Power Development Department has published Survey, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Creation Of 63 Kva & 250 Kvasub Stn. Alongwith Erection Of 11 Kv Line On 9 Mtr St Poles, 30Mm² Acsr Weasel Conductor And Lt Line On 8 Mtr. Long St Poles At Wss Ballian . Submission Date for this Tender is 08-01-2024. Road Cargo Transport Tenders in Udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 01-Jan-2024 | Date Extension Notice I | Date | 08-01-2024 |
Sl. No. | Item Description |
1 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Weasel Conductor at WSS Ballian Stage Zero. |
2 | 9 mtr. Long ST Pole (ST-410 SP-33) |
3 | GI V Cross -arm with top Bracket including clamps |
4 | GI Channel X-arm including clamps and Angle for braces |
5 | 30mm² ACSR weasel conductor |
6 | PG Clamps for 30mm² ACSR conductor |
7 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. |
8 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
9 | Galvanized Nuts and Bolts |
10 | Danger Plates with Clamps |
11 | Anti climbing device with clamps |
12 | Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm |
13 | Painting of 9 mtr ST poles with two coat of Aluminium Paint. |
14 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
15 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
16 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Installation of 63KVA Substation at WSS Ballian Stage-Zero |
17 | 11/0.433 KV, 3-phase distribution Transformer 63 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate |
18 | Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type |
19 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
20 | 11 KV Horn gap fuse set 3 phase 200 A |
21 | 120mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type |
22 | 9 mtr. Long ST poles (ST-410 SP33) |
23 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
24 | GI Channel /Angle/flat of sizes including clamps |
25 | Galvanized Nuts and Bolts. |
26 | Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover |
27 | 11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm |
28 | LT distribution box for 63 KVA DTR with MCCB for incomer and SFU"s for outgoing circuits |
29 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
30 | PG Clamps |
31 | Danger Plates with Clamps |
32 | GI Barbed wire for Anticlimbing |
33 | 3-Phase 4 Wire LT Prodigy Meter with Box. |
34 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
35 | Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint. |
36 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for erection of3 phase 4 wire LT line on 8 mtr. ST pole at WSS Ballian Stage Zero. |
37 | 8 mtr. Long poles (ST-410 SP15) |
38 | GI M Clamps for shackle insulator |
39 | 30mm sq. ACSR Cond. |
40 | Shackle insualtor |
41 | Galvinized Nuts and Bolts. |
42 | Danger Plates with Clamps |
43 | Anti climbing device with clamps |
44 | Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip |
45 | Painting of 8 mtr. Long ST poleswith two coat of Aluminium paint |
46 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
47 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
48 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for erection of 11 KV line on 9 mtr. Long ST pole at WSS Ballian Stage-Ist |
49 | 9 mtr. Long ST Pole (ST-410 SP-33) |
50 | GI V Cross -arm with top Bracket including clamps |
51 | GI Channel X-arm including clamps and Angle for braces |
52 | 30mm² ACSR weasel conductor |
53 | PG Clamps for 30mm² ACSR conductor |
54 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. |
55 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
56 | Galvanized Nuts and Bolts |
57 | Danger Plates with Clamps |
58 | Anti climbing device with clamps |
59 | Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm |
60 | Painting of 9 mtr ST poles with two coat of Aluminium Paint. |
61 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
62 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
63 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for installation of 250 KVA Filter at WSS Ballian Stage-Ist. |
64 | 11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 CopperWound, & with LV Cable box having detachable Aluminium Gland plate |
65 | Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type |
66 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
67 | 11 KV Horn gap fuse set 3 phase 200 A |
68 | 300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type |
69 | 9 mtr. Long ST pole (ST-410 SP33) |
70 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75Positive and 80 KV Negative, creepage distance 320mm |
71 | GI Channel /Angle/flat of sizes including clamps |
72 | Galvanized Nuts and Bolts. |
73 | Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover |
74 | 11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm |
75 | LT distribution box for 250 KVA DTR with MCCB for incomer and SFU"s for outgoing circuits |
76 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
77 | PG Clamps |
78 | Danger Plates with Clamps |
79 | GI Barbed wire for Anticlimbing |
80 | 3-phase HT Trivector meter with CT PT Unit |
81 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
82 | Painting of ST poles 9 mtr. of sub stn. with 1 coat of Red oxide & 2 coat of Al. paint |
83 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for erection of3 phase 4 wire LT line on 8 mtr. ST pole at WSS Ballian Stage Ist |
84 | 8 mtr. Long poles (ST-410 SP15) |
85 | GI M Clamps for shackle insulator |
86 | 50mm² ACSR Rabbit Cond. |
87 | Shackle insualtor |
88 | Galvinized Nuts and Bolts. |
89 | Danger Plates with Clamps |
90 | Anti climbing device with clamps |
91 | Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip |
92 | Painting of 8 mtr. Long ST poleswith two coat of Aluminium paint |
93 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
94 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy