Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Construction Of 33 Kv Stp Jal Nigam Bay Along With Erection Of Structure, Equipment, Pilfer Proof Metering, Supply Of Material And Other Associated Work At 220 Kv S/S Azizpur Under Etd-Shahjahanpur.. Submission Date for this Tender is 20-12-2023. Sewage Treatment Plant Tenders in shahjahanpur Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Erection of following Main & auxiliary structure as per Drawing/BOM is to be carried out by the Contractor at 220KV S/S AzizpurAll the duly stacked members of structure are to be shifted from store to work site, tightening of Nut Bolts ,washers, Fastening of Beams applying with standard practice. All Labour, T&P etc. will be arranged by the contractor at his own cost. |
2 | Main Structure |
3 | EKR(02Set x 0.87017/Set= 1.74034MT) |
4 | BBR(02Set x 0.52051/Set= 1.04102MT) |
5 | APR(02Set x 0.09381/Set= 0.18762MT) |
6 | YMR(02Set x 0.0289/Set= 0.0578MT) |
7 | Auxiliary Structures: |
8 | ABL(03Set x 0.35992/Set=1.07976MT) |
9 | ALP(09Set x 0.12103/Set= 1.08927MT) |
10 | Erection offollowing equipment in proper alignment in switchyard on the erected Structures as per Manufactures Drawingor as per direction of Supervising Engineer, after leveling including shifting the equipment from Store to site of work etc. alongwith their Junction Boxes, Control Cubicles and accessories and all relalted works to complete the erection work at 220KV S/S Azizpur. All Labour , T&P etc. will be arranged by the contractor at his own cost |
11 | 36 KV VCB |
12 | 36 KV Bus Isolator |
13 | 36 KV Line Isolator |
14 | 36 KV C.T. 400/200/1Amp. With Junction Box |
15 | 36 KV P.T. with Junction Box |
16 | 33KV Simplex type Tripple fdr. control & Relay panel |
17 | Metering Cubicle for ABT Energy Meter along with 02 Nos. ABT Meters |
18 | Making of Jumper of all equipment, Jumpring work of all equipment horizontally from equipment to equipment and vertically from bus to equipment with ACSR Panther Conductor ,fitting of suitable clamps including cutting, bending, giving proper shape. All required skilled labour, T&P shall be arranged by the contractor for completion of work. Conductor and Clamp will be provided by the Department. |
19 | 33 KV Line Bay ( Jumpring from 33KV Main Bus to 33KV Transfer Bus) |
20 | Opening of Trench Cover, Laying and dressing of following sizes of Control Cables in cable trench.(Required Control Cable will be provided by Department) |
21 | 2C X 2.5 sq mm |
22 | 4C X 2.5 sq mm |
23 | 6C X 2.5 sq mm |
24 | Termination of control cable(Per Core Both End) of various euipment with switchyard to control panel and drilling of holes in control panel and marshalling box .complete with cable glands, ferrules and other associated works to complete the job. |
25 | Earthing of following Auxiliary Structure, Equipment with the help of 50x6 mm & 25x6 mm size M.S. Flat alongwith cutting, straightening, bending , laying and Painting of all type ofjoints , risers, Strips with one coat of Red Oxide and two coat of Green enamel paint in all side of surface as per Drawing of earthingand standard practice including cost of all required consumable material T&P , labour tec. for proper completion of work. |
26 | Main & Auxiliary Structure(50x6 mm MS Flat): ABL-03, ALP- 09,EKR-02 & Metering Cubicle/C&R Panel |
27 | Equipment(75x10/50x6mm MS Flat) |
28 | 36KV VCB-01 Nos. |
29 | 36KV CT with Junction Box-03 Nos. |
30 | 36KV PT with Junction Box-03 Nos. |
31 | Cable Trench(25x6 mm MS Flat) |
32 | Painting of Earthing strip (R. Mtr.) withcoat red oxide 2 coat paint with green ISI paint including vertical support. |
33 | 25x6 mm |
34 | 50x6 mm |
35 | 75x6mm |
36 | Providing of earthmat in extension portion of switchyard after digging of 0.7 meter deep trench in earth and laying of MS round bar 40mm dia in digged trench with all other associated works. |
37 | Preparing of MS Electrodes 3 meter long in conical shape at one end and driving them in earth as per drawing |
38 | Making lap joint in 40 MM dia MS round Bar and painting them in black bituminous paint. |
39 | Making of cross joint with MS round bar 40 mm dia with painting of each jointwith black bituminous paint. |
40 | Pilfer proofing of the cable with G.I. pipe of followng sizes complete with cutting, bending &fixing of pipe alongwith making threads, elbow and other required material from 33 KV CT & PT in switchyard to energy meter in control room including all other work which are required for complition of work |
41 | G.I. pipe 2 " Dia |
42 | G.I. pipe 1 " Dia |
43 | Supply and installation of 150 Watt LED flood light fitting with lamp of latest design complete with De-Fuser suitable for outdoor installation with IP65 enclosure (Power supply single phase 230 volt 50 Hz AC) . |
44 | InstallationofName plate for New 33KV Bays of size 150x150 mm made of 2 mm thick aluminium sheet cover with 2 mm Retro reflective sheet of following size with details/name written by 3M HIP Retroreflective materials in white colour letter to be fixed with the help of nut and bolts already installed in equipmets in switchyard with all cost of plates nut bolts miscelleneous materials T&P and labour .Work shall be done as per tech. specification under the direction & supervision of concerned AE/JE of 220KV S/S Azizpur. |
45 | Carriage of structure through private truck from EFU Naini (Allahabad) to 220KV Sub-station, Azizpur alongwith sorting, shifting and loading at Naini and unloading and stacking at 220KV S/S Azizpur for construction of 1 Nos. 33 KV bay at 220KV Sub-station, Azizpur. |
46 | Sorting out and stacking of main & auxilary structure as per BOM at EFU Naini (Prayagraj) |
47 | Loading of structure on Pvt. Truck / trailer at EFU Naini. |
48 | Transportation of structure from EFU Naini, Allahabad to 220KV S/S Azizpur(LS 430Km.) |
49 | Unloading and proper stacking of structure parts at 220KV S/S Azizpur as per BOM |
50 | “04”BoltedtypePGClampsdulymadeofLM-6Aluminium Alloy suitable for Zebra to Panther conductor Complete with 4 No. 16 x90,mm size GI Nuts & Bolts, spring/plainwashers as per Sample. |
51 | “03”BoltedtypePGClampsduly madeofLM-6Aluminium Alloy suitableforPanthertoPantherconductorCompletewith3No. 16x90 min size GI Nuts & Bolts, spring/plainwashers as per Sample. |
52 | “04”BoltedtypePGClampsdulymadeofLM-6Aluminium Alloy suitable for Tarantulla to Panther conductor Complete with 4 No. 16 x90,mm size GI Nuts & Bolts, spring/plainwashers as per Sample. |
53 | 36KV Post Insulator |
54 | Hot Dip Galvanized Hexagon Round Hexagon Head Transmission Tower Bolt Nuts and Washers as per Anex.-2 |
55 | HRH 16MM Dia Bolt with NUT 40MM Long- 212.52Kg |
56 | HRH 16MM Dia Bolt with NUT 45MM Long-88.62Kg |
57 | HRH 16MM Dia Bolt with NUT 50MM Long-32.26Kg |
58 | HRH 16MM Dia Bolt with NUT 55MM Long-6.24Kg |
59 | 16MM Dia Flat Washer 5THK-110.11Kg |
60 | Fire fighting System |
61 | Portable AFF mechanical foam type Fire Extinguisher complete with initial charge hose pipe and all other accessories and fittings as per IS 1024 trolley mounted 45/50 lit. cap. |
62 | Supply of following fire extinguisher carbon dioxide as per IS Specn. No. 2878/1986 and as per technical specifications |
63 | 11/9KG |
64 | 4.5KG |
65 | Dry Chemical Powder Type Fire Extinguisher |
66 | Supply of Dry Chemical Powder Type Fire Extinguisher of 4.5Kg Capacity confirming with 2171/1985 and as per technical specifications |