| 1 | Supply of11TR Air Cooled Ceiling Suspended Ductable ACs with indoor & outdoor unit. IDU SS drain pan as per specification complete with suitable capacity drive motor , air-cooled condenser with all accessories, hermetically sealed scroll compressor, electronic microprocessor pendant controller with digital display, first charge refrigerant gas, vibration isolator pads, structural support for fixing IDU/ODU, safety devices including thermal protector, pressure relief valve, overload relay single phase preventer etc., i/c power wiring and control cabling(indoor to outdoor), thermostat wiring, high-low pressure cut out suitable for 3 phase 440V supply etc. complete as required. ( It should be double compressor 5.5 TR each)(Make :- Voltas, Bluestar, Hitachi, Mitshubishi) |
| 2 | Installation,Testing&CommissioningofDuctableACcomplete with providing frame structure. lifting , shifting etc which is reqd withnitrogenpressure testing,vacuumizingandadditionalrefrigerantgascharging,trialrun,providingairbalancingreportandhanding over of the system up to the satisfaction ofEngineer In Charge.(11 TR) |
| 3 | Supply, installation, balancing and commissioning of fabricated at site Aluminium sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Thickness 024 SWG mm sheet |
| 4 | Supplying of 3.5 core x 35sqmm PVC insulated and PVC sheathed al condur steel armoured underground type cable of 1.1KV grade conforming to relevent IS specificaion etc as reqd |
| 5 | Insulated Condensate Water Drain piping constructed out of PVC / HDPE hard pipes, fitting, accessories, bends, elbows, tees, flanges, tapping\"s, wall sleeves, hangers, supports, anchors Fasteners. 32mm Dia PVC Drain Pipe |
| 6 | Supplying and fixing of4 way MCB enclosure made of Sheet Steel, Phosphatised, Powder Painted MCB DBs with Din Rail (In accordance with IS 13032, IS 8623, IEC/BS EN 60439-3) ( Havells make HSN code 8537 Cat No DHDESFP or similar superior) |
| 7 | Supplying and fixing 63 A rating, 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 8 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 9 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 10 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 11 | Supply, installation, testing and commissioning of Aluminium volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. |
| 12 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class \"O\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required 19mm |
| 13 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as requiredUpto 35 sq. mm (clamped with 1mm thick saddle) |
| 14 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 35 sq. mm (32mm |
| 15 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required |
| 16 | Supplying, installation, testing and comissioning of cubical panel board with following MCCB i/c bus bars interconnection, ferruls, Ammeter with CT, Voltmeter, Rotary handle, indicator etc as reqd (1) 250 Amp Capacity 4 pole 35 KA MCCB ( as incomer).(2) 100 Amp capacity 3 pole 25 KA MCCB- 4 nos ( Make- Havells, L&T or similar superior) |
| 17 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 95 sq. mm |
| 18 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as requiredAbove 35 sq. mm and upto 95 sq mm (clamped with 25 x 3 mm MS flat clamp) |
| 19 | Supplying,installation,testing&commisioning of followingcapacityPlugIn/tapoffbox ontheexistingAirInsulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick sheet steelenclosure(IP54)dulypowdercoatedwithprovisionof MCCB/ACB (but without MCCB/ACB) complete etc. as required. 250 A 30kA SC for 1 sec |
| 20 | Supplying and fixing 250 Amp 4 pole MCCB, 35 KA breking capacity adjustable thermal & fixed magnetic type i/c fixing on tap off box i/c connection etc as reqd ( Make- havells/ L&T or similar superior) |
| 21 | Supplying of following size PVC insulated and PVC sheathed al condur steel armoured underground type cable of 1.1 KV grade conforming to relevant IS specification etc as reqd.35 sqmm |
| 22 | Supplying of following size PVC insulated and PVC sheathed al condur steel armoured underground type cable of 1.1 KV grade conforming to relevant IS specification etc as reqd.95 sqmm |
| 23 | Comprehensive annual maintenance contrate (CAMC) all inclusive i/crefrigerent etc (nothing to be paid extra on account of any spare , refrigerent, rewinding, labour etc as reqd) after complition of one year warranty/DLP |