| Sl. No. | Item Description |
| 1 | PART (A): |
| 2 | SUPPLY ITEMSDesign, Engineering, Supply,Inspection, Documentation, dispatch to site for the following items.General Notes:a. All items under Part (A)shall be quoted as per BOQ description,enclosed Single Line Diagrams (SLD), Technical specification and data sheets for supply to site including charges towards TPI, packing & forwarding, loading, transportation, transit insurance, unloading, stacking at project site.b. The respective items shall also include supply of commissioning spares as defined in the Tender.c. Third party inspection (TPI) for the supply items shall be in scope of successfullbidder. d. The TPI agency shall be as per the approved list specified in the tender document. Dispatch clearance by TPI.e. Preparation and submission of drawings/SLDs/Datasheet, wiring diagram etc for approval of IOCL/PMCf. Prior to procurement of materials under supply, clearance of all materials to be supplied shall be based on compliance to approved Technical Specification/ Data Sheet/Drawings to be submitted by successful bidder to IOCL/PMC, including applicable Quality Assurance Plan (QAP)/Inspection Test Plan (ITP) after award of contract.g. Cables: FRLS & FR/FS | FS to be used as per OISD provisions inside the dyke.h) Bidder to note that LT/MV Switchgear/Panels manufactured and tested at OEM\"s works shall only be acceptable. However, LT/MV Switchgear/Panels manufactured and tested at OEM\"s Authorized Channel Partner works may also be acceptable if OEM authorizes such Channel partner for this Project and Design & QC of these Panels are verified and vetted by OEM for this Project. |
| 3 | PART A: Items under this section are categorised under GST rate of 18%.Bidders to confirm the GST rate for each item in the price bid BOQ. |
| 4 | 11kV GANG OPERATED DEVICE : Supply of 11kV Gang Operated Device with Isolator, earth Switch and 200A Fuse along with Lightning arrestor, Outdoor, H-Pole structure mounted as per attached Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1), specification, data sheet. The Outgoing Cable shall be connected by 11kV (E) grade Cable End termination Kits as per required Cable size and conductor material.Location: Switchyard. |
| 5 | Supply of trivector meter as per state electricity approved make for tariff metering including metering enclosure. |
| 6 | 11kV SWITCHBOARD: Supply of 11kV, 1250A, 40kA for 1 sec, VCB Panel, 3 Phase - 3 Wire, Indoor, Single front, Floor mounted, Aluminium Bus bar, IP5X, IAC Internal Arc 40kA for 1 sec (AFLR), fully drawout type ICOG Panel (Incoming and Outgoing Type) comprising Vaccum Circuit Beraker withNumerical relay, MFM, auxiliary relay,CTs,PTs ,indication lamp, switches along with Weather proof double compression Ni plated brass cable gland and crimping type cable lugs for all incoming and outgoing cables as per attached Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1), specification, data sheet. Panel shall be suitable for Top Busduct entry or Bottom cable entry. Location: MCC Room |
| 7 | PART A: Items under this section are categorised under GST rate of 18%.Bidders to confirm the GST rate for each item in the price bid BOQ. |
| 8 | DISTRIBUTION TRANSFORMER & LIGHTING TRANSFORMER: |
| 9 | DISTRIBUTION TRANSFORMER : Supply of 2 MVA, 11kV/0.433kV, Dyn11, Oil filled, ONAN type, %Z=6.25 + 10%, copper winding Transformer withOCTC (+5% TO -5% IN STEPS OF ±2.5%)along with weather proof double compression Ni plated brass cable glands and cable lugs for incoming and outgoing cables and all other accessoriesfor Transformer as per attached specification/Data sheet. Transformer secondary shall be suitable for sandwich busduct. The supply includes first fill of transformer oil and all consumables.Transformer shall be complete with minimum accessories as follows: Complete set of gaskets, Silica Gel Breather, set of valves, Buchholz relay, complete winding temperature indicating equipment (WTI), Oil Temperature Indicating equipment (OTI), Pressure relief device with trip contacts, bushing of each type, CTs of each type for 51G & 64R as per attached Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and Oil Level Gauge etc. as per specification. The item includes Heat run test also as per relevant standard & codes. CTs shall be provided as per SLD.Location: Outdoor |
| 10 | LIGHTING TRANSFORMER(NORMAL POWER): Supply of 150 kVA, 415V/433V, Dyn11, Indoor, copper winding Cast resin Dry type transformer with OCTC +5% to -5% taps in steps of 2.5%along with Weather proof double compression Ni plated brass cable gland and cable lugsfor all incoming and outgoing cables & with all accessories as per attached technical specification/data sheets.Transformer shall be complete with minimum accessories as follows: Complete set of gaskets, winding temperature indicating equipment (WTI), bushing of each type etc. as per Specification/Data sheet/SLD. The item includes Heat run test also as per relevant standard & codes.Location: MCC Room |
| 11 | LIGHTING TRANSFORMER(EMERGENCY POWER): Supply of 100 kVA, 415V/433V, Dyn11, Indoor, copper winding Cast resin Dry type transformer with OCTC +5% to -5% taps in steps of 2.5%along with Weather proof double compression Ni plated brass cable gland and cable lugsfor all incoming and outgoing cables & with all accessories as per attached technical specification/data sheets.Transformer shall be complete with minimum accessories as follows: Complete set of gaskets, winding temperature indicating equipment (WTI), bushing of each type etc. as per Specification/Data sheet/SLD. The item includes Heat run test also as per relevant standard & codes.Location: MCC Room |
| 12 | DIESEL GENERATOR SET ( 1010 KVA Diesel Generator)Supply of 415 V, 1010 kVA (Prime Rated)silent DG Set as per enclosed Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1), Control panel, Control cabling between DG & DG PCC etc., Acoustic encloser, Exhaust system, elbow, bellows, AVM pads, lube oil system, cooling system, Diesel oil system, including External Day Tank of990 litre capacity or more as per technical specifications withmagnetic level switch,inter connecting control cables and cable accessories (including weather proof double compression Ni plated brass cable glands and cable lugs) between DG enclosure & DG PCC, Base Channels etc. as per attached specifications,data sheet & SLD, First filling of engine oil, lubricant etc.complete with all required accessories. Height of Stack shall be as per PCB norms.Performance load test at site, Residential silencer, spark arrestor, complete stack, ladder, provision of testing for pollution, one number Lightning arrestor (1000mm long 20mm dia.).Aviation obstruction lamp ( 2 x 15 W LED ultrabright ( RED) colour ) for DG Set stack shall be in the scope of Bidder. Note: Following items shall be paid seperately in respective items :a. Supply of LT Power cables from DG set to PCC (Refer attached SLD) and external earthing system for DG sets.b. Civil Works for DG/Stack foundations & supporting structural steel arrangement of Exhaust pipe shall be paid seperately.c. Exhaust Pipe including Asbestos rope, glass wool insulation & cladding in Aluminium sheeeting. |
| 13 | Supply of Composite DG Panel (Common for DG-1 & DG-2 of 1010 KVA each) comprising of DG PCC, DG synchronizing and DG AMF Features). The DG PCC shall have IP-65 protection. |
| 14 | DIESEL GENERATOR SET ( 750 KVA Diesel Generator)Supply of 415 V, 1 No x 750 kVA (Prime Rated)silent DG Set with DG PCC comprising of AMFpanel as per enclosed Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1), Control panel, Control cabling between DG & DG PCC etc., Acoustic encloser, Exhaust system, elbow, bellows, AVM pads, lube oil system, cooling system, Diesel oil system, including External Day Tank of990 litre capacity or more as per technical specifications withmagnetic level switch,inter connecting control cables and cable accessories (including weather proof double compression Ni plated brass cable glands and cable lugs) between DG enclosure & DG PCC, Base Channels etc. as per attached specifications,data sheet & SLD, First filling of engine oil, lubricant etc.complete with all required accessories. Height of Stack shall be as per PCB norms.Performance load test at site, Residential silencer, spark arrestor, complete stack, ladder, provision of testing for pollution, one number Lightning arrestor (1000mm long 20mm dia.).Aviation obstruction lamp ( 2 x 15 W LED ultrabright ( RED) colour ) for DG Set stack shall be in the scope of Bidder. Exhaust pipe {(a) Asbestos rope lagging from DG exhaust up to silencerfor insulation (dia 250mm or as per manufacturer) b) Glass wool insulation and cladding in Aluminium sheeting (24 G) for DG sets beyond silencer (dia 350mm or as per manufacturer) as per manufacturer\"s recommendations/CPCB -CEA Regulations}. Note: Following items shall be paid seperately in respective items :a. Supply of LT Power cables from DG set to PCC (Refer attached SLD) and external earthing system for DG sets.b. Civil Works for stack foundations & supporting structural steel arrangement of Exhaust pipe shall be paid seperately.c. Exhaust Pipe including Asbestos rope, glass wool insulation & cladding in Aluminium sheeeting. |
| 15 | Supply of Exhaust Pipe of suitable size as recommended by OEM including Asbestos rope, glass wool insulation & cladding in Aluminium sheeting. Exhaust pipe of suitable size as per IS:1239/3589 schedule 20 {(a) Asbestos rope lagging from DG exhaust up to silencerfor insulation (dia 250mm or as per manufacturer) b) Glass wool insulation and cladding in Aluminium sheeting (24 G) for DG sets beyond silencer (dia 350mm or as per manufacturer) as per manufacturer\"s recommendations/CPCB -CEA Regulations}. Note: The measurement shall be done for the stack length beyond the exhaust silencer. |
| 16 | LT BUSDUCT (FROM TRANSFORMER TO PCC) :Supply of 415V, 3200A, 50kA for 1 sec, 3Phase, 4 Wire , Sandwich type BusDuct with Aluminium Busbar, 2.5 mm thick Aluminium enclosure, nut bolts, straight runs, 90 deg bends, bellows, flanges, Phase change over, Adaptor box, elbows, offsets, flexible connections, wall frame assembly, inspection cover as required. This shall also include supply of space heaters, inside & outside earthing, all hardware complete in all respect. Refer enclosed Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1).Note: a) Roof supports for the bus duct shall be part of the rates to be quoted. Other structural items required shall be measured and paid separately under respective items. b) Measurement of length of bus duct shall be along the central axis of the bus ductc) Busduct & panels shall be designed in such a way that phase cross over shall not be required. If it is required, cost of the same shall be borne by the Contractor without any extra cost to IOCL. |
| 17 | Straight Run Feeder, IP 65 (For Outdoor portion of Busduct) including all accessories such as space heater, nut, bolt washer, Earthing, Threaded rod for supports, including bellows etc. |
| 18 | Straight Run Feeder, IP 54 (For Indoor portion of Busduct) including all accessories such as space heater, nut, bolt washer, Earthing, Threaded rod for supports, including bellows etc. |
| 19 | Flange End with Equilizer/ Shorting Plate |
| 20 | Horizontal bend / Vertical Bend, elbows (Indoor) |
| 21 | Horizontal bend / Vertical Bend, elbows (Outdoor) |
| 22 | Tinned Copper Braided Flexibles (with Hardware - Nuts and Bolts) |
| 23 | Adaptor Box |
| 24 | 415V SWITCHBOARDS:LV switchboards shall be sheet steel enclosure, free standing, floor mounting, compartmentalised & with Aluminium Earth bus bars. Panel shall be with hinged doors, with neoprene gasket, 2 Nos earth terminal shall be provided at the Panel frame with extension link for earthing connections, with pad locking arrangement & along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders . The enclosure of the Panel shall have IP52 degree of protection. Incoming & outgoing feeders with ACB/MCCB, CTs/PTs, Relays/ Contactors, meters, space heaters, MFM, selector switches, indication lamps etc.as per applicable SLDs.Colour shade of final paint shall be RAL 7032 or as approved by IOCL. The item is inclusive of the stenciling/ lettering of the LT/HT Panel Boards/Control Panels/LDBs & PDBs/Motors etc. |
| 25 | POWER CONTROL CENTRE (PCC) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for PCC (18L07-1-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 4000A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), MFM,CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for Top Busduct entry (TPN Sandwich bus duct) and bottom cable entry for outgoing feeders Location: MCC Room |
| 26 | MOTOR CONTROL CENTER 1 (MCC-1, FOR UN-LOADING PUMPS) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MCC 1 (18L07-2-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 630A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders Location: MCC Room |
| 27 | MOTOR CONTROL CENTER 2 (MCC-2, FOR LOADING PUMPS) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MCC 2 (18L07-3-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 800A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MFM, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 28 | MOTOR CONTROL CENTER 3 (MCC-3, MISCELLANEOUS) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MCC 3 (18L07-4-SLD-E-001, Rev-0, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 250A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs (with extended operating handle and LSIG protection), MFM,CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders. Location: MCC Room |
| 29 | MAIN LIGHTING DISTRIBUTION BOARD (MLDB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MLDB (18L07-5-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 400A, 10 kA for 1 second, single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs (with extended operating handle and LSIG protection), MFM, CTs, PTs,indication lamp, main contactor, timer with adjustable time setting & auxiliary contactorsswitches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders. Location: MCC Room |
| 30 | MAIN POWER DISTRIBUTION BOARD (Main PDB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001,Sh. 1 of 1) and SLD for Main PDB (18L07-6-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 800A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders. Location: MCC Room |
| 31 | MOV / ROSOV PANEL (Ref. Electrical Overall SLD (18L07-0-SLD-E-001,Sh. 1 of 1) and SLD for MLDB (18L07-7-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 250A, 10 kA for 1 second, single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs, CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 32 | EMERGENCY LIGHTING DISTRIBUTION BOARD (ELDB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for ELDB (18L07-8-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 250A, 10 kA for 1 second, single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs, CTs, PTs,indication lamps, main contactor, timer with adjustable time setting & auxiliary contactors, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders. Location: MCC Room |
| 33 | EMERGENCY SWITCH BOARD (ESB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for ESB (18L07-9-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 800A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs, CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 34 | AUTOMATIC POWER FACTOR CORRECTION PANEL (APFC PANEL) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for APFC PANEL (18L07-10-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 2000A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs , CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 35 | FIRE PANEL (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for FIRE PANEL (18L07-10-SLD-E-001, Sh. 1 of 1)) Supply of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 250A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs, MFM, CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for bottom cable entry. The enclosure of this Panel shall have IP55 degree of protection.Location: FWPH. |
| 36 | MARSHALLING CABINET: |
| 37 | Supply of floor mounted type Marshalling Cabinet (Interphassing cabinet) having 500 terminalssuitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of non- FLP, Double Compression Cable Glands. |
| 38 | Supply of floor mounted type Marshalling Cabinet (Interphassing cabinet) having 250 terminalssuitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of non- FLP, Double Compression Cable Glands |
| 39 | 415V MOV DISTRIBUTION BOARDS(FLAMEPROOF, WEATHERPROOF TYPE)Supply of 415V, 3Ph & N, 50kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Flameproof with Canopy of 14 gauge CRCA sheet, Non-compartmentalised, Double door, MOV Distribution Boards along with Flameproof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry complete in all respect as per attached SLD (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MOV / ROSOV PANEL (18L07-7-SLD-E-001, Sh. 1 of 1)). |
| 40 | MOV DB-1 (48W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 37 nos |
| 41 | MOV DB-2 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 24 nos |
| 42 | MOV DB - 3 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 20 nos |
| 43 | MOV DB - 4, 5, 6 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 22 nos |
| 44 | MOV DB - 7 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 16 nos |
| 45 | MOV DB - 8 (32W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 26 nos |
| 46 | ROSOV DISTRIBUTION BOARD (ROSOV DB) (FLAMEPROOF, WEATHERPROOF TYPE)Supply of 415V, 3Ph & N, 10kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Flameproof with Canopy of 14 gauge CRCA sheet, Non-compartmentalised, Double door, ROSOV Distribution Boards along with Flameproof double compression Ni plated brass cable glands and lugs, suitable for bottom cable entry complete in all respect as per attached SLD (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MOV / ROSOV PANEL (18L07-7-SLD-E-001, Sh. 1 of 1)) |
| 47 | ROSOV DB-1 (24W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 16 nos |
| 48 | ROSOV DB-2 (24W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 16 nos |
| 49 | AC UPS SYSTEM2 x 10 kVA, 3-phase, 3 wire, 415V, 50Hz Input, 1-phase, 2 wire, 230V, 50 Hz output, IGBT type, Parallel Redundant UPS along with static bypass & suitable rating SMF VRLA battery bank for 30 Min back up as per attached SLD, battery stand (duly powder coated with castors), specification, data sheet for critical lighting loads.UPS shall be supplied along with Weatherproof double compression Nickel plated brass glands and lugs suitable for cable sizes indicated on SLD. The item is inclusive of Heat Run Test. |
| 50 | BATTERY CHARGER & DC BOARD (DCDB)30kVA, 110V DC, 2X100%Float cum boost charger along with 110V DC, 2 wireIntegral DCDB as per technical specification, datasheet & battery bank for 30 minsSLD complete in all respect long with Weatherproof double compression Nickel plated brass glands and lugs suitable. Vendor shall supply suitable batteryof AH rating calculated as per duty cycle/load details attached with datasheet and submit the sizing calculation accordingly.Location- MCC room |
| 51 | LOCAL CONTROL STATION (LCS) (WEATHER PROOF, FLAMEPROOF TYPE)Supply of following Industrial type, Weatherproof, Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65, Local Control Station suitable for Wall / Column / Structure mounting. All LCS shall be made up ofAluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheetwith side cover. LCS shall confirm to attached specification/data sheet. LCS shall be supplied along with Flameproof Double compression, Ni plated brass cable glands & lugs. |
| 52 | LCS with 1 no. mushroom head stay put type emergency stop PB with Keys, 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS) & Suppressed scale ammeter suitable for outdoor installation.LCS shall be suitable for 12Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(ForIE-3 motors including & above 30kW rating) |
| 53 | LCS with1 no. mushroom head stay put type emergency stop PB with Keys and 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS)suitable for outdoor installation. LCS shall be suitable for 7Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(For Motors below 30 kW rating) |
| 54 | Break glass typeEmergency Trip Push Button (ETPB) for transformer: weather proof emergency stop pushbutton(EPB) with ON-OFF LED indication break glass type enclosure, 3mm thick FRP canopy, weatherproof double compression Nickel Plted Brass cable glands(2 nos.) and 1NO+1 NC contact. |
| 55 | LOCAL CONTROL STATION (LCS) (WEATHER PROOF, NON-FLAMEPROOF TYPE):Supply of following Industrial type, Weatherproof, IP 65, Non flame proof Local Control Station suitable for Wall / Column / Structure mounting. All LCS shall be made up ofAluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheetwith side cover. LCS shall confirm to attached specification/data sheet. LCS shall be supplied along with Double compression, Ni plated brass cable glands & lugs. |
| 56 | LCS with 1 no. mushroom head stay put type emergency stop PB with Keys, 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS) & Suppressed scale ammeter suitable for outdoor installation.LCS shall be suitable for 12Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(ForIE-3 motors including & above 30kW rating) |
| 57 | LCS with1 no. mushroom head stay put type emergency stop PB with Keys and 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS)suitable for outdoor installation. LCS shall be suitable for 7Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(For Motors below 30 kW rating) |
| 58 | Break glass typeEmergency Trip Push Button (ETPB) for transformer: weather proof emergency stop pushbutton(EPB) with ON-OFF LED indication break glass type enclosure, 3mm thick FRP canopy, weatherproof double compression Nickel Plted Brass cable glands(2 nos.) and 1NO+1 NC contact. |
| 59 | POWER JUNCTION BOX FOR MOTOR (WEATHER PROOF, FLAME PROOF) : Supply of following 415V,TPN Industrial type, Weatherproof, Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65, Junction Boxes with Aluminium busbar, 50kA/1sec, suitable for Wall / Column / Structure mounting. All JBs shall be made up ofAluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheetwith side cover. JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be finalised during drawing approval only. In case of increase in cable sizes, no extra cost shall be payable.Please note that all cables shall be Aluminium conductor(10 sqmm & above)/Copper conductor(4 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 60 | Power JB having Busbar rating 63AJB suitable for terminating upto 1Rx3Cx70Sq.mm cables at one side and upto 2Rx3Cx35Sq.mm AL cable at other side |
| 61 | Power JB having Busbar rating upto 200AJB suitable for terminating upto 2Rx3Cx300Sq.mm cables at incoming side and upto 2Rx3Cx95Sq.mm AL cable outgoing side |
| 62 | JUNCTION BOXES FOR LIGHTING FIXTURES (WEATHER PROOF, FLAME PROOF): Supply of following 240V, Ph-N, Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure mounting. All JBs shall be made up ofcast Aluminium alloy (LM6 grade) Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 63 | 16A, 4-way, 125 mm (minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos cable glands / Plug, lugs with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable |
| 64 | JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, FLAME PROOF): Supply of following Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure mounting. All JBs shall be made up ofcast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA/AL sheetwith side cover, Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof Double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. Note:Civil & structural works shall be paidunder respective items. |
| 65 | 16A, 415V,TPN, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables. |
| 66 | 16A, 230V, Ph-N, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables. |
| 67 | JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, NON-FLAME PROOF): Supply of following Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure mounting. All JBs shall be made up ofcast Aluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA/AL sheetwith side cover. JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Weatherproof Double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 68 | 16A, 415V,TPN, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables. |
| 69 | 16A, 230V, Ph-N, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables. |
| 70 | INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, FLAMEPROOF TYPE)Socket outlets shall be Flame proof,Industrialtype, (IP65) interlocked with MCB and ELCB and suitable for loop-in loop-out entries for armoured cable as specified, enclosed with Cast Aluminium alloy (LM-6 grade), Ex-d, suitable for installation in Zone-2, Gas group IIA and IIB, temp class T3 with stainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs, earthing terminals, installation hardware and all necessary accessories wired upto terminal box. Integral plug tops shall be also supplied with the power socket outlets.All switch sockets shall be provided with Canopy of 14 gauge CRCA/AL sheetwith side cover and required no. of FLP double compressionNi plated brass cable glands and FLP stopping plug as per attached specification sheets. |
| 71 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 72 | 16A. 230 V AC, 1 phase, 50 Hz, |
| 73 | 6A. 230 V AC, 1 phase, 50 Hz, |
| 74 | INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, NON-FLAMEPROOF TYPE)Socket outlets shall be Non-Flame proof,industrialtype (IP65) interlocked with MCB and ELCB and suitable for loop-in loop-out entries for armoured cable as specified enclosed with Cast Aluminium alloy (LM-6 grade) with stainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs, earthing terminals, installation hardware and all necessary accessories wired upto terminal box. Integral plug tops shall be also supplied with the power socket outlets.All switch sockets shall be provided with Canopy of 14 gauge CRCA/AL sheet with side cover and required no. of double compressionNi plated brass cable glands and stopping plug as per attached specification sheets. |
| 75 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 76 | 16A. 230 V AC, 1 phase, 50 Hz, |
| 77 | 6A. 230 V AC, 1 phase, 50 Hz, |
| 78 | SUPPLYOF 415V LIGHTING PANELS (FLAMEPROOF, WEATHER PROOF TYPE): 415V, 3Ph & N, 10kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Weatherproof with Canopy, Non-compartmentalised, Double door, Lighting Panels along with Flameproof proof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry complete in all respect as per attached SLD , Specification/Data sheet. Note:Civil & structural works shall be paidunder respective items. |
| 79 | Outdoor type Normal Lighting Panel comprising Incomer- 32A, 4P, MCB- 1 no, Sub Incomer-32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-9 nos, (3 nos/ Phase) |
| 80 | Outdoor type Normal Lighting Panel comprising Incomer- 32A, 4P, MCB- 1 no, Sub Incomer-32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-18nos, (6 nos/ Phase) |
| 81 | Outdoor type Normal Lighting Panel comprisingIncomer- 63A, 4P, MCB- 1 no, Sub Incomer-63A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-27nos, (9 nos/ Phase) |
| 82 | Outdoor type Normal lighting panel Incomer : 100A4P, MCCB Outgoings- 25A 4P MCB - 8 nos |
| 83 | 415V LIGHTING PANELS (NON-FLAMEPROOF, WEATHER PROOF TYPE):Supply of 415V, 3Ph & N, 10kA 1 sec, sheet steel enclosure, wall or frame mounted, IP 65 protected, Weatherproof with canopy, Non-compartmentalised, Double door, Lighting Panels along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders, suitable for bottom cable entry complete in all respect as per attached SLD Specification/Data sheet |
| 84 | Outdoor type Normal Lighting Panel comprising Incomer- 32A, 4P, MCB- 1 no, Sub Incomer- 32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-9 nos, (3 nos/ Phase) |
| 85 | Outdoor type Normal/Emergency Lighting Panel comprising Incomer- 32A, TPN, MCB- 1 no, Sub Incomer- 32A, DP RCCB with 30mA sensitivity - 3 Nos. Outgoings- 10A DP MCB-12 nos, (4 nos/Phase) |
| 86 | Outdoor type Normal lighting panel Incomer : 100A4P, MCCB Outgoings- 25A 4P MCB - 8 nos |
| 87 | 415V POWER DB (NON-FLAMEPROOF, WEATHERPROOF TYPE):Supply of 415V, 3Ph & N, 10kA 1 sec, sheet steel enclosure, wall or frame mounted, IP 65 protected, Non-compartmentalised, Double door, Weatherproof, Power Panels along with Weatherproofdouble compression Ni plated brass cable glands and lugs and canopy, suitable forbottom cable entry complete in all respect as per attached SLD , Specification/Data sheet |
| 88 | Outdoor type Normal Power Panel comprisingIncomer- 32A, 4P, MCB- 1 no,Sub Incomer- 32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-6 nos, (2 nos/ Phase) |
| 89 | 415V POWER DB(FLAMEPROOF, WEATHERPROOF TYPE):Supply of 415V, 3Ph & N, 10kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Non-compartmentalised, Double door,Flameproof Power Panel with Canopy along with Flameproofdouble compression Ni plated brass cable glands and lugs suitable for bottom cable entry complete in all respect as per attached SLD,Specification/Data sheet |
| 90 | Outdoor type Flame proof Power Panel comprisingIncomer- 63A, 4P, MCB- 1 no,Sub Incomer- 63A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 16A DP MCB-6 nos, (2 nos/ Phase) |
| 91 | POLES FOR LIGHTING SYSTEM:Supply of Lighting Poles. Galvanization 610 gms / sq. mt. or as per IS-2629 & IS-4759/ISO 1461 shall be provided for all Hot dip Galvanised poles. (Civil Works shall be paid seperately) |
| 92 | Supply of 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with single arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications.The item also includes suitable fixing/clamping arrangement made up of GI on the body of the octogonal pole for fixing of 16A, 4-way, 125 mm (minimum) internal dimensions flameproof junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos cable glands / Plug, lugs with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable. The design shall be submitted for approval of IOCL. The payment for the Junction Box shall be made seperately. |
| 93 | Supply of 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with double arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications.The item also includes suitable fixing/clamping arrangement made up of GI on the body of the octogonal pole for fixing of 16A, 4-way, 125 mm (minimum) internal dimensions flameproof junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos cable glands / Plug, lugs with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable. The design shall be submitted for approval of IOCL. The payment for the Junction Box shall be made seperately. |
| 94 | Supply of 9 Meter high galvanised Octagonal pole with top 90mm(A/F),bottom 158mm (A/F), made up of 3mm thick plate having a baseplate of size min. 285 x 285 x 16 with double arm 1500mm long bracket arm made up of 48 O.D. pipe with EN grade galvanised foundation bolts, nuts,washers & anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications. |
| 95 | Supply of 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with double arm min. 1500mm long decorative bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 2 Nos. of 120W LED luminaries as per enclosed technical specifications. |
| 96 | Supply of 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with single arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications. |
| 97 | 6 Mtr GI Lighting Pole(Octagonal or polygonal section) including foundation bolts for ground mounting suitable for 1 no.x 20 watt Solar Hybrid LED fixturewith weatherproof nickel plated brass cable gland, tinned copper lugs of suitable type & size for termination, weather proof JB at the foot of pole including MCB & terminal block (as applicable), cables from foot of the pole to the light fittings complete with all accessories, GI pipe (Class B) for cable protection,Zinc passivated hardware for fixtures support & pole support, clamps, nuts, bolts, etc. including supply of commissioning spares, as required. |
| 98 | GOOSE / SWAN NECK TYPE POLE FOR WELL GLASS LIGHTING FIXTURESupply of outdoor type 2.5 mtr hot dip galvanised, goose neck type lightingpole(50mm as per IS 1239 - Medium duty) alongwith with flameproof Junction Box suitable for for structural / handrail mounting , complete with all clamping arrangements for cables including accessories , flameproof proof JBs at the foot of the pole along with Flameproof proof double compression Ni plated brass cable glands and lugs & termination block (as applicable), zinc passivated hardware for fixtures support & pole support , clamps, nuts, bolts, etc. including supply of commissioning spares , as requiredfor 1 nos.of well glass light luminaires.The pole shall be epoxy coated GI pole of Class B type. The junction box shall be complete with terminals for loop-in loop-out of cables. |
| 99 | HIGH MAST LIGHTING: Supply of 20 Mtr. height High Mastcomplete with accessories as per specifications. The cost also includes supplying and providing trailing cable of suitable sizefrom Switch Plug & Socket at the foot of high mast to the junction box at the top,FLP Motor, suitable size double compression, cable glands. Note:a) The civil works required for high mast foundations are excluded from scope of this item and shall be paid separately.b) The item includes the S/I of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial (Lightening arrestor), including low intensity LED type double dome aviation obstruction light.c) Tenderers should note thatjunction box shall be provided at the top of the high mast as per specifications.Rates for lighting fixtures and earth pits shall be paid separately.d) Bidder to provide design and drawing for foundation of high mast tower.e) The high Mast system shall be suitable for 55m/sec wind speed (as per IS-875), with head frame, winch mounting bracket, luminaries carriage suitable to install 16 nos. 400W LED FLD in Symmetrical arrangement (0-360Deg). e) The scope includes the supply foundation bolts manufactured from EN 8 grade galvanised steel along with nuts, washers, anchor plate and common template.f) Provision of lowering/raising of light fixutures without removal of cable end termination.20 Mtr. height High Mast complete with accessoriesas per attached specificationof this tender. |
| 100 | HIGH MAST LIGHTING: Supply of 10 Mtr. height High Mastcomplete with accessories as per specifications. The cost also includes supplying and providing trailing cable of suitable sizefrom Switch Plug & Socket at the foot of high mast to the junction box at the top,FLP Motor, suitable size double compression, cable glands. Note:a) The civil works required for high mast foundations are excluded from scope of this item and shall be paid separately.b) The item includes the S/I of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial (Lightening arrestor), including low intensity LED type double dome aviation obstruction light.c) Tenderers should note thatjunction box shall be provided at the top of the high mast as per specifications.Rates for lighting fixtures and earth pits shall be paid separately.d) Bidder to provide design and drawing for foundation of high mast tower.e) The high Mast system shall be suitable for 55m/sec wind speed (as per IS-875), with head frame, winch mounting bracket, luminaries carriage suitable to install 16 nos. 400W LED FLD in Symmetrical arrangement (0-360Deg). e) The scope includes the supply foundation bolts manufactured from EN 8 grade galvanised steel along with nuts, washers, anchor plate and common template.f) Provision of lowering/raising of light fixutures without removal of cable end termination.20 Mtr. height High Mast complete with accessoriesas per attached specificationof this tender. |
| 101 | Supply of flameproof outdoor, made of 14 SWG CRCA sheet, IP-65, stand mounted feeder pillar with 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35-70 sq. mm and out going 12 & 2.5 sq. mm terminals& 1 no. outgoing upto 35-70 sqm for looping. (Necessary Civil Works shall be paid seperately) |
| 102 | Supply of weatherproof outdoor, made of 14 SWG CRCA sheet, IP-65, stand mounted feeder pillar with 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35-70 sq. mm and out going 12 & 2.5 sq. mm terminals& 1 no. outgoing upto 35-70 sqm for looping. (Necessary Civil Works shall be paid seperately) |
| 103 | LIGHTING SYSTEM - Supply of flameproof/weatherproof luminaries of approved makes as per the specifications mentioned below. The item also includes the design & submission of the design/LUX level report as per the provisions of OISD for the entire plant area/sheds/buildings etc. including finalization of locations/coordinates of the high masts based on the selected lumanaires. The design must be submitted for approval from IOCL/PMC. |
| 104 | LIGHTING FIXTURES FOR HAZARDOUS AREA (FLAMEPROOF TYPE)Supply of Flameproof, Ex\"d\" suitable for Gas group IIA/IIB, T3, suitable for Zone 2, Weather proofLED Lighting Fixtures, lamps & Accessories as per attached specifications / data sheet (All Lighting fixtures shall be provided with required no. of double compression nickle plated brass cable glands, lugs and stopping plug.) |
| 105 | 110W LED Flood light suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminal box. |
| 106 | 70W LED, Well glass luminaire suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminal box. |
| 107 | 40W LED, Well glass luminaire suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings enclosure, SS wire guard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminal box. |
| 108 | Design, Supply and Installation of FLP 100 W GLS,110V DC ,well glass type light fittings with reflector and its accessories etc and junction box(if required) |
| 109 | FLP 2 x 20 W LED, Industrial type, lighting fixtures with LED lamp and all other accessories as per specification. |
| 110 | LIGHTING FIXTURES (NON-FLAMEPROOF TYPE) Supply of Weather proofLED Lighting Fixtures, lamps & Accessories as per attached specifications / data sheet(All Lighting fixtures shall be provided with required no. of double compression nickle plated brass cable glands, lugs and stopping plug.) |
| 111 | Supply of WP 60 W GLS,110V DC, bulk head type light fittings with reflector and its accessories etc and junction box (if required) |
| 112 | 36W Weatherproof LED Batten Light suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings |
| 113 | 80W LED undercanopy light (Outdoor type) suitable for surface / recessed mounting from structure |
| 114 | Supply of high-quality integrated LED Flood Light with a minimum system lumen of 53000 Lm and system wattage of nominal 400W with a nominal efficiency 130 lumen/watt. CCT of 5700K with SDCM of < 5 and CRI : 70. The housing should be ofnon-corrosive high-pressure die-cast aluminum to with stand extreme environments. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. with PF > 0.95. Lifetime of 75K hours @L70. Product should be suitable for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP 66 with an IK rating of 08. Optical and control gear compartments shall be maintainable/replaceable without impacting the LED units. The access to the optical and the gear compartment should be separate. While accessing the gear compartment, the optical compartment should not be accessible. The Luminaire should have a 20 KV /10 KA SPD duly bolted in theLuminaire . The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e., Total of 45 hits across all the three modes as per IEEE 62.41.2. The Luminaire should have a breather to ensure that air balance inside and outside of the Compartment .The luminaire should be of Class B Serviceability. The wattage of each LED should be greater than 1 watt and less than 3 Watt. Only high power Single white LED chip with ceramic based suitable for outdoor use is allowed. Multi Chip , array multi die , midpower ,Integrated arrays and COBs are not permitted. The 144 nos. of High-power LED used in the luminaire shall be SMD type only of make LGIT, Lumileds, Osram, Nichia, and CREE & no other make. The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V and have an auto recovery feature. The Drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire. The Dimension of the luminaires should be minimum 595 x 100 x418 mm and have a breather ensuring a stable optical and thermal management. Model no. BVP485 LED530 CW FLNB A1 PSU GR SPD of Philips or equivalent make |
| 115 | Supply of 100 W LED (Light Emitting Diode) light fixture with fittings and accessories for Yard lighting purpose having IP66 protection class with Pressure Die Cast LM6/ADC12/LM24 housing and with toughened glass or UV stabilized polycarbonate cover type of approved make or equivalent as per direction of Engineer-in-charge. The LED driver shall have an in-built high voltage cutoff >= 290 V with power factor of complete fitting greater than 0.90. CCT (Correlated Colour temperature) shall be in the range of 5665 K +/- 355 K as per ANSI standard C78.377, CRI (Colour rendering index) should include all colour range from R1 to R15 and > 70 for outdoor luminaire. LED efficacy shall be greater than 140 lumens/watt @ 350mA drive current. The minimum system lumen efficacy of the luminaire shall be 100 Lumens per Watt. The Surge Protection Device (SPD) should be series type with fail safe, surge protection for minimum 3kV shall be provided. Supply of complete fitting with all accessories as per specification attached and as per direction of engineer in charge. Each lot of fittings shall accompany test certificates LM79/ IS:16106 and reference/ batch nos of LEDs and fittings for verification at site. |
| 116 | DC LIGHTING Supply of Weather proof12V DC lamp with integral charger for FWPH/PMCC/Control Room & Security Room. |
| 117 | HT POWER CABLES11 kV (E) grade HT Cable with stranded compact Aluminium conductor,conductor screened by extruded semi conducting compound, XLPE insulated,colour coded, insulation screened by extruded semi conducting compound followed by a layer of copper tape, cores laid up together suitably extruded PVC innersheathed, strip (for multi core) and overall extruded FRLS PVC outer sheathed cable conforming to IS 7098-2. The Cable End Termination Kits as required to be considered.The item also includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280. |
| 118 | 3Cx300 sqmm.-Al, 11kV(E) Cable |
| 119 | 3Cx300 sqmm. 11kV(E), Al. Cable End termination Kits (Indoor type) |
| 120 | 3Cx300 sqmm. 11kV(E), Al. Cable End termination Kits (Outdoor type) |
| 121 | LT POWER CABLESSupply 1.1 kV grade power XLPE insulated Copper/Aluminium conductor (up to 6 sqmm copper cable shall be selected & above 4 sqmm Aluminium conductor), multi core, steel wire/strip (for multi core) armoured, FRLS/FR PVC outer sheathed cable conforming to IS 7098-1. Note: Before procuring cable, successfull bidder is required to prepare detailed BOQ & Drum Schedule as per site mesaurement. No extra payment shall be made for wastages. The item includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280. The same shall be attached @ max. 30m or at bends whichever is lesser.Cables: FR/FS to be used as per OISD provisions inside the dyke. |
| 122 | 3Cx1.5 sq.mm-Cu |
| 123 | 3Cx2.5 sq.mm-Cu |
| 124 | 3Cx6 sq.mm-Cu |
| 125 | 3Cx10 sqmm.-Al |
| 126 | 3Cx16 sqmm.-Al |
| 127 | 3Cx25 sq.mm-Al |
| 128 | 3Cx35 sq.mm-Al |
| 129 | 3Cx70 sq.mm-Al |
| 130 | 3Cx95 sq.mm-Al |
| 131 | 3Cx150 sq.mm-Al |
| 132 | 3Cx185 sq.mm-Al |
| 133 | 3Cx240 sq.mm-Al |
| 134 | 3Cx300 sq.mm-Al |
| 135 | 3Cx400 sq.mm-Al |
| 136 | 3.5Cx25 sq.mm-Al |
| 137 | 3.5Cx35 sq.mm-Al |
| 138 | 3.5Cx50 sq.mm-Al |
| 139 | 3.5Cx70 sq.mm-Al |
| 140 | 3.5Cx95 sq.mm-Al |
| 141 | 3.5Cx120 sq.mm-Al |
| 142 | 3.5Cx150 sq.mm-Al |
| 143 | 3.5Cx185 sq.mm-Al |
| 144 | 3.5Cx240 sq.mm-Al |
| 145 | 3.5Cx300 sq.mm-Al |
| 146 | 3.5Cx400 sq.mm-Al |
| 147 | 4Cx6 sq.mm-Al |
| 148 | 4Cx10 sq.mm-Al |
| 149 | 4Cx16 sq.mm-Al |
| 150 | 4Cx25 sq.mm-Al |
| 151 | 4Cx35 sq.mm-Al |
| 152 | 4Cx50 sq.mm-Al |
| 153 | LT CONTROL CABLES Supply of LT control cables shall be suitable for 1.1 kV grade, copper Conductor, multi cores, PVC insulated, colour coded, laid up sheathed with extruded PVC inner sheath, hard drawn galvanised strip /wire armoured, and extruded overall FRLS PVC outer sheathed as per IS 1554-1. Note: Before procuring cable, successfull bidder is required to prepare detailed BOQ & Drum Schedule as per site mesaurement. No extra payment shall be made for wastages. The cost is inclusive of Cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280. |
| 154 | 2Cx2.5 sq. mm. |
| 155 | 12Cx2.5 sq. mm. |
| 156 | 5Cx1.5 sq. mm. |
| 157 | 7Cx2.5 sq. mm. |
| 158 | 3Cx4 sq. mm. |
| 159 | 12Cx1.5 sq. mm. |
| 160 | LT POWER CABLE GLANDSupply of double compression, weather proof,flame proof nickel plated brass cable gland for following sizes of XLPE insulated, FRLS cables suitable for Zone-2, EX\"d\", Gas Group IIA/IIB, Temperature class-T3 . Diameter of cable under armour and above armour shall be checked prior to ordering of glands. Glands shall be complete with double seal cone-grip arrangements and check nuts.Glands shall be supplied with PVC hood. Note: Cable shall be 1.1 kV grade power XLPE insulated Copper/Aluminium conductor [up to 4 sqmm copper cable shall be selected & above 4 sqmm Aluminium conductor, multi core, steel wire/strip (for multi core) armoured, FRLS PVC outer sheathed cable conforming to IS 7098-1. |
| 161 | 3Cx1.5 sq.mm-Cu |
| 162 | 3Cx2.5 sq.mm-Cu |
| 163 | 3Cx6 sq.mm-Cu |
| 164 | 3Cx10 sqmm.-Al |
| 165 | 3Cx16 sqmm.-Al |
| 166 | 3Cx25 sq.mm-Al |
| 167 | 3Cx35 sq.mm-Al |
| 168 | 3Cx70 sq.mm-Al |
| 169 | 3Cx95 sq.mm-Al |
| 170 | 3Cx150 sq.mm-Al |
| 171 | 3Cx185 sq.mm-Al |
| 172 | 3Cx240 sq.mm-Al |
| 173 | 3Cx300 sq.mm-Al |
| 174 | 3.5Cx25 sq.mm-Al |
| 175 | 3.5Cx35 sq.mm-Al |
| 176 | 3.5Cx50 sq.mm-Al |
| 177 | 3.5Cx70 sq.mm-Al |
| 178 | 3.5Cx95 sq.mm-Al |
| 179 | 3.5Cx120 sq.mm-Al |
| 180 | 3.5Cx150 sq.mm-Al |
| 181 | 3.5Cx185 sq.mm-Al |
| 182 | 3.5Cx240 sq.mm-Al |
| 183 | 3.5Cx300 sq.mm-Al |
| 184 | 3.5Cx400 sq.mm-Al |
| 185 | 4Cx6 sq.mm-Al |
| 186 | 4Cx10 sq.mm-Al |
| 187 | 4Cx16 sq.mm-Al |
| 188 | 4Cx25 sq.mm-Al |
| 189 | 4Cx35 sq.mm-Al |
| 190 | 4Cx50 sq.mm-Al |
| 191 | LT CONTROL CABLE GLAND (FOR HAZARDOUS AREA)Zone-2, Ex\"d\", Gas group IIA/IIB, Temperature class-T3): Supply of double compression, weather proof,flame proof nickel plated brass cable gland for following sizes of XLPE insulated, FRLS cables suitable for Zone-2, EX\"d\", Gas Group IIA/IIB, Temperature class-T3 .Diameter of cable under armour and above armour shall be checked prior to ordering of glands. Glands shall be complete with double seal cone-grip arrangements and check nuts.Glands shall be supplied with PVC hood. Note: Cable shall be 1.1 kV grade power XLPE insulated Copper/Aluminium conductor [up to 4 sqmm copper cable shall be selected & above 4 sqmm Aluminium conductor, multi core, steel wire/strip (for multi core) armoured, FRLS PVC outer sheathed cable conforming to IS 7098-1. |
| 192 | 2Cx2.5 sq. mm. |
| 193 | 12Cx2.5 sq. mm. |
| 194 | 5Cx1.5 sq. mm. |
| 195 | 7Cx2.5 sq. mm. |
| 196 | 3Cx4 sq. mm. |
| 197 | 12Cx1.5 sq. mm. |
| 198 | LT CONTROL CABLE GLAND (FOR GENERAL AREA- NON HAZARDOUS): Supply of double compression, weather proof nickel plated brass double compression cable glands for 1.1 kV grade control cables of following sizes.Diameter of cable under armour and above armour shall be checked prior to ordering of glands. Glands shall be complete with double seal cone-grip arrangements and check nuts.Glands shall be supplied with PVC hood. Note: Cable shall be 1.1 kV grade power XLPE insulated Copper/Aluminium conductor [up to 4 sqmm copper cable shall be selected & above 4 sqmm Aluminium conductor, multi core, steel wire/strip (for multi core) armoured, FRLS PVC outer sheathed cable conforming to IS 7098-1. |
| 199 | 12Cx2.5 sq. mm. |
| 200 | 5Cx1.5 sq. mm. |
| 201 | 12Cx1.5 sq. mm. |
| 202 | CABLE TRAYS (LADDER TYPE)Supply of Hot dip G.I. LADDER TYPE cable trays of minumum 2.5 M length (with 100mm side flange height for cable tray of width 300 mm & aboveand 75 mm side flange height forcable tray of width below 300 mm) for Straight run, bends, Tees etc. as per enclosed specification & drawings. Item includes all accessories, i.e. Coupler plate, Tray Fixing clamp,Fastener, nut, bolt washer etc. as required. All the hardware i.e. Fasterener, Nut, Bolt, Washers etc. shall be of SS 304. Minimum thickness of galvanisation shall be 610 gm/m2 oror as per IS-2629 & IS-4759/ISO 1461 BIDDER to note that all the accessories mentioned above shall be paid in running meters of cable tray lengths. Separate rate for supply of such accessories shall not be paid. |
| 203 | 600 mm Wide 3 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 204 | 300 mm Wide 2 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 205 | 150mm Wide 2 mm thick - Runner Size- 75 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 206 | CABLE TRAYS (PERFORATED TYPE)Supply of Hot dip G.I. PERFORATED TYPE cable traysof minumum 2.5 M length for Straight run, bends, Tees etc. as per enclosed specification & drawings. Item includes all accessories, i.e. Coupler plate, Tray Fixing clamp,Fastener, nut, bolt washe retc. asrequired. All the hardware i.e. Fasterener, Nut, Bolt, Washers etc. shall be of SS 304.Minimum thickness of galvanisation shall be 610 gm/m2BIDDER to note that all the accessories mentioned above shall be paid in running meters of cable tray lengths. Separate rate for supply of such accessories shall not be paid. |
| 207 | 600 mm Wide 3 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 208 | 300 mm Wide 2 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 209 | 150mm Wide 2 mm thick and 75 mm side flange height , Runner Size- 75 mm x 10 mm |
| 210 | 50mm Wide 2mm thick and 50 mm side flange height,Runner Size- 50 mm x 10 mm |
| 211 | Supply of 1.6 mm thick Hot dip G.I. Cable Tray Cover of minumum 2.5 M length suitable for Cable tray of following sizes including clamps for fixing the cover to cable tray with all accessories. Minimum thickness of galvanisation shall be 610 gm/m2 oror as per IS-2629 & IS-4759/ISO 1461 |
| 212 | 600 mm Wide |
| 213 | 300 mm Wide |
| 214 | 150 mm Wide |
| 215 | 50 mm Wide |
| 216 | Multi Cable Transit (MCT) BLOCKS: Supply of MCT block withSS Frame with EPDM Modules, Stay plate, Compression wedge, Lubricant etc complete with all accessories for following area as per the respective cable schedule/sizes. |
| 217 | MCT-Admin Building (for LT Power Cables- 24 incomer/outoging Cables + 30% Spare blocks ) |
| 218 | MCT-Control room (for LT Power cables -12 incomer/outoging Cables + 30% Spare blocks) |
| 219 | Security Block cum Change Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 220 | Invoice Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 221 | Sample Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 222 | Security Barrack (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 223 | TT Crew Rest Room (for LT Power cables - 6 incomer/outoging Cables + 30% Spare blocks) |
| 224 | Security Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 225 | LIGHTING GROUNDING WIRES |
| 226 | 14 SWG. GI Wire |
| 227 | JUNCTION BOXES |
| 228 | Supply of Weather proof 16A, 240V, 4-way, 125mm(minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. |
| 229 | PVC CONDUIT |
| 230 | 20mm Dia. galvanized rigid Conduit |
| 231 | PART (B): |
| 232 | SECTION-2, PART B: Items under this section are categorised under GST rate of 18%.Bidders to confirm the GST rate for each item in the price bid BOQ |
| 233 | PART (B): INSTALLATION, TESTING & COMMISSIONING For all the items under Part B of this schedule, the rates to be quoted include:(A) Charges towards materials/ equipment handling including loading/ unloading within the site as required during installation. Installation, tetsing (B) Installation, laying, fixing, erection works as per tender specifications including supply of all erection equipment, tools & tackles, labour, consumables/hardware etc required for installation / laying / fixing / erection, testing & commissioning of all the items shall also form part of the items.These items rates to be quoted for installation / laying / fixing / erection of supplied items under Part-A without the cost of supply of materials that is already covered in Part-A.(C) Cutting, aligning to plumb & levels, Structural fabrication, welding including foundations etc as per site requirements ; Testing and Commissioning of all items/ equipment as per attached specifications, data sheets, codes and directions of site in charge and QAP; Chipping of walls, drilling, making holes, patching up works with plastering including bringing the surfaces to original condition etc; Unless otherwise specified, the civil/ structural works required for erection & installation of items under Part B shall be paid separately under respective items.(D)Testing, commissioning of all Motors to be considered. (E) Transformer: Pre-commissioning, testing, replacement of oil, silica gel, oil test, coil test. Dielectric strength etc. as per relevent norms (irrespective of the OEM warranty period) |
| 234 | 11kV GANG OPERATED DEVICE : Receiving from store; transporting to erection site including cable glanding & power/ control cable termination;verification of bill of materials; handling, arrangement of transport vehicle, loading / unloading equipment like crane, slings etc.; preparation of foundation including supply of foundation base material frame & its fixing by welding on foundation insert plates or angles embedded in the foundation; opening packages; identifying, inspecting for physical damages etc., reporting the same to ENGINEEER IN CHARGE and also placing on foundation channel, aligning, plumbing,leveling, positioning, bus bar bolting between transportation sections, bolting / tack welding with foundation channels various shipping section of panels including supply of GI bolts, nuts and washers etc., assembling of shipping sections, connection of inner panel busbars, internal wiring, checking of terminal connection for tightness and proper wiring, leakage in vacuum bottle or air circuit breakers, internal cleaning of all panels, chambers, insulation etc., drying out the bus bar chambers in case of low insulation, vermin/rodent proofing of panel where cut-out & openings have been made , sealing gaps between adjacent panels with gasket, carrying out minor modification in wiring, removal & refixing of components such as CT, switches etc., installation and testing of protecting relay, auxiliary relay, thermal relay, relay setting,caliberation of meters etc.,touch up painting, functional testing & commissioning of following SWITCHBOARDS together with all accessories, all works, labour & materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of switchboard manufacturer and ENGINEER IN CHARGE.Installation, testing & commissioning of 11kV Gang Operated Device with Isolator, earth Switch and 200A Fuse along with Lightning arrestor, Outdoor, H-Pole structure mounted as per attached Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1), specification, data sheet. The Outgoing Cable shall be connected by 11kV (E) grade Cable End termination Kits as per required Cable size and conductor material.Location: Switchyard. |
| 235 | Installation, Testing & Commissioning of trivector meter as per state electricity approved make for tariff metering including metering enclosure. |
| 236 | 11kV SWITCHBOARD: Receiving from store; transporting to erection site including cable glanding & power/ control cable termination;verification of bill of materials; handling, arrangement of transport vehicle, loading / unloading equipment like crane, slings etc.; preparation of foundation including supply of foundation base material frame & its fixing by welding on foundation insert plates or angles embedded in the foundation; opening packages; identifying, inspecting for physical damages etc., reporting the same to ENGINEEER IN CHARGE and also placing on foundation channel, aligning, plumbing,leveling, positioning, bus bar bolting between transportation sections, bolting / tack welding with foundation channels various shipping section of panels including supply of GI bolts, nuts and washers etc., assembling of shipping sections, connection of inner panel busbars, internal wiring, checking of terminal connection for tightness and proper wiring, leakage in vacuum bottle or air circuit breakers, internal cleaning of all panels, chambers, insulation etc., drying out the bus bar chambers in case of low insulation, vermin/rodent proofing of panel where cut-out & openings have been made , sealing gaps between adjacent panels with gasket, carrying out minor modification in wiring, removal & refixing of components such as CT, switches etc., installation and testing of protecting relay, auxiliary relay, thermal relay, relay setting,caliberation of meters etc.,touch up painting, functional testing & commissioning of following SWITCHBOARDS together with all accessories, all works, labour & materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of switchboard manufacturer and ENGINEER IN CHARGE.Installation, testing & commissioning of 11kV, 1250A, 40kA for 3 sec, VCB Panel, 3 Phase - 3 Wire, Indoor, Single front, Floor mounted, Copper Bus bar, IP4X, IAC Internal Arc 40kA for 1 sec (AFLR), fully drawout type ICOG Panel (Incoming and Outgoing Type) comprising Vaccum Circuit Beraker withNumerical relay, MFM, auxiliary relay,CTs,PTs ,indication lamp, switches along with Weather proof double compression Ni plated brass cable gland and crimping type cable lugs for all incoming and outgoing cables as per attached Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1), specification, data sheet. Panel shall be suitable for Bottom cable entry & outgoing. Location: MCC Room |
| 237 | DISTRIBUTION TRANSFORMER & LIGHTING TRANSFORMER:Receiving from store, Transporatation to the erection site, including cable glanding & power / control cable termination ; handling, arrangement of transport vehicle , loading & unloading equipment like crane, slings etc.; placing on foundation; fixing on foundation channels; aligning; levelling including stone / gravel in the transformer yard etc. ; assembling of all accessories / parts supplied loose; drying out or dehydration of transformer as per Indian standards; connection of auxiliary circuits; operation & functional checking; testing & commissioning of following POWER DISTRIBUTION TRANSFORMERS AND LIGHTING TRANSFORMER together with its accessories, all works, labour and materials complete as per drawings, documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE. |
| 238 | DISTRIBUTION TRANSFORMER : Installation, Testing & Commissioning of 2 MVA, 11kV/0.433kV, Dyn11, Oil filled, ONAN type, %Z=6.25 + 10%, copper winding Transformer withOCTC (+5% TO -5% IN STEPS OF ±2.5%) along with weather proof double compression Ni plated brass cable glands and cable lugs for incoming and outgoing cables and all other accessoriesfor Transformer & RTCC panel as per attached specification/Data sheet. Location: MCC Room (Ground Floor) |
| 239 | LIGHTING TRANSFORMER -1 (NORMAL POWER): Installation, Testing & Commissioning of 150 kVA, 415V/433V, Dyn11, Indoor, copper winding Cast resin Dry type transformer with OCTC +5% to -5% taps in steps of 2.5%along with Weather proof double compression Ni plated brass cable gland and cable lugsfor all incoming and outgoing cables & with all accessories as per attached technical specification/data sheets. Location: MCC Room |
| 240 | LIGHTING TRANSFORMER - 2 (EMERGENCY POWER): Installation, Testing & Commissioning of 100 kVA, 415V/433V, Dyn11, Indoor, copper winding Cast resin Dry type transformer with OCTC +5% to -5% taps in steps of 2.5%along with Weather proof double compression Ni plated brass cable gland and cable lugsfor all incoming and outgoing cables & with all accessories as per attached technical specification/data sheets.Location: MCC Room |
| 241 | DIESEL GENERATOR SET ( Set of 02 Nos x 1010 KVA Diesel Generator)Receiving of2x1010KVA DG SET from store, transporting to erection site including cable glanding & power / control cable termination,handling, arrangement of transport vehicle, loading & unloading equipment like crane, slings etc., placing on foundation, fixing on foundation channels, aligning, levelling etc. assembling of all accessories / parts supplied loose,, fuel tank, battery system,AVM pads,Silencer,fuel oil system,lube oil system,Starting system,governing system, dehydration of windings (If required), plugging unused cable gland cutout in alternator terminal box, checking of bearing grease / lubricant, checking of IR values, checking of continuity of windings, checking of direction of rotation, installation of acoustic enclosure for DG set, necessary hardware’s, testing & commissioning of complete DG set together with DG-PCC, functional testing of DG-PCC with all accessories, all performance tests of DG Sets, all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE.Installation, Testing & Commissioning of 2 Nos x 1010 kVA (Prime Rated)silent DG Set with DG PCC comprising of AMFas per enclosed (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1)), Control panel, Control cabling between DG & DG PCC etc., Stack & Supporting Structure of Stack,Acoustic encloser, Exhaust system, elbow, bellows, AVM pads, lube oil system, cooling system, Diesel oil system, all required piping,External Day Tank of990 litre capacity or more as per technical specifications along with all pipings withmagnetic level switch, inter connecting control cables and cable accessories (including weather proof double compression Ni plated brass cable glands and cable lugs) between DG enclosure & DG PCC, Base Channels etc. & all other items mentioned in the supply part,as per attached specifications,data sheet & SLD, First filling of engine oil, lubricant etc.complete with all required accessories |
| 242 | Installation, Testing & Commissioning of the Composite DG Panel (Common for DG-1 & DG-2 of 1010 KVA each) comprising of DG PCC, DG synchronizing and DG AMF Features). The DG PCC shall have IP-65 protection.supplied in part \" A |
| 243 | DIESEL GENERATOR SET ( Set of 01 No x750 KVA Diesel Generator)Receiving of1x750KVA DG SET from store, transporting to erection site including cable glanding & power / control cable termination,handling, arrangement of transport vehicle, loading & unloading equipment like crane, slings etc., placing on foundation, fixing on foundation channels, aligning, levelling etc. assembling of all accessories / parts supplied loose, fuel tank, battery system,AVM pads,Silencer,fuel oil system,lube oil system,Starting system,governing system, dehydration of windings (If required), plugging unused cable gland cutout in alternator terminal box, checking of bearing grease / lubricant, checking of IR values, checking of continuity of windings, checking of direction of rotation, installation of acoustic enclosure for DG set, necessary hardware’s, testing & commissioning of complete DG set together with DG-PCC, functional testing of DG-PCC with all accessories, all performance tests of DG Sets, all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE.Installation, Testing & Commissioning of 1 No x750 kVA (Prime Rated)silent DG Set with DG PCC comprising of AMF & Synchronizing panel as per enclosed (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1)), Control panel, Control cabling between DG & DG PCC etc., Stack & Supporting Structure of Stack,Acoustic encloser, Exhaust system, elbow, bellows, AVM pads, lube oil system, cooling system, Diesel oil system, all required piping,External Day Tank of990 litre capacity or more as per technical specifications along with all pipings withmagnetic level switch, inter connecting control cables and cable accessories (including weather proof double compression Ni plated brass cable glands and cable lugs) between DG enclosure & DG PCC, Base Channels etc. & all other items mentioned in the supply part,as per attached specifications,data sheet & SLD, First filling of engine oil, lubricant etc.complete with all required accessories |
| 244 | Installation, Testing & Commissioning of Exhaust Pipe of suitable size as recommended by OEM including Asbestos rope, glass wool insulation & cladding in Aluminium sheetingExhaust pipe of suitable size as per IS:1239/3589 schedule 20{(a) Asbestos rope lagging from DG exhaust up to silencerfor insulation (dia 250mm or as per manufacturer) b) Glass wool insulation and cladding in Aluminium sheeting (24 G) for DG sets beyond silencer (dia 350mm or as per manufacturer) as per manufacturer\"s recommendations/CPCB -CEA Regulations}. |
| 245 | LT BUSDUCT (FROM TRANSFORMER TO PCC) :Receiving from store, transporting to erection site, Installation, testing & commissioning of 415V, 3200A, 50kA for 1 sec, 3Phase, 4 Wire (Neutral 100%), Sandwich type BusDuct with Aluminium Busbar, 2.5 mm thick Aluminium enclosure, nut bolts, straight runs, 90 deg bends, bellows, flanges, Phase change over, Adaptor box, elbows, offsets, flexible connections, wall frame assembly, inspection cover as required. This shall also include installation of roof supports, space heaters, inside & outside earthing, all hardware complete in all respect . |
| 246 | Straight Run Feeder, IP 65 (For Outdoor portion of Busduct) including all accessories such as space heater, nut, bolt washer, Earthing, Threaded rod for supports, including bellows, Flange End with Equilizer/ Shorting Plate , Horizontal bend / Vertical Bend, elbows (Indoor), Horizontal bend / Vertical Bend, elbows (Outdoor) etc.Note: Measurement of length of bus duct shall be along the central axis of the bus duct. |
| 247 | Installation, Testing, Commissioning of Straight Run Feeder, IP 54 (For Indoor portion of Busduct) including all accessories such as space heater, nut, bolt washer, Earthing, Threaded rod for supports, including bellows, Flange End with Equilizer/ Shorting Plate , Horizontal bend / Vertical Bend, elbows (Indoor), Horizontal bend / Vertical Bend, elbows (Outdoor) etc.Note: Measurement of length of bus duct shall be along the central axis of the bus duct. |
| 248 | Installation, Testing, Commissioning of Flange End with Equilizer/ Shorting Plate |
| 249 | Installation, Testing, Commissioning of Horizontal bend / Vertical Bend, elbows (Indoor) |
| 250 | Installation, Testing, Commissioning of Horizontal bend / Vertical Bend, elbows (Outdoor) |
| 251 | Installation, Testing, Commissioning of Tinned Copper Braided Flexibles (with Hardware - Nuts and Bolts) |
| 252 | Installation, Testing, Commissioning of Adaptor Box |
| 253 | 415V SWITCHBOARDS:Receiving from store, transporting to erection site, Installation, testing & commissioning of supplied 415V Switchboards |
| 254 | POWER CONTROL CENTRE (PCC) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for PCC (18L07-1-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 4000A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), MFM,CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for Top Busduct entry (TPN Sandwich bus duct) and bottom cable entry for outgoing feeders Location: MCC Room |
| 255 | MOTOR CONTROL CENTER 1 (MCC-1, FOR UN-LOADING PUMPS) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MCC 1 (18L07-2-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 630A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders Location: MCC Room |
| 256 | MOTOR CONTROL CENTER 2 (MCC-2, FOR LOADING PUMPS) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MCC 2 (18L07-3-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 800A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MFM, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 257 | MOTOR CONTROL CENTER 3 (MCC-3, MISCELLANEOUS) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and (18L07-4-SLD-E-001, Rev-0, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire (Neutral shall 100%), 50 Hz, AL Bus Bar, 250A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs (with extended operating handle and LSIG protection), MFM,CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders. Location: MCC Room |
| 258 | MAIN LIGHTING DISTRIBUTION BOARD (MLDB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MLDB (18L07-5-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire, 50 Hz, AL Bus Bar, 400A, 10 kA for 1 second, single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs, CTs, PTs,indication lamp, main contactor, timer with adjustable time setting & auxiliary contactors, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for bottom cable entry.Location: MCC Room |
| 259 | MAIN POWER DISTRIBUTION BOARD (Main PDB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for Main PDB (18L07-6-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 800A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for bottom cable entry.Location: MCC Room |
| 260 | MOV / ROSOV PANEL (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MOV/ROSOV (18L07-7-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 250A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for bottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 261 | EMERGENCY LIGHTING DISTRIBUTION BOARD (ELDB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001,Sh. 1 of 1) and SLD for ELDB (18L07-8-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 250A, 10 kA for 1 second, single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs , CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 262 | EMERGENCY SWITCH BOARD (ESB) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for ESB (18L07-9-SLD-E-001,Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 800A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, main contactor, timer with adjustable time setting & auxiliary contactors, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 263 | AUTOMATIC POWER FACTOR CORRECTION PANEL (APFC PANEL) (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for APFC PANEL (18L07-10-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 2500A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for ACBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection,ACB-EDO type with Microprocessor releases, MCCBs (with extended operating handle and LSIG protection), CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable forbottom cable entry for incoming / outgoing feeders.Location: MCC Room |
| 264 | FIRE PANEL(Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for FIRE PANEL (18L07-10-SLD-E-001, Sh. 1 of 1)) Installation, testing & commissioning of of 415V, 3 phase, 4 wire , 50 Hz, AL Bus Bar, 250A, 50 kA for 1 second, Internal Arc 50kA for 0.3 sec (AFLR), single front,fully draw out for MCCBs, compartmentalized, Indoor, Floor MountedPanel with Incomers and Outgoing feeders,Metering and protection, MCCBs, MFM, CTs, PTs,indication lamp, switches etc, as per attached SLD, specification, data sheet. Panel shall be suitable for bottom cable entry. The enclosure of this Panel shall have IP55 degree of protection.Location: FWPH. |
| 265 | MARSHALLING CABINET: |
| 266 | Installation, testing & commissioning of floor mounted type Marshalling Cabinet (Interphassing cabinet) having 500 terminalssuitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of non- FLP, Double Compression Cable Glands |
| 267 | Installation, testing & commissioning of floor mounted type Marshalling Cabinet (Interphassing cabinet) having 250 terminalssuitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of non- FLP, Double Compression Cable Glands. |
| 268 | 415V MOV DISTRIBUTION BOARDS(FLAMEPROOF, WEATHERPROOF TYPE)Installation, testing & commissioning of 415V, 3Ph & N, 50kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Flameproof with Canopy of 14 gauge CRCA sheet, Non-compartmentalised, Double door, MOV Distribution Boards along with Flameproof double compression Ni plated brass cable glands and lugs suitable for bottom cable entry complete in all respect as per attached SLD (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MOV / ROSOV PANEL (18L07-7-SLD-E-001, Sh. 1 of 1)). Receiving from store, transporting to erection site inclduing cable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, assembly of shipping section, interconnection of busbars, interpanel wiring, drilling of gland plates as per required holes for cable entries, plugging of all unused entries and other holes in the boards/panels to make the same dust and vermin proof, making good of wall/columns broken or chipped by cement plastering, checking internal connection for tightness & proper wiring, carrying out minor modification on wiring, fixing of panels with base frame works/supports by welding/bolting including supply of GI hardwares, fixing of canopy for outdoor DB\"s, touch up painting work as required, testing & commissioning of following PANELS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards & instructions/ directions of ENGINEER IN CHARGE.Note:Civil & structural works shall be paidunder respective items. |
| 269 | MOV DB-1 (48W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 37 nos |
| 270 | MOV DB-2 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 24 nos |
| 271 | MOV DB - 3 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 20 nos |
| 272 | MOV DB - 4, 5, 6 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 22 nos |
| 273 | MOV DB - 7 (24W)Incomer- 16A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 16 nos |
| 274 | MOV DB - 8 (32W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 26 nos |
| 275 | ROSOV DISTRIBUTION BOARD (ROSOV DB) (FLAMEPROOF, WEATHERPROOF TYPE)Installation, testing & commissioning of 415V, 3Ph & N, 10kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Flameproof with Canopy, Non-compartmentalised, Double door, ROSOV Distribution Boards along with Flameproof double compression Ni plated brass cable glands and lugs, suitable for bottom cable entry complete in all respect as per attached SLD (Ref. Electrical Overall SLD (18L07-0-SLD-E-001, Sh. 1 of 1) and SLD for MOV / ROSOV PANEL (18L07-7-SLD-E-001, Sh. 1 of 1)) Receiving from store, transporting to erection site inclduing cable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, assembly of shipping section, interconnection of busbars, interpanel wiring, drilling of gland plates as per required holes for cable entries, plugging of all unused entries and other holes in the boards/panels to make the same dust and vermin proof, making good of wall/columns broken or chipped by cement plastering, checking internal connection for tightness & proper wiring, carrying out minor modification on wiring, fixing of panels with base frame works/supports by welding/bolting including supply of GI hardwares, fixing of canopy for outdoor DB\"s, touch up painting work as required, testing & commissioning of following PANELS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards & instructions/ directions of ENGINEER IN CHARGE.Note:Civil & structural works shall be paidunder respective items. |
| 276 | ROSOV DB-1 (24W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 16 nos |
| 277 | ROSOV DB-2 (24W)Incomer- 32A, 4P, MCCB- 1 no,Outgoings- 4A 4P MCB - 16 nos |
| 278 | INSTALLATION, TESTING & COMMISSIONINGOFAC UPS SYSTEM 2 x10 kVA, 3-phase, 3 wire, 415V, 50Hz Input, 1-phase, 2 wire, 230V, 50 Hz output, IGBT type, Parallel redundant UPS along with static bypass & suitable rating SMF VRLA battery bank for 30 Min back up as per attached SLD, battery stand (duly powder coated with castors), specification, data sheet for critical lighting loads.UPS shall be supplied along with Weatherproof double compression Nickel plated brass glands and lugs suitable for cable sizes indicated on SLD. The item is inclusive of Heat Run Test.Location-Control BuildingNote:Civil & structural works shall be paidunder respective items. |
| 279 | INSTALLATION, TESTING & COMMISSIONINGOF BATTERY CHARGER & DC BOARD (DCDB):Receiving from store, transporting to erection site including cable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,handling, arrangement of transport vehicle, loading & unloading equipment like crane, slings etc., preparation of foundation, supply & fixing of base frame by welding on plate insert / angle embedded in the foundation placing on foundation frame, positioning, levelling, aligning, interpanel bus connection, wiring, fixing in the panel parts separately supplied, fixing with base frame by welding/bolting including supply of GI hardware, touch up painting as required, testing & commissioning of following: BATTERY CHARGER & DC BOARD (DCDB)30kVA, 110V DC, 2X100%Float cum boost charger along with 110V DC, 2 wireIntegral DCDB as per technical specification, datasheet & SLD complete in all respect long with Weatherproof double compression Nickel plated brass glands and lugs suitable. complete in all respect including interconnecting cablingwith all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE. Location- MCC room Note: Civil & structural works shall be paidunder respective items. |
| 280 | LOCAL CONTROL STATION (LCS) (WEATHER PROOF, FLAMEPROOF TYPE)Installation, Testing & Commissioning of following Industrial type, Weatherproof, Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65, Local Control Station suitable for Wall / Column / Structure mounting. All LCS shall be made up ofAluminium alloy (LM6 grade) with with Canopy of 14 gauge CRCA sheet with side cover. LCS shall confirm to attached specification/data sheet. LCS shall be supplied along with Flameproof Double compression, Ni plated brass cable glands & lugs. |
| 281 | LCS with 1 no. mushroom head stay put type emergency stop PB with Keys, 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS) & Suppressed scale ammeter suitable for outdoor installation.LCS shall be suitable for 12Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(ForIE-3 motors including & above 30kW rating) |
| 282 | LCS with1 no. mushroom head stay put type emergency stop PB with Keys and 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS)suitable for outdoor installation. LCS shall be suitable for 7Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(For Motors below 30 kW rating) |
| 283 | Break glass typeEmergency Trip Push Button (ETPB) for transformer: weather proof emergency stop pushbutton(EPB) with ON-OFF LED indication break glass type enclosure, 3mm thick FRP canopy, weatherproof double compression Nickel Plted Brass cable glands(2 nos.) and 1NO+1 NC contact. |
| 284 | INSTALLATION, TESTING & COMMISSIONINGOFLOCAL CONTROL STATION (LCS) (WEATHER PROOF, NON-FLAMEPROOF TYPE): Industrial type, Weatherproof, IP 65, Non flame proof Local Control Station suitable for Wall / Column / Structure mounting. All LCS shall be made up ofAluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheet with side cover. LCS shall confirm to attached specification/data sheetReceiving from store, transporting to erection site including cable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures,checking of complete bill of materials , placing on frame works/supports, Installation,testing & commissiong of following Industrial type, Weatherproof, IP 65, Non flame proof Local Control Station suitable for Wall / Column / Structure mounting. Note: Civil & structural works shall be paidunder respective items. |
| 285 | LCS with 1 no. mushroom head stay put type emergency stop PB with Keys, 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS) & Suppressed scale ammeter suitable for outdoor installation.LCS shall be suitable for 12Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(ForIE-3 motors including & above 30kW rating) |
| 286 | LCS with1 no. mushroom head stay put type emergency stop PB with Keys and 1 no. recess type PB for start, Local remote switch (with additional contacts to give the status of Local remote switch to DCS)suitable for outdoor installation. LCS shall be suitable for 7Cx2.5 sqmm Copper conductor, PVC insulated, inner & outer sheated, FRLS, Armoured cable.(For Motors below 30 kW rating) |
| 287 | Break glass typeEmergency Trip Push Button (ETPB) for transformer: weather proof emergency stop pushbutton(EPB) with ON-OFF LED indication break glass type enclosure, 3mm thick FRP canopy, weatherproof double compression Nickel Plted Brass cable glands(2 nos.) and 1NO+1 NC contact. |
| 288 | POWER JUNCTION BOX FOR MOTOR (WEATHER PROOF, FLAME PROOF) : Receiving from store, transporting to erection site includingcable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports.Installation, Testing, Commissioning of following 415V,TPN Industrial type, Weatherproof, Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2), IP 65, Junction Boxes with Aluminium busbar, 50kA/1sec, suitable for Wall / Column / Structure mounting. All JBs shall be made up ofAluminium alloy (LM6 grade) with Canopy of 14 gauge CRCA sheet or equivalent with side cover. JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be finalised during drawing approval only. In case of increase in cable sizes, no extra cost shall be payable.Please note that all cables shall be Aluminium conductor(10 sqmm & above)/Copper conductor(4 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. |
| 289 | Power JB having Busbar rating 63AJB suitable for terminating upto 1Rx3Cx70Sq.mm cables at one side and upto 2Rx3Cx35Sq.mm AL cable at other side |
| 290 | Power JB having Busbar rating upto 200AJB suitable for terminating upto 2Rx3Cx300Sq.mm cables at incoming side and upto 2Rx3Cx95 Sq.mm AL cable outgoing side |
| 291 | INSTALLATION, TESTING & COMMISSIONINGOF JUNCTION BOXES FOR LIGHTING FIXTURES (WEATHER PROOF, FLAME PROOF): Receiving from store, transporting to erection site includingcable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, Installation,testing & commissiong of following 240V, Ph-N, Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure mounting. All JBs shall be made up ofcast Aluminium alloy (LM6 grade) Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables.. Note:Civil & structural works shall be paidunder respective items. |
| 292 | 16A, 4-way, 125 mm (minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos cable glands / Plug, lugs with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable |
| 293 | INSTALLATION, TESTING & COMMISSIONINGOF JUNCTION BOXES FOR POWER SOCKETS (WEATHER PROOF, FLAME PROOF): Receiving from store, transporting to erection site includingcable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, Installation,testing & commissiong of following Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure mounting. All JBs shall be made up ofcast Aluminium alloy (LM6 grade), Flameproof “Ex-d” (suitable for hazardous area of gas group IIA/IIB, temperature class T3 and Zone-2). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Flameproof Double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cablesNote:Civil & structural works shall be paidunder respective items. |
| 294 | 16A, 415V,TPN, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, Canopy of 14 gauge CRCA/AL sheetwith side cover to be provided. |
| 295 | 16A, 230V, Ph-N, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, Canopy of 14 gauge CRCA/AL sheetwith side cover to be provided. |
| 296 | INSTALLATION, TESTING & COMMISSIONINGOF JUNCTION BOXES FOR POWER SOCKETS(WEATHER PROOF, NON-FLAME PROOF): Receiving from store, transporting to erection site includingcable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, Installation,testing & commissiong of following Industrial type, Weatherproof, IP 65 suitable for Wall / Column / Structure mounting. All JBs shall be made up ofcast Aluminium alloy (LM6 grade). JBs shall confirm to attached specification/data sheet. Junction Boxes shall be suitable for cable sizes tentatively as indicated below & shall be supplied along with Weatherproof Double compression, Ni plated brass cable glands, lugs & plugs. However, exact cable sizes shall be indicated during drawing approval only.Please note that all cables shall be Aluminium conductor (10 sqmm & above) / Copper conductor (6 sqmm & below), XLPE insulated, extruded PVC inner & outer sheathed, FRLS, Armoured cables. Note:Civil & structural works shall be paidunder respective items. |
| 297 | 16A, 415V,TPN, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, Canopy of 14 gauge CRCA/AL sheetwith side cover shall be provided. |
| 298 | 16A, 230V, Ph-N, 6-way ,Cast Aluminium (LM-6 ) Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ doublecompression Ni plated brasscable glands with PVC shrouds suitable for 2nos.-3.5cx25sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables,Canopy of 14 gauge CRCA/AL sheetwith side cover shall be provided. |
| 299 | INSTALLATION, TESTING & COMMISSIONING OF INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, FLAMEPROOF TYPE): Flame proof,Industrialtype, (IP65) interlocked with MCB and ELCB and suitable for loop-in loop-out entries for armoured cable as specified, enclosed with Cast Aluminium alloy (LM-6 grade), Ex-d, suitable for installation in Zone-2, Gas group IIA and IIB, temp class T3 with stainless steel hardware, endless neo print gasket, 2nos. of cable entry, stopping plugs, earthing terminals, installation hardware and all necessary accessories wired upto terminal boxAll switch sockets shall be provided withCanopy of 14 gauge CRCA/AL sheetwith side coverand required no. of FLP double compressionNi plated brass cable glands and FLP stopping plug as per attached specification sheets.Receiving from store, transporting to erection site, installationincludingcable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, testing & commissioning ofwall/structure mounted items like FLP/Non FLP Industrial power socket outlets with all accessories, all work, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of engineer-in-charge.Note:Civil & structural works shall be paidunder respective items. |
| 300 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 301 | 16A. 230 V AC, 1 phase, 50 Hz, |
| 302 | 6A. 230 V AC, 1 phase, 50 Hz, |
| 303 | INSTALLATION, TESTING & COMMISSIONING OF INDUSTRIAL POWER SOCKET OUTLETS WITH INTEGRAL PLUG TOPS (WEATHERPROOF, NON-FLAMEPROOF TYPE): Non-Flame proof,industrialtype (IP65) interlocked with MCB and ELCB and suitable for loop-in loop-out entries for armoured cable as specified enclosed with Cast Aluminium alloy (LM-6 grade) with stainless steel hardware, endless neoprene gasket, 2nos. of cable entry, stopping plugs, earthing terminals, installation hardware and all necessary accessories wired upto terminal box. All switch sockets shall be provided with 3mm thick FRP canopy with side cover and required no. of double compressionNi plated brass cable glands and stopping plug as per attached specification sheets.Receiving from store, transporting to erection site, installationincludingcable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, testing & commissioning ofwall/structure mounted items like FLP/Non FLP Industrial power socket outlets with all accessories, all work, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of engineer-in-charge.Note:Civil & structural works shall be paidunder respective items. |
| 304 | 415 V AC, 3 phase, 63A, (3P+N+E), 50 Hz |
| 305 | 16A. 230 V AC, 1 phase, 50 Hz, |
| 306 | 6A. 230 V AC, 1 phase, 50 Hz, |
| 307 | INSTALLATION, TESTING & COMMISSIONINGOF 415V LIGHTING PANELS (FLAMEPROOF, WEATHER PROOF TYPE): Receiving from store, transporting to erection site inclduing cable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, assembly of shipping section, interconnection of busbars, interpanel wiring, drilling of gland plates as per required holes for cable entries, plugging of all unused entries and other holes in the boards/panels to make the same dust and vermin proof, making good of wall/columns broken or chipped by cement plastering, checking internal connection for tightness & proper wiring, carrying out minor modification on wiring, fixing of panels with base frame works/supports by welding/bolting including supply of GI hardwares, fixing of canopy for outdoor DB\"s, touch up painting work as required, testing & commissioning of following PANELS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards & instructions/ directions of ENGINEER IN CHARGE.Note:Civil & structural works shall be paidunder respective items. |
| 308 | Outdoor type Normal Lighting Panel comprising Incomer- 32A, 4P, MCB- 1 no, Sub Incomer-32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-9 nos, (3 nos/ Phase) |
| 309 | Outdoor type Normal Lighting Panel comprising Incomer- 32A, 4P, MCB- 1 no, Sub Incomer-32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-18nos, (6 nos/ Phase) |
| 310 | Outdoor type Normal Lighting Panel comprisingIncomer- 63A, 4P, MCB- 1 no, Sub Incomer-63A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-27nos, (9 nos/ Phase) |
| 311 | Outdoor type Normal lighting panel Incomer : 100A4P, MCCB Outgoings- 25A 4P MCB - 8 nos |
| 312 | 415V LIGHTING PANELS (NON-FLAMEPROOF, WEATHER PROOF TYPE):Receiving from store, transporting to erection site inclduing cable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, assembly of shipping section, interconnection of busbars, interpanel wiring, drilling of gland plates as per required holes for cable entries, plugging of all unused entries and other holes in the boards/panels to make the same dust and vermin proof, making good of wall/columns broken or chipped by cement plastering, checking internal connection for tightness & proper wiring, carrying out minor modification on wiring, fixing of panels with base frame works/supports by welding/bolting including supply of GI hardwares, fixing of canopy for outdoor DB\"s, touch up painting work as required, testing & commissioning of following PANELS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards & instructions/ directions of ENGINEER IN CHARGE.415V, 3Ph & N, 10kA 1 sec, sheet steel enclosure, wall or frame mounted, IP 65 protected, Weatherproof with canopy, Non-compartmentalised, Double door, Lighting Panels along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders, suitable for bottom cable entry complete in all respect as per attached SLD Specification/Data sheet |
| 313 | Outdoor type Normal Lighting Panel comprising Incomer- 32A, 4P, MCB- 1 no, Sub Incomer- 32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-9 nos, (3 nos/ Phase) |
| 314 | Outdoor type Normal/Emergency Lighting Panel comprising Incomer- 32A, TPN, MCB- 1 no, Sub Incomer- 32A, DP RCCB with 30mA sensitivity - 3 Nos. Outgoings- 10A DP MCB-12 nos, (4 nos/Phase) |
| 315 | Outdoor type Normal lighting panel Incomer : 100A4P, MCCB Outgoings- 25A 4P MCB - 8 nos |
| 316 | 415V POWER DB (NON-FLAMEPROOF, WEATHERPROOF TYPE):Receiving from store, transporting to erection site inclduing cable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, assembly of shipping section, interconnection of busbars, interpanel wiring, drilling of gland plates as per required holes for cable entries, plugging of all unused entries and other holes in the boards/panels to make the same dust and vermin proof, making good of wall/columns broken or chipped by cement plastering, checking internal connection for tightness & proper wiring, carrying out minor modification on wiring, fixing of panels with base frame works/supports by welding/bolting including supply of GI hardwares, fixing of canopy for outdoor DB\"s, touch up painting work as required, testing & commissioning of following PANELS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards & instructions/ directions of ENGINEER IN CHARGE.415V, 3Ph & N, 10kA 1 sec, sheet steel enclosure, wall or frame mounted, IP 65 protected, Non-compartmentalised, Double door, Weatherproof, Power Panels along with Weatherproofdouble compression Ni plated brass cable glands and lugs and canopy, suitable forbottom cable entry complete in all respect as per attached SLD, Specification/Data sheet |
| 317 | Outdoor type Normal Power Panel comprisingIncomer- 32A, 4P, MCB- 1 no,Sub Incomer- 32A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 10A DP MCB-6 nos, (2 nos/ Phase) |
| 318 | 415V POWER DB(FLAMEPROOF, WEATHERPROOF TYPE):Receiving from store, transporting to erection site inclduing cable glanding & power/ control cable termination,closing of unused cable entries with FLP/Non FLP threaded plug,verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., supply & fixing frame works/supports grouted or welded to walls/columns/structures, checking of complete bill of materials , placing on frame works/supports, assembly of shipping section, interconnection of busbars, interpanel wiring, drilling of gland plates as per required holes for cable entries, plugging of all unused entries and other holes in the boards/panels to make the same dust and vermin proof, making good of wall/columns broken or chipped by cement plastering, checking internal connection for tightness & proper wiring, carrying out minor modification on wiring, fixing of panels with base frame works/supports by welding/bolting including supply of GI hardwares, fixing of canopy for outdoor DB\"s, touch up painting work as required, testing & commissioning of following PANELS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards & instructions/ directions of ENGINEER IN CHARGE.415V, 3Ph & N, 10kA 1 sec, Aluminium alloy (LM6) enclosure, Ex\"d\", IIA, IIB, T3, wall or frame mounted, IP 65, Non-compartmentalised, Double door,Flameproof Power Panel with Canopy along with Flameproofdouble compression Ni plated brass cable glands and lugs suitable for bottom cable entry complete in all respect as per attached SLD ,Specification/Data sheet |
| 319 | Outdoor type Flame proof Power Panel comprisingIncomer- 63A, 4P, MCB- 1 no,Sub Incomer- 63A, DP RCCB with 30mA sensitivity - 3 Nos.Outgoings- 16A DP MCB-6 nos, (2 nos/ Phase) |
| 320 | INSTALLATION OF POLES FOR LIGHTING SYSTEMReceiving from store, transporting to erection site includingcable glanding & power/ control cable termination, closing of unused cable entries with FLP/Non FLP threaded plug, verification of bill of materials, handling, arrangement of transport vehicle, loading/unloading equipment & accessories etc., Installation, testing & commissiong of following : |
| 321 | 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with single arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications.The item also includes suitable fixing/clamping arrangement made up of GI on the body of the octogonal pole for fixing of 16A, 4-way, 125 mm (minimum) internal dimensions flameproof junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos cable glands / Plug, lugs with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable. The design shall be submitted for approval of IOCL. The payment for the Junction Box shall be made seperately. |
| 322 | 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with double arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications.The item also includes suitable fixing/clamping arrangement made up of GI on the body of the octogonal pole for fixing of 16A, 4-way, 125 mm (minimum) internal dimensions flameproof junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos cable glands / Plug, lugs with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable. The design shall be submitted for approval of IOCL. The payment for the Junction Box shall be made seperately. |
| 323 | 9 Meter high galvanised Octagonal pole with top 90mm(A/F),bottom 158mm (A/F), made up of 3mm thick plate having a baseplate of size min. 285 x 285 x 16 with double arm 1500mm long bracket arm made up of 48 O.D. pipe with EN grade galvanised foundation bolts, nuts,washers & anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications. |
| 324 | 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with double arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 2 Nos. of 120W LED luminaries as per enclosed technical specifications. |
| 325 | 7 Meter high galvanised Octagonal pole with top 70mm (A/F), bottom 130mm (A/F) made up of 3 mm thick plate having a base plate of size min. 220 x 220 x 12 with single arm 1500mm long bracket arm made up of 48 O.D. pipe with EN 8 grade galvanised foundation bolts and anchor plate having fixing arrangement for mounting 1 Nos. of 120W LED luminaries as per enclosed technical specifications. |
| 326 | 6 Mtr GI Lighting Pole(Octagonal or polygonal section) including foundation bolts for ground mounting suitable for 1 no.x 18 watt Solar Hybrid LED fixturewith weatherproof nickel plated brass cable gland, tinned copper lugs of suitable type & size for termination, weather proof JB at the foot of pole including MCB & terminal block (as applicable), cables from foot of the pole to the light fittings complete with all accessories, GI pipe (Class B) for cable protection,Zinc passivated hardware for fixtures support & pole support, clamps, nuts, bolts, etc. including supply of commissioning spares, as required. |
| 327 | GOOSE / SWAN NECK TYPE POLE FOR WELL GLASS LIGHTING FIXTURESupply of outdoor type 2.5 mtr hot dip galvanised, goose neck type lightingpole(50mm as per IS 1239 - Medium duty) alongwith with flameproof Junction Box suitable for for structural / handrail mounting , complete with all clamping arrangements for cables including accessories , flameproof proof JBs at the foot of the pole along with Flameproof proof double compression Ni plated brass cable glands and lugs & termination block (as applicable), zinc passivated hardware for fixtures support & pole support , clamps, nuts, bolts, etc. including supply of commissioning spares , as requiredfor 1 nos.of well glass light luminaires.The pole shall be epoxy coated GI pole of Class B type. The junction box shall be complete with terminals for loop-in loop-out of cables. |
| 328 | HIGH MAST LIGHTING: Installation & Commissioning of 20 Mtr. height High Mastcomplete with accessories as per specifications. The cost also includes supplying and providing trailing cable of suitable sizefrom Switch Plug & Socket at the foot of high mast to the junction box at the top,FLP Motor, suitable size double compression, cable glands. |
| 329 | HIGH MAST LIGHTING: Installation & Commissioning of 10 Mtr. height High Mastcomplete with accessories as per specifications. The cost also includes supplying and providing trailing cable of suitable sizefrom Switch Plug & Socket at the foot of high mast to the junction box at the top,FLP Motor, suitable size double compression, cable glands. |
| 330 | Installation & Commissioning of flameproof outdoor, made of 14 SWG CRCA sheet, IP-65, stand mounted feeder pillar with 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35-70 sq. mm and out going 12 & 2.5 sq. mm terminals& 1 no. outgoing upto 35-70 sqm for looping. (Necessary Civil Works shall be paid seperately) |
| 331 | Installation & Commissioning of weatherproof outdoor, made of 14 SWG CRCA sheet, IP-65, stand mounted feeder pillar with 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35-70 sq. mm and out going 12 & 2.5 sq. mm terminals& 1 no. outgoing upto 35-70 sqm for looping. (Necessary Civil Works shall be paid seperately) |
| 332 | INSTALLATION, TESTING & COMMISSIONING OF LIGHTING FIXTURES:Receiving from store, transporting to erection site including handling, arrangement of transport vehicle, unpacking, inspection, checking of internal wiring, fixing copper conductor, cabling / circuit wiringwith 3x2.5 sq. mm (cu ) or as per required size armoured between LTG Panels to (JB/control gear box wherever applied) to fixtures, painting of circuit nos., wherever required, supply & fixing pipes/GI chains, supply & fixing neoprene/rubber/PVC bushes at fixtures and JBs, erection in position on brick/RCC walls OR on RCC/steel columns/roofs/structures/cable trays OR on poles, cable glanding & termination, crimping of lugs & connections at fixtures/ control gears, supply of all erection materials including supply of necessary GI hardware, GI clamps, GI brackets, civil masonry materials, testing of following types of LIGHTING FIXTURES with all their parts & accessories etc.,including fixing of lamps, all work, labour and materials complete as per drawings and documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE. |
| 333 | LIGHTING FIXTURES FOR HAZARDOUS AREA (FLAMEPROOF TYPE) |
| 334 | 110W LED Flood light suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminal box. |
| 335 | 70W LED, Well glass luminaire suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings enclosure with toughened glass, SS wire guard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminal box. |
| 336 | 40W LED, Well glass luminaire suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings enclosure, SS wire guard, stainless steel hardware, earthing terminal, installation hardware and all necessary accessories wired up to terminal box. |
| 337 | Design, Supply and Installation of FLP 100 W GLS,110V DC ,well glass type light fittings with reflector and its accessories etc and junction box(if required) |
| 338 | FLP 2 x 20 W LED, Industrial type, lighting fixtures with LED lamp and all other accessories as per specification |
| 339 | LIGHTING FIXTURES (NON-FLAMEPROOF TYPE) |
| 340 | WP 60 W GLS,110V DC, bulk head type light fittings with reflector and its accessories etc and junction box (if required) |
| 341 | 36W Weatherproof LED Batten Light suitable for Ceiling/Pole/Structure/MS bracket/Rod/Pipe mountings |
| 342 | 80W LED undercanopy light (Outdoor type) suitable for surface / recessed mounting from structure |
| 343 | LED Flood Light with a minimum system lumen of 53000 Lm and system wattage of nominal 400W (For High-Mast Lights) |
| 344 | 100 W LED light fixture with fittings and accessories for Yard lighting purpose |
| 345 | DC LIGHTING Installation & Commissioning of Weather proof12V DC lamp with integral charger for FWPH/PMCC/Control Room & Security Room. |
| 346 | CABLE LAYING: Horizontal and Vertical Laying of FRLS/FR , XLPE/PVC cables of following sizes and particularson cable racks,RCC trenches, Buried trench , floor slits,in G.I. conduit (including chipping of floor wherever required), on cable trays, trenches, cable racks, cable risers, supports, hangers, saddles etc., Sealing of wall openings and pipe sleeves after cable layingetc., Including handling, transportation from owner\"s store/storage yard to installation site of cables/cable drums, unpacking , inspection, cable dressing, fixing of cable clamps in vertical and if necessary,in horizontalruns,fixingof cable identification tags (At every 10 Mtr. interval all alongthe length); testing before and after laying; supply & installationof Aluminum cable clamps and cable tags, GI saddles and GI saddle bars , GI bolts,nuts and washer screws etc., providing cable route marker for buried cable trenches at every 10 M interval.Actual site measurement shall be taken before cutting the cable from drum to avoid cable joint / waste,measurement of IR value, testing of cables before and after terminations for IR values, all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer-in-ChargeNote: The payment shall be made based on actual mesauremnet of the cable layed from gland to gland/socket.No allowance for the wastages, further terminationwill be added. |
| 347 | Cable core cutting for HT,LT & control cables. |
| 348 | 11 kV (E) grade HT Cable with stranded compact Aluminium conductor,conductor screened by extruded semi conducting compound, XLPE insulated,colour coded, insulation screened by extruded semi conducting compound followed by a layer of copper tape, cores laid up together suitably extruded PVC innersheathed, strip (for multi core) and overall extruded FRLS PVC outer sheathed cable conforming to IS 7098-2.The item also includes fixing of cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280. |
| 349 | 3Cx300 sqmm.-Al |
| 350 | 3Cx300 sqmm. 11kV(E), Al. Cable End termination Kits (Indoor type) |
| 351 | 3Cx300 sqmm. 11kV(E), Al. Cable End termination Kits (Outdoor type) |
| 352 | 1.1 kV grade power XLPE insulated Copper/Aluminium conductor (up to 4 sqmm copper cable shall be selected & above 4 sqmm Aluminium conductor), multi core, steel wire/strip (for multi core) armoured, FRLS PVC outer sheathed cable conforming to IS 7098-1.The cables shall be tied with cable tray fixing ties made of tough flexible virgin Nylon 6.6 in accordance with MIL M20693B and UL 94 V-2 or 20 SWG GI wires. The item also includes fixing of cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280. |
| 353 | 3Cx1.5 sq.mm-Cu |
| 354 | 3Cx2.5 sq.mm-Cu |
| 355 | 3Cx6 sq.mm-Cu |
| 356 | 3Cx10 sqmm.-Al |
| 357 | 3Cx16 sqmm.-Al |
| 358 | 3Cx25 sq.mm-Al |
| 359 | 3Cx35 sq.mm-Al |
| 360 | 3Cx70 sq.mm-Al |
| 361 | 3Cx95 sq.mm-Al |
| 362 | 3Cx150 sq.mm-Al |
| 363 | 3Cx185 sq.mm-Al |
| 364 | 3Cx240 sq.mm-Al |
| 365 | 3Cx300 sq.mm-Al |
| 366 | 3Cx400 sq.mm-Al |
| 367 | 3.5Cx25 sq.mm-Al |
| 368 | 3.5Cx35 sq.mm-Al |
| 369 | 3.5Cx50 sq.mm-Al |
| 370 | 3.5Cx70 sq.mm-Al |
| 371 | 3.5Cx95 sq.mm-Al |
| 372 | 3.5Cx120 sq.mm-Al |
| 373 | 3.5Cx150 sq.mm-Al |
| 374 | 3.5Cx185 sq.mm-Al |
| 375 | 3.5Cx240 sq.mm-Al |
| 376 | 3.5Cx300 sq.mm-Al |
| 377 | 3.5Cx400 sq.mm-Al |
| 378 | 4Cx6 sq.mm-Al |
| 379 | 4Cx10 sq.mm-Al |
| 380 | 4Cx16 sq.mm-Al |
| 381 | 4Cx25 sq.mm-Al |
| 382 | 4Cx35 sq.mm-Al |
| 383 | 4Cx50 sq.mm-Al |
| 384 | LT CONTROL CABLES Supply of LT control cables shall be suitable for 1.1 kV grade, copper Conductor, multi cores, PVC insulated, colour coded, laid up sheathed with extruded PVC inner sheath, hard drawn galvanised strip /wire armoured, and extruded overall FRLS PVC outer sheathed as per IS 1554-1. Note: Before procuring cable, successfull bidder is required to prepare detailed BOQ & Drum Schedule as per site mesaurement. No extra payment shall be made for wastages.The cost is inclusive of Cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280. |
| 385 | 2Cx2.5 sq. mm. |
| 386 | 12Cx2.5 sq. mm. |
| 387 | 5Cx1.5 sq. mm. |
| 388 | 7Cx2.5 sq. mm. |
| 389 | 3Cx4 sq. mm. |
| 390 | 12Cx1.5 sq. mm. |
| 391 | LV POWER CABLE GLANDING AND TERMINATION:Glanding & Cable termination, connections and testing of 1.1kV grade, Al. OR Cu. conductor, XLPE insulated, GI strip/ round wire armoured, FRLS POWER / CONTROL / LIGHTING / EARTHING CABLES of following sizes and particulars including drilling / tapping of gland plate for cable entry OR enlarging existing cable entries as required, fixing of cable glands & terminals supplied loose at equipment end but excluding supply of cable glands. Cable termination also includes supply of cable lugs with stripping of insulation, taping, soldering OR crimping of tinned Cu. / Al. (as required), sockets OR lugs to conductors, connection of leads to equipment terminals etc., ferruling, supply of GI nuts, bolts, washer, screws, insulating tapes, compounds, solders, fluxes, ferrules etc. Closing of unused cable entries to make the equipment dust, moisture & vermin proof, all work, labour and materials complete as per drawings, specifications, codes & standards and instructions / directions of engineer-in-charge. |
| 392 | 3Cx1.5 sq.mm-Cu |
| 393 | 3Cx2.5 sq.mm-Cu |
| 394 | 3Cx6 sq.mm-Cu |
| 395 | 3Cx10 sqmm.-Al |
| 396 | 3Cx16 sqmm.-Al |
| 397 | 3Cx25 sq.mm-Al |
| 398 | 3Cx35 sq.mm-Al |
| 399 | 3Cx70 sq.mm-Al |
| 400 | 3Cx95 sq.mm-Al |
| 401 | 3Cx150 sq.mm-Al |
| 402 | 3Cx185 sq.mm-Al |
| 403 | 3Cx240 sq.mm-Al |
| 404 | 3Cx300 sq.mm-Al |
| 405 | 3.5Cx25 sq.mm-Al |
| 406 | 3.5Cx35 sq.mm-Al |
| 407 | 3.5Cx50 sq.mm-Al |
| 408 | 3.5Cx70 sq.mm-Al |
| 409 | 3.5Cx95 sq.mm-Al |
| 410 | 3.5Cx120 sq.mm-Al |
| 411 | 3.5Cx150 sq.mm-Al |
| 412 | 3.5Cx185 sq.mm-Al |
| 413 | 3.5Cx240 sq.mm-Al |
| 414 | 3.5Cx300 sq.mm-Al |
| 415 | 3.5Cx400 sq.mm-Al |
| 416 | 4Cx6 sq.mm-Al |
| 417 | 4Cx10 sq.mm-Al |
| 418 | 4Cx16 sq.mm-Al |
| 419 | 4Cx25 sq.mm-Al |
| 420 | 4Cx35 sq.mm-Al |
| 421 | 4Cx50 sq.mm-Al |
| 422 | LT CONTROL CABLE GLAND (FOR HAZARDOUS AREAZone-2, Ex\"d\", Gas group IIA/IIB, Temperature class-T3): Glanding & Cable termination, connections and testing of 1.1kV grade, Al. OR Cu. conductor, XLPE insulated, GI strip/ round wire armoured, FRLS POWER / CONTROL / LIGHTING / EARTHING CABLES of following sizes and particulars including drilling / tapping of gland plate for cable entry OR enlarging existing cable entries as required, fixing of cable glands & terminals supplied loose at equipment end but excluding supply of cable glands. Cable termination also includes supply of cable lugs with stripping of insulation, taping, soldering OR crimping of tinned Cu. / Al. (as required), sockets OR lugs to conductors, connection of leads to equipment terminals etc., ferruling, supply of GI nuts, bolts, washer, screws, insulating tapes, compounds, solders, fluxes, ferrules etc. Closing of unused cable entries to make the equipment dust, moisture & vermin proof, all work, labour and materials complete as per drawings, specifications, codes & standards and instructions / directions of engineer-in-charge. |
| 423 | 2Cx2.5 sq. mm. |
| 424 | 12Cx2.5 sq. mm. |
| 425 | 5Cx1.5 sq. mm. |
| 426 | 7Cx2.5 sq. mm. |
| 427 | 3Cx4 sq. mm. |
| 428 | 12Cx1.5 sq. mm. |
| 429 | LT CONTROL CABLE GLAND (FOR GENERAL AREA- NON HAZARDOUS): Glanding & Cable termination, connections and testing of 1.1kV grade, Al. OR Cu. conductor, XLPE insulated, GI strip/ round wire armoured, FRLS POWER / CONTROL / LIGHTING / EARTHING CABLES of following sizes and particulars including drilling / tapping of gland plate for cable entry OR enlarging existing cable entries as required, fixing of cable glands & terminals supplied loose at equipment end but excluding supply of cable glands. Cable termination also includes supply of cable lugs with stripping of insulation, taping, soldering OR crimping of tinned Cu. / Al. (as required), sockets OR lugs to conductors, connection of leads to equipment terminals etc., ferruling, supply of GI nuts, bolts, washer, screws, insulating tapes, compounds, solders, fluxes, ferrules etc. Closing of unused cable entries to make the equipment dust, moisture & vermin proof, all work, labour and materials complete as per drawings, specifications, codes & standards and instructions / directions of engineer-in-charge. |
| 430 | 12Cx2.5 sq. mm. |
| 431 | 5Cx1.5 sq. mm. |
| 432 | 12Cx1.5 sq. mm. |
| 433 | INSTALLATION OF G.I. LADDER TYPE & PERFORATED CABLE TRAY : Installation of Pre-FabricatedG.I. cable tray with accessories like: Coupler Plates,Hold on Clamps , bends etc. and supporting arrangement. The work includes transportation from owners store to erection site, unpacking, inspection; checking, Erection in position on supports, fixing, supply of all erection materials Including necessary hardware. All work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer-in-Charge. |
| 434 | Hot dip G.I. LADDER TYPE cable trays of minumum 2.5 M length (with 100mm side flange height for cable tray of width 300 mm & aboveand 75 mm side flange height forcable tray of width below 300 mm) for Straight run, bends, Tees etc. as per enclosed specification & drawings. Item includes all accessories, i.e. Coupler plate, Tray Fixing clamp,Fastener, nut, bolt washer etc. as required. All the hardware i.e. Fasterener, Nut, Bolt, Washers etc. shall be of SS 304. Minimum thickness of galvanisation shall be 610 gm/m2.BIDDER to note that all the accessories mentioned above shall be paid in running meters of cable tray lengths. Separate rate for supply of such accessories shall not be paid. |
| 435 | 600 mm Wide 3 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 436 | 300 mm Wide 2 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 437 | 150mm Wide 2 mm thick - Runner Size- 75 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 438 | Hot dip G.I. PERFORATED TYPE cable traysof minumum 2.5 M length for Straight run, bends, Tees etc. as per enclosed specification & drawings. Item includes all accessories, i.e. Coupler plate, Tray Fixing clamp,Fastener, nut, bolt washe retc. asrequired. All the hardware i.e. Fasterener, Nut, Bolt, Washers etc. shall be of SS 304.Minimum thickness of galvanisation shall be 610 gm/m2BIDDER to note that all the accessories mentioned above shall be paid in running meters of cable tray lengths. Separate rate for supply of such accessories shall not be paid. |
| 439 | 600 mm Wide 3 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 440 | 300 mm Wide 2 mm thick - Runner Size- 100 mm x 20 mmx 20 mm / Rung Size- 50mm x 20mm x 20mm at 250 mm spacing |
| 441 | 150mm Wide 2 mm thick and 75 mm side flange height , Runner Size- 75 mm x 10 mm |
| 442 | 50mm Wide 2mm thick and 50 mm side flange height,Runner Size- 50 mm x 10 mm |
| 443 | 1.6 mm thick Hot dip G.I. Cover of minumum 2.5 M length suitable for Cable tray of following sizes including clamps for fixing the cover to cable tray with all accessories. Minimum thickness of galvanisation shall be 610 gm/m2 |
| 444 | 600 mm Wide |
| 445 | 300 mm Wide |
| 446 | 150 mm Wide |
| 447 | 50 mm Wide |
| 448 | Installationof Multi Cable Transit (MCT) BLOCKS withSS Frame with EPDM Modules, Stay plate, Compression wedge, Lubricant etc complete with all accessories for following area including necessary civil works such as dismantling the wall, fixing of the block and restoration of the wall. |
| 449 | MCT-Admin Building (for LT Power Cables- 24 incomer/outoging Cables + 30% Spare blocks ) |
| 450 | MCT-Control room (for LT Power cables -12 incomer/outoging Cables + 30% Spare blocks) |
| 451 | Security Block cum Change Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 452 | Invoice Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 453 | Sample Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 454 | Security Barrack (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 455 | TT Crew Rest Room (for LT Power cables - 6 incomer/outoging Cables + 30% Spare blocks) |
| 456 | Security Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks) |
| 457 | LIGHTING GROUNDING WIRES |
| 458 | Installation and Termination of 14 SWG. GI Wire |
| 459 | JUNCTION BOXES |
| 460 | Installation and termination of Weather proof 16A, 240V, 4-way, 125mm(minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. |
| 461 | PVC CONDUIT |
| 462 | 20mm Dia. galvanized rigid Conduit |
| 463 | PART (C): |
| 464 | PART ( C ) : COMPOSITEWORKS |
| 465 | CHEMICAL EARTH ELECTRODE PIT FOR EARTHING & LIGHTNING PROTECTION (REFERENCE DRAWING#OVERALL EARTHING LAYOUT (DRG. NO. 18L07-0-LA-E-001, 2 SHEETS)Supply,installation & testing of Chemical Earthing technology (pipe in pipe) for Electrode Designof specified Current Carrying Capacity in kA for 1 second. Crystaline Conductive mixture which is machine pressed in the pipes should not disintegrade or collapse when the outer pipe corrodes. Resistivity of the Material shall be less than 0.2ohm meter when tested by making a 20cm Cube of the Material & checking the resistance across the opposite faces of the cube. Necessary Test certificate shall be submitted. Concentric Earth Electrode Pipe should be MS of IS:1239 quality & hot Dip galvanised of 150 micronor as per IS-2629 & IS-4759/ISO 1461 . Electrode Material Selection should be as per Clause 9.3: IS-3043. Soil Test shall be done as per IS-3043.The item includes making RCC/Brick earth pit chamber with chequered plate cover as per standard Drwng.Current Capacity:50kA for 1sec.Primary Conductor- Inner pipe dia-40NB,Electrode Outer Pipe Dia-100NBLength of Concentric Pipes:3MItem also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick Aluminium Composite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cm long (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker having details as per Site-in-charge. |
| 466 | PIPE ELECTRODE EARTH PIT Supply, installation & testing of earth electrode with following sizes: 80 mm dia, 3.8 M long heavy duty perforated GI pipe electrode (Galvanisation is 610 gms/sq. mtr or as per IS-4759/ISO 1461.) as per IS:3043providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making RCC/ Brick earth pit chamber and associated civil works with chequered plate cover as per standard Drwng.etc. all complete as per specification & direction of Site-In-charge.Item also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick Aluminium Composite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cm long (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker having details as per Site-in-charge. |
| 467 | Supply & drawing/laying, jointing, connecting, testing and commissioning of Hot Dip Galvanized(Galvanisation is 610 gms/sq. mtr. or as per IS-4759/ISO 1461) earth strip/copper strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following sizes as per direction of Site in-Charge. |
| 468 | 75 x 6 mm GI Strip |
| 469 | 50 x 6 mm GI Strip |
| 470 | 40 x 6 mm GI Strip |
| 471 | 40 x 5 mm GI Strip |
| 472 | 25 x 3 mm GI Strip |
| 473 | 16mm GI Wire Rope |
| 474 | 10mm GI Wire Rope |
| 475 | 8 SWG solid GI Wire |
| 476 | Supply & laying / fixing of PVC insulated AL/Cu conductor Green cable for equipment earthing of following sizes: |
| 477 | 1Cx25 mm2 PVC (Al) cable |
| 478 | Flexible copper cable PVC insulated of 16sqmm for connecting the earth grid/earth strip with the crocodile clip i/c cost of 1 no. crocodile clip - For cable upto 2.5M in length |
| 479 | 1C x6 sq mm green colur copper flexible cable for earthing of fittings |
| 480 | 1C x2.5 sq mm green colur copper flexible cable for earthing of fittings |
| 481 | Designing of earthing System with required quantity of earth pits as per IS 3043 and as mentioned above for plant & non-plant buildings, tanks, sheds, bays, switchyard, etc. For designing the final earthing system, the sucessful bidder is also required to carry out confirmatory tests for soil resistivity including vetting from govt. colleges/ NABL approved lab. The test should be carried out with min 8 nos. of boreholes. |
| 482 | LIGHTNING PROTECTION SYSTEM |
| 483 | Supply & laying / installation of 25 x 3 mm GI strip(Galvanisation is 610 gms/sq. mtr. or as per IS-4759/ISO 1461) as horizontal and down conductor for Lightning protection system to be laid on on wall/ on RCC column/ steel structure/ curb/ roof including jointing by welding, connecting to equipments, painting to welded portion by black bitumen paint. The rates shall be inclusive of hardware required for clamping of earth strip, jointing the strips, test link etc. Cost of insulators for the support of the system as per direction of Site In-Charge is included. As per IEC 62305. |
| 484 | 75 x 6 mm GI Strip |
| 485 | 50 x 6 mm GI Strip |
| 486 | 25 x 3 mm GI Strip |
| 487 | PIPE ELECTRODE EARTH PIT Supply, installation & testing of earth electrode with following sizes: 80 mm dia, 3.8 M long heavy duty perforated GI pipe electrode (Galvanisation is 610 gms/sq. mtr or as per IS-4759/ISO 1461.) as per IS:3043providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making RCC/ Brick earth pit chamber and associated civil works with chequered plate cover as per standard Drwng.etc. all complete as per specification & direction of Site-In-charge.Item also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick Aluminium Composite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cm long (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker having details as per Site-in-charge. |
| 488 | Supply & installation / fixing of Test link (for connection of each down conductor to earth pit)as per attached drawing |
| 489 | Supply & installation of 1000mm long,20 dia. GI air termination rod (lightning rod) with all fixing material, accessories. |
| 490 | Designing of Lightning Protection System as per IEC 62305 and risk analysis for plant & non-plant buildings, tanks, sheds, bays, switchyard, etc. |
| 491 | TESTING AND COMMISSIONING OF MOTORS, MOTOR OPERATED VALVES: Motor / Motor Operated Valves are erected by mechanical contractor at erection site. However, scope of electrical contractorsis dehydration of windings (If required), plugging unused cable gland cut-out in motor terminal box, checking & replenishment / replacement of bearing grease / lubricant, checking of IR values between each winding & motor frame, checking of continuity of motor windings, Control sheme checking inlcuding LCS, checking of direction of rotation, motor shall run in uncoupled condition for 8 hrs. & changing of direction of rotation (If required by changing supply connections), trial runs on NO - LOAD & LOAD test, supply of approved grease / lubricant, installing of canopy, necessary hardware’s, testing & commissioning of following LT MOTORS together with all accessories, all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE. (Contactor to keep proper record of tests on motored for NO - LOAD & ON - LOAD runs.) |
| 492 | Up to 3.7 KW Motor andMotor Operated Valves (i.e. ROSOV, DBBV, MOV , COBV etc.) |
| 493 | 5.5 KW to 22 KW Motor |
| 494 | Above 22 KW to 100 KW Motor |
| 495 | SOLAR SYSTEM(5KWp FOR CONTROL ROOM & 7KWp FOR ADMIN BUILDING) |
| 496 | Design, Supply, Installation and testing and commissioning ofof Roof top Solar system comprising of SPV modules for a total capacity of 12 KWp .SPV module mounting structure suitable for accommodating 12 KWp capacity, SPV modules including foundation on roof of building,PCUs as per specifications, Array Junction Boxes,Main Junction Boxes, DC Distribution board, AC Distribution board, Cables, suitable cable glands & lugs as required at site for full plant commissioning, Lightning arrester complete set, Earthing complete set as per Specification, Battery Bank as per specifications, Spares, tools and tackles for operation and maintenance, Fuses, Transfer Switches, Printed Circuit Boards etc. required for solar lighting system for For Control Room &Admin Building. |
| 497 | COMPOSITE CIVIL & MISC WORKS |
| 498 | Supply & Fixing of B-class G.I. pipe conforming to IS: 1239 for cable protection burried in concrete/ PCC / Brick work or under Earth including cutting to size, threading, bending etc of following sizes |
| 499 | 50 mm dia G.I. Pipe |
| 500 | 75 mm dia G.I. Pipe |
| 501 | 100 mm dia G.I. Pipe |
| 502 | 150 mm dia G.I. Pipe |
| 503 | ANCHOR FASTENERS :Providing & fixing anchor fasteners of approved make like HILTI and any of size on the RCC slab, beam, columns etc. at any height including drilling the holes using drilling machine / tools having carbide tips, scaffolding (If required) for fixing the fasteners and its bolt as per the drawing or as directed by Engineer in charge with all labour, materials, tools and tackles. |
| 504 | Up to 1/4\" BSW x 12 mm dia. |
| 505 | Between 1/4\" BSW x 12 mm to 3/8\" BSW x 25 mm dia. |
| 506 | Supply & laying of Heavy Duty type, High compression strength, IP 67 rated (DWC) Double wall corrugated HDPE Conduits as per IS:14930/ IS:16205. Laying includes with GI pull wires inside the conduits & necessary ends to be filled with sealants, of all complete and as per drawing & specification. |
| 507 | 110 mm |
| 508 | 75 mm |
| 509 | 63 mm |
| 510 | 40 mm |
| 511 | SUPPLY & ERECTION OF MS CHEQUERED PLATE: 6 mm thick chequered plate on cable trench inside swtich room, DG room, earthing pit including cutting, painting, lifting hooks, etc and painting as per Tender specifications. |
| 512 | RCC TRENCH COVER: Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm c/c on both ways , neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming coat , reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge |
| 513 | Supplying & grouting using free flow non shrinkable grout material CONBEXTRA GP-2 or approved euivalentincluding roughening surface, cleaning with compressed air/water jets, ramming, curing etc. complete as per direction of Site in-Charge. |
| 514 | Supplying & Fixing of Electrical insulating mats made of PVC Elastomer 3mm Thick & 1 mtr wide near swichboards, etc as per direction of Engineer In charge. Mat should conform to IS 15652. Class A - suitable for safe workingvoltage of upto 33 kV AC (rms). Test certificate to be provided with supply. Mat\"s top Surface should be Antiskid Dotted & Bottom Surface should be Textured for Floor Grip |
| 515 | Supplying & Fixing of Electrical insulating mats made of PVC Elastomer 2mm Thick & 1 mtr wide near swichboards, etc as per direction of Engineer In charge. Mat should conform to IS 15652. Class A - suitable for safe workingvoltage of upto 3.3 kV AC (rms). Test certificate to be provided with supply. Mat\"s top Surface should be Antiskid Dotted & Bottom Surface should be Textured for Floor Grip |
| 516 | Supply and fixing of shock treatment chart in English, Hindi & local language framed in glass framework. |
| 517 | Charges for preparation of drawings,SLD, Wiring Diagram for the HT Panel, Transformer, PMCC, Panels, Cables, JBs, DBs & Generator,etc., obtaining drawing approval, arranging for inspection, getting safety certificate of complete installation from CEA authorities/Statuary authority for energisation of HT Panel, Transformer, PMCC room & Generator,etc.The contractor shall give 5 sets of approvedas built drawings. Note: a) The statutory payment shall be made by IOCL.b) The job also includes all liasoning to be carried out with State Electricity Board authorities for obtaining necessary approval for successful commissioning of the facilities. |
| 518 | Supply, Fixing & Commissioning of 300 mm dia., heavy duty Flame proof Ex\"d\" exhaust fan complete with motor, cable gland, shutter, louver, bird catcher, mounting bracket, hardware etc. and conforming to IS, heavy dutytype suitable for 240V, single phase AC supply. The fans shall be with louvers / shutters. |
| 519 | Supply, Fixing & Commissioning of 600 mm dia exhaust fan including electrical wiring all shall be with per specification and direction of site In charge. The fans shall be with louvers / shutters. (The job does notinclude making suitable cut out in thewall for fixing the fan). |
| 520 | Supply and fixing of Cable Route markers for HT Cable (11kV grade), CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate. |
| 521 | Supply and fixing of Cable Route markers for LT Cable (415V grade), CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate. |
| 522 | Supply and fixing of Cable Route markers for Control Cable, CI material, 150mm Dia. Round with 5mm-6mm thickness, two holes for mounting, 3mm embossed lettering as appropriate. |
| 523 | Supplying and fixing of 4.5kg CO2 fire extinguisher of approved make Conforming to IS 15683, portable high pressure type. Body seamless Manganese Steel, ISI marked conforming to IS 7285, discharge valve conforming to IS 324,polyethylene flat discharge horn with diffuser,1m wire braded rubber hose, powder coated wall mounting mild steel bracket,stainless steel safety pin of SS 316 grade, CO2 gas with 99.5% purity. Extinguisher shall have anti corrosive treatment of phosphating by hot dipping process to thickness not less than 0.012mm both internally and externally. Epoxy polyester powder coating of minimum 50 micron to all metallic external parts with two bands of yellow colored fluorescent adhesive tape of minimum 20mm thickness of body. Finish of the paint to be PO red as per shade 538 ofIS:5 |
| 524 | Supplying and fixing of 9kg DCP portable,cartridge type Fire extinguisher of approved make,Conforming to IS15683:2006,Body Carbon Steel as per IS:513,EDD grade with no vertical weld joint on the body Neck ring of seamless mild steel tube conforming to IS 1239 part-1, Valve assembly conforming to SS 316 grade or forged brass as per IS 6912 grade FLB, Inlet and outlet siphon tubes of SS 316 grade or of brass as per IS 407, Discharge nozzle of SS 316 grade of forgedbrass as per IS 6912, 500mm long discharge hose of EDPM rubber, powder coated wall mounting mild steel bracket,stainless steel safety Pin of SS 316 grade, Dry Chemical powder ( potassium bi-carbonate & Minimum 90% of the total chemical), ISI marked CO2 Gas cartridge of 200 gms, dia of the body 175mm +/- 10mm & overall height less than 650mm.Extinguisher shall have anticorrosive treatment of phosphating by hot dipping process to thickness not less than 0.012mm both internally & externally. Epoxy polyester powder coating of minimum 50 micron to all metallic external parts with two bands of yellow colored fluorescent adhesive tape of minimum 20mm thickness of body. Finish of the paint to be PO red as per shade 538 ofIS:5 |
| 525 | Supplying & fixing Fire bucket stand- 4 buckets hanging arrangement 1 meter height, made of 50x50x6mm angle frame, painted with 2 coats of primer and 2 coats of Red, synthetic enamel paint. |
| 526 | Supply & fixing of Galvanised Fire buckets of 9 litre capacity, painted white inside and red outside with letters \"fire\" in black, conforming to IS 2546-1974. |
| 527 | Preparation & displaying of Laminated and Aluminum framed as built Single Line Diagram (A1/A0 size) and Electrical Layout as per direction of Site In-Charge. |
| 528 | Preparation & displaying of Laminated and Aluminum framed as built Single Line DiagramandOverall Earthing Layout (A-0/A-1 Size) and Earthing Layout (A-1 /A-3 Size) near each facility as per OISD guidelines & as per direction of Site In-Charge. |
| 529 | Supply & fixing of Enamelled metallicDanger notice plate / caution boardas per IS:2551 and IS-8923 for 6.6 KV. The boards shall be enamelled & written in Hindi/English/ Local Language. |
| 530 | Supply & fixing of Enamelled metallicDanger notice plate / caution boardas per IS:2551 and IS-8923 for 415 V. The boards shall be enamelled & written in Hindi/English/ Local Language. |
| 531 | Supply of First Aid Box |
| 532 | Supply & fixing of Laminated and Aluminium framed posters of “Classes of Fires and Extinguishers”, “Electrical Safety Conditions”, Electrical Safety posters as perNational Safety Council |
| 533 | Supply of 11 KV grade Rubber hand gloves, ISI mark |
| 534 | Supply of 415 V grade Rubber hand gloves, ISI mark |
| 535 | Supply of Artificial Respirator (Above 675V) |
| 536 | Supply ofstandard Transformer sign boards with indicating the a)Transformer rating, b)Voltage ratio, c) Sl.No, d)Last filtration date, BDV value and due date e) Neutral earth resistance and due date. |
| 537 | Supply of 11 kV Discharge Rod |
| 538 | EARTHWORKa) The prices for all excavations are to include for removing and clearing away all shrubs, bushes, roots etc. b) The prices are also to include for all leveling and ramming foundation beds, trimming of sides and bottom grading to proper level as required.c) Removal and carrying shall include for all loading, unloading and handling as may be necessary and also all necessary means of transport (Mechanical or manual as required). d) The prices are also to include removal of water accumulated due to subsoil seepage, rains or from any kind of sources, either by pumping or by bailing or by any suitable method likewell point dewatering etc. if reqd. No extra payment shall be made for dewatering.This also includes for draining out the pumped water to nearby available drainage system.e) Normally payment of earth work shall be made according to the sizes of PCC for trenches/ pits as contemplated in the working drawings. Extra due to widening or deepening of trenches / pits shall not be paid for except for the cases where water / acid proofing would be accepted as per working drawings in such case the mode of measurementshall be as per IS : 1200.f) Nothing extra shall be paid for sorting /screening of excavated materials to obtain good earth for filling.g) Nothing extra shall be paid on account of any liftfor disposal of excavated materials.h) Where excavation are made in excess of the depth required, the contractor shall at his own expense fill up tothe desired level with lean concrete of mix 1:5:10 (1 Cement: 5 Coarse sand: 10 Graded stoneaggregate 40 mm nominal size. |
| 539 | i) Rate shall include Royalty, Taxes, etc., levied by the local authorities, all transportation, loading and unloading, etc., and nothing extra will be paid on this account.j) Soft / loose soil also includes filled up earth / murrum.k) The filling for earth / murrum or sand shall be done in layers not exceeding 20 cm in thickness (consolidated) withSuitable means to achieve 95% dry density at Optimum Moisture Content corresponding to standard Proctor test compaction with vibroroller(8 to 10MT capacity) & vibro compactor in confined spaces.l) For other conditions please refer document. |
| 540 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual meansincluding disposal of excavated earth within and outside site to unobjectionable place, disposed earth to be levelled and neatly dressed including all lead and lifts/depth.All kinds of Soil such as ordinary/hard soil, kankar, murrum, gravel, pebbles, bajri, removal of shrubs, uprooting the tree roots etc. and all types of material encountered in excavation including excavation of saturated soils, mud, sludge etc. |
| 541 | Filling with earth available within premises (excluding rock) under floors in layers not exceeding 20cm in depth, consolidation each deposited layer by ramming and watering for all Lift and Lead as per direction of Site in charge. |
| 542 | Supplying andfillingcoarse sand of Zone IV as per IS Code, in plinth, under floors, under gorund tanks & tank foundations etc. in layers not exceeding 200mm in depth, each deposited layer shall becompacted by mechanical vibration and watering anddressing complete as per technical specifications anddrawings. |
| 543 | HARD-CORE SOLING: Providing and laying dry stone hard soling (with rubble/boulder size of 75 mm & above) of required thickness under floor, ramps, walls, foundation, trenches, etc. & for similar situations at plinth level/ below plinth level including watering, ramming, Bliding, and well consolidating, laying in regular lines , levels, interstices, filled with smaller stones /chips of appropriate size and sand consolidated with copious watering as specified & finished to the required level etc as instructed by site engineer. The soling shall be laid and hand packed true to grade and section and these shall be often checked by borning rods,temple boards,fish line,etc..The grades sections etc.of soling shall correspond to those of the surfacing coming thereon.The soling thus laid shall be finished by knocking out projecting stones and filling depressions by chips to reach up to the grade & camber. (Payment shall be made of finished compacted thickness of hard core) |
| 544 | SHUTTERING & CENTERING: Centering and shuttering including strutting, propping etc. with suitable materials as per Tender conditions & specifications and removal of form for: - |
| 545 | Foundations,footings,bases of columns, etc. for mass concrete RCC |
| 546 | Columns, piers, abutment, pillars,posts & struts |
| 547 | CONCRETE WORK/ REINFORCED CONCRETE WORKa) The prices for concrete in beds and slabs are to include for laying on any type of sub grade, laying to falls, or cambers and for preparing surfaces to receive concrete.b) All concrete surfaces shall be finished to a fair face to give a smooth and even surface. Nothing extra shall bepaid on this account.c) The prices are to include leaving pockets, cut outs and holes and to provide wooden boxes or any other suitable arrangements in RCC for bolt holes in slab, beams, walls, foundation of equipments etc. as per approved working drawing. (Nothing extra shall be paid on this account).d) No deduction in RCC quantity shall be made for pockets and nothing extra shall be paid for providing pockets as mentioned in para \"C\" above.e) Measurement of opening in concrete work/RCC work: For measurement of openings in concrete work / RCC works, shall be as per IS: 1200 Part-III.f) All pocket holes are to be properly covered by suitable means so that dirt, rain water etc. etc., should not enter the pockets/holes etc. (Nothing extra shall be paid on this account.)g) Threads of bolts etc. which have already been fixed in the pockets are to be greased and polythene sheet properly covered with gunny bags to protect it from damages from all sources. (Nothing extra shall be paid on this account.)h) The prices shall include for all rebating, trotting, chamfering weathering, molding etc. to accord withthe details shown on the approved working drawings.i) Nothing extra shall be paid for any intricate concrete work for foundations of equipments and machinery (dynamic/static), RCC wall and other superstructure works or any delay in concreting in small and thin sections in PCC or RCC works. |
| 548 | j) The prices for concrete are to include for hoisting and / or lowering to any height and/or depth required and in any type of form work, packing around reinforcement where required and finishing the surfaces, to fair andeven surface.k) The prices shall include working up or hacking of concrete surface for providing keys for further concrete work and shall also include all plane, rebated or grooved constructional and other joints. l) The design mixes of all controlled concrete of various grades shall be established by the contractor on the basis of weigh batching, at the beginning of work. In all concrete / RCC work graded coarse aggregate shall be used. Any concrete work with honey comb shall be rejected and the work has to be redone by the contractor at his own cost.m) Concrete admixtures for workability if necessary, may be used in RCC if decided by Engineer-in-charge. No extra payment for mixing etc, shall be made on this account. n) Machine and equipment foundations shall mean all foundations including pedestals of vessels, towers, pumps, compressor motors, or any other equipment or machinery (both static and dynamic), pipe supports, etc. and the like.o) The prices are also to include the removal of water caused by rains/seepage etc. either pumping or by bailing out or by special means like well point dewatering etc. that may accumulate in the trenches and foundationpits etc.p) The prices are to include the supply of cement by the contractor. q) Anti shrinkage compound used in grouting shall be paid separately.r) The source of supply for sand and stone chips shall be approved by IOCL. |
| 549 | Following additional points to be noted for Ready Mix Concrete(RMC)a) Ready mix concrete (RMC) of approved vendor at the site of casting including coordinating with Engineer-in-charge, prior to casting, making all arrangement to unload the concrete so as to ensure that RMC is not detained for unloading, placing the concrete at site, vibrating, taking concrete cubes, testing, curing the concrete etc. complete in relevant items.b) Necessary schedule will have to be submitted by agency 3 days in advance so that proper coordination with Engineer-in-charge is done.c) It shall be ensured that shuttering done by contractor shall be adequate to withstand pumping pressure.d) Any loss of material shall be contractor’s responsibility.e) Submission of test results at RMC mixing plant site as well as casting site shall be contractors responsibilityf) Desired design mix shall be got approved from Engineer-in charge before placing order for RMC.g) Any toll taxes applicable to be borne by the contractor.h) Any other taxes as levied by Govt.from time to time shall be deemed to be inclusive in the contract.i) Approved brand of 43 grade cement shall be used for preparing RMC & Cement shall be tested as per relevant IS Codes. Cement supply shall be in contractor’s scope. |
| 550 | PLAIN CEMENT CONCRETE |
| 551 | PLAIN CEMENT CONCRETE: Providing and laying cement concrete in foundation, footings and base for columns/walls including proportioning, mixing in mechanical mixer, laying vibration by means of mechanical vibrators, curing etc. complete including the cost of shuttering:- |
| 552 | Concrete of mix 1:3:6( 1 cement : 4 coarse sand : 8 graded stone aggregate 20 mm nominal size) |
| 553 | Concrete of mix 1:2:4( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 554 | REINFORCEDCEMENT CONCRETE |
| 555 | IN FOUNDATION &PLINTH: Providing and laying in position, machine batched & machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement. Including admixtures in recommended proportions as per IS 9109 to accelerate, retard setting of concrete,improve workability without impairing strength and durability as per direction of Engineer-in-charge -- M-25 grade reinforced cement concrete UP TO PLINTH LEVEL Note :- a. Minimum Cement content considered in this item is @400 kg/cum and accordingly design mix to be done. Less cement used as per design mix (if any) will be recoverable separately. No extra payment against extra cement if used shall be payable.b. Batch mixing plant of capacity to be approved by Site Engineer for the works to be installed by the Contractor at site along with required NOCs from concerned Authorities. Alternatively, Contractor shall also be permitted to use RMC (if available) at no extra cost to IOC & after obtaining prior approval from Engineer In-Charge.c. For small quantities (up to 5 cum per day), mixing & placing of concrete of M25 (1:1:2) using mechanical mixer shall be permitted with the prior approval of IOC.d. Hacking of exposed surface of green concrete (wherever applicable) as Key to plaster shall be done at no extra cost to IOC. |
| 556 | REINFORCEMENT & EMBEDMENTSa) Wastage in cutting will not be paidOnly steel actually fixed in position will be paid by the linear measurement i/c hooks, chairs, dowels and laps. Only authorized hooks and laps approved in bar bending schedule shall be paid. Lapping of bars will be allowed only where the required bar length exceeds the standard lengths available unless otherwise approved. All other laps provided unless otherwise specified in the drawings shall not be measured and paid for. Weight of binding wire shall not be measured for payment.The prices are to include for the supply of all Reinforcement & Embedment at site by the Contractor.b) Reinforcement are to be tack welded in addition to binding by 18 SWG annealed wire wherever necessary to impart fixity. Bars of 28 mm dia & above shall also be provided with stitch weld in additions to binding with annealed iron wire and nothing extra will be paid for stitch welding. Stitch welding shall be done as per IS specifications. No extra claim shall be entertained on this account.c) Supplying,cutting, bending, hoisting, placing in position with proper precast concrete block cover and binding with 18 SWG annealed wire, high yield strength deformed bars as per IS: 1786 for all R.C.C works including all necessary handling at all heights anddepths complete in all respects and as per direction of the Engineer-in-Charge. |
| 557 | Supplying,cutting, bending, hoisting, placing in position with proper precast concrete block cover and binding with 18 SWG annealed wire, high yield strength deformed bars Thermo Mechanically Treated Bars Fe- 500 OR Fe-500 D grade,Conforming to as per IS: 1786 for all R.C.C works including all necessary handling at all heights anddepths complete in all respects and as per direction of the Engineer-in-Charge. |
| 558 | BRICK WORKS & FINISHINGa) The prices are to include for work at any height / depth and for all necessary scaffolding etc. as required.b) The prices shall also include for making to form key for plaster and for all work in narrow width formed angles, chamfered external angles and for making good the faces. c) Plastering shall be measured in sq. meter area of the surface to be plastered, as per IS: 1200 (Part XII). The rate shall include erecting and removal of scaffolding all labour, all materials, equipment, plants, tools and all incidental expenses to complete plastering, pointing, rubbing out joints, cleaning, wetting, filling with cement mortar, troweling etc. and making of drip moulds, grooves, vattas, bands etc. including curing.d)The prices are to include the supply of cement at site by the contractor.e) Sand used for plastering shall be from approved sources. |
| 559 | Providing and laying Brick work with common burnt clay F.P.S (non Modular) bricks of class designation 50 in foundation & plinth |
| 560 | Brick work with Class Designation 50 bricks in Cement mortar 1:4 (1 cement : 4 coarse sand) in Upto Plinth Level |
| 561 | Brick work with Class Designation 50 bricks in Cement mortar 1:4 (1 cement: 4 coarse sand) in superstructure in all shapes & sizes in superstructure ABOVE PLINTH & UP TO FLOOR V LEVEL |
| 562 | Providing and laying cement plaster on surfaces with Fine sand including curing etc. |
| 563 | 12mm cement plaster of mix 1:4 (1 cement: 4 coarse sand) |
| 564 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : Light Duty |
| 565 | 150 mm dia. R.C.C. pipe |
| 566 | 300 mm dia. R.C.C. pipe |
| 567 | 600 mm dia. R.C.C. pipe |
| 568 | STRUCTURAL STEEL |
| 569 | Supplying, transporting, de-rusting, fabricating, erecting, hoisting and fixing in position with necessary welding and/or bolting with MS bolts conforming to property class 4.6 or higher of I.S:1367 at all height as per approved fabrication drawings of all types of structural steel work in rolled steel joints, channels, angles, tees, flats, plates, lattice members built up / compound sections in columns, portals, girders, beams, bracings, trusses, purlins, rafters, staircase, steps, hand-railings pipes, walkway, cat ladder with cages, toe plates, side walling, trestles, Conveyor gantries grating, chequred plate etc. including gusset plates, anchor plates etc., including site and shop fasteners, riveting, bolting, welding at shop or work site at all heights etc. & including applying approved coats of primers, undercoat and finish painting as per Technical specification. Complete as per drawing and direction of Owner / Consultant. (All material supply is in contractor’s scope including paints )Providing and applying Anticorrosive treatment to structural steel surface as per below specifications.a) Surface preparation by shot blasting conforming to SA 2.5 b) Primer coat of INORGANIC ZINC ETHYL SILICATE (DFT 65 – 75 micron)c) Intermediate coat of TWO PACK EPOXY-POLYAMIDE MIO UNDERCOAT (DFT 100 – 125 micron)d) Final coat of TWO PACK ALIPHATIC POLYURETHANE (DFT40-50 micron) Total DFT shall be min 215 micron. Final paint shades shall be as approved by IOCL.Payment will be on the basis of weight of structural steel provided. |
| 570 | Supplying and fixing MS foundation bolts with necessary GI nuts and washers of specified sizes,with suitable anchorage all conforming to relevant Indian Standards and as approved by Engineer-in-charge. The item includes provision of 2 nos. of GI nuts for each bolt. |