Military Engineer Services-MES has published Tender For Repair/ Maint Of Bldg Security Light, Solar Water Heater, Solar Fencing At Dmde Area And Ce Rnd Area Under Age B/R-Ii Secunderabad. Submission Date for this Tender is 27-12-2023. Solar Heater Tenders in hyderabad Telangana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | M&L for complete servicing ofofElectric incinerator including dismantlingcanopy with insulation and sound proofing (general waste incineration system for non hazardous waste like garbage/paper/general and garden waste electrically operated capacity approx 10 Kg per operation with chimney)including cleaning the entire system with blower, replacement of the unserviceable spares i.e. fire/insulation bricks, sensors, heater elements, safety control, connectors etc., and re-assembling the Electric incinerator set after repair including complete removal ofold paint and painting with two coats of fire retardantpaint over a coat of red oxide primer complete all as directed.Arresting the leakage in body of incinerator by providing gasket set and including welding and denting work all as directed by engineer in charge Make : Practice India(Existing) |
2 | S&F following items suitable for existing solar fencing system including necessary tree cutting / trimming fixing accessories and taking down unserviceable items complete all as directed. |
3 | Energizer |
4 | Fence voltage alarm |
5 | 12G HT wire |
6 | Sealed maintenance free battery 12V, 65 AH |
7 | Charge controller |
8 | CP Strain Insulator |
9 | Anti climbing insulator |
10 | Permanent wire lighteners |
11 | S Hooks |
12 | Joint clamps |
13 | Double insulation cable |
14 | Warning sign board |
15 | S&F Corner pole/Intermediate pole (approx 1.5 mtr height) including necessary civil works complete Make for item srl No 2.01 to 2.12 & 3 : Crown solar power fencing ( As per existing) or equivalent make as approved by GE |
16 | S&F following items suitable for existing single lane automatic flap barrier in-built microprocessor based controller including fixing accessories and taking down unserviceable items complete all as directed. |
17 | DC servo motor 12V/30W |
18 | Photo beam sensor |
19 | SMPS (Switched mode power supply) |
20 | Limit switch |
21 | Gear box assembly |
22 | Mother board |
23 | Supply and fixing the following spares suitable for existing sauna heating system and steam bath including taking down unserviceable spares complete all as directed. Make : Linco/Jaquar or equivalent make as approved by GE |
24 | Power circuit board |
25 | Heating element 2 KW |
26 | Steam heater 6 KW |
27 | Timer Unit |
28 | Thermostat |
29 | Contactor |
30 | Digital Sauna heater control panel |
31 | Solenoid valve |
32 | Flexible pipe (Steam) |
33 | Teflon wire for sauna box |
34 | Sauna spring |
35 | Water pipe (PVC) |
36 | M&L for servicing to single person sauna heating system complete all as directed as per OEM direction. |
37 | M&L for servicing to single person steam bath complete all as directed as per OEM direction. |
38 | M&L for servicing to single person jacuzz with hydrojects, air jets complete bath tub complete all as specified and as directed |
39 | S&Fsecurity light fitting bracket made out of GI tubing 40mm dia light grade of size 1.5m long, bent to shape including clamp for bracket made out of 50x6mm MS flat iron with necessary nut & bolts, washers complete and taking down unserviceable bracket complete all as directed. Make : Tata/Jindal/Oswal |
40 | M&L for Refilling of Dry chemical type fire extinguisher capacity 5 Kg complete all as directed. |
41 | M&L for Refilling of Mechanical foam type fire extinguisher capacity 9 Liters complete all as directed. |
42 | Attending complaints of DG sets whenever breakdown reported by JE E/M/Engineer in charge within 3 hours of reporting and replacing the minor defective parts and make the DG set serviceable at site to the satisfaction of Engineer in charge.Note :- Major defective parts will be measured and paid separately.If the contractor failed to attend the complaint within 3 hours of reporting then penalty of Rs 500/- per hour will be leveled on contractor. |
43 | M&L for Point wiring complete with and including 1.5 sq. mm (nominal area) single core multi stranded FRLS copper conductor PVC insulated unsheathed cable 1100 volts grade ISI marked drawn through in and including concealed non metallic rigidPVC conduitwith accessories such as bend ,tees, junction boxes etc. suitable modular boxes for mounting fittings like modular switches, modular socketsand fan regulators etc with modular sheet coversincluding one run of1.5 Sqmm PVC insulated andunsheathed multi strandFRLS copper conductor as green colorearth wire and connected to common earth dully inclulding taking down existing point wiring complete all as specified and directed for the following:- |
44 | one light/fan/bell point controlled by one switch |
45 | one 3 pin socket outlet 5A on independent board |
46 | one 3 pin socket outlet 5A only on same board. |
47 | All as per item No.7 above but with 2.5 sq mm size pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor cable for 3/6 pin socket outlet 15 amp on one independent board. |
48 | S&F Modular Switchone way 6 Amps, 1 module all as specified and directed. |
49 | S&F Modular Socket 2 module for2 / 3 pin 6 Ampall as specified and directed. |
50 | S&F Modular Switchone way 16 Amps, 1 module all as specified and directed. |
51 | S&F in repairs Modular bell push, flush type, 5 amp |
52 | S&F Socket 2 module2 in 1, 3 pin, 6 and 16 Amp, complete all as specified and directed . |
53 | S&F ceiling rosePVC / polycarbonate isolated body 3 terminals with base plate ISI marked including taking down old unserviceable ceiling rose completeall as specified and directed.. |
54 | S&F LED batten surface / wall mountedwith specially designed powder coatedaluminium housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired up to terminal block, power consumption <=20W, luminaries lumen >2000 lm, system efficiency of > 100 lumens/W, driver efficiency>85%, power factor > 0.9, THD <20% as per IEC 61000-3-2, color temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) including taking down old unserviceable light fitting of any description complete all as specified and directed. Make:- Wipro/Philips/Bajaj/polycab/Havells |
55 | S&F LED batten surface / wall mountedwith specially designed powder coatedaluminium housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired up to terminal block, power consumption <=10W, luminaries lumen >2000 lm, system efficiency of > 100 lumens/W, driver efficiency>85%, power factor > 0.9, THD <20% as per IEC 61000-3-2, color temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) including taking down old unserviceable light fitting of any description complete all as specified and directed. Make:- Wipro/Philips/Bajaj/polycab/Havells |
56 | Supply and fix in replacement of single side connection LED T8 tube light rod 20 Watt, 6500K of four feet long into existing T8 conventional fluorescent tube light fitting after changing the necessary electric connections as required at site complete all as specified and directed. Make : Crompton, Cat No : LT8-20-865-2 ,Havells, Cat No : PHOTONULTRA1213T8SSTL20WLED865SPC, PHILIPS Cat no MAS LED tube 1200 mm 18 w 865T8 I - 2100 Lumen or equivalent in Wipro/Philips/Bajaj/polycab/Havells |
57 | Supply and fix in replacement of LED security light fitting 45 watt, 5700K with IP 66 protection comprises of a pressure die cast aluminium housing, heat resistance toughened glass, LED lenses, surge protector, electronic driver, etc and all accessories pre-wired including connecting up with PVC insulated copper conductor cable 1.5 Sq mm, 3 core as required for connections and 32 mm bore light grade G. I. tube mounting bracket of 1.5 meter in length, bend to shape at 140 degree in ‘L’ shape and fixed to wall by means of 02 nos. of 40 x 5 mm flat iron clamps, nuts, bolts and washers etc complete all as specified and directed. Make : Crompton, Cat No : LSTP-45-CDL or equivalent in Wipro/Philips/Bajaj/polycab/Havells |
58 | S&F 2 ft x 2ft recess mountedfull panel LED luminarieswith white powdercoatedhousing acting as heat sink and frame in CRCAsheet, high efficiency LED grade diffuser , in built electronic driver duly wired up to terminal block, power consumption< 36W, luminaries lumen > 3500lm and system efficiency >120lm/W, CRI>80, color temp -5700K, Ingress protection IP 20, , driver efficiency >85%, 50,000 burning hours(min) , range 150-270V AC and safety extra low voltage safe level <60V DC including taking down old unserviceable light fitting of any description complete all as specified and directed. Make:- Wipro/Philips/Bajaj/polycab/Havells |
59 | S&F 2 ft x 2ft recess mountedfull panel LED luminaries ( Warm White)with white powdercoatedhousing acting as heat sink and frame in CRCAsheet, high efficiency LED grade diffuser , in built electronic driver duly wired up to terminal block, power consumption< 36W, luminaries lumen > 3500lm and system efficiency >120lm/W, CRI>80, color temp -3000K, Ingress protection IP 20, , driver efficiency >85%, 50,000 burning hours(min) , range 150-270V AC and safety extra low voltage safe level <60V DC including taking down old unserviceable light fitting of any description complete and fixing of false ceiling paneling all as specified and directed. Make:- Wipro/Philips/Bajaj/polycab/Havells |
60 | Supply and fix in replacement of LED security light fitting 60 watt, 5700K with IP 66 protection comprises of a pressure die cast aluminium housing, heat resistance toughened glass, LED lenses, surge protector, electronic driver, etc and all accessories pre-wired including connecting up with PVC insulated copper conductor cable 1.5 Sq mm, 3 core as required for connections and 32 mm bore light grade G. I. tube mounting bracket of 1.5 meter in length, bend to shape at 140 degree in ‘L’ shape and fixed to wall by means of 02 nos. of 40 x 5 mm flat iron clamps, nuts, bolts and washers etc complete all as specified and directed. Make : Crompton Cat No.LSTP-45-CDL or equivalent in Wipro/Philips/Bajaj/polycab/Havells |
61 | S&F LED post top lantern 30-35 Watts with symmetric light distribution energy saving, environmental friendly IP65 spun aluminium landscape luminary with higher power LED as light source sample as approved by Engineer in charge Make:- Wipro/Philips/Bajaj/polycab/Havells |
62 | S&F LED flood light 250 Watts with aluminium die cast IP 66 with symmetric light distribution energy saving, environmental friendly suitable for high lighting architectural faced all as specified and directed. Make:-Wipro/Philips/Bajaj/polycab/Havells |
63 | S&F LED flood light 100 Watts with aluminium die cast IP 66 with symmetric light distribution energy saving, environmental friendly suitable for high lighting architectural faced all as specified and directed. Make:- Crompton/Philips/Bajaj/Polycab/Havells |
64 | Supply and fix exhaust fans single phase 230/240 Volts heavy duty metalicbody of size 300 mm sweep 1400 RPM ISI marked,and making connection with twisted copper flexibelwire 23/0.076 mm all as specified and directed. Make:- Bajaj/Havells/Crompton/Usha |
65 | Supply and fix exhaust fans single phase 230/240 Volts heavy duty metalicbody of size 225/230 mm sweep 1400 RPM ISI markedand making connection with twisted copper flexible wire 23/0.076 mm all as specified and directed. Make:- Bajaj/Havells/Crompton/Usha |
66 | Supply and fixing wall fan of 400 mm sweep, 220 - 240 volts, AC, 50 Hz 1330 RPM, 55 Watts power input, air delivery 65 Cum/minwith all accessories complete all as directed by Engineer - in - charge. Make:- Bajaj/Havells/Crompton/Usha |
67 | Supply and fix PVC exhaust fan 200 mm sweep AC single phase, 230/240 volts 50 Hz with louvers and making connection from ceiling rose with twisted copper flexible wire 23/0.076 mm all as specified and directed. Make:- Bajaj/Havells/Crompton/Usha |
68 | Supply and fixing ceiling fans complete with blades, down rods and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) all as specified and directed by Engr-in-Charge. Make:- Orient electric / cromptonHavells |
69 | Supply and fixing of stationery storage type electric BEE 5 star rated Hot Water Geyser of capacity 25 Ltr to operate on 230 volt AC,vertical type, white in colour, working pressure min 0.8 Mpa with glass lined coated tank, magnesium anode, adjustable thermostat, enamel coated incology heating element 2 KW, ABS plastic body including 4 nos full threaded fastner of size 100 x 10 mm with 2 Nos washer,complete all as specified and directed. Make: Bajaj/Racold/Usha/venus/Orient electric |
70 | PVC hose for hot /coldwater 450mm long with brass end nuts (ISI marked) suitable for 15mm dia GI tubing complete. |
71 | Material and labor for earthing complete with galvanized mild steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level steel earth plate connected with GI wire 04 mm dia by means oflug, bolts, nuts, check nuts, washers of galvanized iron or steel GI protection pipe 15 mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around GI earth plate, GI pipemedium grade 20 mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40 mm x 40 mm x 3 mm frame for pit cover including testing on completion complete all as specified and directed. |
72 | Supply, Installation, testing in door unit of split type Air Conditioner 1.5 TR single phase, 230 volts complete with all accessories as provided by the manufacturer complete all as directed. Make : Voltas/Dakin/Hitachi/LG/Carrier/Samsung |
73 | Supply, Installation, testing in door unit of split type Air Conditioner 2.0 TR single phase, 230 volts complete with all accessories as provided by the manufacturer complete all as directed. Make : Voltas/Dakin/Hitachi/LG/Carrier/Samsung |
74 | Taking down unserviceable compressor unit from ACs/water coolers/ refrigerators by dismantling all electrical/gas connection and S&F new sealed compressor unit complete including vacuuming, gas charging, connecting all electrical and gas pipe connection and testing completeall as directedfor the following capacities: - |
75 | Split/Window type AC of 1.5 ton capacity |
76 | Split/Window type AC of 2 ton capacity |
77 | Vertical type AC of 3 ton capacity |
78 | Split (Cassette type) AC of 3 ton capacity |
79 | Split (Cassette type) AC of 4 ton capacity |
80 | Tower AC of 1.5 ton capacity. |
81 | Water cooler 40/80 Ltr |
82 | Water cooler 60/120 ltr Make for srl item Nos. 36.01 to 36.08 :- Voltas/Carrier/LG/DAIKIN/ as per OEM |
83 | Taking down unserviceable condensor unit from AC by dismantling all electrical/gas connection and S&F new condensor unit complete including vacuuming, gas charging, connecting all electrical and gas pipe connection and testing completeall as directedfor the following capacity: - |
84 | Split/Window type AC of 1.5 ton capacity |
85 | Split/Window type AC of 2 ton capacity |
86 | Supply and fixing in repair Power circuit board of 1.5 TR Split AC |
87 | Supply and fixing in repair Power circuit board of 2.5 TR split AC |
88 | Supply and fixing in repair Power circuit board of inverter type split ac 1.5/2 TR |
89 | Supply and fixing in repair Power circuit board of window type ac 1.5/2.0 TR |
90 | Supply and fixing of remote control unit of spilt / window ac of 1.5 to 3 TR |
91 | Supply and fixing in repair Blower motor for fan of window type ac Make : AUE/CG/Usha/Bajaj |
92 | Supply and fixing in repair of Relay assembly of spit type AC Make : Sriram/Annapurna/C&S/L&T/ABB/SEIMENS |
93 | Supply and fixing of Over load protection of Windown and Split type AC Make : Sriram/Ranutrol//C&S/L&T |
94 | Supply and fixing ofRunning capacitorof Split and window type ac of capacities |
95 | Supply and fixing of repair of Starting capacitor for Window and Split type Acs Make for srl items Nos.41 & 42 :- Usha/Universal/ Bhel/ TIBCO/CAPCO |
96 | M&L for Dismantling of fans for rewinding with super enameled copper wire as per existing gauge /number of turns including heat varnish, overhauling, greasing and replacement of bearings complete with spray painting of the whole fan with blade and testing complete all as directed by Engineer-in-Charge for the following sizes: |
97 | Ceiling fan 1200 / 1400 mm |
98 | Exhaust fan 230 /300 mm |
99 | Pedestal/Wallmounted fan 400 mm |
100 | S&F Modular Electronic fan regulator 120Wincluding taking down old unserviceable fan regulator complete all as specified and directed. |
101 | S&F Electronic voltage stabilizer of 5 KVA capacity (suitable for wall mounted) for automatic operation, indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5%stabilizer complete all as directed. Make - V-GUARD / KEELINE / BLUE GUARD |
102 | Supply and fixing Power contactor 4 pole, 315 amps, 415Vincluding required cabling work complete and taking down unserviceable contactor all as directed. |
103 | Supply and fixing Auxiliary contactor suitablefor up to 400 KVA DG SetAMF Panel including taking down unserviceable contactor complete all as directed. |
104 | Supply and fixingControl Relay suitable for DG Set AMF panel of capacity up to 400 KVA including taking down unserviceable control relay complete all as directed. |
105 | Supply and fixingOverload Relay suitable for up to 400 KVA DG Set AMF Panel including taking down unserviceable over load relay complete all as directed. |
106 | Supply and fixingElectronic Timer suitable for up to 400 KVA DG Set AMF Panel including taking down unserviceable timer complete all as directed. |
107 | Supply and fixingLine voltage monitor suitable for up to 400 KVA DG Set AMF Panel including taking down unserviceable line voltage monitor complete all as directed . |
108 | Supply and fixingbattery charger unit suitable for 63 KVA to 400 KVA DG Setthrough AMF Panel including taking down unserviceable battery charger complete all as directed. |
109 | Servicing of DG Set by adjusting the fan belt with proper tension, cleaning the sulphated material deposited on battery terminals and refixing duly applying petroleum jelly and supply & fixing of Lubrication oil filter, Preline filter cartridge, Fuel filter cartridge, Air cleaner primary element, Air cleaner safety element, Filter coolant, Water separator, gaskets, Washers and leaking pipes/hoses including taking down unserviceable item complete all as directed for the following capacity DG set :- Note: (i) Servicing of DG Set shall be done by the OEM and the cost shall be included in the quoted rate. (ii) The required transportation, repairing tools shall be arranged by the contractor and the cost shall be included in the quoted rate. |
110 | DG Set 40 KVA( As per existing make - Kirloskar Green) |
111 | DG Set 63 KVA (As per existing make - Kirloskar) |
112 | DG Set 100 KVA(As per existing make - Kirloskar) |
113 | DG Set 125 KVA (As per existing make - Kirloskar) |
114 | DG Set 200 KVA(As per existing make - Cummins) |
115 | DG Set 400 KVA(As per existing make - Kirloskar) |
116 | Supply and filling of premium blue 15W /40 W lubricating oil and draining out the existing lubricating oil from the oil tank complete all as directed. Make: Kirloskar oil super/Cummins/Castrol |
117 | Supply and filling of coolant 50-50 premix and draining out the existing coolant from the radiator complete all as directed . Make: Kirloskar cool super plus/Cummins/Castrol |
118 | Excavation in trenches for laying of GI water tubing etc., getting out in soft/loose soil n.exc 1.5m wide and n.exc 1.5m depth complete all as specified and directed. |
119 | Returning,filling in trenches including spreading,leveling, watering and in layers n.exc 25cms thickwithout damaging pipes/special fittings as inany type of soil complete all as specified and directed. |
120 | Removing excavated materialsto a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed. |
121 | Taking up or down steel tubing and connections and supply and fixing 15mm dia GI tubing, medium grade with all fittings and fixed complete to walls and ceiling or laid in trenchescomplete all as directed. |
122 | All as per item no 58.01 but20 mm dia |
123 | All as per item no 58.01 but 25 mm dia |
124 | All as per item no 58.01 but 40 mm dia |
125 | All as per item no 58.01 but 50 mm dia |
126 | Supply and fix gun metal gate valve (ISI)marked with iron wheel head screwed both ends for iron pipe suitable for following bore of pipe including taking down old existing gate valve complete all as specified and directed for 15 mmborepipe |
127 | All as per item no 59 but20 mm dia |
128 | All as per item no 59 but 25 mm dia |
129 | All as per item no59but 40 mm dia |
130 | All as per item no 59 but 50 mm dia |
131 | M & L for attending complaints like no water supply in service tank, pipe line leakages etc and also removing air lock in married / OTM accommodation with help of required tools all as specified and directed including required minor fittings i.e. Tees, bends, nipple, union etc jointing material M seal etc for following sizes |
132 | 15 mmborepipe |
133 | 20 mmborepipe |
134 | 25 mmborepipe |
135 | 40 mm bore pipe |
136 | 50 mm borepipe |
137 | Checking the refrigerant system of window/split type AC of capacity 1.5/2/3/4 ton / tower ACfor detecting leaks and arresting the leaks with necessary brazing work after vacuuming the system and recharge the system with refrigerant gas including testing complete all as directed |
138 | Supply only refrigerant R-22 / 32 gas including charging to the required pressure for window/split type AC of any capacity and any make complete all as directed. |
139 | Supply only refrigerant R-134a/410 gas including charging to the required pressure for water cooler/refrigerator of any capacity and any make complete all as directed. |
140 | S & F Copper tube of the following size for gas/liquid with insulation for split type AC to be fixed on wall up to third floor including allarrangements and taking down unserviceable tube complete all as directed. |
141 | 5/8" size |
142 | 1/4" size |
143 | PVC water drain pipe 15/20mm dia including saddles and other accessories Note : (i) The ladders and safety equipment shall be provided by the contractor and cost of the same shall be deemed to be included in the quoted rate. (ii)While quoting the rate, height of the building up to 4 floors shall also be considered. |
144 | Shifting of Split type AC, any type/capacity up to third floor, from one position to a new position by removing all electrical connection and copper tube connection with proper way and making good the old existing position by cement plaster and painting with existing color and fixing of AC at new position including making all electrical connection, copper tube connection and all arrangements for fixing complete all as directed. Note :- Gas charging , extension of copper tube and cord cable shall be measured and paid separately under relevant item. |