| 1 | CIVIL WORKS:Earthwork in excavation of foundation in hard soil including dressing & levelling of bed within initial lead of 50mt. & lift of 1.5mtr etc complete as per the direction of the Engineer-in-charge. |
| 2 | Filling in foundation & plinth with sand including watering & ramming etc complete as per the direction of the Engineer-in-charge. |
| 3 | Excavation in hard soil such as Hard stiff clay, stiff black cotton, hard red earth, shales, moorum ordinary gravels with in 50mtr. initial lead and 1.5mtr. initial lift including rough dressing and breaking clods and stacking rubble or spreading and levelling with the site as the case may be etc. complete as per direction of the Engineer-in-Charge.( Mechanical 60% & mannual 40%) |
| 4 | Filling in F & P with excavated materials including well watered and rammed in hard soilsuch as Hard stiff clay, stiff black cotton, hard red earth, shales, moorum ordinary gravels with in 50mtr. initial lead and 1.5mtr. initial lift including rough dressing and breaking clods and stacking rubble or spreading and levelling with the site as the case may be etc. complete as per direction of the Engineer-in-Charge.( Mechanical 60% & mannual 40%) |
| 5 | Cement concrete (1:4:8) with 4cm size h.g.c.b. metal of approved quality from approved quarry with ramming watering and curring etc. complete including cost, taxes, royalty convence charge of all material to worksite, supply of cement T&P required etc. complete as per the direction of the Engineer-incharge. |
| 6 | R.R.H.G. Stone massonry(1:6) in foundation and plinth with cost and carriage of all material from approved source including all costs, taxes and cess etc. complete as per direction of Engineer-in-charge. |
| 7 | C.B.Brickmasonry 25cm x 12cm x 8cm size having crushing strength not less than 75kg / cm2 with dimensional tolerrance + 8% in cement mortar (1:6) in foundation & plinth etc. complete as per the Engineer-in-charge. |
| 8 | R.C.C. work in C.C. (1:2:4) including hoisting & laying & curring for 28 days using 12mm. Size clean black hard granite crusher broken chips of approve quality and from approve quarry including cost taxes conveyance charges of all materials to the worksite with supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge. |
| 9 | C.B. Brick masonry 25cm x 12cm x 8cm size having crushing strength not less than 75kg / cm2 with dimensional tolerrance + 8% in cement mortar (1:6) in Super structure etc. complete as per the Engineer-incharge. |
| 10 | Rigid smooth centering & shuttering for R.C.C. works including false work & dismateling then after including cost of materials in ground floor complete as directed by the Engineer-in-charge. |
| 11 | Cement Concrete (1:2:4) with 12cm size h.g.c.b. Chips of approved quality from approved quarry with ramming watering and curring etc. complete including cost, taxes, royalty convence charge of all material to worksite, supply of cement T&P required etc. co |
| 12 | M.S. reinforcement for R.C.C. work including supplying, straightening, cutting, bending, binding & tying the grills & placing in position including cost of binding wire 18 to 20 guage per Qntl. Including cost of HYSD Still Bar (FE 415/ FE 500) |
| 13 | 12mm cement plaster in cement mortar (1:6) finished smooth to brick work after racking out joints including waterring and curring with cost, taxes, royalty and conveyance charges of all material to the worksite and supply of all labour and T&P required for the work etc complete as directed by the Engineer-in-charge. |
| 14 | 20mm cement plaster in cement mortar (1:6) finished smooth to brick work after racking out joints including waterring and curring with cost, taxes, royalty and conveyance charges of all material to the worksite and supply of all labour and T&P required for the work etc complete as directed by the Engineer-in-charge. |
| 15 | Cost of Outlets |
| 16 | Supply and fitting of M.S. Door (1 no.: size 1.2m x 1.98m)with G.I. Frame and Ventilator(2 nos.: size 0.30m x 0.45m) including all costs. |
| 17 | Dry Brick Khoa of 10cm thick well watered & rammed to receive A.S.Flooring complete including all cost of all labour, materials , transportation, taxes etc. complete. |
| 18 | 2.5cm A.S.Flooring in CC (1:2:4) including punning with 12mm HG Chips |
| 19 | Priming of M.S.Door with approved primer |
| 20 | Painting of 2 coats with approved shade of paint including cost of paint and labour etc complete |
| 21 | White washing 2 coats with shell lime over 2 coat white washing. |
| 22 | Filling the foundation and plinth with excavated material as directed by the Engineer-incharge. |
| 23 | Labour charges for letter writting on display board in black colour on yellow back ground painting including cost of material, labour etc. complete. |
| 24 | Foundation Nut & Bolt inclusive of cost., taxes etc. complete. |
| 25 | Fitting of A.R. valve including all costs and taxes etc. |
| 26 | Dismantling of Lime concrete, cement concrete grade M 10 and below including T & P and scaffolding whereever necessary, sorting the dismantled material, disposal of unserviceable materials with all lift and lead. |
| 27 | Monoblock pump set total head of 18 mtrs capable to discharge 1700 LPM with 10 HP/7.50 KW squirrel cage induction motor fitted with bronze impeller TB-2 of IS 318/1981, companion flanges & Class \"F\"insulation suitable for operation 415 volt +6%-15% 3 phase, 50Hz AC poweer supply suction/deliveery= 100mmx100mm with BEE Star rated energy efficiency Pump & as per IS-9079/2002 with overall efficiency 62 to 65% of reputed brand having wide dealership net work for easy availability of spares.The materials of construction as given below (a) Casing: FC 200 as per IS 210/1978 (b) Impeller: Bronze grade LTB-2 of IS 318/1981 |
| 28 | Automatic Star Delta starter sheet steel enclosure suitable for operation of squirrel cage Induction motor upto 15 HP (13-20) with 16. Amp (AC-3) contactor at 415 volt +6%-15%, 3 phase, 50 Hz, AC supply with suitable overload relay & No volt coil with electric pnemutic timer suitable for operation at voltage range of 300-440 volt including cost of transportation to site The starter should provide dependable protection against overload and single phasing & should be of reputed brand having wide dealership network for easy availability of spares. |
| 29 | Cost of 63 Amp. Triple pole Main Switch& natural of voltage range 440 volt of re-wirable fuse and shall confirming to IS-4064(PT-I & II ) with ISI marking of reputed company with utilisation capacity category AC-22including all taxes etc. |
| 30 | Empty Outdoor Irrigation Pannel Board size (0.45mtx0.25mtx1.20m of 18 SWG Cold Rolled M.S Sheet with 4legs of 300 size with one coat of Red Oxide Primer and two coats of Smoke grey /Navy bluetwo coats of powder coated paint of approved quality on both side (Inside & Outside) suitable to mount 3Phase Starter, Main Switch and Capacitor inside the Panel Board vertically over 18 SWG M.S.Sheet and the danger board fixed on the top of the Panel Door. |
| 31 | Motor hood size (0.45mx0.45mx0.60m) made with 18 SWG (cold rolled M.S.Sheet with one coat of red axide primer and two coats of powder coated paint of approved quality on both side (inside & outside) suitable to cover centrifugal monoblock Pump Set from 10 HP to 15 HP and having provision for attachement with the groves on rear side of the pannel board. |
| 32 | Base frame for panel (size 0.40mx0.20m) made with 3 size M.S. channel having suitable holes for fitting of panel Board, coloured with one coat of red oxide primer and two coats of powder coated paint of approved quality & Base frame for motor (size 0.50mx0.27m) made with 3 size M.S. channel having suitable holes for fittings of different size and make 3 phase centrifugal monoblock pump set from 10 HP. to 15 H.P. coloured with one coat of red oxide primer & two coats of powder coated paint of approved quality. |
| 33 | 4KVAR Power ShuntCapacitor with ISI mark of reputed company. |
| 34 | 3x10 sqmm PVC insulated (HD) tropoder armoured Electric Cable with alluminum conductor for use in 3 phase power system of working voltage upto & including 1100 volts at 50Hz confirming to IS 7098(Pt-II) including cost of transportation to site and laying below 0.9mtr of the ground and filling the excavated materials including watering and rammin including all taxed etc. |
| 35 | 4mm2 PVC Single Core Copper Wire ISI mark of reputed Company. |
| 36 | Cost of Electrical earthing including cost of 30mm dia.X3m. long G.I. earthing pipe with proper sloting(TATA make), 30mm dia G.I.Flange for earth pipe, No. 6 G.I. wire, 100 amp cable socket, Al-ka-pea, 50mm dia flexible conduit pipe, 50mm long TVS nut & bolt including petty materials like charcoal, common salt etc. complete, transportation of all earthing materials & tools including loading and unloading, storing & shifting to project site complete and cost of labour for earth works involved including taxes and other charges if any all complete. |
| 37 | Electrical installation and energisation (including cost of volt meter-5 nos, CT type Amp. Meter-5 nos, selector switch- 5 nos, CT - 2 nos(100:5), indicator - 15 nos,100 Amp Kit kat - 15 nos, cable socket, internal and external wiring at pump chamber etc. |
| 38 | 100mm dia nominal bore G.I.pipe having wall thickness 4.5mm electrical resistance welded of medium class confirming to IS- 1239(part-1/2004) with latest ammendments, screwed at both ends as per IS-554 with socketed at one end and the other end protected with plastic threaded protector including its transportation and unloading at L.I.P. site. The socket confirming to ISI 1239(part II/1992) with latest ammendments in random length of 4 to 7 mtr. Each pipe should bear IS certification and manufacturers name/trade mark. |
| 39 | 219 mm dia M.S.Pipe (6.30mm thickness) IS 3589:2001 with ISI mark of reputed company. |
| 40 | 100mm dia G.I.Bend( Medium Duty) conforming to IS No-1239 (part II/1992) with ISI mark of reputed company. |
| 41 | 100mm dia C.I. Screw boss Foot Valve of swing type friction less with single disc conforming to IS-4038/1979 of reputed brand with ISI mark of reputed company having wide dealership network. |
| 42 | 100mm dia G.I.Flange( Medium Duty) conforming to IS No-6392/1971 with ISI mark of reputed company. |
| 43 | Rubber Insertion and Nut& Bolt etc. |
| 44 | 100mm dia C.I.Double Flanged Non Return Valve swing type PN-1.0 (IS-5312(Part-I-2004) with bypass arrangement with ISI mark of reputed company. |
| 45 | 50mm dia C.I.Air Release Valve (single action) with saddle and Raiser pipe conforming to IS 14845 (SI) with ISI mark from reputed company. |
| 46 | 12mm thick M.S.Plate Flange 219mm dia ISI mark of reputed company. |
| 47 | 200 mm dia HDPE Bend of ISI specification for water supply and with ISI mark in it\"s body with exfactry cost, transportation andcess etc complete except G.S.T. |
| 48 | 200x200x160 mm SpigotMoulded Reducing HDPE Tee 10 Kg. of ISI specification for water supply and with ISI mark in it\"s body with exfactry cost, transportation andcess etc complete except G.S.T. |
| 49 | 200 mm dia HDPE Pipe End with 2 Nos. flanges of ISI specification for water supply and with ISI mark in it\"s body with exfactry cost, transportation andcess etc complete except G.S.T. |
| 50 | 200mm dia HDPE End cap of ISI specification for water supply and with ISI mark in it\"s body with exfactry cost, transportation andcess etc complete except G.S.T. |
| 51 | 200 MM HDPE Tail Piece 200 mm Long of ISI specification for water supply and with ISI mark in it\"s body with exfactry cost, transportation andcess etc complete except G.S.T. |
| 52 | 200 mm F HDPE Slipon Flange of ISI specification for water supply and with ISI mark in it\"s body with exfactry cost, transportation andcess etc complete except G.S.T. |
| 53 | 100mm x 100mm x 25mm dia G.I. Priming Tee with Plug with ISI specification from of reputed manufacturere. |
| 54 | Miscellaneous welding charges for \"Z\" joint, \"S\" bend etc. |
| 55 | Laying, Welding and Fitting of 200 mm dia M.S. Pipes including all costs of welding materials, tools & plants and labour etc complete. |
| 56 | Labour charges for Installation of pumpset and delivery pipes and fittings including fitting of Sluice Valve, NR Valve, Air Release Valve, Riser Tee, lowering of pump and transportation etc complete. & fixing suction and delivery pipe to motor, NR Valve, Foot Valve, Sluice Valve and other fitting materials including cutting, welding etc. complete (as the case may be) as per the direction of the Engineer-incharge. |
| 57 | Thick Rubber Insertion 3mm thick. |
| 58 | Nuts and Bolts |
| 59 | Supply of 200mm dia HDPE PE 80- PN 4 ISI marked High Density Polyethylene (HDPE) Pipes for water supply as per IS-4984/2016 with proper grade and pressure rating including ex-factory rate, entire cost involved inPre-delivery test & Post delivery test with correspoding test marking on the body of pipes along with name & address of manufacture , cost of transportation from factory to project site including loading & unloading, storage at site stock yard, watch and ward etc. and handing over to Pani Panchayat President or Secretary with due approval of authority including all taxes and cess etc. complete but excluding cost of GST. Pre-delivery test & Post deliver tests are to be conducted at the facility ofCIPET, Bhubaneswar and test reports thus obtained from CIPET, Bhubaneswar are to be submitted to the Engineer-in-Charge. |
| 60 | Fitting of200mm dia HDPE PE 80- PN 4 ISI marked High Density Polyethylene (HDPE) Pipes for water supply as per IS-4984/2016 with proper grade and pressure rating with supply of all required accessories materials , labour, T&P for jointing of 160mm diaHigh Density Polyethylene Pipes by butt fusion welding method as per specification & laying in trenches with desired leveling, testing including fitting and fixing up of required no. of attachments for Outlets and Shaddles andRiser Nipples, fitting air valve, equal Tee etc. complete includingcost of transportation from factory to project site stock yard and from stock yard to work site complete as per direction of the Engineer-in-Charge. |
| 61 | 200mmx200mmx110mm dia Weldless G.I.Tee(3.6mm thickness) with bend, closing and opening arrangement of reputed company. |
| 62 | 200mm diaC.I. Butter Fly Valve BS:5155/15: 13095-CI MOC Lever Operated PN-1.0 with ISI mark of reputed company. |
| 63 | ELECTRIFICATION WORKS:Construction of 3 phase 11 KV HT line as per REC standard confirming to IE Rules 1956 with 300 kg 9 M long PSC Pole with 55 Sqmm Insulated Conductor average span length40mtr with ,11 KV \"V\" Cross arm, with required No.of 11 KV T & C Disc. Polymer Insulators in tension point &11 KV Pin Polymer insulators, Couping & Padding of Poles with all G.I.Channels. Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & double stay at end point with 18 mm G.I.H.T.Stay, concreting of Stay with Anchor plate, guarding at Road crossings etc if required including cost of all materials, labour transportation,inspection & commissioning etc. complete. |
| 64 | Construction anderection of 11 /0.4 KV ,25 KVA Double Pole mounted Substation with5mtrx3mtrx1.5mtr height mesonary toe wall /G.I. Flat fencing boundary wall withFlat with Polymer insulator ,L.T DistBox with MCCB , Aluminim bus bar of single bay with kitkat fuse , sand filling and metal spearding with M.S.Grill gate ,all Channel matrials should be G.I , 7 Nos earthing with chamber with 3mtr G.I pipe of40mm dia with connecting of 25mmx 5mm G.I flat to all earthing including 25KVA BIS Leble-II Star rated Transformer confirming to RE Rules 1956, mounted on 2.44 Mtr. Long structure, supported in 300 kg 9 mtr long PSC pole,transformer hard channel & top channel made of 2.8 M long 100 X 50 X 6 mm G.I.Channel, Transformer belting on 2.80 M long 50mm X 50mm X 5 mm G.I.Angle, (all REC SPN Std.F-3) with all accessories like 3 pole 11 KV HG Fuse(F-5)& A.B.Switches(F-9) both mounted on 2.8 M long 75mm X 40mm X 6 mm G.I.Channel and supported by 1.0 M long 50 X 50 X 5 mm G.I.Angle, with 3 No. 11 KV Lightening Arrestors and Danger board at each Pole, Anti climbing Devices & all other necessary fittings i.e required size Nuts & Bolts, Brackets, Cable, Cable Sockets as per TPCOCL specification etc. including cost of all materials, labour , transportation complete with liasioning for testing inspection & commissioning as per specification of TPCODL etc complete. |
| 65 | Construction of 3 Phase L.T.line as per REC standard confirming to RE rule 1956 with 300Kg 9 Mtr long PSC pole support in 0.33M span length with 3x35mm² +1x25 mm ² LT, XLPE AB cable with coil earthing device, LT dead end clam, Suspension clamp with G I hook , stay accessories such as wire insulator , clamp etc. nut bolts, alongwith concreting copping & padding of polesand stayset as per direction of Engineer in Charge. |