Military Engineer Services-MES has published Tender For Repair /Maintenance To Eot/Hot Cranes ,Boom Barrier And Other Connected Work At Tech Area Under Ge (Af) Jamnagar No 1. Submission Date for this Tender is 23-12-2023. Mechanical engineering Service Tenders in jamnagar Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

40899765
Tender For Repair /Maintenance To Eot/Hot Cranes ,Boom Barrier And Other Connected Work At Tech Area Under Ge (Af) Jamnagar No 1
Open Tender
Indian
Gujarat
jamnagar
23-12-2023

Tender Details

Tender For Repair / Maintenance To Eot / Hot Cranes , Boom Barrier And Other Connected Work At Tech Area Under Ge ( Af ) Jamnagar No 1

Key Value

Document Fees
INR 500 /-
EMD
INR 79600.0 /-
Tender Value
INR 39.80 Lakhs /-

BOQ Items

Name of Work: REPAIR/MAINT TO EOT/HOT CRANES, BARRIERS AND OTHER CONNECTED WORK AT TECH AREA UNDER GE(AF) JAMNAGAR NO.1
Sl. No. Item Description
1Deployment of tools / equipment for & including Comprehensive load testing of HOT/EOT gantry crane of capacity 0.3 Ton to 3 Ton (once in a completion period of contract)all as directed .
2Deployment of tools / equipment for & including Comprehensive load testing of HOT/EOT gantry crane of capacity 5 Ton to 10 Ton(once in a completion period of contract)all as directed . Note for item No 1& 2:- (i) Required load for testing of crane will be provided by the contractor under his own arrangement. (ii) Load testing shall be carried out through authorise service provider of OEM/as per specifided and directed by Engineer-in-charge and Contractor shall produce certificate after load testing for the same. (iii) Each EOT/HOT crane shall be measured and paid as one unit.
3Comprehensive maintenance of HOT gantry crane of capacity 1 Ton to 2 Ton, greasing & oiling of components, checking of serviceability of all components complete all as specified and directed .
4Comprehensive maintenance of EOT gantry crane of capacity 0.3 Ton to 3 Ton, greasing & oiling of components, checking of serviceability of all components, complete all as specified and directed .
5Comprehensive maintenance of EOT gantry crane of capacity 5 Ton to 10 Ton, greasing & oiling of components, checking of serviceability of all components, complete all as specified and directed . Note for item No 3 to 5:- (i) Replacement of unserviceableSpare part will be measured & paid separately under respective item of Schedule (ii) Each EOT/HOT crane under respective items shall be measured & paid as one unit.
6Materialand labour for changing of gear oil ofEOT crane of capacity 0.3 to 10 ton after draining out old oil including cleaning of gear box etc complete all as directed .
7S&F in repairs power contactor of capacity 16 Amp 3 pole, 415/110 volt fixed to EOT crane & connecting complete all as directed .
8S&F in repairs power contactor of capacity 32 Amp 3 pole, 415/110 volt fixed to EOT crane & connecting complete all as directed .
9S&F in repair powers contactor of capacity 40 Amp 3 pole, 415 /110 volt fixed to EOT crane & connecting complete all as directed .
10Supply and fix in repairs, single phase preventer for EOT crane & connecting complete all as directed .
11S&F in repair Flame proof PendentofEOT crane with capacity 0.3 ton to 5 ton including (Forward & Reverse, Left & Right, Start & Stop, Up & Down, Emergency Stop) allconnecting functioncomplete all as directed .
12Dismantling & Refixing ofwire rope of EOT/HOT crane fromRope Drum ofcapacity of 0.3 ton to 10 ton connectingcomplete all as directed . (Note - Quoted rate is deemed to include for Checking of wire for its strenghing capacity and serviceability of steel wire rope.)
13S&F in repairs flexible control cable, PVC insulated, PVC sheathed with multistranded, copper conductor, of size 4 sqmm 4 core, suitable for EOT crane & connecting complete all as directed .
14S&F in repairs flexible control cable, PVC insulated, PVC sheathed with multistranded, copper conductor, of size 1.5 sqmm 16 core, suitable for EOT crane & connecting complete all as directed .
15S&F in repairs of brakeliner & lock set suitable for 2 ton to 3 ton capacity HOT crane complete all asdirected .
16S&F in repairs Limit Switches to control the movement of wheels of EOT crane of capacity 0.3 to 3 ton, fixed in position & connecting complete all as specified & directed.
17S&F in repairs Limit Switches to control the movement of wheels of EOT crane of capacity 5to 10 ton, fixed in position & connecting complete all as specified & directed.
18M&L for Repairing of 1 HPcapacity electric motorof EOT crane, AC 3 phase, by dismantling the motor and taking out the old winding wires, cleaning the slots, rewinding the motor with appropriate size of super enamelled copper winding wire, and varnishing complete including replacing the worn out bearing reassembling the motor fixing in same position and testing complete all as specified and directed.
19M&L for Repairing of 2 HP capacity electric motorof EOT crane, AC 3 phase, by dismantling the motor and taking out the old winding wires, cleaning the slots, rewinding the motor with appropriate size of super enamelled copper winding wire, and varnishing complete including replacing the worn out bearing reassembling the motor fixing in same position and testing complete all as specified and directed .
20S & F in replacement voltage surge protection device (SPDs) for low voltage power distribution system 3 phase, 4 wire system 415 V type II (8/20 micro sec) 40 Ka, 3 Phase + neutral, 4 module complete all as directed and directed . Make: Legrand , ABB, L&T, Havells
21Supply and fix in replacement of PCB suitable for EOT crane capacity upto 10 Ton
22Supply and fix in replacement of VFD suitable for EOT crane capacity upto 10 Ton input voltage AC 3PH 380-480V 50/60 Hz 14.0A/10A output -AC3PH 0-480V-0400Hz 11.1A/9.2A Model no CIMRVTGA001BBA (ROHS)
23Supply and fix in repair technical manual MCB Changeover switch, two way centre off, Four pole,40 A, 415 V - 50 Hz, rated impulse voltage 4 KVfixed in existing panel & connecting complete all as specified & directed .
24Supply & fix in repairs of boom of boom barrier any length fabricated with aluminium rectangular section of size 45 mm x 100 mm x wall thickness 1.5 mm, cut to size including powder coating & reflective sheet band complete as directed & as per manufacture instruction.
25Supply & fix in repairs barrier lock for the safety of mother board, motor from dust and better serviceability complete all as specified and directed .
26Supply & fix in repairs wireless Remote control unit with battery for opening & closing of boom of boom barrier complete all as specified and directed .
27Supply andfixin repairs of complete Mother Board, comprising control board of boom barrier, Limit switch interface, radio receiving interface complete all as specified and directed .
28Supply andfixin repairs of Radio receiver for communicate with remote and control board complete all as specified and directed .
29Supply and fix in repairs MCB 63 Amp, Four Pole, breaking capacity 10 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed.
30Supply and fix in repairs MCB 32/40 Amp, Four Pole, breaking capacity 10 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed.
31S&F in repairs LED Traffic signal light, 24W, viewing angle 23°,high intensity, ,polycarbonate body with IP65 protection, fire retardant, glass epoxy,FR4 printed circuit board with protection cover and clear polycarbonate concave lenses, input voltage 210-240V,working temperature -40°C to 80°C in colour indication of Green/Red for giving signal to move or stop for vehicle/person fixed on existing pole all as specified & directed . Make:- Nucleonics / Trafitronics or equivalent approved by GE
32M/L for painting of Voltage stabilizer / Isolation Transformer with two coats synthetic enamelled paint of existing colour after proper cleaning and dusting, de-oiling the surface of capacity upto 400 KVA complete all as specified and directed by Engineer in charge
33Material and labour for provision of earthing complete with copperearth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to Copper strip 32 x6 mm by means of bolts, nuts, check nuts and washer of copper, watering pipe of 20 mm bore galvanised iron medium grade and 40 mm bore galvanised iron light grade for earth strip protectionincluding all excavation, earth work in any type of soil,...
34.... PCC pitin PCC 1:2:4 type B-1 and RCC 1:2:4 type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion including dismantling of old earthing. Note : (i)Earth result after installation completely should be less than 5 Ohm .(ii)Quoted rates shall be deemed to include for earth strip with protection pipe of 7.5 M length.
35M & L for provision for chemical earthing using mixture of Magnesium sulphate (MgSO4) 100kg, common Salt 200 Kg and charcol 300 Kg complete with copper earthing plate 90Cmx60Cmx5mm complete burried on ground vertically below the ground level with top edge of the plate at a depth not less than 2.95 meter below ground level and mixture shuld be filled 15 cm above top edge of earth plate to active result not less than one ohm resistance ,including copper strip 50x6mm size by means of brass bolts,nuts,check nuts and washeres and brazing of copper earth strip protected by galvonised steel pipe 60mm bore light grade connected to main switch board or any othe electrical switch board or any othe electrical equipmentall as shown in electrcal plateno 3 of SSR part Iand including necessory excavation ,......
36...earth work in any type of soil and earth pit should be refill with black cotten /clay soil, 20mm medium grade water GI pipe for watering ,funnel with wire mesh ,PCC (1:2:4)type B1 reinforced with XPM of weight not less than 4 kg/Sqm and MS frame etc all as specified and directed by Engineer in charge including dismantling of old earthing. Note: (i)Earth result after installation completely should be less than 1 Ohm (ii)Quoted rates shall be deemed to include for earth strip with protection pipe of 7.5 M length. (iii) Black soil to be arranged by the conrteractorfor mixing charcol,Crystal salt,Magnesium sulphate & Vegitable oiland also for filling balance portion of pit in layer is deemed to be included in quoted rate (iii) Tools and plants to be required for making depthupto 4 Mtr is to be arranged by the contractor,charges for the same is included in the quoted rate
37Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 75KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including taking down old AMF panel , Controller with battery charger 12/24 V all as specified and directed& Consisting of the followingequipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint
38...over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts including taking down existing unserviceable chamber of any description all as specified and as directed (a) 4 Pole 125 Amp powerContractor,AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB,125 Amps 4 pole 25KA 50 Hz - 02 Nos (c) Panel should beInternally prewired with suitable size of copper conductor PVCinsulated cable with colour coding- 01 job (d)2pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No (e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos
39(g) push button with element-PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j)Digital type DC Voltmeter, 0 to 30 VDC- 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted- 01 No
40(l) Miniature circuit breaker, 1 pole 6 Amps with over load & short circuit protection , short circuit strength 10 kA - 06 Nos (m) Miniature circuit breaker, 1 pole 10 /16 Amps with over load & short circuit protection , short circuit strength 10 KA. - 02 Nos (n)Neutral link rated current 15 A-01 No (o)Auxsupply 12V/24 DC , voltage sensing relay415 VAC.- 02 Nos Note :- (a) Quoted rate includes excavation, earth work and PCC work and connection & testing complete.(b) PCC 1:3:6 platform with angle iron frame for mounting AMF panel 1.2m above ground level, all as directed by Engineer in Charge. (c)AMF Panel should be mounted on platform of PCC (1:3:6) and supported by Angle sections complete all as directed by Engg-in- Charge.
41S&F in repairs 4 Pole, 32 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 03 and cat no.CS97011) or equivalent of make mentioned in Appendix BB of P.S
42S&F in repairs 4 Pole, 63 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 12 and cat no.CS97014) orequivalent of make mentioned in Appendix BB of P.S
43S&F in repairs 4 Pole, 95/100 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 22 and cat no.CS97017) orequivalent of make mentioned in Appendix BB of P.S
44S&F in repairs 4 Pole, 125/130 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 23 and cat no.CS970118) or equivalent of make mentioned in Appendix BB of P.S
45S&F in repairs 4 Pole, 160 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCequivalent of make mentioned in Appendix BB of P.S
46S&F in repairs 4 Pole, 200 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 33 and cat no.CS97021) or equivalent of make mentioned in Appendix BB of P.S
47S&F in repairs 4 Pole, 225/255 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 34 and cat no.CS97022) or equivalent of make mentioned in Appendix BB of P.S
48S&F in repairs 4 Pole, 325 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 41 and cat no.CS97023) or equivalent of make mentioned in Appendix BB of P.S
49S&F in repairs 4 Pole, 400 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 43 and cat no.CS97025) or equivalent of make mentioned in Appendix BB of P.S
50S&F in repairs 4 Pole, 600/630 Amp power contactor,AC 3 rating,415 V andConforms to IS / IEC 60947-4-1 & IEC 60947-4-1fixed in existing panel & connecting complete all as specified & directed Make:- L&T (Type MCX 45 and cat no.CS97027) or equivalent of make siemens/ABB
51S&F in repairs MCCB 400 Amps, 4 pole, breaking capacity 35/36 kA with thermal & Magnetic release range 320 Amps to 400 Amps, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
52S&F in repairs MCCB 250 Amps, 4 pole, breaking capacity 35/36 kA with thermal & Magnetic release range 200 Amps to 250 Amps, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
53S&F in repairs MCCB 160 Amps, 4 pole, breaking capacity 25 kA,with thermal & Magnetic release range 120 Amps to 160 Amps fixed typefixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
54S&F in repairs MCCB 100 Amps, 4 pole, breaking capacity 25 kA,with thermal & Magnetic release range 60 Amps to 100 Amps fixed typefixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.
55Deployment of manpower and cable fault locator machine duly mounted on vehicle for detection of HT UG cable fault of any size & make by applying upto 15 KV supply to locate the fault. Necessary arrangements requiredshould be provided by the contractor. (Note:Payment under this item shall be measured and made only if any fault is detected)
56Taking out HT underground cable from duct from existing / pole etc, aluminium conductor of size95 to 120 sqmm 3 core including cable cover complete all as specified and as directed.
57Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt (Earthed) grade of size 95 Sqmm 3 core laid in duct passing through pipe / duct or fixed on pole and connectingcomplete all as specified and as directed.(Note :-GI pipeshall be measured & paid for separately.)
58Supply, laying, jointing and testing XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip, heavy duty, HT underground cable ISI marked with aluminium multistranded conductor 11000 volt (Earthed) grade of size 120 Sqmm 3 core laid in duct passing through pipe / duct or fixed on pole and connectingcomplete all as specified and as directed.(Note :-GI pipeshall be measured & paid for separately.)
59Supply and fixing in repairs Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
60Supply and fixing in repairs Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 complete all as specified and directed.
61Supply and fixing in repairs Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95sqmm complete all as specified and directed.
62Supply and fixing in repairs Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed.
63Supply and layingGI tubing 100 mm dia bore ,light grade, fixing on pole / wall for cable protection with necessary fittings etc including taking down old tubing complete all as specified and directed.
64Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed.
65Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed.
66Removal of surplus excavated soil to a distance not exceeding50metre and depositing where directed at a level not exceeding1.5metre above the starting point,complete all as specified and directed.
67M&L for providing dry river sand as in sand cushioning to under ground PVCcable including punning down of sand in layer all as specified and directed. (Note: Work shall be executed as per clause 19.75 of standard schedule of rates part-1 (2009) for measurement purpose thickness of sand after punning down will be considered.
68Supplying and laying un-reinforced precast concrete cable cover, classHV, Type 1, flat, size 300mmx l80mm x 40mm complete all as specified and directed by Engineer in charge
69Meterial and labour for attending complaints in EOT/HOT crane, locating faults ,caliberating controller panel and replacement of unserviceable parts , control wiring and componentsin EOT/HOT crane 0.3 Ton to 10 Ton and testing on completion , complete all as specified and directed Note: The quoted rate includes the following: (a)Taking down of unserviceable parts. (b)Any minor repair, replacement of minor parts such as screws, gasket, nuts, bolts, washers, cleaning .(c)Defective parts will be measured & paid separately