor cable (FRLS), cable alleys, cable gland plates in two half, i/c providing following switchgears / accessories as per specifications. |
| 7 | M.V. PANELIncomer-I & II04 Nos ACB 2500 A, 50 kA, 4 Pole, Microprocessor release Horizontal drawout typeof fault breaking capacity 50KA (Ics=lcu=Icw) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with Independent Electrical & manualspringclosing mechanism, Microprocessorrelease (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary interlocking with PLC auto controls with all protection i/eEarth fault, Under/Over Voltage, Under/Over Frequency, Current Unbalance, etc. and Real-time on-line display of measurements, Current : phase / neutral / earth, average, max, % loading, Voltage : Phase, Line and with communication port facility etc. Each Incomer shall have following Items :- i)Intelligent multi function digital meter to read V,A,kVA, KW, kVAR, PF, Hz etc with communication facility (RS485 port) and LED display with required Nos CTs, 2500/5 , 15 VA, class 0.5 and control circuit wiring with 2 Amp MCB for controling % THD and individual order Harmonics upto 15th order.ii)1 Set of Indication Lamps, LED type, R,Y,BPhase indicating lamp with 2 Amp MCB for controling.iii)1 Set of Indication Lamps, LED type for breaker \"ON\" ,\"OFF\",\"TRIP\" & spring chargedlamps with 2 Amp MCB for controling. iv) Digital Voltmeter of suitable range (to measure 0-500V), for 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB .v) Digital Ammeter of suitable range withfor 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB & suitable rating CT.Buscoupler01 Nos. 2500A, 50 kA, 4 Pole, (EDO) Air Circuit Breaker Horizontal drawout typeof fault breaking capacity 50KA (Ics=lcu =Icw upto 433V) Electrical Draw Out Motorised operated,Independent Electrical / manualspringclosing mechanism fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with neccessary Auxillary contact & MCB as per Drawing/specification.Buscoupler shall have -i) Phase Indication Lamps, LED type, for RYB with 2 Amp control MCB.ii) Breaker \"ON\" ,\"OFF\",& spring charged LED lampswith 2 Amp MCB for controlling.iii) Electrical & Mechnical Interlocking between both incomers & BuscouplerBusbars4P aluminium bus bars of3000 A capacity with heat shrinkable coloured sleeves incl. SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA for 1 sec.Outgoings14 Nos. MCCB, 400A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection.10 Nos. MCCB, 250A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection.6 Nos. 160A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection.6 Nos. 100 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection. Eachoutgoing shall have-1) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCB.2) On/OffLED indication lamp with 2 Amp control MCB.3) Necessary spreader terminals, rotary handle, suitable for mounting arrangement. |
| 8 | Switch Room 012 Nos. MCCB, 400A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection. fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with Independent Electrical & manualspringclosing mechanism, Microprocessorrelease (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary interlocking with PLC auto controls with all protection i/eEarth fault, Under/Over Voltage, Under/Over Frequency, Current Unbalance, etc. and Real-time on-line display of measurements, Current : phase / neutral / earth, average, max, % loading, Voltage : Phase, Line and with communication port facility etc.Each Incomer shall have following Items :- i)Intelligent multi function digital meter to read V,A,kVA, KW, kVAR, PF, Hz etc with communication facility (RS485 port) and LED display with required Nos CTs, 1250/5 , 15 VA, class 1.0 and control circuit wiring with 2 Amp MCB for controling % THD and individual order Harmonics upto 15th order.ii)1 Set of Indication Lamps, LED type, R,Y,BPhase indicating lamp with 2 Amp MCB for controling.iii)1 Set of Indication Lamps, LED type for breaker \"ON\" ,\"OFF\",\"TRIP\" & spring chargedlamps with 2 Amp MCB for controling. iv) Digital Voltmeter of suitable range (to measure 0-500V), for 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB .v) Digital Ammeter of suitable range withfor 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB & suitable rating CT.Buscoupler01 Nos. 400A, 35 kA, 4 Pole, microprocessorrelease with O/L, S/C & inbuilt E/F protection with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with neccessary Auxillary contact & MCB as per Drawing/specification.Buscoupler shall have -i) Phase Indication Lamps, LED type, for RYB with 2 Amp control MCB.ii) Breaker \"ON\" ,\"OFF\",& spring charged LED lampswith 2 Amp MCB for controlling.iii) Electrical & Mechnical Interlocking between both incomers & Buscoupler.Busbar4P aluminium bus bars of600 A capacity with heat shrinkable coloured sleeves incl. SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA for 1 sec.Outgoings2 Nos. MCCB, 250A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection.02 Nos. 160A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection. 06 Nos. 100 A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection. 10 Nos. 63A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection.Eachoutgoing shall have-1) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCB.2) On/OffLED indication lamp with 2 Amp control MCB.3) Necessary spreader terminals, rotary handle, suitable for mounting arrangement. |
| 9 | Switch Room 022 Nos. MCCB, 250A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection. fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with Independent Electrical & manualspringclosing mechanism, Microprocessorrelease (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary interlocking with PLC auto controls with all protection i/eEarth fault, Under/Over Voltage, Under/Over Frequency, Current Unbalance, etc. and Real-time on-line display of measurements, Current : phase / neutral / earth, average, max, % loading, Voltage : Phase, Line and with communication port facility etc. Each Incomer shall have following Items :- i)Intelligent multi function digital meter to read V,A,kVA, KW, kVAR, PF, Hz etc with communication facility (RS485 port) and LED display with required Nos CTs, 1250/5 , 15 VA, class 1.0 and control circuit wiring with 2 Amp MCB for controling % THD and individual order Harmonics upto 15th order.ii)1 Set of Indication Lamps, LED type, R,Y,BPhase indicating lamp with 2 Amp MCB for controling.iii)1 Set of Indication Lamps, LED type for breaker \"ON\" ,\"OFF\",\"TRIP\" & spring chargedlamps with 2 Amp MCB for controling. iv) Digital Voltmeter of suitable range (to measure 0-500V), for 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB .v) Digital Ammeter of suitable range withfor 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB & suitable rating CT.Buscoupler01 Nos. 250A, 35 kA, 4 Pole, microprocessorrelease with O/L, S/C & inbuilt E/F protection with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with neccessary Auxillary contact & MCB as per Drawing/specification.Buscoupler shall have -i) Phase Indication Lamps, LED type, for RYB with 2 Amp control MCB.ii) Breaker \"ON\" ,\"OFF\",& spring charged LED lampswith 2 Amp MCB for controlling.iii) Electrical & Mechnical Interlocking between both incomers & Buscoupler.Busbars4P aluminium bus bars of300 A capacity with heat shrinkable coloured sleeves incl. SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA for 1 sec.Outgoings02 Nos. 100 A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =25 KA) with inbuiltO/L & S/C protection.08 Nos. 63A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =25 KA) with inbuiltO/L & S/C protection.Eachoutgoing shall have-1) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCB.2) On/OffLED indication lamp with 2 Amp control MCB.3) Necessary spreader terminals, rotary handle, suitable for mounting arrangement. |
| 10 | Switch Room 032 Nos. MCCB, 400A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection. fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with Independent Electrical & manualspringclosing mechanism, Microprocessorrelease (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary interlocking with PLC auto controls with all protection i/eEarth fault, Under/Over Voltage, Under/Over Frequency, Current Unbalance, etc. and Real-time on-line display of measurements, Current : phase / neutral / earth, average, max, % loading, Voltage : Phase, Line and with communication port facility etc. Each Incomer shall have following Items :- i)Intelligent multi function digital meter to read V,A,kVA, KW, kVAR, PF, Hz etc with communication facility (RS485 port) and LED display with required Nos CTs, 1250/5 , 15 VA, class 1.0 and control circuit wiring with 2 Amp MCB for controling % THD and individual order Harmonics upto 15th order.ii)1 Set of Indication Lamps, LED type, R,Y,BPhase indicating lamp with 2 Amp MCB for controling.iii)1 Set of Indication Lamps, LED type for breaker \"ON\" ,\"OFF\",\"TRIP\" & spring chargedlamps with 2 Amp MCB for controling. iv) Digital Voltmeter of suitable range (to measure 0-500V), for 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB .v) Digital Ammeter of suitable range withfor 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB & suitable rating CT. Buscoupler01 Nos. 400A, 35 kA, 4 Pole, microprocessorrelease with O/L, S/C & inbuilt E/F protection with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS-13947-2 1993 as amended up-to-date complete with neccessary Auxillary contact & MCB as per Drawing/specification.Buscoupler shall have -i) Phase Indication Lamps, LED type, for RYB with 2 Amp control MCB.ii) Breaker \"ON\" ,\"OFF\",& spring charged LED lampswith 2 Amp MCB for controlling.iii) Electrical & Mechnical Interlocking between both incomers & Buscoupler. Busbars4P aluminium bus bars of600 A capacity with heat shrinkable coloured sleeves incl. SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 KA for 1 sec.Outgoings2 Nos. MCCB, 250A,4P, 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection.02Nos. 160A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =25 KA) with inbuiltO/L & S/C protection.06 Nos. 100 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =25 KA) with inbuiltO/L & S/C protection.08 Nos. 63 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =25 KA) with inbuiltO/L & S/C protection.Eachoutgoing shall have-1) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCB.2) On/OffLED indication lamp with 2 Amp control MCB.3) Necessary spreader terminals, rotary handle, suitable for mounting arrangement. |
| 11 | CCR PANELIncomer-I & II2 Nos. 400A, 4P MCCB,Microprocessor based release (Ics = Icu = 35kA) with inbuilt O/L , S/C & E/F protection as per specification. Each incomer shall have i) 1 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCBii) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCBiii) Electrical & Mechnical Interlocking between both incomers & Buscoupleriv) Digital Voltmeter of suitable range (to measure 0-500V), for 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB.v) Digital Ammeter of suitable range withfor 3 phase 4 wire operation with LED display and in built-in-selector switchcontrol with 2 Amp MCB & suitable rating CT.vi) Necessary spreader terminals, rotary handle, suitable for mounting arrangement.Buscoupler1 Nos. 400A 4P MCCB, Microprocessor basedrelease (Ics = Icu = 35kA) with inbuilt O/L , S/C & E/F protection as per specification and has following items:-i) 1 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCBii) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCBiii) Electrical & Mechnical Interlocking between both incomers & Buscoupler iv) Necessary spreader terminals, rotary handle, suitable for mounting arrangement.Busbars4P aluminium bus bars of600A capacity with heat shrinkable coloured sleeves incl. SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 35 KA for 1 sec.Outgoings4 Nos. 250A 4P MCCB , 35 kAwith adjustable setting , microprocessorrelease with O/L, S/C & inbuilt E/F protection.4Nos. 160A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection.6Nos. 100A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection.2Nos. 63A 4P MCCB with built in thermal magnetic release with adjustable thermal setting (Ics= Icu =35 KA) with inbuiltO/L & S/C protection. Eachoutgoing shall have-1) PhaseIndication Lamps, LED type, for RYB with 2 Amp control MCB.2) On/OffLED indication lamp with 2 Amp control MCB.3) Necessary spreader terminals, rotary handle, suitable for mounting arrangement. |
| 12 | D.G SYNCHRONISINGPANEL.Design, manufacture Supply, Installation, Testing and Commissioning of D.G Synchronising cum PCC Panel with AMF for 3 nos. DG Sets (2 nos. x 750 KVA and 1 no. x 500 KVA), load sharing & power distribution facilities, cubicle type, made of 2 mm thick sheet steel, totally enclosed, IP 4X, free standing, floor mounting, dust and vermin proof ,indoor, compartmentalised, powder coated painting suitable for operation on 3 Phase and neutral, 415v, 50 Hz AC supply from D.G Sets (individual or in sync. & parallel load sharing mode as per load requirements) & Mains power with Al. busbars extensible on both sides, interconnections including supply & installation of following items/components (but not limited to) and as per Technical specification & site requirement complete as required:DG INCOMER- 1 & 21250 A TP EDO ACB (50kA) with built-in Microprocessor Based Release for (O/C, S/C, E/F Protection) with RS485 communication port facility, closing coil, Under Voltage Release - 2 No.800 A Neutral isolation contactor -2 Nos., Shunt release -2 No., Breaker Control Switch with (T-N-C) -2 No., Auto/Manual Selector Switch -2 Nos., Auxiliary Contactor 2NO+2NC - 4 Nos.Intelligent multi function digital meter to read V,A,kVA, KW, kVAR, PF, Hz etcwithcommunicationfacility(RS485port),THDandIndividualorder harmonics upto 31st Order, Cl.-1.0, 96x96sq.mm., Flush Mounted - 2 No.Digital energy meter with RS-485 comm. Port CL1.0 -2 No.CTs 1250/5A, Class-0.5, 15VA for Metering (Resin Cast) -6 No.CTs 1250/5A, Class-PS, 15VA for Metering (Resin Cast) -8 No.Single Phase Preventer - 2 No.Phase Reversal Relay (Phase Sequence Relay) - 2 No.3Phase,4WireUnder&OverVoltageRelay(Auto/ManualReset,TripTime & Power ON Delay 1-10 Sec.) OV/UV - Adjustable - 2 No.Restricted Earth Fault Relay -2 No.Indicating lamps - R/Y/B/ON/OFF/TRIP/Spring Charged - 14 No.2A SP Control MCB (10kA), C-Curve -16 No., SPD - Class B - 2 No., 63A TP MPCB -2 No.DG INCOMER-3630A TP EDO ACB (50kA) with built-in Microprocessor Based Release for (O/C,S/C,E/FProtection)(andwithRS485communicationportfacility, closing coil, Under Voltage Release - 1 No.400 A Neutral isolation contactor -1 Nos., Shunt release -1 No., Breaker Control Switch with (T-N-C) -1 No., Auto/Manual Selector Switch -1 Nos., Auxiliary Contactor 2NO+2NC - 2 Nos.Intelligent multi function digital meter to read V,A,kVA, KW, kVAR, PF, Hz etcwithcommunicationfacility(RS485port),THDandIndividualorder harmonics upto 31st Order, Cl.-1.0, 96x96sq.mm., Flush Mounted - 1 No.Digital energy meter with RS-485 comm. Port CL1.0 -1 No.CTs 630/5A, Class-0.5, 15VA for Metering (Resin Cast) -3 No.CTs 630/5A, Class-PS, 15VA for Metering (Resin Cast) -4 No.Single Phase Preventer - 1 No.Phase Reversal Relay (Phase Sequence Relay) - 1 No.3Phase,4WireUnder&OverVoltageRelay(Auto/ManualReset,TripTime & Power ON Delay 1-10 Sec.) OV/UV - Adjustable - 1 No.Restricted Earth Fault Relay -1 No.Indicating lamps - R/Y/B/ON/OFF/TRIP/Spring Charged - 7 No.2A SP Control MCB (10kA), C-Curve -8 No., SPD - Class B - 1 No., 63A TP MPCB -1 No.BUSCOUPLER2500AFPEDOACB(50kA)WITHOUTPROTECTIONRELEASE, with Under Voltage Release- 1 No., Breaker Control Switch with (T-N-C) - 1 No., Auto/Manual Selector Switch - 1 No., Auxiliary Contactor 2NO+2NC - 2 No., Indicating lamps - ON/OFF/TRIP - 3No., 2A SP Control MCB (10kA), C-Curve - 7No.BUSBARCommon bus ,main outgoing Bus bars of 3000 Amps, TPN, Aluminium Busbars.INTERLOCKINGMicroPLCInterlockingamong incomersfromD.G.Sets(3Nos),Mains power (2 No.) and 1no. Bus Coupler - 1 Set as required.OUTGOINGS2500 A TP EDO ACB (50kA) with built-in Microprocessor Based Release for (O/C, S/C, E/F Protection) with RS485 communication port facility - 2 No.Shunt release -2 No., Breaker Control Switch with (T-N-C) -2 No., Auto/Manual Selector Switch -2 Nos., Auxiliary Contactor 2NO+2NC - 4 Nos.Digital Ammeter with built-in selector switch CL 0.5 -2 No.CTs 2500/5A, Class-0.5, 15VA for Metering (Resin Cast) -6 No.Indicating lamps - ON/OFF/TRIP - 6 No.2A SP Control MCB (10kA), C-Curve -14 No.AUTO SYNCHRONISING FOR 3 NOS. DG SETS:-GensetController - 3Set, MICROPLC FOR LOAD MANAGEMENT - 3Set, DG Set Selector Switch - 1 No., Communication cabling for CAN protocol - as required. Instrumentation cabling - as required.Voltage monitoring devices, Manual/PLC/ Selector Switch - 1 No.,12-Window Annunciator - 3 No., Mimic diagram-1 Set, Engine Cranking relay - 6 No., Battery Charger with Ammeter & Voltmeter - 3 Set, Power Supply 24V DC - 3 No., UPS 1KVA - 1 No., Aux. Relays - 1 Set, Indicating lamps - 1 Set, Push Button - 1 Set, Hooter - 3 No., Control MCB - 1 Set.The complete panel shall be of TTA TYPE& comply to IEC : 61439& shall be complete in all respect for sync. operation, load sharing, load management, AMF operation & control of 2 X 750 KVA + 1X 500 KVAD.GSets&powerdistributionprovisionsasper technical specification & site requirements etc as required. |
| 13 | Hybrid Panel 200 KVAR(Automatic Power Factor Correction & Harmonic Filters)Design, fabrication, assembly, wiring, supply, erection , testing and commissioning of Hybrid Solution consisting of APFC Panel and AHF, to achieve 0.99 Lag and THDI / THD Voltage within IEEE 519 limits.The Hybrid panel should have an incomerof 400 Amps,4 Pole,Horizontal draw out type ACB of faultbreakingcapacity50KA(Ics=lcu=Icw=50KAfor1secsat440V),TheHybrid Panelshouldbe certified as per IS16636 and IEC 61921, The capacitor bank shall comprise of capacitor units rated at 525 volt, 14% de tuning reactors, PF controllers, circuit breakers etc.The AHF should be 3 Phase, 4 Wire System. The switching device of the active compensation system shall be 3 / 2 level IGBT based. The active compensation system should filter harmonics from 2nd to 51st individual harmonic order and shall be selectable for the entire range. The active compensation systemshould also have feature to improve PF correction. The active compensation systemshould have a Multi master and Master Slave operation. The active compensation system shall have Auto de- ratingfeatureifambienttemperature exceeds 50 DegC.Response timeshallbe100 microSecor less.Thereactorshallbefittedwithatemperaturesensitiveswitchtotripcircuitsincaseofhigh operating temperature (Panel shall be of Form 3b compartmentalization).ThePassivesectionshallbemicroprocessororintegratedDSPcontrollerbasedforActiveand Passive section and shall be able to sense the reactive current requirement of the network and shall switch ON / OFF the required stages of a capacitor bank. The Capacitor Bank shall be of type tested design as IS 16636.Theheavydutycapacitorunitsshallberatedat525V.Thecapacitorandreactorcombination representsaseriesresonantcircuit.Thecircuitshouldbetunedsuchthattheseriesresonant frequency should be below the lowest harmonic order expected to be present in the electrical network. If the lowest harmonic order expected to be present in the electrical network is likely to the 150Hz (3rd orderharmonics)thentheseriesde-tuningreactorsshouldbeof135Hz(2.7tuningorder)witha relative impedance 14%.TheHybridSolutionshouldcompriseofActivefilteri.e.200 AandPassivei.e. kVAr.Incomer of Hybrid Panel should be 400 A, 35kA, 4 Pole MCCB.-TheActiveharmonicfiltershouldhavea 250 Amp MCCB. -· The14%de-tunedcapacitorbankwithcapacitordutycontactorsuitablefor followingstepratings:2 nos. x 50 KVAR + 2 nos. x 25 KVAR + 5 nos. x 10 KVAR 50 KVAR- 02 No. MCCB, 100 Amps, TP, (Ics = Icu = 35 KA) with thermal magnetic release. 25 KVAR - 02 No. MCCB, 63 Amps, TP, (Ics = Icu = 35 KA) with thermal magnetic release 10 KVAR - 05 No. MCB, 25 Amps, TP.-Thede-tunedcapacitorbankshouldhaveIntegratedDSPcontrollerwhichshallcontrolboththe capacitorsaswellasActiveFilter.HeavydutyCapacitorshallbeasperMPPlowlossasper standards.- Each stage of the capacitor bank should have suitable rating fuse protection.- The Solution should havesurge arrestors and over temperature protection.The system should be with compatible with Grid Power OR D.G. Power Supply.The capacitor banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted along with the offer.The Hybrid Solution described as above complete in all respect as per specification enclosed, up to theentiresatisfactionofengineerInCharge.Switchgearsshallbeasperfollowingsandasper specifications.LED indication lamps for RYB, breaker \"ON/ OFF/ TRIP with 2Amp control MCBs Set of Digital flush type calibrated Intelligent multifunction meters (with communication port), class - 0.5 accuracy , showing V, A, PF, Hz, KW,KWH,KVAR , Total harmonic distortion with 3 Nos.castresincurrenttransformersofdualcoreCT\"sof400 /5Ampratio,15VAClass0.5 metering.Bus Bar400 Amps with heat shrinkable coloured sleeves having 50% neutral bus as that of phase i/c DMC / SMC bus bars supports at required intervals complete as required.Set of Digital flush type calibrated Intelligent multifunction meters (with communication port), class - 0.5 accuracy , showing V, A, PF, Hz, KW,KWH,KVAR , Total harmonic distortion with 3 Nos.castresincurrenttransformersofdualcoreCT\"sof400 /5Ampratio,15VAClass0.5 metering. |
| 14 | Supply and laying of LT Cable |
| 15 | Supply of following size1.1 KV grade multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable as perIS : 7098:1988 (Part 1) with upto date amendment complete as required. |
| 16 | 4 X 16 sq. mm |
| 17 | 4 X 35 sq. mm |
| 18 | 3½ X 70 sq. mm |
| 19 | 3½ X 185 sq. mm |
| 20 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required. |
| 21 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 22 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required. |
| 23 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 24 | Laying of additional 1 no. 63 mm dia OD DWC Pipe along with all accessories like sockets, bends, couplers etc. complete with fitting, cutting and jointing etc. in existing trench (75 cm below ground level) complete as required. |
| 25 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on surface of wall/ culvert etc. as required. |
| 26 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 27 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 28 | Above 95 sq. mm and upto 185 sq. mm. (clamped with 25/40x3mm MS flat clamp) |
| 29 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size in the existing RCC/ HUME/ METAL/ HDPE pipe as required. |
| 30 | Upto 35 sq. mm |
| 31 | Above 35 sq. mm and upto 95 sq. mm |
| 32 | Above 95 sq. mm and upto 185 sq. mm |
| 33 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonary open duct as required. |
| 34 | Upto 35 sq. mm |
| 35 | Above 35 sq. mm and upto 95 sq. mm |
| 36 | Above 95 sq. mm and upto 185 sq. mm |
| 37 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 38 | 4 X 16 sq. mm (28mm) |
| 39 | 4 X 35 sq. mm (32mm) |
| 40 | 3½ X 70 sq. mm (38mm) |
| 41 | 3½ X 120 sq. mm (45mm) |
| 42 | 3½ X 185 sq. mm (57mm) |
| 43 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 44 | 3½ X 185 sq. mm |
| 45 | Dismantling of the following Electrical panels of oldPower house and safely shifting to AAI store or designated space with in the permises as directed, complete as required. |
| 46 | MV EssentialPanel Dimensions 6400 MM x1000 MM x 2150 MM |
| 47 | MV Non EssentialPanel Dimensions 6900 MM x1400 MM x 2450 MM |
| 48 | DG Synchonous Panel Dimensions 1600 MM x750 MM x 18000 MM |
| 49 | CapacitorPanel160 KVAR Dimensions 2000 MM x1000 MM x 2150 MM |
| 50 | HT PANEL (Oil Type) 11 KV Dimensions 1700 MM x1020 MM x 1900 MM |
| 51 | Transformer 750 KVA,11/0.433 KV |
| 52 | DG Set 320 KVA |
| 53 | SITC of following AluminumSandwi?ch type Busduct suitable for indoor & outdoor application (IP-55 & 66) including supports and accessories? etc andas per technical specifications avaliable in this tender document complete as required. |
| 54 | 2500A, 100% Neutral 100 kA 415V TPN AluminumSandwi?ch type Busduct IP-55 suitable for indoorapplication. |
| 55 | 1250A, 100% Neutral 100 kA 415V TPN AluminumSandwi?ch type Busduct IP -66suitable foroutdoor application. |
| 56 | 1250A, 100% Neutral 100 kA 415V TPN AluminumSandwi?ch type Busduct IP-55 suitable for indoorapplication. |
| 57 | Supply and laying of HT Cable |
| 58 | Supply of 3 Core x 185 Sq. mm., 33 KV grade XLPE insulated & PVC sheathed, armoured, Aluminium conductor cable conforming to IS : 7098:1988 (Part II) with the upto date amendment complete as required. |
| 59 | Supply of 125 MM outer dia PE-100 grade PN 10 rated HDPE pipeconfirming to Indian Standard IS 4984:2016 with latest amendment,complete with all associated assessorieslike end cap etc as per site requirment complete as required. |
| 60 | Laying of 125 MM outer dia PE-100 grade PN 10 rated HDPE pipe in ground upto 3 mtr depth as per site requirment through HDD(Horizontal drillinbg ) method including joints by welding ,fixing necessary acceserioes like end plugs etc ,providing suitable pull wire for pulling cales as required |
| 61 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 33 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 62 | Above 120 sq. mm and upto 400 sq. mm |
| 63 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 33 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 64 | Above 120 sq. mm and upto 400 sq. mm |
| 65 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 33 KV grade as required : |
| 66 | 3 X 185 sq. mm |
| 67 | Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 33 KV grade as required : |
| 68 | 3 X 185 sq. mm |
| 69 | Earthing |
| 70 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 71 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 72 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 73 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 74 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia medium class G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 75 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia medium class G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |