Tender For Maintenance, Repair And Replacement Of Defective Items Of Lt Distribution System, Distribution Boards, Mcbs, Cables And Allied Services Under Ge (Af) Lohegaon At 9Brd Af Stn Pune

Issued by Statutory Bodies & Commissions/Committees · Pune, Maharashtra
Tender Value
30 Lakhs
Estimated cost
Bid Submission
11 Dec 2023
0 days left
EMD
60000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Maintenance, Repair And Replacement Of Defective Items Of Lt Distribution System, Distribution Boards, Mcbs, Cables And Allied Services Under Ge ( Af ) Lohegaon At 9Brd Af Stn Pune

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 30-Nov-2023 REVISED CRITICAL DATE Date 04-Dec-2023
2 04-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-Dec-2023

BOQ

Name of Work:MAINTENANCE, REPAIR AND REPLACEMENT OF DEFECTIVE ITEMS OF LT DISTRIBUTION SYSTEM, DISTRIBUTION BOARDS, MCBs, CABLES AND ALLIED SERVICES UNDER GE (AF) LOHEGAON AT 9BRD AF STN PUNE
Sl. No. Item Description
1Dismantling cross-arms of M.S. channel or angle sections, clamps, nut bolts etc. complete all as specified and directed.
2Dismantling / taking out insulator of any size / type from existing electric LT lines complete.
3Dismantling of existing stay assembly any type / size from its stay rod, cutting stay rods (above ground portion) dismantling MS clamps, nuts, bolts, stay bow, loop insulators, stay wire etc complete
4Dismantling / taking out existing ACSR conductor any size from existing over head lines incl disconnection complete all as directed.
5Disconnecting of incoming / outgoing cables and earthing lead and taking out existing unserviceable outdoor feeder pillar box / Paneland removing unserviceable pillar box / Panel with frame from the PCC foundation complete all as directed.
6Taking down Old unserviceableLT UG cable of service connection or distribution systemof any size and removing from site all as directed.( Excavation and earth work will be measured seperately)
7M&L for scrapping of old alum paint of steel tubular pole 9/11 mtr by means of emery paper for preparation of smooth surfaces andpainting with two coats of alum paint on pole , brackets old junction boxes channels etc inclalternate 30 cm wide white andblue strip painting up to 1.5 Mtr height from ground level complete all as specified and directed by Engr -in-Charge.
8Material & Labour forpainting to feeder pillar box / LT panel & duct coveretc, including angle iron frame with two coat of grey synthetic enamel paint includingwelding of door with proper size new hinges of suitable size and locking arrangementswhere required complete as specified.
9Cutting/trimming of treesupto 150 mmgirth including cutting of upper portion of branches above poleclearance up to 10 mtrs and disposal ofsame at a distance not exc 50 mtr and clearing of site complete as directed.(Note:Tools/ladder required for cutting/trimming of trees will be provided by the contractor at no extra cost and cost of the same be deemed to be included in the quoted rate.)Note:Each Span will be measured from one pole to another pole
10Provn ofservices for cable fault locationfor LT UG cable, XLPE insulated 1100 Volts, of any size with fault detector machine complete all as specified and as directed.
11Material and labour for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed including excavation in any strata, taking out cable, and making disturbed surface after relaying the cable making joints suitable for aluminium conductor of size given below all as specified and directed.
1225 to 50 sqmm 3.5 core
1370 to 150 sqmm 3.5 core
14185-240 sqmm 3.5 core
15300-400 sqmm 3.5 core
16Supply and fix GI Pipe Light gradewith all connected accessoriesof sizes100 mm completed as directed
17Supply and fix GI Pipe Light gradewith all connected accessoriesof sizes80 mm completed as directed
18Supplying and erecting ( in true vertical position) steel tubular swaged poles complete with cast iron base plate final taper plug, bolts nuts and screws all as specified of type 410-SP-31 (9.0 mtr length) complete all as specifed in IS 2713 (part-II) 1980 including one coat or red oxide primer and two coats of aluminium paint to exposed surfaces and with blach bituminous paint for embedded portion of pole all as specified and directed at site.
19Material and labour for cross arms, bracing supports, clamps and back plates fabricated from structural steel sections, including nut bolts, washer welding bending cold/ hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one premer coat of red oxide primer, one under coat and one finishing coat of aluminium paint all as directed and as specified.
20S&F shackle type insulator vitreous procelain white / brown / greenwith and including galvanised mild steel straps, washer insulator, bolts and nuts, insulator of size 100mm height and 115 mm max dia with working pressure 1100 volt and galvanised steel straps 3 to 5 mm size and suitable size nut and bolts all as directed and as specified.
21M&L for providing pin type procelain white / brown / green / insulator including galvanised mild steel spindle, two galvanised iron.Washer and one galvanised iron nut, 100mm height 65 mm dia for 1100 volts grade all as directed.
22M& L for danger notice plate 1.6 mm thick mild steel sheet vitreous enamelled white with letter figures and conventional skull and tongue in signal red colour and fixed with MS clamps bolts nuts of approved size LT, 20x15cm all as directed
23M&L for cement concrete (1:4:8) type D2 in foundation filling and mass concrete using 40mm graded stone aggregate for pole/stay foundation or as required on siteetc complete all as directed by Eng-in-Charge
24M&L for cement concrete (1:3:6) type C2 in foundation filling and mass concrete using 40mm graded stone agg for pole/stay foundation or as required on siteetc complete all as directed by Eng-in-Charge
25M&L for cement concrete (1:2:4) type B1 in foundation filling and mass concrete and coping of poles incl necessary form work using 20 mm graded stone aggregate etcor as required on siteetc complete all as directed by Eng-in-Charge
26Supplying, spreading & leveling stone aggregate size of 40 mm grade to the existing sub station or all as specified and directed by Engineer-in-Charge.
27Supplying ,Laying, jointing, testing and commissioning of LT under ground cable 1100 volts grade XLPE(cross linked polythene ) armoured with galvanised round steel wire or steel strip , electric power cable heavy duty, with multi stranded aluminium conductor, laid in trenches, ducts fix on walls/poles with proper size saddles and clamp laid under roads/path/ drain /colverts or enclosed in GI pipe/ fix complete all as specifiedfor following size:-
2810 sqmm 2 core
2916 sqmm 4 core
3025 sqmm 3.5 core
3135 sqmm 3.5 core
3250 sqmm 3.5 core
3370 sqmm 3.5 core
3495 sqmm 3.5 core
35120 sqmm 3.5 core
36150 sqmm 3.5 core
37185 sqmm 3.5 core
38240 sqmm 3.5 core
39300 sqmm 3.5 core
40Relaying ofold serviceable LT/HT under groundPVC/XLPE cable any grade and any size in trenches/fixed to wall/pole/roof/laid in floor including necessary connections and thimbling complete all as specified and as directed by Engineer-in-charge. (Earth work, brick & sand cushioning shall be measured and paid for separately under appropriate item).
41Excavation in trenches not exc 1.5 m wide andnot exc 1.5 m in depth and getting it out for laying of cable / pole etc.
42Soft/loose soil
43Hard/dense soil
44Soft/disintegrated rock
45Returning/ Refilling of excavated soil including spreading levelling and well ramming in layers for any type of soil.
46Removing the surplus spoil to a distance not exceeding 50 mtrs from the starting point and depositing at a height not exceeding 1.5 m above ground level.
47Material and labour for stone dust sand cushioning to under ground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable all as specified and directed.[Note : Measuremenet will be done after punning]
48M&L for brick protection covers laid over cables of sub class\"B\" bricks old size all as specified and directed.
49Supply and fix in repair / replacement of MCCB FP 630 Amps Adjustable type with breaking capacity50 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
50Supply and fix in repair / replacement of MCCB FP 400 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
51Supply and fix in repair / replacement of MCCB FP 250 AmpsAdjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
52Supply and fix in repair / replacement of MCCB FP 200 AmpsAdjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
53Supply and fix in repair / replacement of MCCB FP 160 AmpsAdjustable type with breaking capacity36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
54Supply and fix in repair / replacement of MCCB TP 200 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
55Supply and fix in repair / replacement of MCCB TP 160 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
56Supply and fix in repair / replacement of MCCB TP 100 Amps Fixed type with breaking capacity 16 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
57Supply and fix in repair / replacement of MCCB TP 63 AmpsFixed type with breaking capacity16 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
58Supply install, test and commissioning of Powder coated LTpanel cubical out door type Channel mounted compartmentalized in construction allConfirming to IS 8623 Part 1 1993CPRI approved factory fabricatedmade out of 3 mm thick CRCA sheet & suitable size to accomodate all accessories / fittings, to accommodate incoming MCCB and TPN Copper bus bars of 400 A. incomer MCCB and outgoing feeder.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. Thecubicle shallhaveabottomchannel. A detachable predrilled gland plateof thickness not less than 3 mm thickpowder coated should be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front & back openable lockable /openable by key from both side.The panel shall be Dust, vermin proof and powder coated of approved thickness complete including CTs, control wiring by 1.5Sqmm Wireand consisting the following, including taking down of old unsv panel after disconnecting Existing cables & Reconnecting the cables to new panels and including PCC foundation, excevation, grouting boltsa) Copper bus bar 400 Amps for 3 phase andNeutralb) MCCB FP 250 Amps415 Volt 25 KA - 1 Nosc) MCCB FP 100 Amps - 415 Volt 16 KA- 2 Nos d) MCCB FP 63 Amps 415 Volt16 KA - 4 Nose) 3 Phase digital voltmeter-1 f) 3 Phase digital Ammeter-1g) RYB Indicators - 1 Set Note - The lay out drawing of the panel shall be got approved by the contractor before panel fabrication and shall be fabricated from CPRI approved manufacturer
59All as per item no 58 but with the following acessoriesa) Copper bus bar 400 Amps for 3 phase andNeutralb) MCCB FP 315 Amps415 Volt 36 KA - 1 Nosc) MCCB FP 100 Amps - 415 Volt 16 KA- 6 Nos d) MCCB FP 63 Amps 415 Volt16 KA - 2 Nos d) MCCB FP 125 Amps - 415 Volt 18 KA- 1 Nos e) 3 Phase digital voltmeter-1 f) 3 Phase digital Ammeter-1g) RYB Indicators - 1 Set Note - The lay out drawing of the panel shall be got approved by the contractor before panel fabrication and shall be fabricated from CPRI approved manufacturer
60All as per item no 58 but with the following acessoriesa) Copper bus bar 400 Amps for 3 phase andNeutralb) MCCB FP 160 Amps415 Volt 36 KA - 1 Nose) 3 Phase digital voltmeter-1 f) 3 Phase digital Ammeter-1g) RYB Indicators - 1 Set Note - The lay out drawing of the panel shall be got approved by the contractor before panel fabrication and shall be fabricated from CPRI approved manufacturer
61Note for item No. 58, 59, 60 : Contractor must take priordrawing approval for pannels before placing order to manufactorers
62S & F VTPNDB 4 Waysheet metal enclosure double door suitable for MCCB incommer andMCBs outgoing including MCCB 4P 125 Amps 10 KAcomplete all as speccified and directed including making good disturbed surfaces complete.
63Supply and fixing SP 5 To 32 Amps rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing andcommissioning.
64All as above butSPN 32 Amps
65All as above butTP 25 to 63Amps 415 Volts
66S & F Sub Main Wiringwith PVC Insulatedmultistranded copper conductorwires ofsize2x6.0 sq. mm + 1x6.0 sq. mm earth wireincluding PVC cassing and capping complete all as specified and directed
67Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25 X 4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plateNo. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm),funnel with wire mesh, watering pipe of 20 mm bore medium grade, including galvanised iron strip 25X4 mm with GI protection pipe of 40 mm medium grade up to 7.5 meter length, etc complete all as specified.
68S & F GI earth continuity conductor or main earthing lead of size 25x4 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
69Opening/disconnecting the electrical connection of defective/burnt out underground LT Cable of any size 2 to 4 core from main switch/DB/ junction box / LT panel /LT OH line etc. Taking out the required length of cable from existing loop, cutting the defective portion of cable, providing required thimbles/ connectors at cable end and reconnecting the cable in previous location with existing main switch/ DB/Junction box /LT Panel/ OH line etc complete all as directed.
70Material and labour for Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out removing of grass and vegetation grown around the electrical installations like transformers, LT panels, 2 pole structure, HT panels and complete area inside the fencing all as specified and directed by Engr-in-Charge Note : Item may be measured and paid more than one time as per site requirement to clean the E/M Installations
71Supply and fix all in one solar street light fitting 20 watt having high lumen efficiency, includinginbuilt solar panel and long life maintenance free lithium ferro phosphate battery micro controller based integrated MPPT charge controler with driver complete all as specified and directed by engr-in-charge.
72M&L for Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25 X 4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plateNo. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm),funnel with wire mesh, watering pipe of 20 mm bore medium grade, including galvanised iron strip 25X4 mm with GI protection pipe of 40 mm medium grade up to 7.5 meter length, etc complete all as specified.
73M/L for providing earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to copper earth strip 20 x 3 mmby means of bolts, nuts, checknuts & washers of copper and connecting to test point, providing charcoal and common salt ,all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade and lugs,including copper earth strip 20 x 3 mmwith GI protection pipe of 25 mm medium grade 7.5 meter long, etc complete all as specified.Note-- (i) Vendors are bound to get earthing result upto1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3ohm with single earthing, Any additional work and material required to achive the required result is included in the cost. (ii) Excavated material to be removed from the site and deposit at the distance not exceeding 50m distance and levelled.(iii) Refill the pit with M&L for black cotton soil 1 cum.
74Supply and fix in repair / replacement of MCCB FP 1250 Amps Thermal magnetic Adjustable type microprocessor release with breaking capacity65 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
75S& F in replacement 3 Phase Digital voltmeter 0-1100V Range including selector push btton suitable for fixing in existing panel including control wiring complete.
76S& F in replacement 3PhaseDigital Ammeter 0-800AmpRange including selector push btton suitable for fixing in existing panel including control wiring complete.
77Supply and fixing in replacement PVC insulated stranded aluminium conductor cable sheathed 6 Sqmm flat twin core for connection for street light fitting with over head lines / service connection complete all as specified and as directed by Engineer-in-charge.
78M/L for sub main wiring with two runs of single core 2.5 Sq mmFRLS PVC insulated unsheathed multi stranded copper conductor1100 V grade with colour code and one run of 2.5 Sq mmsingle core FRLS PVC insulated unsheathed multi stranded copper conductor green colour cablefor continuous earthing complete in & including PVC casing & caping with all fttiing & fixtures all as directed and specified.(Note:- Two runs of 2.5 Sqmm copper cable & one run of 2.5 sqmm copper cable including PVC casing & caping shall be mesured and paid as one length)
79S&F of Sub main wiringwith 4 X 10 sqmm single core cable PVCinsulated unsheathed of copper multi strandard conductorcable , 1100 votls grade drawnin PVC casing caping and including PVC casing caping and insulated 1X 10 sqmm unsheathed multistranded FR-LS copper conductor cable for earth continuity and connected to common earth dollycomplete all as specified and directed by Engineer-in-charge. (Note:- 4 lengths of 10 Sqmm & 1 length of 10 sqmm cable and PVC casing caping will be measured as one length).
80M&L for Servicing of APFC panel of rating upto 200KVA including checking of CTs, control wiring, cleaning of panel and capacitor banks, tightning incoming and outgoing connections, supply and replacement of contactor, checking of capacitor banks, contact relayetc complete upto satisfaction of Engr-In-Charge. (Note : Any minor/major spare partfound faulty during checking such as contactor, CTs,contact relay and cable lugs , minor wire pieces including cost of T&P, multimeter etc shall be included in quoted rates of this item)

AI Tender Summary

OUR REF NO 40619219
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 30 Lakhs
LAST DATE 11-12-2023
Authority
Authority Name Military Engineer Services
Work Description Maintenance, Repair And Replacement Of Defective Items Of Lt Distribution System, Distribution Boards, Mcbs, Cables And Allied Services Under Ge ( Af ) Lohegaon At 9Brd Af Stn Pune
Basic Detail
Tender No 8753
Bidding Type Tender
Location
City Pune
State Maharashtra
Key Dates
Publish Date 04 Dec 2023
Submission Date 11 Dec 2023
Open Date 18 Dec 2023
Finance
Tender Value 30 Lakhs
Tender Fee 500
EMD 60000
Exemption Not Available
Document List
43d80be5-5028-4a87-b771-3645947cfb7b.html
8753T.pdf
BOQ_703040.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Dec 04, 2023
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 04, 2023
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Dec 11, 2023
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Completed
Dec 11, 2023
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Dec 18, 2023

Bid Opening Date

Technical bids will be opened and evaluated.