Tender For 85868 Provision Of 140 Kva Generator Set And 62.5 Kva Sound Proof Silent Dg Set With Amf Panel At Mintsd Under Under Ge (South) Pune, pune-Maharashtra

Military Engineer Services-MES has published Tender For 85868 Provision Of 140 Kva Generator Set And 62.5 Kva Sound Proof Silent Dg Set With Amf Panel At Mintsd Under Under Ge (South) Pune. Submission Date for this Tender is 11-12-2023. Diesel Generators Tenders in pune Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

40731620
Corrigendum : Tender For 85868 Provision Of 140 Kva Generator Set And 62.5 Kva Sound Proof Silent Dg Set With Amf Panel At Mintsd Under Under Ge (South) Pune
Open Tender
Indian
Maharashtra
pune
11-12-2023

Tender Details

85868 Provision Of 140 Kva Generator Set And 62.5 Kva Sound Proof Silent Dg Set With Amf Panel At Mintsd Under Under Ge ( South ) Pune

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Nov-2023 85868 Corrigendum No. 1 BOQ BOQ 04-12-2023
2 04-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-12-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 61200.0 /-
Tender Value
INR 30.60 Lakhs /-

BOQ Items

Name of Work : PROVISION OF 140 KVA GENERATOR SET AND 62.5 KVA SOUND PROOF SILENT DG SET WITH AMF PANEL AT MINTSD UNDER UNDER GE (SOUTH) PUNE
Sl. No. Item Description
1Supply, install, testing and commissioning of Silent Diesel Engine Generaing Set, 112 KW/140 KVA, 1500 RPM, 3 phase, 415V, 50 c/s, power supply alternator along with fuel tank,control panel,battery and complete set installed in sound accoustic enclosure and standard accessories and fittings, with power factor 0.8, PCC foundation suitable for the generator set as per manufacturer"s instructions, (Items requied for PCC foundation of DG Set shall be measured and paid seperately) tools and spares complete all as specified and directed and comprising of the following:-
2Item No. 1.00 Contd.... (a) Engine : Diesel engine, 6 cylinder engine developing required 184 BHP @ 1500 RPM for prime rating of suitablefor140 KVA alternatorwith provision of 10% over load for one hour in every 12 hour running confirming to BS 5514/ISO 3046 and revised editions as applicable standard Totally enclosed, electric star, compression ignition, 4 stroke. The engineshall consists of following specification:-
3Item No. 1.00 Contd.... (i) Fly wheel to suit flexible coupling with starter ring, cooling radiator with blower fan,fuel hoses,mico fuel pump with mechanical governor,oil bath type air cleaner,exhaust silencer, SS expansion bellow, lubricating oil filter,fuel oil filter, 24 V electric starting system, battery charging alternator,engine control panel consisting of ON/OFF START key, lub oil pressure guage, water temp guage,ammeter battery chargingsafely devices such as:low lubricating oil pressure, light water temperature ect as per latest standards.
4Item No. 1.00 Contd.... (ii)   Instrument panel consisting of: Starting switch with key lubricating oil,temperature guage, lubricating oil pressure gauge, water temperature guage, battery charging indicatinglamp, hour meter with RPM indicator, safety control against high temperature of water,over speed stop with double driver adapter.
5Item No. 1.00 Contd.... (iii) Alternator: Self excited self regulated,floor mounted with all and / or roller bearings, statically and dynamically balanced screen protected SPDP enclosures confirming to IS 4722 / BS 2613, single shaft extensive type with damper with damper winding on pole ‘H’ class insulation automatic voltage regulated from no load to full load,ammeter capacity of delivery 112KW/140 KVA,415 volts,3 phase,50cycles andlagging for AC supply and will be suitable for tropical conditions.
6Item No. 1.00 Contd.... (b) OTHER FITTINGS : (i) Battery Charger : Battery charger having electric circuit consisting of rectifiers, capacitors and resistance etc. The battery charger should be able to charge 12 volts 65 AH battery 2 Nos at a time (ii) Fuel tank of suitable capacity as per manufacturer recommendation mounted on steel frame at suitable height with all connecting pipes and fittings upto fuel pump and over flow pipe from engine to tank including level indicating gauge duly marked and drain valve and air vent plug etc. (iii) Sealed Maintenance Free (SMF) batteries 12 Volt, 65 AH = 02 Nos with adequate current capacity copper lead & battery terminals all as specified & directed. (iv) First fill of lubricating oil shall be provided as per manufactuers recommendation without extra cost. Maintenance Spares : (i) Lub Oil filter elements - 05 Nos (ii) Fuel filter element - 05 Nos (iii)Vee Belt set- 02 Sets (iv)Air cleaner element - 01 Set(v) Flexible coupling for Gen set - 01 No
7Item No. 1.00 Contd.... (c)DG set shall be supplied along with acoustic original enclosure of the manufacturer’s suitable for 140 KVA DG Set as per latest CPCB Norms revised from time to time by Govt of India. (d) The DIESEL OIL, LUBE OIL etc. for smooth functioning of DG SET during PH-I& PH-II complete testing and full tank filling of DIESEL OIL after PH-I & PH-II testing, topping of LUB OIL etc. required for commissioning and testing of DG set will be arranged by the contractor. (e)Excavation,earthwork and provn of PCC plinth of suitable sizes for installation of DG set & connected accessories complete as per manufacturers recommendation will be measured and paid seperately. (f) Standby fuel tankof capacity 500 Litre made out of MS Sheet 2mm thickmounted on angle iron stand duly painted with one coat of red oxide primer and two two coats of synthetic enamel paint all as specified and directed. (g) Supply and installcubical outdoor type, weather type, weather proof IP-65, AMF Control panel fabricated out of 3.0 mm thick CRCA MS sheet for outer panel and 1.6 mm MS sheet for internal compartments,powder coated incorporating the following items including control wiring etc complete all as specified and as directed.
8Item No. 1.00 Contd.... (Note: (a) Suitable PCC plinth for mounting the AMF panel not less than 500 mm height from the ground with adequate space not less than 600 mm in front of the panelfor smooth operation shall be provided by the contractor for fixing the panel (Rates quoted are deemed to be included for this item i.e. PCC / Plinth) (b) Adequate space shall be provided for cable entry and exit and Necessary PCC plinth for mounting the DG set as per manufacture design. (c) The panel drawing to be approved by accepting officer before to place order. (d)Excavation, earth work, PCC, brickwork, plaster etc. required for machine foundation of DG set as per manufacturers instruction shall be measured and paid seperately under relevant items)
9Item No. 1.00 Contd.... AMF D.G. Control Panel (140 KVA) (a)Power Contactor - 04 Pole, 250 Amp, AC-1 Duty, Coil voltage, 240 V AC, 2NO+2NC AUX Contacts = 02 Nos. (b)HRC Fuse Fittings with 250Amp HRC Fuses/ Links = 06 Nos. ©Electronic KWH Meter, 5A-60A, 3x240V AC, 3 Phase 4 wire 50 Hz = 01 No. (96 x 96 mm flush mounting) (d)Current Transformer, CTR-300/5A, ACC-CL-1, 5A = 03 Nos (e)Current Transformer, CTR-150/5A, ACC-CL-5P10, 5VA = 01 No. (f)Electronic Earth Fault Relay, 5 A, 240V AC, 2 C/O Contacts, Surface Mounting with Test & Reset PB = 01 No. (g)Microprocessor Based (AMF Unit) 415 V AC, 3 Phase, 4 Wire, 50 Hz, Sensing for mains & DG (ALT.) Current Input 5 A, Protection U/V, O/V, O/F, for mains and DG (OC for DG only) Battery Voltage Low & Operating Voltage 8-32 V DC, DG Metering (A+V+Hz+PF+KWH) = 01 No. (h)Electronic Hooter 24 V DC, 96 x 96 Flush Mounting = 01 No. (j) Aux relay 24 V DC with LED, Free Wheeling Diode, 3/4 change over contacts at 10 A rating DIN Rail mounting and plugin base module type = 02 Nos. (k)Aux relay 24 V DC with LED, Free Wheeling Diode, 4 change over contacts at 5 A rating DIN Rail mounting and plugin base module type = 04 Nos.
10Item No. 1.00 Contd.... AMF D.G. Control Panel (140 KVA) (l)Aux relay 24 V DC with LED, Free Wheeling Diode, 2 change over contacts at 5 A rating DIN Rail mounting and plugin base module type = 03 Nos. (m)AUX contactor, 240 V AC with suitable NO + NC Contacts = 01 No. (n)LED Indicating lamp 240 V AC = 02 Nos. (o)LED Indicating lamp 24 V DC = 02 Nos. (p)Push Button with elements = 07 Nos. (q)Stayput type Push Button with elements = 01 No. (mounted on accoustic enclosure) (r)Control switch 2 Pole, 10 A, ON / OFF (DC supply) = 01 No. (s)Selector Switch 6 Pole, 2 way, 10 A, without Off (Auto / Manual ) = 01 No. (t)MCB SP, 10 Amp, 6/10 KA (C Curve) = 02 Nos. (u)MCB SP, 6 Amp, 6/10 KA (C Curve) = 01 No. (v)Glass Fuse Fitting 2A, Glass Fuse Links Drawout Type = 10 Nos. (w)Glass Fuse Fitting 2A, Glass Fuse Links Drawout Type (To be fitted in the panel) = 02 Nos. (x)Neutral Link 10 A, (Disconnectable type) = 06 Nos.
11M & L for Earthing complete with galvanised "steel earth plate electrode "60 cm × 60 cm.× 6mm thick, buried "directly in ground (earth pit not less "than 2.25 metres deep below normalground "level) with top edge of the plate not "less"than 1.5 metres below normal "ground level, connected to "galvanisediron strip 32 x 6 mm by means of bolts, nuts, check "nuts and washers of galvanised iron "or steel earth strip protected by provision of GI medium grade pipe 50 mm dia including provision of concrete pit in PCC (1:2:4) type B1 using 20mm graded stone aggregate with 40mm thick RCC cover in CC 1:2:4 type B1 reinforced with XPM (weight not less than 4 kg/sqm) and frame made outin MS angle iron of size25x25x3mm with lugs02 Nos and withMShandle made in 6mm dia round bar made to shape, including GI medium grade 20mm bore pipe for watering, perforated at bottom 1.75m long placed on top edge of earth plate including provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate, test point made out of
12Item No. 2.00 Contd.... phosphorus bronze with fixing arrangement ,funnel, wire mesh and earth work in hard/dense soil returning filling in and removal of surplus soil to a distance not exceeding 50mtr all as shown in electrical plate No. 3 of SSR Part I 2009connected to earthing test "point all as specified or indicated "including testing on completion. (NOTE :- GI strip and GI pipe 50mm bore medium grade for encasing GI strip beyond 7.50m lengthper earthing if so required at site shall be measured and paid separately under relevant items.)
13Supply and lay cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 V grade with stranded aluminium conductor of size 240 sqmm 3 ½ core complete all as specified and as directed.
14Supply and lay cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 V grade with stranded aluminium conductor of size 120 sqmm 3 ½ core complete all as specified and as directed.
15Excavating in trenches n exc 1.5m wide & n exc 1.5m in depth; for foundation, etc. or for manholes etc n.exc. 10 Sqm on plan and n.exc.1.5m in depth and getting out in soft/ loose soil complete all as specified and directed
16Returning filling in, including spreading, levelling, watering and well ramming in layers n.exc. 25cm in soil complete all as specified and as directed
17Removing of excavated soil to a distance not exc. 50m anddeposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
18Supply, installation, commission and testingof outdoor typeFeeder pillar box Outdoor type, compartmentalised made out of CRCA sheet 3.15 mm thick (width of panel shall not be less than 60 cm in any respect ) with powder coated painting and four Nos 400 amps Aluminium strip/bars (not less than 65 mmx10 mm duly insulated mounted on insulators /suitable size backelite sheet ) mounted on angle iron frame of made out of 40mmx6mm angle iron and comprising the following :-
19Item No. 8.00 Contd.... (a)MCCB4pole 315 Amp,415 volt ,16 KA,with thermal magnetic protection(overload &short circuit protection)-1No .(main incoming) (b) ditto butoutgoing MCCB ,4 pole, 100A, 16KA 415 V Ics = 100 % Icu =04 no ( c)-do- butoutgoing MCCB 4 pole, 63A,16KA,Ics = 100 % =04 Nos (d)-do- butoutgoing MCCB 4 pole, 100 A, 16 KA, lcu =100% lcuwith thermal release range =01 N0 ( standby) (e)Digital Voltmeter range 0 to 500 voltsize 96 x96 sq mm with selector switch-1No (f) Digital Ammeter range 0 to 100 Amp size 96 x96 sq mm =01 with selector switch and CT"S- 03Nos (g)LED phase indicating lamps(red, yellow, Blue)=01 SET (Set of 3) (h) On Load change over switch 320A, 4Pole, 415V interconnected to two main supply and DG supply all as specified and directed (Note : - The LT panel should be designed so as to accommodate 10% extra spacefor future expansion)
20M&L for laying ofReinforced concrete pipes, class NP2 with one collar per lengh of pipe of dia 100 mm ,2 nos half round ( for bottom and top )and before laying exacaved area shall be leveling all as specified and directed Engr-in-charge.
21M&L forgalvanised tubing 100 mm light grade with all fittings laid in trenches all as directed by engineer in charge.
22M&L for Brickwork with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in cement mortor 1:6 complete all as specified and as directed by Engr-in-Charge.
23M&L for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 complete all as specified and as directed by Engr-in-Charge.
24M&L for hardcore of gauge exc 63 mm but n.exc 100 mm deposited, spread and leveled in layers n.exc 15 cm thick, watered and rolled/rammed to a true surfaces in broken stone or boulder complete all as specified and as directed by Engr-in-Charge.
25M&L for 100 mm thick PCC 1:4:8 type D-2 using 40 mm graded stone agg as in sub base complete all as specified and as directed by Engr-in-Charge.
26M&L for 100 mm thick PCC 1:3:6 type C-2 using 40 mm graded stone agg as in sub base complete all as specified and as directed by Engr-in-Charge.
27M&L for 100 mm thick PCC 1:2:4 type B-1 using 20 mm graded stone agg as in floor finished even and smooth complete all as specified and as directed by Engr-in-Charge.
28Supply and installation of silent Diesel Engine driven generating set of capacity 50 KW/ 62.5 KVA, 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with PCC foundation (as per OEM design and Items requied for PCC foundation of DG Set shall be measured and paid seperately ), control panel with necessary meter and sound proof canopy as per latest CPCB norms of GOI as revised from time to time.
29Item No. 17.00 Contd.... (a) Engine : Diesel engine, 4 cylinder engine developing required 84 BHP @ 1500 RPM for continuous duty of suitablefor62.5 KVA alternatorwith provision of 10% over load for one hour in every 12 hour running confirming to BS 5514/ISO 3046 and revised editions as applicable standard Totally enclosed, electric star, compression ignition,4 stroke. The engineshall consists of following specification:-
30Item No. 17.00 Contd.... (i) Fly wheel to suit flexible coupling with starter ring,cooling radiator with blower fan,fuel hoses,mico fuel pump with mechanical governor, air cleaner paper element type, exhaust silencer,SS expansion bellow, lubricating oil filter,fuel oil filter, 12 V electric starting system, battery charging alternator,engine control panel consisting of ON/OFF START key,lub oil pressure guage, water temp guage,ammeter battery chargingsafely divices such as:low lubricating oil pressure,light water temperature ect as per standards.
31Item No. 17.00 Contd.... (ii)   Instrument panel consisting of: Starting switch with key lubricating oil,temperature guage,lubricating oil pressure gauge, water temperature guage,battery charging indicatinglamp,hour meter with RPM indicator,safety control against high temperature of water,over speed stop with double driver adopter.
32Item No. 17.00 Contd.... (iii) Alternator: Self excited self regulated,floor mounted with all and / or roller bearings, statically and dynamically balanced screen protected SPDP enclosures confirming to IS 4722 / BS 2613,single shaft extensive type with damper with damper winding on pole ‘H’ class insulation automatic voltage regulated from no load to full load,ammeter capacity of delivery 62.5 KVA, 415 volts, 3 phase, 50cycles andlagging for AC supply and will be suitable for tropical conditions.
33Item No. 17.00 Contd.... (b) OTHER FITTINGS: (i) Battery Charger : Battery charger having electric circuit consisting of rectifiers, capacitors and resistance etc. The battery charger should be able to charge 12 volts 65 AH battery 2 Nos at a time (ii) Fuel tank of suitable capacity as per manufacturer recommendation mounted on steel frame at suitable height with all connecting pipes and fittings upto fuel pump and over flow pipe from engine to tank including level indicating gauge duly marked and drain valve and air vent plug etc. (iii)Sealed Maintenance Free (SMF) battery 12 Volt, 65 AH with adequate current carrying capacity, copper lead & battery terminals all as specified and as directed. (iv) First fill of lubricating oil shall be provided by the contractor as per manufacturers recommendation without extra cost. Maintenance Spares: (i) Lube Oil filter elements - 05 Nos (ii) Fuel filter element - 05 Nos (iii)Vee Belt set- 02 Sets (iii)Air cleaner element - 01 Set (v) Flexible coupling for Gen set - 01 No(vi)Anti Vibration Pads for DGBase plate all as specified and directed.
34Item No. 17.00 Contd.... (c)DG set shall be supplied along with acoustic original enclosure of the manufacture’s suitable for 62.5 KVA DG Set as perlatest CPCB Norms revised from time to time by Govt of India (d) The DIESEL OIL, LUB OIL etc. for smooth functioning of DG SET during PH-I& PH-II complete testing and full tank filling of DIESEL OIL after PH-I & PH-II testing, topping of LUB OIL etc. required for commissioning and testing of DG set will be provided by contractor. (e) Standby fuel tankof capacity 200 Litre made out of MS Sheet 2mm thickincl inlet,outlet, & connection with MS Pipe 15mm stop cock 15mm mounted on angle iron stand duly painted with one coat of red oxide primer and two two coats of synthetic enamel paint all as specified and directed.
35Item No. 17.00 Contd.... (f) Supply and installcubical outdoor type, weather type, weather proof IP-65, AMF Control panel fabricated out of 3.0 mm thick CRCA MS sheet for outer panel and 1.6 mm MS sheet for internal compartments,powder coated incorporating the following items including control wiring etc complete all as specified and as directed.
36Item No. 17.00 Contd.... AMF D.G. Control Panel (62.5 KVA) (a)Power Contactor - 04 Pole, 125 Amp, AC-1 Duty, Coil voltage, 240 V AC, 2NO+2NC AUX Contacts = 02 Nos. (b)HRC Fuse Fittings with 100Amp HRC Fuses/ Links = 06 Nos. ©Electronic KWH Meter, 5A-60A, 3x240V AC, 3 Phase 4 wire 50 Hz = 01 No. (d)Current Transformer, CTR-100/5A, ACC-CL-1, 5A = 03 Nos (e)Electronic Hooter 24 V DC, 96 x 96 Flush Mounting = 01 No. (f)Aux relay 24 V DC with LED, Free WHeeling Diode, 4 change over contacts at 5 A rating DIN Rail mounting and plugin base module type = 02 Nos.
37Contd from above..... AMF D.G. Control Panel (62.5 KVA) (g)Aux relay 12 V DC with LED, Free WHeeling Diode, 2 change over contacts at 5 A rating DIN Rail mounting and plugin base module type = 01 No. (h)AUX contactor, 240 V AC with suitable No. NO + NC Contacts = 01 No. (j)LED Indicating lamp 240 V AC = 02 Nos. (k)Push Button with elements (PBI Stayput type) = 05 Nos. (l)Stayput type Push Button with elements = 01 No. (to be mounted on accoustic enclosure) (m)Selector Switch 6 Pole, 2 way, 10 A, without Off (Auto / Manual ) = 01 No. (n)MCB SP, 6 Amp, 6/10 KA (C Curve) = 01 No. (o)Glass Fuse Fitting 2A, Glass Fuse Links Drawout Type = 06 Nos. (p)Glass Fuse Fitting 2A, Glass Fuse Links Drawout Type (To be fitted in the panel) = 01 No. (qx)Neutral Link 10 A, (Disconnectable type) = 04 Nos.
38Item No. 17.00 Contd....: (a) Quoted rate is deemed to be included for suitable PCC plinth for mounting the AMF panel not less than 500 mm height from the ground with adequate space not less than 600 mm in front of the panelfor smooth operation shall be provided by the contractor for fixing the panel (b) Adequate space shall be provided for cable entry and exit. Add Necessary PCC plinth for mounting the DG set as per manufacture design. (c) The panel drawing to be approved by accepting officer before to place order.)
39Supply, laying, jointing, testing and commissioning LT cable 1100 volts grade, XLPE cable of 95 Sqmm 3.5Core insulated armoured and PVC sheathed with stranded aluminium conductor heavy duty, conforming to IS 1554 Part I, ISI marked,with and including cable glands, cable lugs etc to suitable size, laid in trenches, fixed along the polesor through G.I. Pipe laid under floors road etc complete all as specified and as directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail