Tender For Repairs Maintenance Of Solar Water Heating System Solar Security Light Dg Sets And Repair Maintenance Of Refrigeration Air Conditioning Appliances At Ranikhet And Chaubattia Under Ge Ranikhet, ranikhet-Uttarakhand

Military Engineer Services-MES has published Tender For Repairs Maintenance Of Solar Water Heating System Solar Security Light Dg Sets And Repair Maintenance Of Refrigeration Air Conditioning Appliances At Ranikhet And Chaubattia Under Ge Ranikhet. Submission Date for this Tender is 06-12-2023. Diesel Generators Tenders in ranikhet Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

40570487
Corrigendum : Tender For Repairs Maintenance Of Solar Water Heating System Solar Security Light Dg Sets And Repair Maintenance Of Refrigeration Air Conditioning Appliances At Ranikhet And Chaubattia Under Ge Ranikhet
Open Tender
Indian
Uttarakhand
ranikhet
06-12-2023

Tender Details

Repairs Maintenance Of Solar Water Heating System Solar Security Light Dg Sets And Repair Maintenance Of Refrigeration Air Conditioning Appliances At Ranikhet And Chaubattia Under Ge Ranikhet

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Nov-2023 Corrigendum No 01 BOQ 29-11-2023
2 29-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-12-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 88400.0 /-
Tender Value
INR 44.20 Lakhs /-

BOQ Items

Name of Work: REPAIR/MAINT OF SOLAR WATER HEATING SYSTEM, DG SETS & REPAIR/MAINT OF REFRIGERATION AND AIR CONDITIONING APPLAIANCES AT RANIKHET AND CHAUBATTIA UNDER GE RANIKHET.
Sl. No. Item Description
1BOQ ( Sch A ) Solar Heating System Taking up or down 15 mm bore unserviceable water tubing and connection including cleaning for refixing and removal from sitecomplete all as specified and dircted
2All as per item No 1 here in before but bore of pipe 20 mm
3All as per item No 1 here in before but bore of pipe25 mm
4Supply and fixing Steel water tubingmedium grade galvanised with all GI fittings (such as bend, elbows,tees, connections, short pieces, back nuts, unions, caps & plugs etc) laid in trenches, on wall or in floorbore of pipe 15mm complete all as specified and directed.
5All as per item No 4 here in before but bore of pipe20 mm
6All as per item No 4 here in beforebut bore of pipe 25mm
7Refixing only 15 mm boresteel water tubingwith and including all GI fittings and accessories etc laid in trenches or open surfaces complete all as specified and directed.Note:- Seviceable GI tubing retreived from item No 1 will be reused )
8All as per item No 7 here in before but 20mm dia bore complete all as specified and directed.( Note:- Seviceable GI tubing retreived from item No 2 will be reused )
9All as per item No 7here in before but 25mm dia bore complete all as specified and directed.( Note:- Seviceable GI tubing retreived from item No 3 will be reused )
10Supply, fixing , testing& commissioning of solarcollector ( 1 Mtr X 2 Mtr ) complete all as specified and directed.
11Supply, fixing , testing& commissioning of solarcollector ( 1.2 Mtr X 1.8 Mtr ) complete all as specified and directed.
12Supply, fixing , testing& commissioning oftoughened U.V Glass( 1 Mtr X 2 Mtr ) and as per existing size of glass for collectorcomplete all as specified and directed.
13Supply, fixing , testing& commissioning oftoughened U.V Glass( 1.2 Mtr X 1.8 Mtr ) and as per existing size of glass for collectorcomplete all as specified and directed.
14Material & Labourfor Descaling of collector using very mild mineral acid to clear the deposites of temporary hardness in side of collector tubes including brazing of leaking joint as required at sitecompleteall as specified and directed.Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
15Supply andfixingrubber washer complete all as specified and directed.
16Supply, fixing , testing& commissioning ofinsulation materials for hot / cold water pipe any size and size of insulation on pipe 5 cm thick glass wool / mineral wool with chicken mesh and Aluminium cladding 26 swg complete all as specified and directed.
17Material and labourfor descaling of heat exchanger in side of hot water tank and hot water tank after repair , testingof hot water tanks capcity 1500/1000 ltrs including replacementcold water pipe/ hot water pipecomplete all as specified and directed. Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
18Material and labourfor descaling of heat exchanger in side of hot water tank and hot water tank after repair , testingof hot water tanks capcity 200/500 ltrs including replacement of old cold water pipe/ hot water pipecomplete all as specified and directed. Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
19Material and labour for Gas welding of leaking joint in the flat panel collector complete all as specified and directed.
20Supply andfixingheating element 2 KWcomplete all asall as specified and directed.
21Supply andfixingthermostate for heating element 2 KWcomplete all asall as specified and directed.
22Material & labour for sub main wiring with 1100 volt grade two single core PVC insulated and unsheathed cable with multi stranded copper conductor 6 sqmm (FRLS) drawn into and including electrical grade PVC conduit not less than 25 mm dia with IS 9537 (PART-III) 1983 marked or relevant ISI marked with all accessories fixed concealed including chase cutting in brick/ stone/ precost PCC block masonry for fixing conduit and making good the disturbed surfaces of wall as per existing including 4 sqmm multi - stranded copper conductor as earth wire in green colour includingtaking down existing unserviceable sub main wiringcomplete all as specified and directed. NOTE: - 2 runs of 6 sqmm single cable , one run of 4 sqmm earth wire cable and PVC conduit shall be considered as one unit/1Rm)
23Supply & Fixingcolouredrotational moulded polythene water storage tanks Triple layered (cylindrical vertical with closed top) hoisted and fixed in postion 1000 ltrs capacity with and including 20mm dia ball valves, high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe minimum weight 210 gram complete all as specified and directed.
24Supply & Fixingcolouredrotational moulded polythene water storage tanks Triple layered (cylindrical vertical with closed top) hoisted and fixed in postion 500 ltrs capacity with and including 20mm dia ball valves, high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe minimum weight 210 gram complete all as specified and directed.
25Supply and fixing in repair ball brass valve high pressure with polyethene float and fly nut complete screwed for iron pipe of size 25 mm complete all as specified and directed .
26Supply and fixing in repair ball brass valve high pressure with polyethene float and fly nut completescrewed for iron pipe of size 20 mm complete all as specified and directed .
27Material and labour for insulation of hot water tank of cap1000/1500ltrs with thick ness of insulation 10 cm around the tank and aluminium sheet of size 24 SWG complete all as specifide and directed . Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
28Material and labour for insulation of hot water tank of cap200 /500 ltrs with thick ness of insulation 10 cm around the tank and aluminium sheet of size 24 SWG complete all as specifide and directed . Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
29Supply and fixing in replacementhot water tank of cap1000/1500ltrs with thick ness of insulation 10 cm around the tank and aluminium sheet of size 24 SWGas per existing sample including make up tank & connection with existing pipe line complete all as specified and directed . Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
30Supply and fixing in replacementhot water tank of cap200 ltrs with thick ness of insulation 10 cmaround the tank and aluminium sheet of size 24 SWGas per existing sample including make up tank & connection with existing pipe line complete all as specifide and directed . Note:- The quoted rate shall include the cost of cutting &refixing of monkey cagingas required at site . Nothing extra shall be admissible on this acconut.
31Material and labour for connecting & testing of CI air release valve 25mm size ISI markedflanged type including jointing material such as fibre board , nut , bolt, washers and welding etc complete all as specified and directed.
32Material and labour for connecting & testing of CI air release valve 20mm size ISI markedflanged type includingjointing material such as fibre board , nut , bolt, washers and welding etc complete all as specified and directed.
33Material and labour for connecting & testing of CI air release valve 15mm size ISI marked flanged type including jointing material such as fibre board , nut , bolt, washers and welding etc complete all as specified and directed.
34Taking out old unserviceablegun metal, globe orgate valveandincluding Supply and fixinggun metal, globe or gate valves ISI marked class-I, with iron wheel head, screwed both ends, for iron pipe bore dia of pipe 25mm complete all as specified and directed.
35All as per item No 34 here in before butbore dia of pipe 20 mm
36All as per item No 34 here in before butbore dia of pipe 15 mm
37Supply and fixing of sheet metal enclosure for DB’s (Double door type) when MCB’s to be used, single pole and neutral, 8 ways with 200 Amp rated bus bar, 240 volts including blanking plates fixed sunk / flush to the wall or niche complete all as specified and directed.
38Supply & Fixingin repair 240 V, 10 KA "B" curve miniature circiut breaker ( MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB complete with connection testing and commissioning complete all as specified and directed.
39Supply & Fixingin repair 240 V, 10 KA "B" curve miniature circiut breaker ( MCB) of single polesneutral ( SPN) andcurrent carrying capacity 32 AMP, in the MCB DB complete with connection testing and commissioning complete all as specified and directed.
40Supply & Fixingservice connection cable, 1100 volts grade heavy duty PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mmsuspensionwire, one twin core cable flat or circular, 10sqmm multi stranded aluminium conductor complete all as specified and directed.
41Supply andfixingexpanded metal weightnot exc 4 kg per square metre, cut to lengthbent to shape required and tying with and including annealed mild steel wire not less than 0.9mm dia or fixing with galvanised steel staples and fixed to wood or steel member complete all as specified and directed
42Supply & Fixingframed work such as in grill,grating etc with ends of bars shouldered and/or rebated,or forged into spike frame guard bars,wake way,railing,frame work of water tank and similar work such as purlin, truss, square tube etc confirming to Fe-290-w (Gde 165) complete all as specified and directed.
43Material & Labour forpreparation of new or previously untreated steel and iron surfaces of any description, over 10 cm width or girth, not otherwise described and applying two coats of synthetic enamel paint (ordinary tint) over a coat of red oxideprimer, complete all as specified and directed.
44Material and labour for complete cleaning and descaling of heat exchanger installed at swimming pool using very mild mineral acid including complete opening and reassembling the same and testing for its proper functioning all as specified and directed by Engineer-in-charge.
45Disconnecting/ Taking outof old non return valve, including supply & fixing brassnon return valve of size 20 mm bore with and including nut, bolts & washerscomplete all as specified and as directed.
46Disconnecting/ Taking outof old non return valve, including supply & fixing brassnon return valve of size 15 mm bore with and including nut, bolts & washerscomplete all as specified and as directed.
47M & L for opening of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR) water cooled by unscrewing nuts, bolts and servicing of DG set with checking of oil, coolant, V belt, greasing and oiling of parts and topping up, cleaning the inner body, tank and radiator by removing sludge, repair/ replacement of stopper key etc and reassembling the DG set after repair/ replacement of unserviceable parts of DG set and testing at Ranikhet & Nagpani complete all as specified and directed. (NOTE :- Any major defective part which are required to be replaced to make the DG set functional shall be measured and paid seperately under respective items
48Supply & Fixingfuel filter of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
49Supply & Fixing lube oil filter of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
50Supply & Fixing air filter of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
51Supply & Fixing copper washer of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
52Supply & Fixingbanjo bolt of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
53S & F fuel pipe of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
54S & F hose water pipe for radiator of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
55S & F warm drive H / clip of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
56S & F V – belt of DG set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)complete all as specified and directed.
57S & F asbestos rope of size 20mm dia on exhaust pipe of DG set 180 KVA (existing make CUMMINS)complete all as specified and directed.
58S & F PVC superior quality coolant side box for 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR)DG set complete all as specified and directed.
59M & L for opening of DG set 45/50/63/62.5 KVA water cooled of existing Make KRILOSKAR by unscrewing nuts, bolts and servicing of DG set with checking of oil, coolant, V belt, greasing and oiling of parts and topping up, cleaning the inner body, tank and radiator by removing sludge etc and reassembling the DG set after repair/ replacement of unserviceable parts of DG set and testing complete all as specified and directed. Note:- Any major defective part which are required to be replaced to make the DG set functional shall be measured and paid seperately under respective items
60S & F fuel filter of DG set 45/50/63/62.5 KVA complete all as specified and directed.
61S & F lube oil filter of DG set 45/50/63/62.5 KVA complete all as specified and directed.
62S & F air filter of DG set 45/50/63/62.5 KVA complete all as specified and directed.
63S & F copper washer of DG set 45/50/63/62.5 KVA complete all as specified and directed.
64S & F banjo bolt of DG set 45/50/63/62.5 KVA complete all as specified and directed.
65S & F fuel pipe of DG set 45/50/63/62.5 KVA complete all as specified and directed.
66S & F hose water pipe for radiator of DG set 45/50/6362.5 KVA complete all as specified and directed.
67S & F warm drive H / clip of DG set 45/50/63/62.5 KVA complete all as specified and directed.
68S & F V – belt of DG set 45/50/63/62.5 KVA complete all as specified and directed.
69S & F fuel pump for 45/50/62.5/63KVA DG as per sample complete all as specified and directed.
70M & L for opening of DG set 15 KVA water cooled of existing Make KIRLOSKAR by unscrewing nuts, bolts and servicing of DG set with checking of oil, coolant, V belt, greasing and oiling of parts and topping up, cleaning the inner body, tank and radiator by removing sludge etc and reassembling the DG set after repair/ replacement of unserviceable parts of DG set and testing complete all as specified and directed. NOTE :- Any major defective part which are required to be replaced to make the DG set functional shall be measured and paid seperately under respective items
71S & F fuel filter of DG set 15 KVA complete all as specified and directed.
72S & F lube oil filter of DG set 15 KVA complete all as specified and directed.
73S & F air filter of DG set 15 KVA complete all as specified and directed.
74S & F copper washer of DG set 15 KVA complete all as specified and directed.
75S & F banjo bolt of DG set 15 KVA complete all as specified and directed.
76S & F hose water pipe for radiator of DG set 15 KVA complete all as specified and directed.
77S & F warm drive H / clip of DG set 15 KVA complete all as specified and directed.
78S & F V – belt of DG set 15 KVA complete all as specified and directed.
79M & L for opening of DG set 7.5/10 KVA water cooled of existing Make : KIRLOSKAR by unscrewing nuts, bolts and servicing of DG set with checking of oil, coolant, V belt, greasing and oiling of parts and topping up, cleaning the inner body, tank and radiator by removing sludge etc and reassembling the DG set after repair/ replacement of unserviceable parts of DG set and testing complete all as specified and directed. NOTE :- Any major defective part which are required to be replaced to make the DG set functional shall be measured and paid seperately under respective items
80S & F fuel filter of DG set 7.5 /10KVA complete all as specified and directed.
81S & F lube oil filter of DG set 7.5/10 KVA complete all as specified and directed.
82S & F air filter of DG set 7.5 /10KVA complete all as specified and directed.
83S & F copper washer of DG set 7.5/10KVA complete all as specified and directed.
84S & F banjo bolt of DG set 7.5/10 KVA complete all as specified and directed.
85S & F hose water pipe for radiator of DG set 7.5/10 KVA complete all as specified and directed.
86S & F warm drive H / clip of DG set 7.5/10 KVA complete all as specified and directed.
87S & F V – belt of DG set 7.5/10 KVA complete all as specified and directed.
88Supply and filling coolant in 05 (Five)litre packing, Make :Servo / CRB Plus/HP complete all as specified and directed.
89Supply and filling distilled water 05 (Five) litre packing complete all as specified and directed.
90Supply & filling engine oil of recommended grade 15W40, Make: Servo / CRB Plus/HP complete all as specified and directed.
91S & F lead acid battery 12 Volt 150 AH for DG set, Make:Exide Xp / Amaron / Luminous including taking out old unserviceable battery complete all as specified and directed.
92S & F lead acid battery 12 Volt 180 AH for DG set, Make:Exide Xp / Amaron / Luminous including taking out old unserviceable battery complete all as specified and directed.
93S & F battery terminal brass complete with GI nuts & bolts including taking out old unserviceable battery terminal brass complete all as specified and directed.
94S & F battery lead wire as per existing size and length, flexible copper conductor single core including taking out old unserviceable battery lead wire complete all as specified and directed.
95Repair to self starter assembly of DG set of cap 45/50/63/62.5 KVA by cutting of old burnt winding wire and winding with new copper winding wire as per existing size / gauge including insulation materials, varnishing, heating / drying up etc complete all as specified and directed.
96Supply and fix self starter assembly completeof DG set of cap 45/50/62.5/63 KVA by taking outof old burnt self starteras per existing size / gaugeetc complete all as specified and directed.
97Supply and fixing rotary hand pump for filling of fuel from barrel to DG set tank with PVC pipe of size 20 mm dia sureior quality of lenght ten mtrcomplete all as specified and directed.
98M&L for repair of DG Set 180 KVA (existing make CUMMINS) / 125 KVA (existing make KIRLOSKAR), Opening of cylender head, FIP, self start assembly, cleaning all the parts of engine and chamber by Kerosin oil, removing connecting rod,crank shaft, removing all the piston rings from piston and replacing of piston ring, connecting rod bush of all pistonof existing size and shape replacing all engine valve, replacing cylinder head, over hauling of caliber of FIP as per required including the nozzel, replacing all the gasket including cylinder head gasket as required, ofgenerator set 180/125 KVAcleaning , checking and adjusting of aneroid oil, throttle linkage, fuel tank breather, crankcase breather, air piping, oil bath air cleaner tray screen and belt including replacing of engine oil, full flow oil filter , by pass filter air compressor breather element, fuel filter primary and secondary, cleaning of radiators, repair/ replacement of unserviceable injector 6 Nos, change of valve and kit in head of DG Set etc all as specified and directed by the Engr-in-charge.
99M&L for repair of DG Set 62.5/63 KVA of existing Make KIRLOSKAR, Opening of cylender head, FIP, self start assy, cleaning all the parts of engine and chamber by Kerosin oil, removing connecting rod,crank shaft, removing all the piston rings from piston and replacing of piston ring, connecting rod bush of all pistonof existing size and shape replacing all engine valve, replacing cylinder head, over hauling of caliber of FIP as per required including the nozzel, replacing all the gasket including cylinder head gasket as required, ofgenerator set 62.5/63 KVAcleaning , checking and adjusting of aneroid oil, throttle linkage, fuel tank breather, crankcase breather, air piping, oil bath air cleaner tray screen and belt including replacing of engine oil, full flow oil filter , by pass filter air compressor breather element, fuel filter primary and secondary etc all as specified and directed by the Engr-in-charge.
100S & F in repairs of control pannel inside DG set of 45/50/62.5/63 KVA, replacement of unserviceable MCBs, indicators, start stop buttons, sensors, wiring with suitable size cable and checking entire circuit complete all as specified and directed.
101M&L for earthing complete with galvanised steel,earth plate electrode 600x600mm x 6mm thick burried directly in ground verticaly (earth pit not less than 2.25 mtrs belowground level ) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanised strip 32x6mm as earth leadby means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electrical plate No 3 on page 497 of MES schedule 2009 part - I connected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in hard/dense soil, common salt and charcoal dust mixed and packed 150mm thick all round the GI earth plate, watering pipe 20mm dia GI medium grade. GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150c/c both ways and pit/chamber in PCC 1:3:6 type C1 with suitable lifting handleto cover, GI protection pipe 15mm dia light grade up to 7.5mtr from electrode GI pipe to be fixed with complete all as specified and directed. Note :- (i) Earth lead beyond 7.5 mtr from electrode to earth terminal point/main switch & GI pipe light grade 15mm dia for protection against mechanical damage to lead shall be measured separately. (ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone by the contractor at his own expensis and no extra payment on this account shall be made by the Govt.
102Supply and fixaluminium lugs of size 300 sqmm complete all as specifide and directed .
103Supply and fixaluminium lugs of size 240 sqmm complete all as specifide and directed .
104Supply and fixaluminium lugs of size 185 sqmm complete all as specifide and directed .
105Supply and fixaluminium lugs of size 150sqmm complete all as specifide and directed .
106Supply and fix changeover switch AC 23 side handle 4 pole , 415 Volt 40Amp complete all as specifide and directed .
107Supply and fix changeover switch AC 23 side handle 4 pole , 415 Volt 63Amp complete all as specifide and directed .
108Supply and fix changeover switch AC 23 side handle 4 pole , 415 Volt 100 Amp complete all as specifide and directed .
109Supply and fix changeover switch AC 21 side handle 4 pole , 415 Volt 200 Amp complete all as specifide and directed .
110Supply and fix changeover switch AC 21 side handle 4 pole , 415 Volt 320 Amp complete all as specifide and directed .
111Replacement of MCCB of Cap 100 Amp, 4 Pole, 25 KA, with adjustable thermal release and earth fault protection, 415 volt gradeincluding cutting and welding work for fixing of MCCB in existing panels any type and model complete all as specifide and directed .
112All as per item No. 112 above butCap 200 Amp, 36 KA.
113All as per item No. 112 above butCap 350 Amp, 36 KA.
114Supply, laying, jointing and commissioning 120 Sqmm, 3.5 core LT XLPE 1100 volts grade heavy duty cable PVC insulated, multi stranded aluminium conductor served with inner sheathing of PVC tape, armoured with GI steel or tape and over all PVC sheathing laid in trenches, floor through pipes or induct or on poleand roads etc complete all as specifide and directed .
115All as per item No. 114 above butof size 95 Sqmm, 3.5 core.
116All as per item No. 114 above butof size 70 Sqmm, 3.5 core.
117Excavation in trenches in hard/dense soil not exc 1.5 mtrs wide and not exc 1.5 m in depth for laying cables and getting out incl jointing bottom surface to the reqd level/slope etc complete all as specified and directed.
118Returning fillingin, incl spreading, leveling, watering and well ramming in layers notexc 25 cm in hard/dense soil complete all as specified and directed.
119Removing excavated material (soil) to a distance not exc 50 mtr and deposting where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
120M&L for laying of fine river sand, free from sharp material for cable cushioning in trenches all as specified and directed. Note: Punned thickness of sand shall be measured and paid
121Material and labour for brick protection to cable using old size class "B" bricks, laid flat, dry butt jointed, laid lengthwise perpendicular to the axis of cable complete all as specified and directed.
122M&L for 80 mm bore GI pipe light grade with all GI fittings fixed to pole and laid to floor/ground for mechanicalprotection of cable complete all as specified and directed.
123M&L for 50 mm bore GI pipe light grade with all GI fittings fixed to pole and laid to floor/ground for mechanicalprotection of cable complete all as specified and directed.
124Supply and fixing ignition transformer for the oil fired chamber as per sample, incoming voltage 230 volts and outgoing voltage 14500 voltss installed at MH Ranikhet complete all as specified and directed.
125.Supply and fixing Solenoid valve as per existing Cat part No. 8510113200 for oil fired incinerator of Make Thermex, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
126Supply and fixing Burner nozzle 2.5 GPH 80 degree PY - 75/100 as per existing Cat part No. 8904111400 for oil fired incinerator of Make Thermex, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
127Supply and fixing Diffuser plate assembly for MI as per existing Cat part No. 1061602630 for oil fired incinerator of Make Thermex, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
128Supply and fixing Photo cell type - 8205 as per existing Cat part No. 8603111400 for oil fired incinerator of Make Thermex, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
129Supply and fixing Pressure gauge Cat 0 - 40 Kg/cm 1/2 BSP as per existing Cat part No. 8451114100for oil fired incinerator of Make Thermex, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
130Supply and fixing Metalic hose 40 Kg / cm as per existing Cat part No. 8911104000 for oil fired incinerator of Make Thermex, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
131Supply and fixing electrode for oil fired incinerator, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
132Supply and fixing glass wool for oil fired incinerator, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
133Supply and fixing filter assembly for oil fired incinerator, capacity 50 Kg / hours installed at MHRanikhet complete all as specified and directed.
134Supply & Fix in replacement smoke and waste discharge/ exhaust assembly to Chimney of incinerator complete including IED Fan as per existing size, fan chamber and GI Pipe (150mm) & flange with necessary cutting and welding work so as to fit the existing system and matching the disturbed surface with the existingsurface all as specified and directed.
135Supply and fixing in repair the chimney top mounted indication/signal lamp with red light for emergency signal as per existing size and complete testing after installation complete all as specified and directed.
136S & F in repair water tubingmedium grade galvanised with all GI fittings (such as bend,elbows,tees, connections, short pieces, back, nuts, unions, caps & plugs, reducer etc) of size 20 mm bore laid in trenches or fixed on walls or on open surfaces complete all as specified and directed.
137M & L for complete cleaning of sludge collection chamber/reservoir of incinerator incl cleaning of inlet and outlet and treatment with chemicalon base to make the sludge flow obstruction free and painting the reservoir/chamber all as directed and specified by Engineer-in-charge.
138Supply & Fixing in replacement LED solar street light fitting 24 watt including galvanised steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor and testing after installationall as specified and directed.
139M&L for PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) as in foundation filling & mass concrete including use of form work and finishing all exposed faces of concrete fair and even complete all as specified and directed
140Overhauling & servicing ofRefrigerator any capacity and make by carrying out the following works at different location of different establishment complete all as specified and directed by Engineer-in-charge (a) Inspection, taking down opening & dismantling descaling brushing cleaning of refrigerator (b) Check and correct earth continuity of electrical items (c) Check thermostate and test its functioning (d) Check & correct all electrical wiring and its functioning (e) Testing of Refrigerator after repairs (f) Replacing defective spare parts
141Petty repair complaints for Refrigerator of any capacity and make installing in site of Ranikhet & chaubattia and rectifying the complaints from 0900 hrs to 1700 hrs incl Sunday & Holidays complete all as specified and as directed by Engineer-in-charge. Note : Any defective part which are required to be replaced to make functional refrigrator shall be measured and paid separately under respective item
142S&F in replacement to unserviceable Vegetale tray as per existing make & capacity
143S&F in replacement to unserviceable Thermostate switch as per existing make & capacity
144S&F in replacement to unserviceable Starting relay as per existing make & capacity
145S&F in replacement to unserviceable electronic timer unit as per existing make & capacity
146S&F in replacement to fused Bulb as per existing
147S&F in replacement to unserviceable capillary & filter as per existing
148S&F in replacement to unserviceable Freezer tray as per existing
149S&F the refrigerant gas to Refrigerator up to required level after detecting & repairing leakage improvement of efficiency testing complete all as specified and directed
150S&F in replacment of condensor coil of refrigerator as per existing incl brazing of all associated pipe lines complete all as specified and directed
151S&F in replacement new compressor for refrigerator of capacity 165 to 320 ltrs as per existing make & model including brazing work pressure testing dehydration complete all as specified and directed
152S&F in replacement of unserviceable fan unit of refrigerator and providing electrical connection as per existing make & model complete all as specified and directed
153Overhauling and servicing of split type AC of capacity 1.5/2.0 TR of any make at different locations of different establishment, testing the unit complete with the following :- (a) Overhauling & servicing (b) Inspection opening washing the condensor coil and cooling coil with chemical followed with water complete (c) Inspection of leakage of refrigerant in the system (d) Checking the operation of blower motor condensor motor for noise free operations (e) Oiling of condensor / blower motors and checking the earth continuity (f) Inspection all electrical parts / connections and removing if any defect (g) Checking the functional of electronic remote control complete all as specified and as directed
154Petty repairs complaints for split type AC of capacity 1.5 / 2.0 TR, rectifying the defects and making machine satisfactory functional. Note : Any defective part which are required to be replaced to make functional split type ACs shall be measured and paid separately under respective items.
155S&F in replacement of unserviceable starting relay of Split typein lieu of providing new starting relay all as per existing.
156S&F in replacement of unserviceable starting capacitor 120-150 mfd
157S&F in replacement of unserviceable starting capacitor 100-120 mfd
158S&F in replacement of unserviceable contactor as per existing
159S&F in replacement of unserviceable propeller fan for split type AC of capacity 1.5 / 2.0 TR as per existing all as specified and directed
160S&F in replacement of unserviceable but new condensor fan motor of any type of split type ACs of capacity 1.5 /2.0 TR
161S&F in replacement of unserviceable blower motor for split type AC 1.5 / 2.0 TR as per existing
162S&F in replacement of unserviceable blower for split type AC 1.5 / 2.0 TR as per existing
163S&F in replacement of unserviceable 3 core flexible copper cable of size 70/0.0076 complete all as specified and as directed by Engineer-in-charge
164S&F in replacement of unserviceable 3 core flexible copper cable of size 80/0.0020 complete all as specified and as directed by Engineer-in-charge
165S&F in replacement new compressor for split type AC of capacity 1.5 TR as per existing including brazing work extra copper tubing pressure testing dehydration complete all as specified and directed
166M&L for rewinding of condensor fan motor for split type AC including replacement of gun metal bushes, testing complete all as specified and as directed
167M&L for rewinding of blower motor for split type AC including replacement of gun metal bushes, testing complete all as specified and as directed
168S&F in repair sheet metal enclosure single pole and neutral with a two pin and earth plug and socket complete with one single pole MCB 240 Volts 20 Amps complete all as specified and directed.
169M&L for Gas charging R-22/R-410/407/410 at site as per requirement of ACs any capacity including removal and replacement copper tubing of required size of liquid filter, capillary including testing on full load for summer season complete all as specified and as directed.