| 1 | Providing, installation, connectionand testing of Capacitor Duty Contactors (AC Control) 3 pole415 volt 50 Hz Ac,AC3 Rating (A) 70 Amp, AC1 Rating (A) 100 Amp, MNX 70, Reference - CS97076 suitable for 15/20 KVAR capacitor bank, Special Contactors designed for switching of 3 Phase, single or multi step capacitor bank Conforms to IS Conformance to Conforms to IS / IEC 60947-4-1 & IEC 60947-4-1,Range from 9A – 650A AC-3,Click fit type construction up to 40A, available with conventional / universal AC/DC electronic coil version,Coil on top design in 95A and above, also replace the faulty conteactor including drilling holes in cubicle panel, making connections, etc. as required Make Schenider/L&T/Havells/Simence/ABB |
| 2 | Providing, installation, connectionand testing of Auto Manual Contactors (AC Control) 4 pole AC-15,4A at 415 volt 50 Hz Ac, MO0 22E (2NO + 2NC), Reference - CS91625 suitable for Conforms to IS Conformance to IEC 60070 and 60831, UL, CSA, also replace the faulty conteactor including drilling holes in cubicle panel, making connections, etc. as required Make Schenider/L&T/Havells/Simence/ABB |
| 3 | Replacement of 440V 50Hz-2KVAR 3PH, Reference No - QHBTMC5002X0, Heavy Duty Boxtype capacitor bank (Schenider/EPCOS /BCH /L&T /Havells make) i/c connection testingetc as reqd. |
| 4 | Replacement of 420V 50HZ-5KVAR 3PH, Reference No - QHBTMC5005X0,Heavy Duty Boxtype capacitor bank (Schenider/EPCOS /BCH /L&T /Havells make) i/c connection testingetc as reqd. |
| 5 | Replacement of 415V 50HZ-15KVAR 3PH ,Ref. No. QHBTMC5015X0Heavy Duty Boxtype capacitor bank (Schenider/EPCOS /BCH /L&T /Havells/Simence make) i/c connection testingetc as reqd. |
| 6 | Providing, installation, connectionand testing of 12 Stage With LCD display Automatic Power Factor Correction Relay (APFC relay) Automatic/ Linear/ rotational switching modes of banks, Selectable 5A current input, LCD version with RT12, 440 V, 5 Amp , Reference No -51213 (Make - Schenider/L&T/Havells/ABB/C & S/EPCOS/Simence/) i/c connection testingetc as reqd. |
| 7 | Providing, installation, connectionand testing of Multifunction Energy meter with NextGen features like Harmonics & Min/Max Monitoring,Energy Standard – Class 0.2/0.5S/1 as per IEC 62053-22 / 21, Power quality analysis with THD & individual harmonics upto 15th over communication Digital security, 13 different wiring configuration scheme, Volts, Amps, PF, THD, F, W, Wh, VA, VAh, Var, Varh, Runhrs, Onhrs, Interupts, Preloaded Demand & Import /Export, Class accuracy Cl1.0, POP, Reference -METSEEM6400NGPOCL1 With LCD display (Make - Schenider/L&T/Havells/ABB/C & S/Simence/) i/c connection testingetc as reqd. |
| 8 | Replacement of 20 Amp Fuse Bolted type, Suitable for type HD 20H/20P/20B, HD 32H/32P/32B fuse base(Schenider/Simence//BCH /L&T /Havells make) i/c connection testingetc as reqd. |
| 9 | Dismantling and Rewiring ofexisting contrlo wiring of APFC Panel 12 stage-based pre-programmable microcontrollers that automatically trigger capacitor banks of appropriate capacity in many stages by directly detecting the reactive load using the VAR (Volt Ampere Reactive) sensing concept tends to keep the PF near to unity. The capacitor banks, on the other hand, are chosen in stages of 12 based on the load pattern as specified by the requirements i/c connection testingetc as reqd.. |
| 10 | Replacement of ON/OFF Push Button Switch as per color code(Red & Green) on the existing APFC Panel (Havells/Schenider/C&S/BCH /L&T /ABB/Simence/ make) i/c connection testingetc as reqd. |
| 11 | Supplying and Fixing of 10 Amp, 3 P 2W Auto-Manual Selector Switch on the existing APFC Panel (Havells/Schenider/C&S/BCH /L&T /ABB/Simence/ make) i/c connection testingetc as reqd. |
| 12 | Providing, installation, connectionand testing ofCT, Primary Current of CT 500 Secondary Current 5 Amp, 15 VA, CT Type - EOT55 in the existing Panel etc. as required. Make - Elmex/Fuji Electric/L&T /Havells/Simence/ABB/AE |