Construction Of 33 Kv Stp Jal Nigam Bay Along With Erection Of Structure, Equipment, Pilfer Proof Metering, Supply Of Material And Other Associated Work At 220 Kv S/S Azizpur Under Etd-Shahjahanpur., shahjahanpur-Uttar Pradesh

Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Construction Of 33 Kv Stp Jal Nigam Bay Along With Erection Of Structure, Equipment, Pilfer Proof Metering, Supply Of Material And Other Associated Work At 220 Kv S/S Azizpur Under Etd-Shahjahanpur.. Submission Date for this Tender is 20-12-2023. Sewage Treatment Plant Tenders in shahjahanpur Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

40950596
Construction Of 33 Kv Stp Jal Nigam Bay Along With Erection Of Structure, Equipment, Pilfer Proof Metering, Supply Of Material And Other Associated Work At 220 Kv S/S Azizpur Under Etd-Shahjahanpur.
Open Tender
Indian
Uttar Pradesh
shahjahanpur
20-12-2023

Tender Details

Construction Of 33 Kv Stp Jal Nigam Bay Along With Erection Of Structure, Equipment, Pilfer Proof Metering, Supply Of Material And Other Associated Work At 220 Kv S / S Azizpur Under Etd-Shahjahanpur.

Key Value

Document Fees
INR 885 /-
EMD
INR 5000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : Construction of 33 KV STP Jal Nigam Bay alongwith Erection of Structure, Equipment, Pilfer Proof Metering, Supply of material and other associated Work at 220 KV S/S Azizpur under ETD-Shahjahanpur.
Sl. No. Item Description
1Erection of following Main & auxiliary structure as per Drawing/BOM is to be carried out by the Contractor at 220KV S/S AzizpurAll the duly stacked members of structure are to be shifted from store to work site, tightening of Nut Bolts ,washers, Fastening of Beams applying with standard practice. All Labour, T&P etc. will be arranged by the contractor at his own cost.
2Main Structure
3EKR(02Set x 0.87017/Set= 1.74034MT)
4BBR(02Set x 0.52051/Set= 1.04102MT)
5APR(02Set x 0.09381/Set= 0.18762MT)
6YMR(02Set x 0.0289/Set= 0.0578MT)
7Auxiliary Structures:
8ABL(03Set x 0.35992/Set=1.07976MT)
9ALP(09Set x 0.12103/Set= 1.08927MT)
10Erection offollowing equipment in proper alignment in switchyard on the erected Structures as per Manufactures Drawingor as per direction of Supervising Engineer, after leveling including shifting the equipment from Store to site of work etc. alongwith their Junction Boxes, Control Cubicles and accessories and all relalted works to complete the erection work at 220KV S/S Azizpur. All Labour , T&P etc. will be arranged by the contractor at his own cost
1136 KV VCB
1236 KV Bus Isolator
1336 KV Line Isolator
1436 KV C.T. 400/200/1Amp. With Junction Box
1536 KV P.T. with Junction Box
1633KV Simplex type Tripple fdr. control & Relay panel
17Metering Cubicle for ABT Energy Meter along with 02 Nos. ABT Meters
18Making of Jumper of all equipment, Jumpring work of all equipment horizontally from equipment to equipment and vertically from bus to equipment with ACSR Panther Conductor ,fitting of suitable clamps including cutting, bending, giving proper shape. All required skilled labour, T&P shall be arranged by the contractor for completion of work. Conductor and Clamp will be provided by the Department.
1933 KV Line Bay ( Jumpring from 33KV Main Bus to 33KV Transfer Bus)
20Opening of Trench Cover, Laying and dressing of following sizes of Control Cables in cable trench.(Required Control Cable will be provided by Department)
212C X 2.5 sq mm
224C X 2.5 sq mm
236C X 2.5 sq mm
24Termination of control cable(Per Core Both End) of various euipment with switchyard to control panel and drilling of holes in control panel and marshalling box .complete with cable glands, ferrules and other associated works to complete the job.
25Earthing of following Auxiliary Structure, Equipment with the help of 50x6 mm & 25x6 mm size M.S. Flat alongwith cutting, straightening, bending , laying and Painting of all type ofjoints , risers, Strips with one coat of Red Oxide and two coat of Green enamel paint in all side of surface as per Drawing of earthingand standard practice including cost of all required consumable material T&P , labour tec. for proper completion of work.
26Main & Auxiliary Structure(50x6 mm MS Flat): ABL-03, ALP- 09,EKR-02 & Metering Cubicle/C&R Panel
27Equipment(75x10/50x6mm MS Flat)
2836KV VCB-01 Nos.
2936KV CT with Junction Box-03 Nos.
3036KV PT with Junction Box-03 Nos.
31Cable Trench(25x6 mm MS Flat)
32Painting of Earthing strip (R. Mtr.) withcoat red oxide 2 coat paint with green ISI paint including vertical support.
3325x6 mm
3450x6 mm
3575x6mm
36Providing of earthmat in extension portion of switchyard after digging of 0.7 meter deep trench in earth and laying of MS round bar 40mm dia in digged trench with all other associated works.
37Preparing of MS Electrodes 3 meter long in conical shape at one end and driving them in earth as per drawing
38Making lap joint in 40 MM dia MS round Bar and painting them in black bituminous paint.
39Making of cross joint with MS round bar 40 mm dia with painting of each jointwith black bituminous paint.
40Pilfer proofing of the cable with G.I. pipe of followng sizes complete with cutting, bending &fixing of pipe alongwith making threads, elbow and other required material from 33 KV CT & PT in switchyard to energy meter in control room including all other work which are required for complition of work
41G.I. pipe 2 " Dia
42G.I. pipe 1 " Dia
43Supply and installation of 150 Watt LED flood light fitting with lamp of latest design complete with De-Fuser suitable for outdoor installation with IP65 enclosure (Power supply single phase 230 volt 50 Hz AC) .
44InstallationofName plate for New 33KV Bays of size 150x150 mm made of 2 mm thick aluminium sheet cover with 2 mm Retro reflective sheet of following size with details/name written by 3M HIP Retroreflective materials in white colour letter to be fixed with the help of nut and bolts already installed in equipmets in switchyard with all cost of plates nut bolts miscelleneous materials T&P and labour .Work shall be done as per tech. specification under the direction & supervision of concerned AE/JE of 220KV S/S Azizpur.
45Carriage of structure through private truck from EFU Naini (Allahabad) to 220KV Sub-station, Azizpur alongwith sorting, shifting and loading at Naini and unloading and stacking at 220KV S/S Azizpur for construction of 1 Nos. 33 KV bay at 220KV Sub-station, Azizpur.
46Sorting out and stacking of main & auxilary structure as per BOM at EFU Naini (Prayagraj)
47Loading of structure on Pvt. Truck / trailer at EFU Naini.
48Transportation of structure from EFU Naini, Allahabad to 220KV S/S Azizpur(LS 430Km.)
49Unloading and proper stacking of structure parts at 220KV S/S Azizpur as per BOM
50“04”BoltedtypePGClampsdulymadeofLM-6Aluminium Alloy suitable for Zebra to Panther conductor Complete with 4 No. 16 x90,mm size GI Nuts & Bolts, spring/plainwashers as per Sample.
51“03”BoltedtypePGClampsduly madeofLM-6Aluminium Alloy suitableforPanthertoPantherconductorCompletewith3No. 16x90 min size GI Nuts & Bolts, spring/plainwashers as per Sample.
52“04”BoltedtypePGClampsdulymadeofLM-6Aluminium Alloy suitable for Tarantulla to Panther conductor Complete with 4 No. 16 x90,mm size GI Nuts & Bolts, spring/plainwashers as per Sample.
5336KV Post Insulator
54Hot Dip Galvanized Hexagon Round Hexagon Head Transmission Tower Bolt Nuts and Washers as per Anex.-2
55HRH 16MM Dia Bolt with NUT 40MM Long- 212.52Kg
56HRH 16MM Dia Bolt with NUT 45MM Long-88.62Kg
57HRH 16MM Dia Bolt with NUT 50MM Long-32.26Kg
58HRH 16MM Dia Bolt with NUT 55MM Long-6.24Kg
5916MM Dia Flat Washer 5THK-110.11Kg
60Fire fighting System
61Portable AFF mechanical foam type Fire Extinguisher complete with initial charge hose pipe and all other accessories and fittings as per IS 1024 trolley mounted 45/50 lit. cap.
62Supply of following fire extinguisher carbon dioxide as per IS Specn. No. 2878/1986 and as per technical specifications
6311/9KG
644.5KG
65Dry Chemical Powder Type Fire Extinguisher
66Supply of Dry Chemical Powder Type Fire Extinguisher of 4.5Kg Capacity confirming with 2171/1985 and as per technical specifications
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail