Municipal Copr Of Greater Mumbai-MCGM has published Supply Installation Testing And Commissioning Of Fire And Electrical Works At Pedestrian Subway On Vasudev Balwant Phadke Chowk Near Metro Cinema In ‘A’ Ward. Submission Date for this Tender is 20-12-2023. Electrical Maintenance Tenders in ghatkopar Maharashtra. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying and installing, testing, perfect aligning and proper leveling and commissioning of fire service main pump, of 2820 LPM (Litres/min.) at 88m centrifugal type pump |
2 | SITC of Jockey Pump of 240 LPM at 88m head, |
3 | SITC of Booster Pump of 450 LPM at 35 m head |
4 | SITC of cubical typefloor mounted Fire Pump Control Panel fabricated from14g M.S. Sheet dulypowder coated finish of approvedshade |
5 | 200 mm |
6 | 150 mm |
7 | 100 mm |
8 | 80 mm |
9 | 65 mm |
10 | 50 mm |
11 | 25 mm |
12 | 200 mm |
13 | 150 mm |
14 | 100 mm |
15 | 80 mm |
16 | 65 mm |
17 | 50 mm |
18 | 25 mm |
19 | Supplying & Installing cast iron double flange butterfly valve 200 mm pls confirm this is butterfly valve |
20 | 150 mm |
21 | 100 mm |
22 | 80 mm |
23 | 50 mm |
24 | double flange NRV 200 mm |
25 | double flange NRV 150 mm |
26 | double flange NRV 100 mm |
27 | double flange NRV 80 mm |
28 | Providing & fixing bourden type Pressure guages of capacity 0 to 21 kg./sq.cm & least count of 0.25 kg/cm2, SS-Body Syfon Mounted with required accessories |
29 | Supplying and installing pressure switch with 12/15 mm Ø isolation valve, G.I. nipple, elbowetc. in an approved manner as per specification. |
30 | 3.5C x 95 Sq.mm Cu armoured cables |
31 | Cable End Termination For Aluminium Cables – 3.5C x 95Sq.mm |
32 | Earthings (GI) Strip, GI 50 x 6 mm |
33 | 2c x 1.5sqmm cable glands |
34 | Supplying and fabrication of MS Support with accessories. 50 x 50 x 6 mm of M.S.angle. |
35 | Providing & Fixing gunmetal breaching head as per IS:904 specification tested for 20 kg/cm. with 63 mm Dia4 nos. instantaneous type inlet and 150 mm dia flanges outlet with built in non-return valve for fire brigade connection to fire risers including companion flanges of Table E withnuts, bolts & washers etc. |
36 | Supplying & installing moulded HDP / Fibrewater tank. for -ve suction only, having capacity 1000 ltrs.fitted with necessary accessories complete as per specification |
37 | Supplying and fixing of Air release valve 25 NB, GunmetalCap release Type - Valevwith ball valve & accessories. |
38 | Supplying and installing Air Vessel of 300 mm Ø 1.5m in height M.S. tank installed inside pump house as per specification |
39 | C.I. GATE VALVE 150 mm dia |
40 | C.I. GATE VALVE 100 mm dia |
41 | Supplying and installing gun metal singleoutlet hydrant valve fitted with necessary accessories |
42 | Supplying Stainless Steel branch Pipe 63 mm Ø fitted with 20 mm dia detachable hexagonal nozzle as per specifications |
43 | Providing and fixing in position 2 lengths of 15 M long flexible canvas rubber lined hose reels 63 dia |
44 | Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve (size 400 x 400 x 400mm.) |
45 | Supplying and installing fire brigade Header (Siamese Connection) of 150 mm Ø for supplying water to wet riser system as per specification |
46 | Providing coating of Bitumen Paint & 4mm thick Wrapping as per IS 10221 for underground 100 mm Ring Main of Fire Fighting System. |
47 | Excavation for Underground piping |
48 | Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m high pressure polypropylene (Polyhose) long fitted with necessary accessories complete as per specification |
49 | Supplying, installing, testing and commissioning45 Deg & 90 Deg, Equal Tee ,Reducing Tee,Mechanical Tee ,Reducing Coupling, End Cap Coupling of MS pipe Supports and Universal Clamp with 10mm Tie Rod , Anchor fastner etc |
50 | Cement concrete foundation using M-20 cement concrete mix with J shaped foundation bolts where required. SUPPLYING |
51 | 120 mm OD / 103.5 mm I.D.Supply & Laying of double wall corrugated ( DWC) pipes of HDPE for underground cable protection as per IS |
52 | Excavating the trenches and refilling the same after the cable is laid in approved manner (Size of trench: 750 mm deep, 600 mm wide) in concrete/ masonary / asphalt. 1 Cu. Mtr. = 2.2 RMT. And reinstatement. |
53 | Providing, detailing, composite fabricating members like Trusses, Nsteel members fabricated using M.S. hollow tubular steel sections (circular & rectangular pipes), of TATA Structura Make or equivalent conforming to IS 1239 part 1 and 2 and of grade Fe 250 as per specifications and approved fabrication drawings (which are to be prepared by Contractor and got approved from Engineer), including transportion of the same to site, erection of structural steel members for all heights & at all levels, provision of necessary erection bolts, fixing bolts, nuts, washers, cleats, stiffeners, gussets, base plate, and all necessary operations like preheating as per specifications, straightening, bending, cutting, drilling, grinding, machining if specified, welding, grinding, removing the welding burr and preparing surface for painting with wire brush cleaning and applying two coats of epoxy red oxide zinc phosphate primer of 30 microns each and two coats of Epoxy Corrosion Resistant Enamel paint of 30 microns after fabrication including touching up with spray painting after erection etc complete as directed by Engineer |
54 | Bare Galvalume/zincalume sheets for roofing |
55 | Rubber mat 2mm thick size 3x5 feet |
56 | Earthing station with 600 mm x 600 mm x 6 mm galvanised iron plate |
57 | Supply & installation of Earth conductor |
58 | Bare G.I. Conductor size 10 SWG |
59 | G.I.Heavy grade "C" class pipes 40 mm |
60 | G.I.Heavy grade "C" class pipes 32 mm |
61 | Supplying & erecting vane type water flow detector suitable for detecting flow of water |
62 | Providing and fixing 15mm gunmetal sprinkler head with quartzoid bulband set to operate at specified temperature pendent/ upright/ side wallas per the location indicated on the drawings. sprinklers 68 degree C FOC/UL/FM approved complete with socket nipple, adaptoretc. Sprinkler shall be pendant type. Temperature of operation 68 deg.C A. Side wall type in brass chrome finish |
63 | Providng and fixing in position sprinkler guards/Rosset Plateto protect open sprinkler in basement from mechanical damage. |
64 | Providing & fixing of Stainless steel corrugated flexible pipe (hose) for dropping sprinklers below false ceiling, pipe shall be 16 bar pressure rating and 1000 mm long 25 mm dia with union / reducer collar, clamps etc. as required. |
65 | Providing and fixing 150mm installation control valve assembly with turbine type automatic alarm to be connected with control valve, drainvalve, test valve and piping as per manufacturer’s specifications complete in all respects. |
66 | Supplying and erecting D.C.P. type Fire Extinguisher 6 kg capacity cartridge type with Gun Metal cap 150 gram CO2 gas cartridge |
67 | Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 9 kg capacity with necessary clamp for erection on Wall. |
68 | CO2 Fire Extinguisher 4.5 kg |
69 | Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs |
70 | Supplying & Fixing fire retardant curtains with window Rod |
71 | Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, |
72 | Supply, Installation, testing & commissioning of addressable 2 loop main fire alarm electronic control panel, expendable up to 4 loop & having maximum 250 devices (any combination detectors plus devices) per loop & Audio/ Visual alarm complete as per IS: 2189 specification |
73 | SITC of Active Repeater panel with all accessories, which shall be replica of main fire alarm panel with control keys I,e. Mute, silent & sounder alarm. |
74 | SITC of expandable Loop card for main fire alarm electronic control panel, shall support 254 devices both detectors and modules and shall support both class "A" & class "B" wiring. |
75 | SITC of Intelligent multi- criteria Detector along with mounting box & termination glands. |
76 | SITC of Intelligent Photoelectric Smoke Detector along with mounting box & termination glands. |
77 | SITC of Addressable Manual call point/ station with mounting back box |
78 | SITC of Addressable control Relay module with required accessories along with junction box, glands and terminators ( For AC trip off, Access trip off, PA system, sprinkler flow switch, lift interface, sounder, fire fighter & telephone jack) |
79 | Supply, installation, testing & commissioningof Addressable type fault Isolator for isolating shorted, de-linked and loose circuits between two successive fault isolators with automatic resetting arrangement to be interconnecting to loop cable complete as required conforming to BS5839 Standards and Duly Approved byEN54/LPCB |
80 | Supply, installation, testing & commissioningof Response Indicators outside the rooms for getting fire indications of detectors installed above false ceiling area interconnecting to loop cable complete as required |
81 | SITC of Strobe Lights along with mounting box & termination glands |
82 | Supply, installation Cable Gland of 16 mm |
83 | SITC of 2C x 1.5 Sq.mm FRLS-H Armoured cable. ATC conductor stranded, PVC insulated to form a core, Cores laid up, Overall shielded with Alu-mylar tape with tinned copper drain wire of size 0.5 Sq. mm, PVC innersheathed G.I. Wire armoured, PVC sheathed cable.(RED COLOR) |
84 | Supply and installation of Booster amplifier 500W with all accessories. |
85 | Supply, installation, testing & commissioningof Dynamic Vocal& Speech Microphone |
86 | 6W/100V. PA Ceiling Speaker |
87 | Supply & installation of 6W/100V wall mounting box speakers. |
88 | Speaker wiring using 40/36 cable with PVC conduit |
89 | SITC of Auto glow signage for Emergency Fire Exit |
90 | SITC of Auto glow signage for Do not use lift in case of Fire etc |
91 | Providing and fixing fire doors with 2 hour fire rating conforming to IS: 3614 (Part 2), BS 476 (Parts 20 & 22), ISO 834 ; 45 mm thick fully flush, double skin door shell with lock seam joints at stile edges made from 1.25 mm thick galvanized steel sheet including door frames made from 1.6 mm thick galvanized steel sheet formed to double rebate profile of size 143 mm x 57mm as per manufacturer"s instructions, door frames and shutter primed with Zinc Phosphate stoving Primer and finished with Polyurethane Aliphatic grade or epoxy paint including ironmongery consisting of stainless steel ball bearing butt hinges 3 mm thick fixed flush to the frame and shutter, full width horizontal handles (panic bar), concealed flush bolts, door closers, other standards fixtures and fasteners, etc. complete for the following clear opening sizes: |
92 | CSMC 5% for 2nd year after completing 1 year DLP. |
93 | CSMC 5% for 3rdyear |
94 | CSMC 5% for 4thyear |
95 | CSMC 5% for 5thyear |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy