Tender For Increasing Capacity Of 33/11Kv S/S Dahgwa From 10+5 Mva To 2X10 Mva In District Badaun., badaun-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Tender For Increasing Capacity Of 33/11Kv S/S Dahgwa From 10+5 Mva To 2X10 Mva In District Badaun.. Submission Date for this Tender is 10-11-2023. Substation Tenders in badaun Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

40518047
Tender For Increasing Capacity Of 33/11Kv S/S Dahgwa From 10+5 Mva To 2X10 Mva In District Badaun.
Open Tender
Indian
Uttar Pradesh
badaun
10-11-2023

Tender Details

Tender For Increasing Capacity Of 33 / 11Kv S / S Dahgwa From 10+5 Mva To 2X10 Mva In District Badaun.; 1 Loading, Unloading And Safe Carriage Of The Following Materials From Any Electy. Store Center Of Electricity Store Division Of Bareilly Zone. 2 M.S. Channel 125X65mm 3 M.S.Angle 75X75x8mm 4 Control Pannel I / C For 33 Kv Single Feeder 5 33 Kv O / D Ct Ctr 400 / 200 / 1 6 11 Kv 3X300 Mm2 Xlpe Cable 7 11 Kv Cable Jointing Kit 3X300 Mm2 I / D 8 11 Kv Cable Jointing Kit 3X300 Mm2 O / D 9 Earthing Of Indoor & Outdoor Equipments Of Sub-Station After Proper Welding Of Joints And Painting Of Earth Strip Above Soil With Proper Clamp Etc. As Per Respo Approved Drawing & Resistance Of Earthing Should Be Not More Than 2O As Per Details Given Below. 10 Making Of Triangular Bridge By Using Ms Electrode, Gi Strip 50X6mm And Gi Pipe 40 Mm Dia With Providing Of Well Type Pipe Earthing Upto 15 Mtr. Depth Below Ground Level Including Welding Etc. By Boaring Process At T / F Neutral, La And Newly Erected Structure Including Cost Of Gi Pipe Of Size 40 Mm Dia 15 Mtr. Long Of Isi Mark. ( All The Required Material Will Be Supllied By The Contractor ) . 11 Supply Of Gi Strip Of Size 50X6mm For Earthing Of All Newly Erected Structures And Equipments In Switchyard Including Cutting, Fixing & Proper Welding With Equipments. All La Will Be Seprately Earth Also As Per Respo Norms. ( All The Required Materials Will Be Provided By Firm. ) 12 Fabrication, Erection And Grouting Of The Following Structures As Per Resspo / Approved Drawing And Its, Plinth 30Cm Above Ground Leval As Directed By The Engineer Incharge ( All Steel Sections Will Be Provided By Deptt ) . 13 Fuse Set Structure 14 Installation Of Followig Equipments On Their Respective Structures Including Mechanical & Electrical Fixing After Proper Adjustment On Their Structure. 15 33 Kv Ct 16 33 Kv Fuse Set 17 Dismantling Of Existing Following Damage Equipments On Their Structure. 18 33 Kv Fuse Set 19 33 Kv Ct 20 Complete Laying And Termination Of Copper Control Cables From 10 Mva Power T / F, 33 Kv Vcb, 33 Kv Ct In The Out Door Switch Yard To The Existing Transformer Relay Control Panel Inside The Control Room Including Cost Of All Materials And Labour Required For Proper Completion Of Works As Per Resspo Drawings, Including Cost Of Testing Of Transformer, Vcb, Ct, Relay Pannel & Proper Relay Settings As Per Requirement Etc. 21 Control Cable 4X2.5 Mm2 22 Control Cable 2X2.5 Mm2 23 Erection & Testing Of 1 No. 33 Kv Single Feeder Control Penel In Substation Control Room Including Grouting Of Anchor Bolts Of Panel And Making Of Pocket For Control Cable To Insert In Panel From Trench And Complete Filling Of Control RoomS Tranches By River Sand. 24 Repairing Of Existing 33Kv Vcb In Switchyard Including Repalcement Of All Required Accessories As Motor, Intrruptor Etc. All Type Of Material Should Be Provided By The Firm. 25 Laying Of 11Kv Cable Of Different Size From Power T / F To Control Room I / C . 11 Kv Cable Will Be Layed In Brick Trench Constructed Below 750Mm To The Ground Level Over The Ganga Sand. Brick Trench Will Be Constructed By Ist Class Bricks Covering Three Sides Of Cable, After Laying 11 Kv Cable Brick Trench Will Be Filed By Ganga Sand & Then Will Be Covered By Bricks & Backfill Of Soil Over Cable Trench As Per Respo Norms. 26 Termination Of 33 Kv 3X300sqmm Size Xlpe Cable By Filling 33 Kv Heat Shrinkable Type Cable Boxes Including Hoisting Of Cable And Proper Connection Withbus Bar Gantry And Bus Isolatorby Providing Suitable Connectors. 27 Painting Of The Fabicated Structures With One Coat Of Red Oxide Primer And Two Coats Of Synthetic Enamel Alumm. Paint / Green Paint Of Isi Mark Alongwith Earthing Strip Above Ground Level. 28 Safely Shifting And Dragging Of 33 / 11 Kv 5 Mva Transformer From Its Plinth To Safe Site At Sub-Station. Including Its Proper Disconnecting Of Ht, Lt Side Connection, Neutral , Body Earthing Etc. 29 Shifting And Dragging Of 33 / 11 Kv 10 Mva Transformer From Road Side To Its Plinth Alongwith Its Erection Including Fixing Of All Assessories And Top-Up Of T / F Oil. 30 Carriage Of Old Scrap Material From Site To Store Center Badaun 31 Complete Repairnig Of Swichyard Fencing.

Key Value

Document Fees
INR 1180 /-
EMD
INR 3900.0 /-
Tender Value
INR 3.90 Lakhs /-

BOQ Items

Name of Work: INCREASING CAPACITY OF 33/11KV S/S DAHGWA FROM 10+5 MVA TO 2X10 MVA IN DISTRICT BADAUN
Sl. No. Item Description
1Loading, unloading and safe carriage of the following materials from any Electy. Store Center of Electricity store division of Bareilly zone.
2M.S. Channel 125x65mm
3M.S.Angle 75x75x8mm
4Control pannel I/C for 33 KV Single feeder
533 kv O/D CT CTR 400/200/1
611 KV 3x300 mm2 XLPE Cable
711 KV Cable jointing Kit 3x300 mm2 I/D
811 KV Cable jointing Kit 3x300 mm2 O/D
9Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2O as per details given below.
10Making of triangular bridge by using MS electrode, GI strip 50x6mm and GI Pipe 40 mm dia with providing of well type pipe earthing upto 15 Mtr. depth below ground level including welding etc. by boaring process at T/F neutral, LA and newly erected structure including cost of GI pipe of size 40 mm dia 15 mtr. long of ISI mark.(all the required material will be supllied by the contractor).
11Supply of GI strip of size 50x6mm for earthing of all newly erected structures and equipments in switchyard including cutting, fixing & proper welding with equipments. All LA will be seprately earth also as per RESPO norms. (All the required materials will be provided by firm.)
12Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing and its, plinth 30cm above ground leval as directed by the Engineer Incharge (All steel sections will be provided by Deptt).
13Fuse Set Structure
14Installation of followig equipments on their respective structures including mechanical & electrical fixing after proper adjustment on their structure.
1533 KV CT
1633 KV Fuse Set
17Dismantling of existing following damage equipments on their structure.
1833 KV Fuse set
1933 KV CT
20Complete laying and termination of copper control cables from 10 MVA power T/F, 33 KV VCB, 33 KV CT in the out door switch yard to the existing transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings, including cost of testing of transformer, VCB, CT, relay pannel & proper relay settings as per requirement etc.
21Control Cable 4x2.5 mm2
22Control Cable 2x2.5 mm2
23Erection & testing of 1 No. 33 KV single feeder Control penel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room"s tranches by river sand.
24Repairing of existing 33KV VCB in switchyard including repalcement of all required accessories as motor, intrruptor etc. All type of material should be provided by the firm.
25Laying of 11KV cable of different size from power T/F to control room I/C . 11 KV Cable will be layed in brick trench constructed below 750mm to the ground level over the ganga sand. brick trench will be constructed by Ist class bricks covering three sides of cable, after laying 11 KV Cable brick trench will be filed by Ganga sand & then will be covered by bricks & backfill of soil over cable trench as per RESPO norms.
26Termination of 33 KV 3x300sqmm size XLPE cable by filling 33 KV heat shrinkable type cable boxes including hoisting of cable and proper connection withbus bar gantry and bus isolatorby providing suitable connectors.
27Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
28Safely shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site at Sub-station. Including its proper disconnecting of HT, LT side connection, neutral , Body earthing etc.
29Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth alongwith its erection including fixing of all assessories and top-up of T/F oil.
30Carriage of old scrap material from site to store center Badaun
31Complete repairnig of swichyard fencing.
Disclaimer :