Tender For Cleaning And Repairs In Water Supply Installations, Over Head Reservoirs, Underground Sump And Pump At Mil Stn Fazilka., fazilka-Punjab

Military Engineer Services-MES has published Tender For Cleaning And Repairs In Water Supply Installations, Over Head Reservoirs, Underground Sump And Pump At Mil Stn Fazilka.. Submission Date for this Tender is 18-12-2023. Pump Supply Tenders in fazilka Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

40731547
Corrigendum : Tender For Cleaning And Repairs In Water Supply Installations, Over Head Reservoirs, Underground Sump And Pump At Mil Stn Fazilka.
Open Tender
Indian
Punjab
fazilka
18-12-2023

Tender Details

Tender For Cleaning And Repairs In Water Supply Installations, Over Head Reservoirs, Underground Sump And Pump At Mil Stn Fazilka.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 11-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 18-12-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 30000.0 /-
Tender Value
INR 15 Lakhs /-

BOQ Items

Name of Work: CLEANING AND REPAIRS IN WATER SUPPLY INSTALLATIONS, OVER HEAD RESERVOIRS, UNDERGROUND SUMP AND PUMP AT MIL STN FAZILKA.
Sl. No. Item Description
1Cleaning of clear water underground Sumpof capacity 1,00,000 Gallons manually by trained and skilled manpower of working in under ground sumps/reservior with suitable T&P andsafety equipments, Toolsand safty measures. Draining out the contaminated muddywater from the bottom surfaceof sump and cleaning the side walls with the help ofwire brushincluding removal green fungs leaves and other dustand dirt, scraping of dissolved impurities, removal of surface mud /silt ,cleaningwith waterand draining out complete unwanted meterial obtained from cleaning as well asapply spray of suitable approved disinfactant chemical on inner surface of the sump safe for human being and two coat spray painting with sky colour water proofing paint and two coats samocem on outer surface and writting the date of cleaning with synthetic enamal paint complete all as specified by Engineer-in-Charge.
2Cleaning of Raw water jack well of capacity 20000Gallons at Filteration plant manually by traind and skilled manpower of working in under ground sump/reservior with suitable T&P and safty equipments, Toolsand safty measures. Draining out the contaminated muddywater from the bottom surfaceof reserviorand cleaning the side walls with the help ofwire brushincluding removal green fungs leavesand other dustand dirt ,scraping of dissolved impurities, removal of surface mud /silt ,cleaningwith waterand draining outcompleteunwanted meterial obtained from cleaning complete all as specified by Engineer-in-Charge.
3Cleaning of inner surface of over head reservior 50,000 Gallons capacity manually by trained and skilled manpower for working in over head reservoir with suitable T&P and safety equipment, tools and safety measures. Darining out the contaminted muddy water from the bottom surface of the over head reservoir, scraping inner surface with the help or wire brush, incliding removal green fungs leaves and other dust and dirt, of dissolved impurties, removal of surface mud/ silt, cleaning with water and draining out complete unwanted material obtained form cleaning as well as apply spray of suitable approved disinfactant chemical safe for human being on inner surface and two coats spray painting with water proofing paint on inner wall of the tank,andwriting the date of cleaning with synthetic enamel paint complete all as specified and directed by Engr-in-Charge.
4Cleaning of inner surface of over head reservior 1,00,000 Gallons capacity manually by trained and skilled manpower for working in over head reservoir with suitable T&P and safety equipment, tools and safety measures. Darining out the contaminted muddy water from the bottom surface of the over head reservoir, scraping inner surface with the help or wire brush, including removal green fungs leaves and other dust and dirt, of dissolved impurties, removal of surface mud/ silt, cleaning with water and draining out complete unwanted material obtained form cleaning as well as apply spray of suitable approved disinfactant chemical safe for human being on inner surface and two coats spray painting with water proofing paint on inner wall of the tank,andwriting the date of cleaning with synthetic enamel paint complete all as specified and directed by Engr-in-Charge.
5Cleaning the clarifloculator Semi UG sump of diameter; 14.5 meter and depth not exceeding 7.5 meter by removing mud, sediments manually by trained and skilled manpower who has experience to working in UG sumps/ reservoir with safety messures, including scraping the inner surface by wire brush, brooms and removing the mud, green fungs, leaves, dust and dirts, draining out complete unwanted materials obtainedfrom cleanning and two coats spray painting with sky colour water proofing paint on Inner surface of wall and two coats samocem on outer surface and writting the date of cleaning with synthetic enamel paint complete all as specified by Engineer-in-Charge.complete all as specified and directed.
6Cleaning of inner surface of semi under ground jack well of capacity 20000 Gallonsmanually by trained and skilled manpower with suitable T&Pwith safety equipment, tools and safety measures. Darining out the contaminted muddy water form the bottom surface of the tank and cleaning the inner side walls with scraping by wire brush, incliding removal green fungs leaves and other dust and dirt, scraing of dissolved impurties, removal of surface mud/ silt, cleaning with water and draining out complet unwanted material obtained form cleaningas wel asapply sprayof suitableapproved disinfactant chemical safe for human being on inner surface of the tank and two coat white wash on inner surface andtwo coat spray painting with sky colour water proofing paint and samocem on outer wall and writing the date of cleaning with synthetic enamel paint complete all as specified and directed by engineer in Charge.
7Dewatering the stagnated polluted water from 50 lakh gallons capacity raw water tank of size 140 m x 140 m x 4.5 mt r( Note depth not more than 4.5 meter) by pumping out using diesel engine operating pumping set or electricity operated pumping set and draining out the polluted water liquid mud water to distance not exc 100 mtr away from the edge of the tank complete all as specified and directed by Engr-in-charge. (Note:- Dewatering shall be carried out by pumping system using diesel operated engine pumping set or electrically operated pumping set at the discreation of the contractor . In case the pumping is done by using electrically operated pumping set then electricity shall be supplied by the MES and shall be charged at rates indicated in particular specification - 1)
8Desilting of Raw Water tank manually including bailing out mud/sludge by pumps/ manually without damaging bottom lining of tank all as specified.
9Taking down cement plaster from brick/ concrete walls incl raking out joints , hacking for key scrubbing down with water etc.
10Rendering 15 mm thick in CM(1:4) on fairor other than fair faces of brick concrete walls, surface finished even and smooth w/o using extra cement.
11Demolition of brick work any description built in cement mortaror cement lime mortar
12M & L brick work in cement mortar (1:6) all as specified using sub class " B"old size brick straight or curved on plan exc 6 m means radius complete all as specified anddirected by Engr-in-charge.
13Dewatering the stagnated polluted water from 30 lakh gallons capacity raw water tank ( Note depth not more than 4.5 meter) by pumping out using diesel engine operating pumping set or electricity operated pumping set and draining out the polluted water liquid mud water to distance not exc 100 mtr away from the edge of the tank complete all as specified and directed by Engr-in-charge. (Note:- Dewatering shall be carried out by pumping system using diesel operated engine pumping set or electrically operated pumping set at the discreation of the contractor . In case the pumping is done by using electrically operated pumping set then electricity shall be supplied by the MES and shall be charged at rates indicated in particular specification - 1)
14Desilting of Raw Water tank manually including bailing out mud/sludge by pumps/ manually without damaging bottom lining of tank all as specified.
15Taking down cement plaster from brick/ concrete walls incl raking out joints , hacking for key scrubbing down with water etc.
16Rendering 15 mm thick in CM(1:4) on fairor other than fair faces of brick concrete walls, surface finished even and smooth w/o using extra cement.
17Demolition of brick work any description built in cement mortaror cement lime mortar
18M & L brick work in cement mortar (1:6) all as specified using sub class " B"old size brick straight or curved on plan exc 6 m means radius complete all as specified anddirected by Engr-in-charge.
19M&L for Repair/Replacementof chemical dosing pump (for injection for disinfection of water treatment ) injection of capacity @ 15 LPH(type MAGDO/MD/20/40) having 15 LPH at 10 kg per cm2 working pressure solenoid driven, electrically control 220 volts, maximum current 3.3 Amps, maximum power 70 watt with IP 65 protection and "F" class insulation, with standard fittings, with stoke length suitable from 0-100%,stock frequency suitable from 0-to 100% minimum, including all accessories such as footvalve, line injection valve, suction valve, delivery valve and PE tubing consistencey in performancecomplete all as specified and directed. Make : JESCO/VERIMA/ION EXCHANGE
20Supply& fixing of Pump centrifugal type with mounting base, compatiable for electric motor, 440 volts AC three phase voltage rated 50Hz frequency , electric driven,supplied and installed complete 5HP three phase of head 20 mtrs all as specified and directed. Make Crompton/Kirloskar/CRI
21Supply& fixing of Pump centrifugal type with mounting base, compatiable for electric motor, 440 volts AC three phase voltage rated 50Hz frequency , electric driven,supplied and installed complete 10HP three phase of head 20 mtrs all as specified and directed. Make Crompton/Kirloskar/CRI
22Supply& Commissioning of Pumping sets, Monobloc AC three phase voltage rated 50Hz frequency , electric driven,supplied and installed complete 5HP three phase of head 20 mtrs all as specified and directed. Make Crompton/Kirloskar/CRI
23S&F in replacement fully automatic star delta starter 3 phase 415 volts, 50 HZ in steel metal encloser type MV with SSP feature suitable for 40HP motor & relay rangeas recommended by manufactureretc incl taking out unserviceable startr from existing position complete incl taking down the existing all as specified and directed by Engr-in-Charge Make- Bentex
24All as per ser Noabovebut 20/25 HP motor & relay rangeas recommended by manufacturer
25All as per ser Noabovebut 10/15 HP motor & relay rangeas recommended by manufacturer
26DOLstarter 5/7 .5HP motor & relay rangeas recommended by manufacturer
27Supply& fixing of motor electric, 440 volts AC three phase voltage rated 50Hz frequency for centrifugal type pump of capacity 5HP three phase of head 20 mtrs all as specified and directed. Make Crompton/Kirloskar/CRI
28Supply& fixing of motor electric, 440 volts AC three phase voltage rated 50Hz frequency for centrifugal type pump of capacity 10HP three phase of head 25 mtrs all as specified and directed. Make Crompton/Kirloskar/CRI
29Supplying and fixingas in replacement ofreflux (Non -return) valve flanged type rating PN 1.6 size 100mm bore conforming to IS 5312 with necessary gasket, nuts, bolts and washers etc. and jointingincludingtesting for leakage complete all as specified and directed by Engineer – in – Charge.
30Supplying and fixingas in replacement ofreflux (Non -return) valve flanged type rating PN 1.6 size 150mm bore conforming to IS 5312 with necessary gasket, nuts, bolts and washers etc. and jointingincludingtesting for leakage complete all as specified and directed by Engineer – in – Charge.
31Supply & Fixing in replacement flat copper conductor submersible cable 1100 volts grade of size 6 Sqmm, 3 core all as specified and directedby Engineer -in-Charge.
32Supply & Fixing in replacement flat copper conductor submersible cable 1100 volts grade of size 10 Sqmm, 3 core all as specified and directedby Engineer -in-Charge.
33Supply and fixing in replacement foot valve flanged type of size 80mm borewith necessary gasket, nuts, bolts and washers etc. including testing for leakage completeall as specified and directed by Engineer – in – Charge.
34Supply and fixing in replacementfoot valve flanged type of size 100mm bore with necessary gasket, nuts, bolts and washers etc. including testing for leakage completeall as specified and directed by Engineer – in – Charge.
35Supply and fixing in replacement cast ironsluice valve flanged type ofsize 80mm bore dia (Class PN 1.6 )drilled both endshaving cast iron handle, brass spindle, ISI Marked (IS: 14846-2000 & class PN 1.6) with necessary gasket, nuts, bolts and washers etc. and jointing including testing for leakage completeall as specified and directed by Engineer – in – Charge.
36Supply and fixingin replacement sluice valve flanged type Class PN 1.6 size 100mm bore with necessary gasket, nuts, bolts and washers etc. and jointing including testing for leakage completeall as specified and directed by Engineer – in – Charge.
37Supply and fixingin replacement sluice valve flanged type Class PN 1.6 size 150mm bore with necessary gasket, nuts, bolts and washers etc. and jointing including testing for leakage completeall as specified and directed by Engineer – in – Charge.
38Supply and fixing in replacement sluice valve flanged type Class PN 1.6 size 200mm bore with necessary gasket, nuts, bolts and washers etc. and jointing including testing for leakage completeall as specified and directed by Engineer – in – Charge.
39Supply and fixing in replacement sluice valve flanged type Class PN 1.6 size 250mm bore with necessary gasket, nuts, bolts and washers etc. and jointing including testing for leakage completeall as specified and directed by Engineer – in – Charge.
40Supply and fix in replacement Cast Iron Air Valves with single air Outlets, conforming to IS 14845 of size 80 mm dia bore and fixing up in Ductile Iron Water supply mains of size 250 mm dia.
41S &FAgitator electric motor 3 HP with 950RPM Nos - 02 , with gear box greaves AD- 32, 1.50along with 3 core cable of size 10 sqmm flat water proof cable of length 90 Mtrs etc all as specified and directed by Engr-in -Charge.
42S & F in repalcement of gear box with connecting GI pipe mixer for motor3HP motor with mounting bracket connected with drive chain with suitable gear ratio as per existing specification
43M&L DOL starter 3HP capacity Nos-02 complete all as specified and directed.
44M&L for removing Beehives of any nos, size and at upto height of 22 mtrs with all safety gear while removing hives with precautions at height andladders required for climbing will carry, all as directed by engr-incharge.
45Supply& commissioning of Pumping sets, Submersivle 10 HP clear water having discharge of 1200 LPM with 16 Mtrs head , AC three phase voltage rated 50Hz frequency , electric driven,supplied and installed completeall as specified and directed. Make Crompton/Kirloskar/CRI
46Supply & fixing of lithium based energy efficient integrated solar hybrid light 40 watt in single phase FRP body, encases with mono crystaline solar PV panel of 80 Wp, lithium battery 11.1/12.8 V, 39.6 AH with inbuilt BMS , IP 65 High brightness W-LED (160-1801lm/watt) lamp with aluminum reflector for better light distribution, CRI>80, color temp 5700K-6500K, Hybrid micro controller based charge controller cum driver operate on AC & DC supply with dimming function (first four hour at full brightness & rest fo the time at lower level with PIR motion sensor) Dusk to dawn operation, Lux output 30-40 (from 5/6 mtr height), working temp (-) 10 deg Centigrade to (+) 50 deg Centigrade with weight of 8-10 kg, 65mm medium class galvanised pole of 5 to 6 mtr lengthrtc complete al as directed. Make:Bajaj/Phillips/Axxon
47M&L disconnecting/dismantling and strip opening of worn out/defective Centrifugalelectric motor of capacity 15 HP/ 20 HP mono block type, taking out brunt stator winding, services cleaning of stator slots, bearing bushes etc rewinding of stator coils with superior quality of copper enamel wire of existing size and specification including insulating material, varnishing and drying, assembling, installing and connected at original location complete all as per specified and directed with entire satisfaction of Engineer-in-Charge. Make of winding wire shall be ATLAS/Devi dayal / BPL
48M&L disconnecting/dismantling and strip opening of worn out/defective Centrifugal pump of capacity 15 HP/ 20 HPmono block type, taking out unserviceable bush, sleeve & sleeve joint etc repair to Impeller & shaft with proper brass brazing welding & lath work, assembling, testing, installing and connected at original location complete all as per specified and directed with entire satisfaction of Engineer-in-Charge.
49M&L for disconnecting/dismantling of Unsv 3 phase 415 Volt 50 Hz AC Electric motor5 HP/ 7.5 HP,transportation to Civil workshop andstrip opening of worn out/ defective brunt stator winding, services cleaning of stator slots, bearing bushes etc rewinding of stator coils with superior quality of copper enamel wire of existing size and specification including insulating material, varnishing and drying, reassembling, installing and connected at original location complete all as per specified and directed with entire satisfaction of Engineer-in-Charge. Make of winding wire shall be ATLAS/Devi dayal / BPL(Note - defect libility for motor and pump shall be one year from date of Repair
50M&L disconnecting/dismantling and strip opening of worn out/defective Centrifugal pump of capacity 5 HP/ 7.5 H mono block type, taking out unserviceable bush, sleeve & sleeve joint etc repair to Impeller & shaft with proper brass brazing welding & lath work, assembling, testing, installing and connected at original location complete all as per specified and directed with entire satisfaction of Engineer-in-Charge.
51Sevicing,repair maintenance of RO Plant of capacity 1000 litre per hour output of treated water 8040 element, designed pressure of 600 psiincluding dismantling and opening of unserviceable spare partsof the RO plant and cleaning, removing and checking of its all parts for serviceability and replacement of defective parts and minor spares required for proper functioning of RO Plant without any type of leakage and re-assembling complete parts with testing on load to the entire satisfaction of Engr-in-Charge.Note :- 1. All major defective/unserviceable spare parts/items reqd for replacement inshall be measured and paid separetely under appropriate items as mentioned in following here-in-after. 2. Contractor should provide technical inspection of each RO Plant by an engineer of corresponding MAKEinstalled at site before supplying of material and incorporate the same at the site.
52Supplying and fixing in replacement RO membrane to deliver for 1000 upto 3000 litre per hour output of treated water 8040 element, designed pressure of 600 psi incl testing after completion and taking out old unserviceable membrane complete all as specified and directed by Engineer-in-Charge. Make : Hydronautic/Dow/Koch U.S.A
53Supply and fixing in replacement of ultravoilet tube model AP-30 etc complete all as specified and directed by Engineer-in-charge. Make : Philips/TATA/Alpha or equivalent as approved by GE
54Supplying and applying media porous sand quaratz of different size to meet raw water requirement for pressure sand filter complete all as specified and directed by Engineer-in-charge. Make : Chloromax/AQUA/ Thermax Limited/ION EXCHANGE
55Supplying and applying activated carbon filter media initialy charged of 800 Iodine value to meet raw water requirement complete all as recommended by manufacturer and as specified and directed by Engineer-in-charge. Make : Chloromax/AQUA/ Thermax Limited/ ION EXCHANGE
56Supply only Sealing kitto match with multi stage pumping set (15 stage)
57Supply only Bearing as per existing size and maketo match with multi stage pumping set (15 stage)
58S&F in replacement100mm bore High density poly-ethlyene pipes (HDPE) of pressure rating 6 Kgf/cm2 laid in open/wall with all fittings and fixed complete all as specified and directed by Engineer-in-Charge
59S& F fibre sheet 2mm thick reinforced translucent plain sheeting with drilling pinching corrougated with coach screw and washer etc in angle walol and painting with black color of two coats and othwe necessary items, complete all as specified.
60S& Fstructural steel work in tubular trusses including special shaped washer etc complete using ERW or induction butt welded tubes grade St-240complete all as specified and as shown in drawing and directed by Engr-in-charge.