Tender For Improvement Of Lux Level Throughout Tank Wagon Siding Perimeter Boundary And Tank Farm Manifold Area Of Lumding Terminal, lumding-Assam

Indian Oil Corporation Limited-IOCL has published Tender For Improvement Of Lux Level Throughout Tank Wagon Siding Perimeter Boundary And Tank Farm Manifold Area Of Lumding Terminal. Submission Date for this Tender is 05-01-2024. Industrial Trucks Tenders in lumding Assam. Bidders can get complete Tender details and download the document.




Tender Notice

40897128
Corrigendum : Tender For Improvement Of Lux Level Throughout Tank Wagon Siding Perimeter Boundary And Tank Farm Manifold Area Of Lumding Terminal
Open Tender
Indian
Assam
lumding
05-01-2024

Tender Details

Improvement Of Lux Level Throughout Tank Wagon Siding Perimeter Boundary And Tank Farm Manifold Area Of Lumding Terminal

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 26-Dec-2023 Extension of Bid Submission Date 05-01-2024

Key Value

Document Fees
Refer document
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work: Improvement of Lux level throughout Tank Wagon Siding, Perimeter, Boundary and Tank farm Manifold area of Lumding Terminal.
Sl. No. Item Description
1Supply, erection, installation & commissioning of 30M High Mast Light Pole having 3 segments of 10.5M length and wall thickness of 4mm for the upper two segments & 5mm for the bottom section along with head frame, winch mounting bracket, luminaries carriage, required no. of ropes to keep the lantern carriage in horizontal position irrespective of loads on it, raising / lowering system comprising of double drum FLP Motorised/Manual winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial, FLP Terminal box for trailing cable connection including supply of anchor bolts with nuts, washers, anchor plate, common template and all accessories required as per specifications all complete. The Door to access the winch, motor & junction box shall be 1200mm X 300mm. The galvanisation shall not be less than 95 microns. Erection of High Mast to be done with the help of suitable tools, Hydra, crane & equipment and plants, for laying of Trailing Cable, wiring of luminaires with all wiring materials like EPR insulated, EPR sheathed flexible cable of suitable copper conductor and all labour, inside the hazardous area required all complete.
2Supply, installation and commissioning of aviation warning lights on High Masts with all accessoriesrequired as per specifications all complete
3Supply, installation and commissioning of FLP 12 Way DB -   FLP Distribution Board with Three Phase incoming 63A TPN MCB and suitable terminals for connecting Aluminium Armoured cable 3.5 c x 50 sq mm and 10A MCB 8 nos outgoing Feeders with all accessories required as per specifications all complete. The Panels should be of PESO/ATEX Approved Makes viz. Baliga, Stahl, FlexproMake or equivalent make
4Supply, installation and commissioning of FLP Feeder Pillar DB -   FLP Distribution Board with Three Phase incoming 63A TPN MCB with suitable terminals for connecting Aluminium Armoured cable 3.5 c x 50 sq mm and Three Nos outgoing of 16A TPN MCB for Pole Lights Lantern supply suitable for 6Sq.mm 5 Core Cable, Astronomical electronic timer for automatic control of light switching, Forward/Reverse DOL Starter with 12A AC3 Duty Contactors for Raising/Lowering, microprocessor-based Over-Load Relay suitable for 3.7kW 3 Phase FLP Motor, suitable terminals for Limit Switch connections of upper limit & lower limit, Indication Lamps for Raise/Lower/Off/Tripp, & Push Buttons for Raise/Lower/Stopwith all accessories required as per specifications all complete. The Panels should be of PESO/ATEX Approved Makes viz. Baliga, Stahl, FlexproMake or equivalent make
5Supply, installation and commissioning of Lighting DB Panel with 400A Microprocessor-based Release as Incomer, with phase indication, LED lamps, On/Off/Trip Indication LED Lamp, Voltmeter with Selector Switch, Ammeter with Selector Switch, Resine cast CTs & Front Drive for MCCB with all accessories required as per specifications all complete. The 20 Nos. 63A TPN MCBs with On/Off LED indications as outgoing feeders in Free Floor Mounted Sheet Steel Enclosure, conforming to IP 52 degree of protection having side cable alley & bottom entry of 16 Nos. 50 Sq.mm Armoured Cables as out Going & One No. 150Sq.mm 3.5 Core Armoured cable as incomer.
6Supply, installation and commissioning of 4 Way FLP JB of PESO/ATEX Approved Makes viz. Baliga, Stahl, FlexproMake or equivalent make with all accessories required as per specifications all complete. TECHNICAL DATA: Construction acc. To: IEC/EN 60079-1,-7,-18, GAS - Explosion protection: II 2 G Ex eb IIC T6 Gb, Dust - Explosion protection: II 2 D Ex tb IIIC T80°C Db, ATEX Certificate: PTB 09 ATEX 1108 IECEx Certificate: IECEx PTB 09.0048, Special Certificate: PESO, temperature: -20° C ... +40° C, Degree of protection: IP66 acc. to IEC/EN 60529, Material: SS316L with 2 mm cover / 1.5 mm enclosure thickness. Finish: Brushed. Gaskets material: Silicone foam, Mounting: Wall, ENCLOSURE Degree of protection IP66, 01 X 8150/1-0236-0176-150-3311, 01 X GI Mounting Plate, 04 X Wall Mounting Brackets, TERMINAL: 10 X 2.5Sq.mm Gray color Spring type Terminal Block- Wago/Phoenix or equivalent make stated in tender, 01 X 2.5Sq.mm Spring type Earth Terminal Block- Wago/Phoenix or equivalent make stated in tender, 01 X M10 Earth stud(Internal & External). 01 X Terminal Rail CABLE ENTRY 04 X Through Hole 3/4"@ Bottom 02 X Ex certified Br-Ni E1FW Cable Gland M20 - CMP (OD: 12.5 to 20.9mm) With all accessories 02 X Ex certified Br-Ni Stopping Plug M20 - CMP.
7Supply, Fixing and Commissioning of Pendent Type LED (Light Emitting Diode) 80 Watts with fittings and accessories, having IP65 protection class with Pressure Die Cast LM6/ADC12/LM24 housing and with toughened glass or UV stabilized polycarbonate cover type of approved make stated in tender or as per direction of Engineer-in-charge. The LED driver shall have an in-built high voltage cutoff >= 290 V with a power factor of complete fitting greater than 0.90. CCT (Correlated Colour temperature) shall be in the range of 5665 K +/- 355 K as per ANSI standard C78.377, CRI (Colour rendering index) should include all colour range from R1 to R15 and > 70 for the outdoor luminaire. LED efficacy shall be greater than 140 lumens/watt @ 350mA drive current. The minimum system lumen efficacy of the luminaire shall be 100 Lumens per Watt. The Surge Protection Device (SPD) should be the series type with fail-safe, surge protection for a minimum 3kV shall be provided. Supply of complete fitting with all accessories required as per specification. Each lot of fittings shall accompany test certificates LM79/ IS:16106 and reference/ batch nos of LEDs and fittings for verification at site. The supply of LED lighting shall be covered by a warranty of minimum 60 months from the date of supply of the lighting and the LED light fitting shall be complete in all respects including LED, LED Driver, Electronic circuitory, Luminaire etc.
8Supply, installation and Commissioning of non-integral LED flood light luminaire with 350W watt LED Radiators. Supply will include non-integral flood light luminaire with pressure die-cast aluminium housing and heat resistant toughened flat glass, Ingress protection IP66, Mech. impact protection code IK08, Surge Protection level until 4 kV to be supplied with Manufacturer"s Test Certificate with all accessories required as per specifications all complete
9Supply, installation & commissioning of non-integral LED Street light luminaire with 150W watt LED Radiators. Supply will include non-integral street light luminaire with pressure die-cast aluminium housing and heat resistant toughened flat glass, Ingress protection IP66, Mech. impact protection code IK08, Surge Protection level until 10 kV to be supplied with Manufacturer"s Test Certificate with all accessories required as per specifications all complete
10Supply, Installation & commissioning of Siemens make type No.3VA2340-5HL42-0AA0 & front drive type No. 3VA9467-0FK51400A microprocessor-based release MCCB, Phase & ON/OFF/TRIPLED indication Lamps in an existing compartment of PMCC in the ESD Bus section of the Panel with necessary cutouts on the front cover of the compartment, disconnecting & removal of any component in the compartment of the selected compartment with all accessories required as per specifications all complete
11ii) S/E of 9 Meter high galvanised Octagonal pole with top 90mm(A/F),bottom 158mm (A/F), made up of 3mm thick plate having a baseplate of size 285 x 285 x 16 with double arm 1500mm long bracket arm made up of 48 O.D. pipe with EN grade galvanised foundation bolts & anchor plate on suitable concrete foundation as per standard drawings enclosed herein (Civil & Electrical works shall be paid separately) having fixing arrangement for mounting 2 Nos. Of 250W Metal halide luminaries (on opposite sides)
12Supplying & drawing inside the poles 3 core 2.5 sq.mm PVC insulated flexible copper conductor, fixing of junction box at the pole base (excluding supply of JB), making all connections on both ends, all complete as per specification and direction of Engineer In-charge.
13i) "Y" Pole
14Supply & fixing of weatherproof125 mm dia junction box (4 way entry) of BALIGA/CEAG-FCG/FLEXPRO/FEPL makeincluding clamping arrangement, all complete as per specification & direction of Engineer In-charge.
15Supply & laying of XLPE insulated PVC sheathed aluminium/copper conductor, 1.1 kV grade armoured cable conforming to IS:7098, as per approved make in ground/ trench/surface/pipe, etc. whereever required as per direction of Engineer In-charge. Note: The rate of Installation should be inclusive of Cable clamps, tags Saddles, Consumables etc. Trays/pipes, trenches, fabricated tray supports etc will be covered & paid in Separate Items. Cable will be supplied with Manufacturer"s Test Certificate and Third Party Inspection Certificate. After Installation of Cable the Insulation test certificate must be submitted after carrying out the same at site with Insulation Meggar.
16iv) 3 Core x 2.5 sq. mm Copper Cable FRLS
17v) 4 Core x 2.5 sq. mm Copper Cable FRLS
184core 4Sq.mm Copper Armoured XLPE
194core 10Sq.mm Copper Armoured XLPE
20xiv) 4 Core x 16 sq. mm Aluminium Cable FRLS
21xvii) 3.5 Core x 35 sq. mm Aluminium Cable FRLS
22xviii) 3.5 Core x 50 sq. mm Aluminium Cable FRLS
23xxii) 3.5 Core x 150 sq. mm Aluminium Cable FRLS
24ii) Providing earthing with 80 mm dia,3.0 M long GI (Heavy duty) perforated pipe as per IS:3043 (with latest ammendment) including providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making earth pit chamber with chequered plate cover as per standard Drwng.etc. all complete as per specification & direction of Engineer-In-charge
25Supply & drawing/laying, jointing, connecting, testing and commissioning of GI earth strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following including supply of Lightning arrestor spike and laying of Strip through bakelite for lightning arrestor:
26iii) 50 x 6 mm G.I. Strip
27ii) 32 x 6 mm G.I.strip
28Supplying, fabricating and installing the following sizes of perforated GI cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required of size 200mmX50mmX2mm and duly suspended from the ceiling and/or fix to steel/RCC columns, beams or any other structure members with MS suspenders, angles, channels, etc complete as per the direction of IndianOil
29FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination(FLP):Providing termination of 1.1 kV grade armoured cable for the following sizes including supply of FLP heavy duty double compression cable glands, Baliga/CEAG-FCG /Flexpro/ FEPL make, crimping lugs and allied jointing materials, etc. all complete as per specification & direction of Engineer In-charge. Copper lugs for copper cables and aluminium lugs for aluminium cables shall be used.
30xiv) 4 Core x 16 sq. mm
31xvii) 3.5 Core x 35 sq. mm
32xviii) 3.5 Core x 50 sq. mm
33vii) 3 Core x 2.5 sq. mm
34xi) 4 Core x 2.5 sq. mm
35CABLE TERMINATION GLANDS NON-FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination (NON FLP): Providing termination of 1.1 kV grade armoured cable for the following sizes including supply of NON FLP heavy duty Double Compressoncable glands, crimping type lugs and allied jointing materials, etc. all complete as per specificationand direction of Engineer In-charge. Glands and lugs shall be of approved make. Copper lugs for copper cables and aluminium lugs for aluminium cables shall be used.
36xxii) 3.5 Core x 150 sq. mm
37xviii) 3.5 Core x 50 sq. mm
38xvii) 3.5 Core x 35 sq. mm
39vii) 3 Core x 2.5 sq. mm
40xxiii) 6 Core x 2.5 sq.mm
41Providing and laying inposition specified grade ofreinforced cement concreteexcludingthecostofcentering,shuttering, finishing and reinforcement - All work up to plinth level
42ii) RCC 1 Cement :1½ Coarse Sand: 3 Graded Stone Aggregate 20mm
43Supply of Steel reinforcement for R.C.C. including straightening, cutting, bending, placing in position and binding all complete at all levels
44ii) Thermo Mechanically Treated Bars of Fe- 500D grade or more, conforming to IS1786
45CenteringCenteringand shutteringincludingstrutting,proppingetc. and removal of form work for Foundations,footings,bases of column
46Excavating trenches of required width for pipes, cables etc including excavation for sockets & dressing of sides, ramming of bottoms,depth upto 1.5m including taking out excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing surplus excavated soil as directed, within or outside site at unobjectionable place in all kinds of soil
47i) Pipes,cables etc. not exceeding 80mm dia
48ii) For extra depth of >1.5m < 3mfor dia upto 80mm
49iii) For extra depth of >3m< 4.5mfor dia upto 80mm
50Providingand laying class-B 50mm dia GI pipe for cable routing under flooring/ EB post leading including sealing both ends with jute and Bitumen
51Supplying and installing of GI cable route marker with 100mm x 100mm x5mm thick GI Plate with inscription thereon, bolted/welded to 35mm x 35mm x 6mm angle iron, 600mm long and fixing the same in ground as per drawing & direction of IndianOil Job includes painting with one coat of redoxide & finishing paint
52Structural steel work riveted,bolted or welded in built up sections, trusses & framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete:
53Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in widthas well as 10 sqm on plan) including taking out and disposal of excavated earth within or outside site to unobjectionable place and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. Extra for levelling & neatly dressing of disposed soil completely to be paid separately as per item no. MPLCN00600
54i) All kinds of Soil
55Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level:
56viii) 1:4:8(1 Cement :4 Coarse Sand :8 Graded stone aggregate of 40mm)
57Dismantling Steel work in built up sections in angles, tees, flats channels etc. including all gusset plates, bolts nuts, cutting rivets welding etc. including dismembering and stacking within premises
58Supplying and filling in plinth with sand within specified grading zone of fine aggregates specified in table 3.1, clause 3.1.3 of attached specifications under floors, etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming including watering, consolidating and dressing complete.
59i) Local Fine Sand within grading zone IV
60Construction of Temporary firescreen wall wherever required to be provided for carrying out hotworks inside closed zone at any height (max. height 17m; dia 42m)including supply of all necessary materials. The fire screen wall shall be erected around the work place
61"FIRE SCREEN WALL ( For First Time use): Construction of Temporary firescreen wall wherever required to be provided for carrying out hotworks inside closed zone at any height (max. height 17m ; dia 42m)including supply of all necessary materials. The fire screen wall shallbe erected around the work place. New GI corrugated sheet minimum 24Gauge shall be fixed with suitable structural with required type &quantity of hooks/fasteners etc to the supporting structure.Supprting structure should be capable ofwith standing wind pressure as perrelevent IS code and able to maintain safety and security of Terminal as well worker. The contractor shall be fully responsible for safety of the substructure and super structure of the fire screen wall and firescreen wall to be dismantalled and foundations, removal of materials,rubbish etc. from the site to an objectionable place immediately aftercompletion of works etc all complete as per terms, conditions,specification and direction of engineer. The job includes the dismantalling of the fire screen wall, structures etc. and cleaning theworking place as per the direction of site-in-charge. After dismantllingthe dismantalled materials would be the Contractor"s property."
62"FIRE SCREEN WALL (Using materials 2nd time & Onward): Dismantling of earlier constructed Fire Screen Wall, handling,shifting and re-fixingto a new location / position. Contractor shall provide require supporting structures along with hooks/ fasteners etc. to construct safe and secured Fire Screen Wall suitablefor doing hot work safely"
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail