Name of Work:Replacement of outdoor typeCTPT unit& TOD meter atTE KUTTIPURAM ( MLP BA)
Sl. No.
Item Description
1
SITC of out door type oil cooled copper wound CT PT unit complete with oil and other accessories suitable for 11 KV systemON BUY BACK SCHEME including testing the CT PT unit at TMR unit of KSEB by making payment of testing fee, liaisoning with KSEB, submitting reports etc. dismantling the existing CT/PT unit from the pole structure, without making any damages to the installations etc. complete as required (Any KSEB approved make) (Note: All liaisoning works with KSEB authorities, Necessary Fee for testing CT PT etc. shall be arranged by the firm)
2
a] 3 Nos single phase CTs of ratio 5/5 A, having burden confirming to the latest KSEB norms with, with accuracy class 0.2S, suitable for system voltage of 11000 Volts
3
b] 1 No 11000 / 110 Volts 3 Phase 3 limb potential transformer having burden confirming to the latest KSEB norms, accuracy class 0.2, with HT & LT fuses, HT bushing suitable for over Head connections etc as reqd.
4
Complete as above
5
SITC of KSEBL approved & ISI Marked TOD Meter of 3 phase, 4 wire, HT CT/PT operated, Uni- directional, accuracy class 0.2S for both Active and Reactive energy, -/5A, HT static tri vector meter with TOD register, DLMS compliant & AMR compatible with optical port and RS 232 port, suitable for measurement of active kWh, reactive energy kVARh and apparent energy kVAh and kVA MD, kW MD atnominal frequency in the range of 47.5 Hz to 52.5 Hz in balanced as well as unbalanced load conditions, including testing the meter at the Meter testing division of KSEB after paying required testing fee and submission of test report etc as reqd (Note :The fee for testing the CTPT unit and TOD meter at TMR and necessary Liaisoning with the KSEB is included in the above scope of work and nothing extra shall be paid on this account.)
6
Supply and laying of 10 C x 2.5 sq mm Cu. Conductor armoured UG Cable from CT/PT Unit to TOD Meter cubicle including Glanding, Termination and connections, supporting the cable etc as required. (Polycab orSS BSNL approved make)
7
Replacing the test terminal block in the TOD meter box i/c dismantling the old one, fixing the new one etc complete as required