Tender For Additional/Alternator To Building No P-33 At Air Force Station Udhampur, udhampur-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Additional/Alternator To Building No P-33 At Air Force Station Udhampur. Submission Date for this Tender is 11-01-2024. Building Work Tenders in udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

41114855
Corrigendum : Tender For Additional/Alternator To Building No P-33 At Air Force Station Udhampur
Open Tender
Indian
Jammu And Kashmir
udhampur
11-01-2024

Tender Details

Tender For Additional / Alternator To Building No P-33 At Air Force Station Udhampur ; 2 Fibrette Tile Of Wood Fiber Cement Composite 1Mm Width Wood Fiber 20 / 25 Mm Thick ( Accoustical Wall Panel ) Of Size 600X600 / 600X1200mm Having Excellent Noise Absorption Of 1 Nrc As Per Iso : 354, Density 400 Kg / M3, Meets Fire Ratings As Per Bs 476 Part 5, 6, 7 Class 1 And P, Water Resistance And Thermal Insulated. Instaled On Gi Stud 600X600 Mm Centre To Centre 2400Mmx50 Web Thickness 0.5Mm, Flanges 15 And 50Xx Fully Knurled Giving It High Strength, Hot Dipped Galvanised Steel With 120 Gsm Zinc Coating With A Backing Of 50 Mm 1000 Gsm Thick Absorb Wool Tested As Per Fire Resistance Is 15061 For Excellent Results Complete All As Specified And As Directed By Engr-In-Charge.Notes : ( I ) Colour As Approved By The Ge. ( Ii ) Work To Be Executed Upto Height Of 7M From The Floor Level. Unit Rates Are Deemed To Be Included In The Quoted Rates And Necessary Required Arrangement For The Same Are Deemed To Be Included In The Quoting Rates. Nothing Extra Shall Be Admissible On This Account. ( Iii ) Contractor Will Give The Warranty From Manufacturer On An Affidavit For Minimum Period Of 2 Year Or ManufacturerS Warranty Period Which Ever Is Higher. 3 M&L For Brick Work With Sub Class B Bricks Using Old Size Bricks, Straight Or Curved On Plan Exc 6 M Mean Radius Built In Cm 1:4 Complete All As Specified And As Directed. 4 M&L For Vitrified Ceramic Tiles Light Shade 10Mm Thick ( Square / Rectangular ) Polished, Area Of Each Tiles Not Exceeding 0.36 Sqm But Not Exceeding 0.42Sqm, In Floors Etc, Set And Jointed In Neat Cement Slurry And Pointed In White Or Coloured Cement Match Including 15Mm Thick Screed Bed In Cm 1:6. 5 M&L For Glazed Ceramic Tiles In Vertical Surface 350X250x7mm / 450X350x7mm Thick Set And Jointed In Neat Cement Slurry And Pointed In White Or Colour Cement To Match Including 10 Mm Thick Screed Bed Completed All As Specified And As Directed. 6 S&F For Powder Coated Aluminium Doors Shutters, ( Thickness Of Powder Coating Not Less Than 50 Micron ) Aluminium Section Weighing Exc 0.55 Kg / M Including Necessary Joining Cleats, Glazing Clips Rubber Neoprene Packing, Handle 2 Nos In Each Door, Fixed With Floor Hinges Anodised Aluminium Snap Beading Screws Etc Completed All As Specified And As Directed. 7 S&F Power Coating Aluminium ( Minimum Thickness Of Powder Coating 50 Micron ) Bar For Doors, Window, Ventilators And Partitions ( Fixed Positions ) With Extruded Built Up Standard Tubular Section / Appropriate Z Section And Other Section Of Approved Make Conforming To Is: 733 And Is: 1285, Fixing With Dash Fasteners Of Required Dia And Size Incl Necessary Filling Up The Gaps At Junctions, I.E. At Top, Bottom And Sides With Required Epdm Rubber / Neoprene Gasket Etc Aluminium Sections Shall Be Smooth, Rust Free, Straight Mitred And Jointed Mechanical Whereever Required Incl Cleat Angle Aluminium Snap Beading For Glazing / Panelling, Cp Brass / Stainless Steel Screw, Complete All As Specified And As Directed. 8 S&F Aluminium Power Coated Of Any Colour ( Thickness Of Powder Coating Not Less Than 50 Micron ) , In Frame For Doors, Window, Ventilators, Partition Wall Etc, With One Or More Rebates, Shutters, Grills Including Joining Cleat For Fixing Etc. Complete All As Specified & Directed By Engr-In-Charge. 9 S&F 5.5 Mm Thick Ordinary Quality Glass Fixed To Doors, Window And Partion But Exc 0.5 Sqm In A Each Pane Complete All As Specified And Directed. 10 S&F Rubber Beading For Fixing Of Glass For Partition Complete All As Specified And Directed. 11 S&F Alum Snap Beading For Fixing Of Glass For Partition Complete All As Specified And Directed. 12 S&F Aluminium Composite Panel ( Acp Sheet ) 5 Mm Thick Both Side Laminated Fixed In Position Side Partition Complete All As Specified And Directed. 13 S&F Roof Trusses ( Framed ) , Purlins, Crane Gantries, Rails And Fastenings And Heavy Bracket Framing ( Beam, Tee, Angle Channel Or Falt Sections ) Incl Distance Pieces, Cleats Etc Similar Works And Fixing Complete Fe-410W ( Gde E250 Quality A ) Incl Structural Steel Is Painted One Shop Coat Zinc Chromate Primer Paint ( Incl Preparation ) Comlete All As Specified And As Directed. 14 Cutting Chases, Pinning In, Making Good To Facings Where Required And Pointing In Cement Mortar 1:3 To Ends Or Edges Of Landing Steps Cillis Shelves Linjtels Etc And Making Good In Cement Concrete 1:2:4 Type B-1 Complete All As Specified And As Directed. 15 Cutting Holes In Brick Walls Built In Cement For Exceeding Half Brick Wall But Not Exceeding One Brick Wall For Inserting Holdfasts Or Similar Work Making Good Dismantling Proportion In Cement Mortar 1:3 Or Cement Concrete 1:2:4 Type B-1 Complete All As Specified And As Directed. 16 Excavating In Post Holes ( Or Similar Holes ) Each Not Exceeding 0.5 Cum Getting Out, Returning Filling In And Ramming Earth Or Broken Rubble Mixed With Earth Around, In Layers Not Exceeding 25 Cm, Watering And Removing Surplus Soil To A Distance Not Exceeding 50 M And Making Good Surface Hard / Dense Soil. 17 M&L For Pre Painted Galvalume Aluminium Zinc Coating Gi Based Corrugated Steel Sheet 0.50 Mm Thick Of An Colour Having Tensile Strength Of 550 Mpa As In Roof Covering / Cladding To Wall, Fixed With Self Tapping Screws As Specified. 18 S&F Pre-Painted Galvalume Aluminium Zinc Coating Gi Based Plain Steel Sheeting 0.50 Mm Thick Of Any Colour Having Tensile Strength Of 550 Mpa As In Roof Covering / Cladding To Wall Fixed With Self Tapping Screws Complete All As Specified And As Directed. 19 Preparation Of New Or Previously Untreated Steel Surfaces Of Any Description Over 10 Cm Width Or Girth, Applying Two Coats Of Synthetic Enamel Paint Over One Coat Of Red Oxide Primer Complete All As Specified And Directed By Engr-In-Charge. 20 M&L For Pcc 1:2:4 Type B1 Using 20 Mm Graded Stone Aggregate For Emedding Ms Pipes Complete All As Specified And As Directed By Engr-In-Charge. 21 Surface Excavation Not Exceeding 30 Cm Deep And Averaging 15 M Deep And Getting Out Only Type Of Cement Complete All As Specifed And As Directed By Engr-In-Charge. 22 Removing Excavated Material Not Exceeding 1.50 Km Depositing Where Directed. 23 M&L For Hardcore Of Broken Stone Of Guage Not Exceeding 63 Mm Deposited, Spreaded & Levelled In Layers Not Exceeding 15 Cm Thick Including Watering And Ramming Etc Complete All As Specified And As Directed By Engr-In-Charge. 24 M&L For 100 Mm Thick Pcc 1:4:8 Type D-2 ( 40 Mm Graded Stone Aggregate ) As In Sub Base Of Flooring Complete All As Specified And As Directed By Engr-In-Charge. 25 M&L For Providing 50 Mm Thick Cement Concrete 1:3:6 Type C-1 Using 20Mm Graded Stone Aggregate As In Plinth Protection Laid In Alternate Bays ( Not Exceeding 2.0 Sqm Each ) And Finished Even And Smooth Without Using Extra Cement And Providing Joints Through The Thickness Of The Plinth Protection Filled With Mastic Filling Compressing One Part Of Bitumen 85 / 25 Graded And Three Parts Of Sand By Weight Complete All As Specified And As Directed. 26 M&L For Providing 100 Mm Thick Cement Concrete Type B-2 1:2:4 ( 40 Mm Graded Stone Aggregate ) As In Sub Base Of Floor Complete All As Specified And As Directed. 27 M&L For Granite ( Of Any Type ) Work ( Table Rubbed And Polished ) In Steps, Jambs, Pillars, Window Cills, Cooking Platforms And Like Cm ( 1:4 ) Including Pointing In White Cement 1;2 Using Marble Dust With Admixture Of Pigment To Match With Shade Of Granite Complete Including Screed Bed Bedding Layer Of 15 Mm Thick In Cm 1:4 Complete All As Specified And Polishing Complete. 28 M&L For Rcc Type B1 1:2:4 ( 20 Mm Graded Aggregate ) Slabs Supported On Walls, Beams And Columns In Floors, Roofs, Landings, Balconies, Canopies, Deck Slabs And In Shelves And The Like Complete All As Specified And Directed. 29 M&L For Mild Steel Tmt Bars 10 Mm Dia And Over, Cut To Length, Bent To Shape Required, Including Cranking, Bending Spirally For Hooping For Columns, Hooking Ends And Binding With And Including Mild Steel Wire ( Annealed ) Not Less Than 0.9 Mm Dia Or Securing With Clips Complete All As Specified And Directed. 30 M&L For Mild Steel Tmt Bars 5 Mm Dia And Over Upto And Including 10 Mm Dia In Stirrups, Spacers And Binders Complete All As Specified And Directed. 31 M&L For Formwork To Soffits Of Suspended Slabs Such As Roof Slabs, Floor Slabs, Landings And Similr Work; Not Exceeding 200Mm Thick ( Horizontal Or Sloping ) & Fair Finished Concrete Surface Complete All As Specified And Directed. 32 M&L For Rendering 10 Mm Thick On Fair Faces Of Brick Work Or Concrete Surfaces Finished Even And Smooth ( Without Using Extra Cement ) In Cm 1:6 Complete All As Specified And Directed. 33 M&L For Preparing Newly Plastered Surfaces Of Wall And Applying 2 Coat Of Whitewash Complete All As Specified And Directed. 34 S&F 18 / 19 Mm Thick Termite Proof, Chemically Well Pressed, Block Boards, Grade 1 Quality, Exterior Grade, Commercial Type, Fixed With Screws To Timber Frame Work, Including 1 Mm Thick Pvc Moulding All Around Including Edging, Complete All As Specified And Directed. 35 S&F 0.9 Mm Thick Decorative Laminate Type 1 Of Surface Finish, Colour And Pattern As Approved, Fixed With Approved Adhesive As Per ManufacturerS Instructions Complete All As Specified And Directed. 36 S&F 100 Mm Brass Handles, Cast Type, Polished Bright Complete All As Specified And Directed. 37 S&F 30 Mm ( Width Of Flaps ) Continuous ( Piano ) Hinges Of Mild Steel, Bright Finish Complete All As Specified And Directed. 38 S&F Mild Steel Screw Bolt 5 Mm To 10 Mm Dia Machine Made With Hexagonal Or Square Heads At One End And Screwed The Other End With Washer And One Hexagonal Or Square Not Exceeding 5 Cm And Not Exceeding 10 Cm Long Complete All As Specified And Directed. 39 M&L For Providing And Fixing Stainless Steel ( Gde 304 ) Railing Made Of Hollow Tunes, Channels Plates Etc. Including Welding, Grinding, Buffing, Polishing And Making Curvature ( Where Ever Required ) And Fitting The Same With Necessary Accessories And Stainless Steel Dash Fasteners, Stainless Steel Bolts Etc. Of Required Size, On The Top Of Floor Or The Side Of Waist Slab With Suitable Arrangement Complete All As Specified And Directed. 40 E / M Portion 41 M&L Earthing Complete With Copper Earth Plate Electrode Of Size 60 Cm X 60 Cm X 3.15 Mm Thick As Earth Electrode Burried Directly In Ground ( Earth Pit Not Less Than 2.25 Meter Deep Below Ground Level ) With Top Edge Of The Earth Plate Not Less Than 1.5Mtr Below Ground Level Using Copper Earth Strip 20 X 3 Mm Dia As Earth Continuity Conductor Connected To Earth Plate By Means Of Copper Thimbles, Nuts, Bolts, Washers Including Brazing Etc Of Earth Electrode And Earth Wire By Means Of Welding, All As Directed Including Providingwatering Pipe 20Mm Dia With Wire Mesh And Funnel At Top, Earth Pit Andpit Cover Made Of Ms Sheet 2 Mm Thick Duly Fixed To Angle Iron Frame With Hinges Of Appropriate Size By Welding And Having Locking Arrangement, Adequate Quantity Of Charcoal Dust And Salt All Around The Earth Plate, Earth Work In Any Type Of Soil , Removing Surplus Excavated Material All As Required At Site And As Specified In Ep No 3 Of Mes Ssr Part-I ( 2009 ) Directed By Engineer-In-Charge Including Testing On Completion. . 42 Earth Continuity Conductor 20 X 3.00 Mm Copper Strip Or Main Earthing Lead Fixed To Walls On Batten Or Recess Or Chassis Or Buried In Ground Or Drawn In Conduit / Pipe Or Fixed To Poles Or Any Other Indicated Situation For Loop Earthing Etc Complete All As Specified And Directed By Engr-In-Charge 43 Supply And Fix For Pcc Block Size 10Cmx10cmx10cm Made Of 1:2:4 Cement Agrigate 20Mm For Running Of Earth Strip Overtop Surface All Including Fixing Of Earth Strip Wiring Clamps, Screw, Nut Bolt Bracket Etc All As Directed By Engineer In Charge. Note : Block Shall Be Constructed On Site Shall Be Attened To Roof Surface Using Pcc / Cement Etc. 44 S&F Gi Tubes, Medium Grade, Galvanised, With All Fitting Laid In Walls / Trenches Of 40Mm Dia Complete All As Specified & Directed . 45 Supply And Fixing Dmc Insulator Suitable Gi / Copper Strip As Ground Requied With Excellent Materials Strangth, Seamless Finish, Durable , Weather Proof Heat Resistant Including Sitable Size Of Hole Fastner, Screw , Nut Bolts And Washers Etc Complete All As Specified And As Direcetd By Engr-In-Charge. 46 M&L For Point Wiring Complete With Pvc Insulated And Unsheathed Cable 1.5 Sqmm ( Nominal Area ) Isi Marked Multi-Stranded Copperconductor Single Core Including Isi Marked 20Mm Dia Medium Grade Pvc Conduit For Point Wiring Concealed In Wall / False Ceiling / Surfaceconduit / Casing Caping With Pressed Steel Concealed Sunken Boxes Not Less Than 1.6Mm Thick Of Reqd Size ( Factory Painted ) And With Top Cover 3 Mm Thick Of Hylam Sheets Of Required Colour, Painting Sunken Boxes Inside And Out Side With One Coat Of Red Oxide Primer Completeincluding 1.5 Sqmm Pvc Insulated And Unsheathed Isi Marked Copper Cable To Common Earth Connected To Earth Dolly Colour Coding Of Cable As Per Ie Rulecompleteall As Specified & Directed. [ Make Of Cable - Finolex / HavellS / Anchor / Kei / Polycab ] 47 M&L For Point Wiring Complete With Pvc Insulated And Unsheathed Cable 2.5 Sqmm ( Nominal Area ) Isi Marked Multi-Stranded Copperconductor Single Core Including Isi Marked 20Mm Dia Medium Grade Pvc Conduit For Point Wiring In Concealed In Wall / False Ceiling / Surfaceconduit / Casing Caping With Pressed Steel Concealed Sunken Boxes Not Less Than 1.6Mm Thick Of Reqd Size ( Factory Painted ) And With Top Cover 3 Mm Thick Of Hylam Sheets Of Required Colour, Painting Sunken Boxes Inside And Out Side With One Coat Of Red Oxide Primer Completeincluding 2.5 Sqmm Pvc Insulated And Unsheathed Isi Marked Copper Cable To Common Earth Connected To Earth Dolly Colour Coding Of Cable As Per Ie Rulecompleteall As Specified & Directed. [ Make Of Cable - Finolex / HavellS / Anchor / Kei / Polycab ] 48 M&L Switch Piano, Flush Type, 5 Amps Single Pole, One Way 49 M&Lswitchsocketcombination3 Pin, Flush Type, 16 Amps . 50 M&L Of Ceiling Rose 3 Phase / Pvc / Polycarbonate, Isolated Bodycomplete All As Specified And As Directed.. 51 M&Lsub Main Wiring Using Approved Colour Coding As Per Is With Two Single Core, Pvc Insulated, Unsheathed Frls Multistranded Copper Conductor Of Size 1000 Sqmm ( Nominal Area ) 1100 Volts Grade And One Single Core, Pvc Insulated, Unsheathed Frls Multistranded Copper Conductor Of Size 10.00 Sqmm ( Nominal Area ) 1100 Volts Grade Cable As Earth Wire Including Suitable Size Of Pvc Conduit Drawn Through Rigid Concealed In Wall / False Ceiling / Surfaceconduit / Casing Capingand Connected To Main Board And Making Good Disturbed Surface Complete All As Specified And As Directed.Make Of Conductor : Havells / Polycab / Keinote: Two Runs Each Of 10.00 Sqmm Main Cable Andone Rm Of 10.00 Sqmm Cable As Earth Wire Together Alongwith Conduit Shall Be Considered As 1 Running Metre For Payment Purpose. 52 M&Lsub Main Wiring Using Approved Colour Coding As Per Is With Two Single Core, Pvc Insulated, Unsheathed Frls Multistranded Copper Conductor Of Size 6.00 Sqmm ( Nominal Area ) 1100 Volts Grade And One Single Core, Pvc Insulated, Unsheathed Frls Multistranded Copper Conductor Of Size 6.00 Sqmm ( Nominal Area ) 1100 Volts Grade Cable As Earth Wire Including Suitable Size Of Pvc Conduit Drawn Through Rigid Concealed In Wall / False Ceiling / Surfaceconduit / Casing Capingand Connected To Main Board And Making Good Disturbed Surface Complete All As Specified And As Directed.Make Of Conductor : Havells / Polycab / Keinote: Two Runs Each Of 6.00 Sqmm Main Cable Andone Rm Of 6.00 Sqmm Cable As Earth Wire Together Alongwith Conduit Shall Be Considered As 1 Running Metre For Payment Purpose. 53 M&Lsub Main Wiring Using Approved Colour Coding As Per Is With Two Single Core, Pvc Insulated, Unsheathed Frls Multistranded Copper Conductor Of Size 4.00 Sqmm ( Nominal Area ) 1100 Volts Grade And One Single Core, Pvc Insulated, Unsheathed Frls Multistranded Copper Conductor Of Size 4.00 Sqmm ( Nominal Area ) 1100 Volts Grade Cable As Earth Wire Including Suitable Size Of Pvc Conduit Drawn Through Rigid Concealed In Wall / False Ceiling / Surfaceconduit / Casing Caping And Connected To Main Board And Making Good Disturbed Surface Complete All As Specified And As Directed.Make Of Conductor : Havells / Polycab / Keinote: Two Runs Each Of 4.00 Sqmm Main Cable Andone Rm Of 4.00 Sqmm Cable As Earth Wire Together Alongwith Conduit Shall Be Considered As 1 Running Metre For Payment Purpose. 54 Supply And Fixing Led Street Light Fitting 35 Watt 6500K Pf >.90 Efficency 100Lm / W 230 V Ac Outdoor Type With High Pressure Die Cast Aluminum Hosing And Heat Resistantcomplete With Driver, Lampfixing Of Wall, Pole, Buildingwith Impact And Corrosion Resistant Including Thermal Management In Multiple Optics Complete With Ip 65 Protectioncomplete All Asspecified And As Directed. 55 Street Light Bracket Made Out Of 30 / 32 Mm Dia Gi Light Grade Tubing Not Less Than .75 Mtr Long Bend To Shape Including Pole Clamps / Fastners Clips Nailsmade Outflat Iron And Nuts, Bolts And Washers Etc Complete All As Specified And Directed. 56 M&Lsheet Metal Enclosures For Single Pole And Neutral Enclosure With A Two Pin And Earth Plug And Socket Complete With Single Pole Mcb 32 / 20 Amp 240 Voltcomplete All As Specified And As Directed. 57 M&Lsheet Metal Enclosures For Dbs Spn 8 Wayflush Mounted Double Door Including Accessories Therein And Disposing Off Complete All As Specified And Directed. 58 M&Lsheet Metal Enclosures For Dbs Spn 12 Wayflush Mounted Double Door Including Accessories Therein And Disposing Off Complete All As Specified And Directed. 59 M&L Of Mcb Spn 63 Amps, 240 Volts, Having Breaking Capacity 10 Ka, C Charactersticcomplete All As Specified And As Directed. 60 M&L Mcb Spn40 Amps, 240 Volts, Having Breaking Capacity 10 Ka, C Characterstic Complete All As Specified And As Directed. 61 M&Lmcb Sp 6-32 Amps, 240 Volts, Having Breaking Capacity 10 Ka, C Characterstic Complete All As Specified And As Directed. 62 M&L For Mcb Tpn40-100 Amps, 415 Volts, Having Breaking Capacity 10 Ka, C Characterstic Complete All As Specified And As Directed. 63 M&L Forvtpnvertical Three Phase Distribution Board, Vtpn, 4 Way 440 Volts Having Ip-54Isolated Busbar Assembly Ik 09 Mechnical Impact Strength Door Earthing Protection, Double Door With Provision For Fixing Ofmccbs As Incomer Up To 125 Ampsand Mcbs As Outgoing Complete All As Specified And As Directed . ( Make: Indoasian Or Its Equivalent / Legrand / Cg ) 64 Supply And Fixing Mccb 4P 125 Amps / 415Volts , Having Breaking Capacitywith Complete Accessories As Per Existing Suitablesize Complete All As Specified And As Directed 65 Supply And Fixing Ofwallmounted Fan 400 Mm Motor , Mounting Accossireskit Blade , Guard Set Guard Ring 1350Rpmcomplete All As Specified And As Directed 66 S&Frecess Mounting Type Led Indoor Luminaire Powder Coated, Crca Or Powder Coated Aluminium Panel 2 X 2 ( Appx ) System Wattage 35 Watt To 36 Watt ( Cool White ) , Minimum System Lumen Efficacy Not Less Than 100 Lumper Watt, Cri Not Less Than80, Colour Temperature Not Less Than 6000 K, Power Factor Not Less Than 0.95, Led Driver Ip Protection Ip 20, Powder Coated Housing With Ashthetic Bottom Frame, Suitable For Any Type Of Ceiling System Including Connection With Pvc Insulated Copper Conductorcomplete All As Specified. ( Make Havells / Bajaj / Cg Or Equivalent. ) 67 Supplylaying, Connecting Andtestingxlpe Insulated, Armoured Heavy Duty Electric Cable With Aluminium Conductor, 1100 Volts Grade, Of Size 50 Sqmm3.5 Core Laid In Trenches Or Passing Through Pips / Ducts Completeall As Specified And Directed By Engineer In Charge 68 S&F Pvc Conduit 40 Mm Pipe Suitable For Cable Protation Including Clips Elbow Screws Nuts Bolts Drilling Of Hole Walls Drains Making Good Condition Complete All As Specified And As Directed. 69 Supply And Fixingdigital Grounding Device Mobile Transporatble Earthing Pit Advance Chemical Sealed Electrode Boxtype Light Weight ( Generation-5 ) Advance Chemical Sealed Electrode Box Type Light Weight Gi Horizontal Electrode Designed For Use In Any Type Of Soil Condition. Each Electrode To Be Designed In Box Shape Using Gi, 2Mm Thick Plates Of 600X450mmx100mm As Outers Of The Box. Two 50Mm Sockets Are To Be Placed On Top With Removable Caps And Two Handles To Faciltate Hanging. The Inner Space Between Plates Is To Filled With About 28 Kg Of Specialized Asem-Gb An Extremely Low Resistvity ( 0.05Ohm / M & Below ) ( High Conductivity ) Hygroscopic, Non- Soluble Stable Material. The Material Is Filled In The Electrode In Very Slury Form Made With Water. After Filling The High Conductive Salt In The Box Both The Sockets Are Crapped And Closed. A Cu Terminal 200X40x6mm Is To Be Fixed Along The Centre Protruding On The Socket Centre The Necessary Connection / Bonding. A 1.5 Mtr Length Of Pvc Insulated 50 Sq Mm Copper Flexible Cable Is To Be Provided With Each Electrode For Necessary Connection To Distribution Bvox Or Bonding Between Two Electrodes. One Galvanized Iron Sheet Junction / Distribution Box Is To Be Provided With Every Two Electrodes. The Electrode Duplicacy / Copy Of The Equipment Is Subject To Legal Content 70 M & Labour Of Ss Guy Rope Wire 4 Mm Hard ( 7X7 Construction ) Complete All Specified And As Direcetd . 71 M&L Ss U Clamp 5 Mmcomplete Set Suitable For Each Thore Type Earthing All Specifed And As Directed. 72 M&L Ofconstructions ) Ss D Clamp 6 Mm Completeset Suitable For Each Thore Type Earthing Allspecified And As Directd . 73 M&L Ss Adjustable Clamp 8 Mm Completeset Suitable For Each Thore Type Earthing All Specifed Anddirectd. 74 Excavation In Trenches Not Exceeding 1.5 Metre Wide And Not Exceeding 1.5 Metre In Depth For Laying Of Cable And Foundation Of Poles, Stays And Getting Out In Any Type Of Soil, All As Specified. 75 Returning Filling In Including Spreading, Levelling, Watering And Well Ramming In Layers Not Exceeding 25 Cm Thick Each Layer In Any Type Of Soil Complete All As Specified And As Directed By Engineer-In-Charge. 76 Removing Surplus Excavated Material To A Distance Not Exceeding 50M And Depositing Where Directed At A Level Not Exceeding 1.5M Above The Starting Point Complete, All As Specified And As Directed By Engineer-In-Charge. 77 Common Burnt Sub Class ‘B’ Brick Laid Flat In Trenches Over And Across The Length Of Cable With Length Of Brick Perpendicular To The Direction Of Cable Adjacent / Abutting Each Other Complete All As Specified And Directed For Cable Protection. 78 M & L For Sand Cushioning To Underground Cable, Provided With A Layer 8 Cm Before And 15 Cm After Laying And Stretching Jointing And Testing The Cable Complete All As Specified And Directed By Engineer-In-Charge.Note : After Punning Down Shall Be Measured 18Cm. 79 Supply And Installhot And Cold Typeinvetor Splitsmart Accopper Woundwallmounted Indoor / Outdoor Complete With Cordless Remote Control Unitof Capicity Of 2.0Ton3 Star , Cooling Capicity 6350 Watt Heating Capicity 5600 Watt, R-32, Refrigrant, Low Indoor Noice Less Than 48 Db, Dust Filter Air Purifierstablizer Free Operation, Cu Connecting Pipe Length Upto 5 Mtr / Connecting Cable Upto 5 Mtr All Including Outdoor Unit Mounting Bracket Making Holes In Wall And Makinggood Complete All As Specified And As Directed. Make : Lg / Daikin / Loyed / Hitachi. 80 S&F Route Pipe ( Copper Tube ) Of Size 5 / 8 Dia With Insulation Complete All As Specified And Directed By Engineer-In-Charge. 81 Supply And Fixing Ofheavey Duty Ac Stand For Mounting Outdoor Unit With Wall, Stand / Bracket Upto Capacity 160Kgscomplete All As Specified And As Directed. 82 Supply And Fixing Voltage Stabilizer For Automatic Operation, Single Phase Naturally Air Cooled Indoor Type & Designed For Input Variation Between 140 V To 280 Vac With Output Voltage Stabilized At 230 V With Accuracy Of ± 2.5% And Of Capacity 5 Kva Complete All As Specified And As Directed. 83 M&L For Sheet Metal Enclosures For Single Pole And Neutral Enclosure With A Two Pin And Earth Plug And Socket Complete With Single Pole Mcb 20 Amp 240 Voltcomplete All As Specified And As Directed. 84 M&L Formild Steel Powder Coated Perforated Sheets Of Size 30 Cm Width As Cable Duct Trays And Similar Work Cut To Size Holes Punched Including Round Headed Screqs Clout Nails Or Rixet Revets And Fixed To Wood Or Steel Framing With Olain 40 Mm Lap Joints With Revetted Seams Including Bending Or Turning Up Mitered Angles Etc As Required Of 3.15 Mm Thick Sheet Complete As Specified And Directed. 85 M & L Perforated Angle Of Size 40X40x4 Mm Powder Coated For Holding Cable Trays With Complete Nuts And Bolts And Washers To Match With The Colour With Cable Tray Complete All As Specifed And Directed. 86 Supply And Fixing Of Surge Protection Device Single Phase Type I ( Spd ) With Serviceability Indicator Single Phase With Neutral For Protection Of Equipment Against Lightning And Switching Surges With Daettachable Type, Of Phase Descriptionun 275 Volts, Iin 5 Ka , Voc 6Kv Imax 10 Ka , Iimp 12.5 Ka And Neutraluc 275 Volts, I Imp 30, Voc 6Kvka, In 30 Ka , Imax 60 Ka Includingprotected Ip20complete Confiring To Iec / En 61643-Ii All As Specified Make : Havells / Schneider Electric / L&T / Abb All As Specified 87 Supply And Fixing Of Surge Protection Device Single Phase Type Ii ( Spd ) With Serviceability Indicator Single Phase With Neutral For Protection Of Equipment Against Lightning And Switching Surges Withdraw Able Type, Of Phase Descriptionun 275 Volts, Iin 5 Ka , Voc 6Kv Imax 10 Ka , Iimp 12.5 Ka And Neutraluc 275 Volts, I Imp 30, Voc 6Kvka, In 30 Ka , Imax 60 Ka Includingprotected Ip20complete Confiring To Iec / En 61643-Ii All As Specified Make : Havells / Schneider Electric / L&T / Abb All As Specified 88 M & L For Brazing Work With Copper Brazing Alloy Rod With Help Of Oxygen And Lpg Cylinder Using Required Copper Strip Of Size 20Mm X 3Mm , 32X6 Mm Upto 30 Cm Length Along With Cleaning Work Of Strip With Descaling Solution / Emery Paper Which Are Laid As Roof / Down Conductor On Any Height Of Buildingup To 15 Mtr Building Height Complete All As Specified And Directed By Engr-In-Charge. 89 Cutting Of Road ( In Hard / Dense Soil ) For Laying Pipe Line Or Repair To Pipes Of Any Size Upto 0.50 Mtr. Depth And Getting Out Including Forming Bottom Surface To Required Level And Making Good The Road As Per Existing Bitumens, Concrete Complete All As Specified And Directed By Engineer-In-Charge

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Dec-2023 FINANCE Financial Bid 04-01-2024
2 26-Dec-2023 BOQ BOQ 04-01-2024
3 04-Jan-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-01-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 87000.0 /-
Tender Value
INR 43.50 Lakhs /-

BOQ Items

Name of Work : ADDN / ALTN TO BLDG NO P-33 AT AF STATION UDHAMPUR
Sl. No. Item Description
1B/R Portion
2Fibrette Tile of "Wood Fiber Cement Composite" 1mm width wood fiber 20/25 mm thick (accoustical wall panel) of size 600x600 / 600x1200mm having excellent noise absorption of 1 NRC as per ISO : 354, Density 400 Kg/m3, meets Fire Ratings as per BS 476 part 5, 6, 7 class 1 and P, water resistance and thermal insulated. Instaled on GI stud 600x600 mm centre to centre 2400mmx50 web thickness 0.5mm, flanges 15 and 50xx fully knurled giving it high strength, hot dipped galvanised steel with 120 GSM zinc coating with a backing of 50 mm 1000 GSM thick absorb wool tested as per Fire Resistance IS 15061 for excellent results complete all as specified and as directed by Engr-in-Charge. Notes : (i)Colour as approved by the GE. (ii)Work to be executed upto height of 7m from the floor level. Unit rates are deemed to be included in the quoted rates and necessary required arrangement for the same are deemed to be included in the quoting rates. Nothing extra shall be admissible on this account. (iii)Contractor will give the warranty from manufacturer on an affidavit for minimum period of 2 year or manufacturer"s warranty period which ever is higher.
3M&L for brick work with sub class "B" bricks using old size bricks, straight or curved on plan exc 6 M mean radius built in CM 1:4 complete all as specified and as directed.
4M&L for Vitrified ceramic tiles light shade 10mm thick (square/rectangular) polished, area of each tiles not exceeding 0.36 sqm but not exceeding 0.42sqm, in floors etc, set and jointed in neat cement slurry and pointed in white or coloured cement match including 15mm thick screed bed in CM 1:6.
5M&L for Glazed ceramic tiles in vertical surface 350x250x7mm/450x350x7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match including 10 mm thick screed bed completed all as specified and as directed.
6S&F for powder coated aluminium doors shutters, (thickness of powder coating not less than 50 micron) aluminium section weighing exc 0.55 Kg/m including necessary joining cleats, glazing clips rubber neoprene packing, handle 2 Nos in each door, fixed with floor hinges anodised aluminium snap beading screws etc completed all as specified and as directed.
7S&F Power Coating Aluminium (Minimum thickness of powder coating 50 micron) bar for doors, window, ventilators and partitions (Fixed positions) with extruded built up standard tubular section/appropriate Z section and other section of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size incl necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc aluminium sections shall be smooth, rust free, straight mitred and jointed mechanical whereever required incl cleat angle aluminium snap beading for glazing/panelling, CP brass/stainless steel screw,complete all as specified and as directed.
8S&F Aluminium Power Coated of any colour (thickness of powder coating not less than 50 micron), in frame for doors, window, ventilators, partition wall etc, with one or more rebates, shutters, grills including joining cleat for fixing etc. complete all as specified & directed by Engr-in-Charge.
9S&F 5.5 mm thick ordinary quality glass fixed to doors, window and partion but exc 0.5 sqm in a each pane complete all as specified and directed.
10S&F rubber beading for fixing of glass for partition complete all as specified and directed.
11S&F Alum snap beading for fixing of glass for partition complete all as specified and directed.
12S&F aluminium composite panel (ACP Sheet) 5 mm thick both side laminated fixed in position side partition complete all as specified and directed.
13S&F Roof trusses (framed), purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, Tee, angle channel or falt sections) incl distance pieces, cleats etc similar works and fixing complete FE-410W (GDE E250 quality A) incl structural steel is painted one shop coat Zinc chromate primer paint (incl preparation) comlete all as specified and as directed.
14Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landing steps cillis shelves linjtels etc and making good in cement concrete 1:2:4 Type B-1 complete all as specified and as directed.
15Cutting holes in brick walls built in cement for exceeding half brick wall but not exceeding one brick wall for inserting holdfasts or similar work making good dismantling proportion in cement mortar 1:3 or cement concrete 1:2:4 Type B-1 complete all as specified and as directed.
16Excavating in post holes (or similar holes) each not exceeding 0.5 cum getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering and removing surplus soil to a distance not exceeding 50 m and making good surface hard/dense soil.
17M&L for Pre painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of an colour having tensile strength of 550 MPA as in roof covering/cladding to wall, fixed with self tapping screws as specified.
18S&F pre-painted galvalume aluminium zinc coating GI based plain steel sheeting 0.50 mm thick of any colour having tensile strength of 550 MPA as in roof covering/cladding to wall fixed with self tapping screws complete all as specified and as directed.
19Preparation of new or previously untreated steel surfaces of any description over 10 cm width or girth, applying two coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
20M&L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate for emedding MS pipes complete all as specified and as directed by Engr-in-Charge.
21Surface excavation not exceeding 30 cm deep and averaging 15 m deep and getting out only type of cement complete all as specifed and as directed by Engr-in-Charge.
22Removing excavated material not exceeding 1.50 Km depositing where directed.
23M&L for Hardcore of broken stone of guage not exceeding 63 mm deposited, spreaded & levelled in layers not exceeding 15 cm thick including watering and ramming etc complete all as specified and as directed by Engr-in-Charge.
24M&L for 100 mm thick PCC 1:4:8 type D-2 (40 mm graded stone aggregate) as in sub base of flooring complete all as specified and as directed by Engr-in-Charge.
25M&L for providing 50 mm thick cement concrete 1:3:6 type C-1 using 20mm graded stone aggregate as in plinth protection laid in alternate bays (not exceeding 2.0 sqm each) and finished even and smooth without using extra cement and providing joints through the thickness of the plinth protection filled with mastic filling compressing one part of bitumen 85/25 graded and three parts of sand by weight complete all as specified and as directed.
26M&L for providing 100 mm thick cement concrete Type B-2 1:2:4 (40 mm graded stone aggregate) as in sub base of floor complete all as specified and as directed.
27M&L for granite (of any type) work (Table rubbed and polished) in steps, jambs, pillars, window cills, cooking platforms and like CM (1:4) including pointing in white cement 1;2 using marble dust with admixture of pigment to match with shade of granite complete including screed bed bedding layer of 15 mm thick in CM 1:4 complete all as specified and polishing complete.
28M&L for RCC Type B1 1:2:4 (20 mm graded aggregate) slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.
29M&L for Mild steel TMT bars 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed.
30M&L for Mild steel TMT bars 5 mm dia and over upto and including 10 mm dia in stirrups, spacers and binders complete all as specified and directed.
31M&L for Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similr work; not exceeding 200mm thick (Horizontal or sloping) & fair finished concrete surface complete all as specified and directed.
32M&L for rendering 10 mm thick on fair faces of brick work or concrete surfaces finished even and smooth (without using extra cement) in CM 1:6 complete all as specified and directed.
33M&L for preparing newly plastered surfaces of wall and applying 2 coat of whitewash complete all as specified and directed.
34S&F 18/19 mm thick termite proof, chemically well pressed, block boards, grade 1 quality, exterior grade, commercial type, fixed with screws to timber frame work, including 1 mm thick PVC moulding all around including edging, complete all as specified and directed.
35S&F 0.9 mm thick Decorative laminate type 1 of surface finish, colour and pattern as approved, fixed with approved adhesive as per manufacturer"s instructions complete all as specified and directed.
36S&F 100 mm Brass handles, cast type, polished bright complete all as specified and directed.
37S&F 30 mm (width of flaps) continuous (Piano) hinges of mild steel, bright finish complete all as specified and directed.
38S&F mild steel screw bolt 5 mm to 10 mm dia machine made with hexagonal or square heads at one end and screwed the other end with washer and one hexagonal or square not exceeding 5 cm and not exceeding 10 cm long complete all as specified and directed.
39M&L for providing and fixing stainless steel (Gde 304) railing made of hollow tunes, channels plates etc. including welding, grinding, buffing, polishing and making curvature (Where ever required) and fitting the same with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size, on the top of floor or the side of waist slab with suitable arrangement complete all as specified and directed.
40E/M Portion
41M&L Earthing complete with copper earth plate electrode of size 60 cm x 60 cm x 3.15 mm thick as earth electrode burried directly in ground (earth pit not less than 2.25 Meter deep below ground level) with top edge of the earth plate not less than 1.5mtr below ground level using copper earth strip 20 x 3 mm dia as earth continuity conductor connected to earth plate by means of copper thimbles, nuts, bolts, washers including brazing etc of earth electrode and earth wire by means of welding, all as directed including providingwatering pipe 20mm dia with wire mesh and funnel at top, earth pit andpit cover made of MS sheet 2 mm thick duly fixed to angle iron frame with hinges of appropriate size by welding and having locking arrangement, adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil , removing surplus excavated material all as required at site and as specified in EP No 3 of MES SSR Part-I (2009) directed by Engineer-in-charge including testing on completion. .
42Earth continuity conductor 20 x 3.00 mm copper strip or main earthing lead fixed to walls on batten or recess or chassis or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed by Engr-in-Charge
43Supply and fix for PCC Block size 10cmx10cmx10cm made of 1:2:4 cement agrigate 20mm for running of earth strip overtop surface all including fixing of earth strip wiring clamps,screw,Nut bolt bracket etc all as directed by engineer in charge. Note : Block shall be constructed on site shall be attened to roof surface using PCC/Cement etc.
44S&F GI tubes, "medium grade", galvanised, with all fitting laid in walls/ trenches of 40mm dia complete all as specified & directed .
45Supply and fixing DMC insulator suitable GI/Copper strip as ground requied with excellent materials strangth,seamless finish,durable ,weather proof Heat resistant including sitable size of hole fastner,screw ,nut bolts and washers etc complete all as specified and as direcetd by Engr-in-Charge.
46M&L for point wiring complete with PVC insulated and unsheathed cable 1.5 sqmm (nominal area) ISI marked multi-stranded copperconductor single core including ISI marked 20mm dia "medium grade" PVC conduit for point wiring concealed in wall/false ceiling/surfaceconduit /casing caping with pressed steel concealed Sunken boxes not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer completeincluding 1.5 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rulecompleteall as specified & directed. [ Make of cable - Finolex / Havell"s / Anchor/KEI/Polycab ]
47M&L for point wiring complete with PVC insulated and unsheathed cable 2.5 sqmm (nominal area) ISI marked multi-stranded copperconductor single core including ISI marked 20mm dia "medium grade" PVC conduit for point wiring in concealed in wall/false ceiling/surfaceconduit /casing caping with pressed steel concealed Sunken boxes not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer completeincluding 2.5 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rulecompleteall as specified & directed. [ Make of cable - Finolex / Havell"s / Anchor/KEI/ Polycab ]
48M&L switch piano, flush type, 5 Amps single pole, one way
49M&Lswitchsocketcombination3 pin, flush type, 16 Amps .
50M&L of ceiling rose 3 phase /PVC/polycarbonate,isolated bodycomplete all as specified and as directed..
51M&LSub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 1000 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 10.00 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of PVC conduit drawn through rigid concealed in wall/false ceiling/surfaceconduit /casing capingand connected to main board and making good disturbed surface complete all as specified and as directed.Make of conductor : Havells/polycab/KEI Note: Two runs each of 10.00 sqmm main cable andone RM of 10.00 sqmm cable as earth wire together alongwith conduit shall be considered as 1 running metre for payment purpose.
52M&LSub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 6.00 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 6.00 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of PVC conduit drawn through rigid concealed in wall/false ceiling/surfaceconduit /casing capingand connected to main board and making good disturbed surface complete all as specified and as directed.Make of conductor : Havells/polycab/KEI Note: Two runs each of 6.00 sqmm main cable andone RM of 6.00 sqmm cable as earth wire together alongwith conduit shall be considered as 1 running metre for payment purpose.
53M&LSub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4.00 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4.00 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of PVC conduit drawn through rigid concealed in wall/false ceiling/surfaceconduit /casing caping and connected to main board and making good disturbed surface complete all as specified and as directed.Make of conductor : Havells/polycab/KEI Note: Two runs each of 4.00 sqmm main cable andone RM of 4.00 sqmm cable as earth wire together alongwith conduit shall be considered as 1 running metre for payment purpose.
54Supply and fixing LED street light fitting 35 Watt 6500K pf >.90 efficency 100lm/W 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistantcomplete with driver, lampfixing of wall,pole,buildingwith impact and corrosion resistant including thermal management in multiple optics complete with IP 65 protectioncomplete all asspecified and as directed.
55Street light bracket made out of 30/32 mm dia GI light grade tubing not less than .75 Mtr long bend to shape including pole clamps/fastners clips nailsmade outflat iron and nuts, bolts and washers etc complete all as specified and directed.
56M&LSheet metal enclosures for single pole and neutral enclosure with a two pin and earth plug and socket complete with single pole MCB 32/20 Amp 240 Voltcomplete all as specified and as directed.
57M&LSheet metal enclosures for DBs SPN 8 wayflush mounted double door including accessories therein and disposing off complete all as specified and directed.
58M&LSheet metal enclosures for DBs SPN 12 wayflush mounted double door including accessories therein and disposing off complete all as specified and directed.
59M&L of MCB SPN 63 Amps, 240 Volts, having breaking capacity 10 kA, "C" charactersticcomplete all as specified and as directed.
60M&L MCB SPN40 Amps, 240 Volts, having breaking capacity 10 kA, "C" characterstic complete all as specified and as directed.
61M&LMCB SP 6-32 Amps, 240 Volts, having breaking capacity 10 kA, "C" characterstic complete all as specified and as directed.
62M&L for MCB TPN40-100 Amps, 415 Volts, having breaking capacity 10 kA, "C" characterstic complete all as specified and as directed.
63M&L forVTPNVertical three phase distribution board, VTPN, 4 way 440 volts having IP-54isolated busbar assembly IK 09 Mechnical impact strength door earthing protection, double door with provision for fixing ofMCCBs as incomer up to 125 Ampsand MCBs as outgoing complete all as specified and as directed .(Make: Indoasian or its equivalent/legrand /CG )
64Supply and fixing MCCB 4P 125 Amps/415Volts ,having breaking capacitywith Complete accessories as per existing suitablesize complete all as specified and as directed
65Supply and fixing ofwallmounted fan 400 mm motor ,mounting Accossireskit blade ,guard set guard ring 1350RPMcomplete all as specified and as directed
66S&FRecess mounting type LED indoor luminaire powder coated, CRCA or powder coated aluminium panel 2" x 2" (Appx) system wattage 35 watt to 36 watt (cool white), minimum system lumen efficacy not less than 100 lumper watt, CRI not less than80, colour temperature not less than 6000 K, power factor not less than 0.95, LED driver IP protection IP 20, powder coated housing with ashthetic bottom frame,suitable for any type of ceiling system including connection with PVC insulated copper conductorcomplete all as specified. (Make Havells/Bajaj/CG or Equivalent.)
67Supplylaying, connecting andtestingXLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, of size 50 sqmm3.5 core laid in trenches or passing through pips/ ducts completeall as specified and directed by Engineer in charge
68S&F PVC conduit 40 mm pipe suitable for cable protation including clips Elbow screws nuts bolts drilling of hole walls drains making good condition complete all as specified and as directed.
69Supply and fixingDigital Grounding Device Mobile Transporatble Earthing Pit Advance Chemical Sealed Electrode BoxType light weight (Generation-5) Advance Chemical Sealed Electrode Box Type light weight GI horizontal electrode designed for use in any type of soil condition. Each electrode to be designed in box shape using GI,2mm thick plates of 600x450mmx100mm as outers of the box. two 50mm sockets are to be placed on top with removable caps and two handles to faciltate hanging. The inner space between plates is to filled with about 28 KG of Specialized ASEM-GB an extremely low resistvity (0.05ohm/m & below) (High Conductivity) hygroscopic, non- soluble stable material. The material is filled in the electrode in very slury form made with water. After filling the high conductive salt in the box both the sockets are crapped and closed. A cu terminal 200x40x6mm is to be fixed along the centre protruding on the socket centre the necessary connection/bonding. A 1.5 mtr length of PVC insulated 50 sq mm Copper Flexible cable is to be provided with each electrode for necessary connection to Distribution Bvox or bonding between two electrodes. One galvanized iron sheet junction/Distribution Box is to be provided with every two electrodes. The electrode Duplicacy/copy of the Equipment is subject to legal content
70M & Labour of SS Guy Rope wire 4 mm Hard (7x7 construction ) complete all specified and as direcetd .
71M&L SS U Clamp 5 mmComplete set suitable for each thore type earthing all specifed and as directed.
72M&L ofConstructions)SS D Clamp 6 mm completeset suitable for each thore type earthing allspecified and as directd .
73M&L SS Adjustable Clamp 8 MM Completeset suitable for each thore type earthing all specifed anddirectd.
74Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for laying of cable and foundation of poles, stays and getting out in any type of soil, all as specified.
75Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each layer in any type of soil complete all as specified and as directed by Engineer-in-Charge.
76Removing surplus excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete, all as specified and as directed by Engineer-in-Charge.
77Common burnt sub class ‘B’ brick laid flat in trenches over and across the length of cable with length of brick perpendicular to the direction of cable adjacent/abutting each other complete all as specified and directed for cable protection.
78M & L for Sand cushioning to underground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and directed by Engineer-in-Charge. Note : After punning down shall be measured 18cm.
79Supply and installHOT and COLD typeinvetor splitsmart ACCopper woundwallmounted indoor/outdoor complete with cordless remote control unitof capicity of 2.0Ton3 Star ,cooling capicity 6350 watt heating capicity 5600 Watt,R-32, refrigrant,low indoor noice less than 48 DB, dust filter Air Purifierstablizer free operation, Cu connecting pipe length upto 5 Mtr/ connecting cable upto 5 mtr all including outdoor unit mounting bracket making holes in wall and makinggood complete all as specified and as directed. Make : LG/Daikin/Loyed/Hitachi.
80S&F route pipe (copper tube) of size 5/8" dia with insulation complete all as specified and directed by Engineer-in-Charge.
81Supply and fixing ofHeavey duty AC Stand for mounting Outdoor unit with Wall,stand /Bracket upto capacity 160Kgscomplete all as specified and as directed.
82Supply and fixing Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 140 V to 280 VAC with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified and as directed.
83M&L for Sheet metal enclosures for single pole and neutral enclosure with a two pin and earth plug and socket complete with single pole mcb 20 Amp 240 Voltcomplete all as specified and as directed.
84M&L forMild steel powder coated perforated sheets of size 30 cm width as cable duct trays and similar work cut to size holes punched including round headed screqs clout nails or rixet revets and fixed to wood or steel framing with olain 40 mm lap joints with revetted seams including bending or turning up mitered angles etc as required of 3.15 mm thick sheet complete as specified and directed.
85M & L Perforated angle of size 40x40x4 mm powder coated for holding cable trays with complete nuts and bolts and washers to match with the colour with cable tray complete all as specifed and directed.
86Supply and fixing of surge protection device single phase Type I (SPD) with serviceability indicator single phase with neutral for protection of equipment against lightning and switching surges with daettachable type,of phase descriptionUn 275 volts,Iin 5 kA , voc 6kv Imax 10 kA ,Iimp 12.5 kA and neutralUc 275 volts,I imp 30,voc 6kvkA,In 30 kA ,Imax 60 kA includingprotected IP20complete Confiring to IEC/EN 61643-II all as specified make : Havells/schneider electric/L&T/ABB all as specified
87Supply and fixing of surge protection device single phase Type II (SPD) with serviceability indicator single phase with neutral for protection of equipment against lightning and switching surges withdraw able type,of phase descriptionUn 275 volts,Iin 5 kA , voc 6kv Imax 10 kA ,Iimp 12.5 kA and neutralUc 275 volts,I imp 30,voc 6kvkA,In 30 kA ,Imax 60 kA includingprotected IP20complete Confiring to IEC/EN 61643-II all as specified make : Havells/schneider electric/L&T/ABB all as specified
88M & L for brazing work with copper brazing alloy rod with help of oxygen and LPG cylinder using required copper strip of size 20mm x 3mm ,32X6 mm upto 30 cm length along with cleaning work of strip with descaling solution/emery paper which are laid as roof/down conductor on any height of buildingup to 15 mtr building height complete all as specified and directed by Engr-in-Charge.
89Cutting of road (in hard/ dense soil) for laying pipe line or repair to pipes of any size upto 0.50 mtr. Depth and getting out including forming bottom surface to required level and making good the road as per existing bitumens, concrete complete all as specified and directed by Engineer-in-Charge
Disclaimer :