Tender For Provision Of One 40 Kva Apfc Panel At Rameswaram And Provision Of Qty 05 Chemical Earthing Pit At Kanyakumari Under Ge Af Trivandrum, trivandrum-Kerala

Military Engineer Services-MES has published Tender For Provision Of One 40 Kva Apfc Panel At Rameswaram And Provision Of Qty 05 Chemical Earthing Pit At Kanyakumari Under Ge Af Trivandrum. Submission Date for this Tender is 03-01-2024. Power Factor Panel Tenders in trivandrum Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

40882884
Corrigendum : Tender For Provision Of One 40 Kva Apfc Panel At Rameswaram And Provision Of Qty 05 Chemical Earthing Pit At Kanyakumari Under Ge Af Trivandrum
Open Tender
Indian
Kerala
trivandrum
03-01-2024

Tender Details

Provision Of One 40 Kva Apfc Panel At Rameswaram And Provision Of Qty 05 Chemical Earthing Pit At Kanyakumari Under Ge Af Trivandrum

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 29-12-2023
2 29-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 03-01-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 7100.0 /-
Tender Value
INR 3.55 Lakhs /-

BOQ Items

Name of Work:
Sl. No. Item Description
1Supply installing, testing and commissioning of Automatic Power Factor Correction (APFC) panel indoor type CPRI type tested factory made of 40 KVAR capacity ready to use design confirming to IS 5039/ IS 8623 and relevantIS/ IEC Codes rated for short circuit rating of 50 KA, front openable and lockable by keys having louvers and air vent, gasket and totally vermin proof and suitable for 415/440 V, 3 phase 50 Hz, AC and housed in elegant enclosure fabricated from minimum 2.00 mm thick CRCA sheet and min 1.6 mm thick for partitions anti corrosive coating to improve power factor to 0.99 and finally powder coated in texture siemens grey RAL 7032 both internally and externally & as directed by Engineer-in-Charge comprising the followings:-
2200 Amp capacity for phase and 100 amps for neutral,Copper bus bar duly insulated with colour coaded heat shrinkable sleeves and mounted on suitable DMC/epoxy insulators. (b) A set of heavy duty, capacitor, type MPPH, 440 volts, box type,with output 40 KVAR capacity, capacitor bank in 6 steps of 40 (5+5+5+5+10+10) KVAR in any configuration to accommodate all possible set ups. (c)MCB"s TP, "C" series, 415 volts, of required sizes with required numbers and suitable ratings as per the capacity of capacitors .
3Micro processor based control suitable for power factor correction relay with its unique features of fire retardent operation automatic C/K ratio selection.The APFC controller should ON/OFF the capacitor banksof 40 KVAR capacity capacitor bank in 6 steps of 40 (5+5+5+5+10+10) KVAR in any configuration to accommodate all possible set ups with indication whether it is lagging or leading. (e) Thyristor switches shall be provided for connecting /disconnecting the capacitor banks to the bus bar. (f) The APFC panel provided with two terminal and it is connected through GI strip 32 x 6mm size to existing transformer earthing/panel earthing all as specified and directed.
4Auxiliary contactor with required quantity of "NO & NC" (l) Auto/ Manual switch-01 No. (m) MCB for line protection as per requirement and as approved (n)Indicator lamp LED based with lamp holder 2 Nos for each capacitor for ON/OFF position (p)Current transformer (CT) of ratio 100/5 amps , measuring class accuracy 0.5 to 1.0 for capacitor panel. (q) Incoming MCCBcapacity 100 amp , 4 pole, 415V, 50 Hz 16 KA fixed manual type - 1 No. (r) Detuning reactor of suitable size shall be provided to maintain THD less than 7 percent. (s) ON/OFF push buton for each capacitors.
5Earthing complete by using GI earth plate electrode 60cm × 60cm × 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below groundlevel) with top edge of the plate not less"than 1.5 metres below normal ground level, connected to using GI earth strip of size 32mmx6mm by means of bolts, nuts, check nuts and washers etc made of galvanised iron and protected by galvanised iron light grade 40 mm bore & 20mm dia galvanised medium grade for watering and including funnel, wire mesh,including CI pit cover with frame over PCC chamber with PCC 1:3:6 type C2 including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 m, charcoal, lugs, common salt complete all as specified and as shown on plate No.3 of SSR Part-I .
6Supply laying testing of XLPE insulated screenedPVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 V grade with stranded aluminium conductor confirming to IS 7098/1985 ISI marked including necessary glands, lugs etc of sizes 3.5 x 25 sqmm alas specified.
7Supply of "Earthing sets" comprising of 17.2 mm dia 3 mtr long Earth electrode of low carbon steel electrode with 250 micron copper bonding & 1 bag of Eco-safe Based environment friendly backfill and suitable clamp, Back-fill earthing enhancing compound should strictly be a Eco Safe Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 15.5 D of IEEE : 80 standard.Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction, size of bore not less than 80mm dia, 12 feet deep, complete all as specified and directed. Back-fill compound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground.Back-fill compound shall not be mixed with any soil while pouring in the bore hole. Test Certificate as per as per IEC : 62561-7 for Back-fill compound shall be submitted along with the material including PVC earth pit cover.
8Supply & fix test link with FRB junction box in order to disconnect the earth termination system for enabling measurements and to connect Round Conductor to Flat to meet the requirement ofIS/IEC - 62305 complete all as specified and as directed.
9Supply and fixing of of 25 X 3 mm Copper strip in ground/ walls & roof with saddles all as specified.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail