Tender For Repair Replacement Of Lt Cable And Maint Of External Lt Electric Supply Street Light Security Light And Solar Light And Comprehensive Maint Of Eot And Certain Works At Admin Area Cpe Tech Area Taku And Mes Camp Area Itarsi Under Ge Bhopal, itarsi-Madhya Pradesh

Military Engineer Services-MES has published Tender For Repair Replacement Of Lt Cable And Maint Of External Lt Electric Supply Street Light Security Light And Solar Light And Comprehensive Maint Of Eot And Certain Works At Admin Area Cpe Tech Area Taku And Mes Camp Area Itarsi Under Ge Bhopal. Submission Date for this Tender is 30-11-2023. Electrification Work Tenders in itarsi Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

40514581
Corrigendum : Tender For Repair Replacement Of Lt Cable And Maint Of External Lt Electric Supply Street Light Security Light And Solar Light And Comprehensive Maint Of Eot And Certain Works At Admin Area Cpe Tech Area Taku And Mes Camp Area Itarsi Under Ge Bhopal
Open Tender
Indian
Madhya Pradesh
itarsi
30-11-2023

Tender Details

Repair Replacement Of Lt Cable And Maint Of External Lt Electric Supply Street Light Security Light And Solar Light And Comprehensive Maint Of Eot And Certain Works At Admin Area Cpe Tech Area Taku And Mes Camp Area Itarsi Under Ge Bhopal

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 30-11-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 92000.0 /-
Tender Value
INR 46 Lakhs /-

BOQ Items

Name of Work : REPAIR/ REPLACEMENT OF LT CABLE AND MAINT OF EXTERNAL LT ELECTRIC SUPPLY AND REPAIR AND REPLACEMENT OF STREET LIGHT, SECURITY LIGHT AND SOLAR LIGHT AND COMPREHENSIVE MAINT OF EOT AND CHAIN PULLY CRANE, ELECTRICALLY OPERATED GATE, DG SETS AT ADMIN AREA CPE, TECH AREA TAKU AND MES CAMP AREA, ITARSI UNDER GE (M) BHOPAL
Sl. No. Item Description
1Note :(i) Please refer Sch A/ BOQ Notes before quoting the tender for all phases/ items mentioned below. (ii) Amount of Schedule of credit shall be deducted offline
2Excavation in trenches in soft/loose soiln.exc 1.5 m wide and n.exc 1.5 m in depth and getting out for foundation of pole, laying under ground cables etc and getting out complete all as specified and directed.
3Excavation in trenches in soft/disintegrated soil exceeding 1.5 mtr wide and n.exe 3 mtr depth including getting out complete all as specified and directed.
4Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 cm in soil complete all as specified and directed.
5Removing of excavated soil to a distance n.exc 50m and deposited at a level n.exc 1.5m above the starting point complete all as specified and directed.
6M&L for river washed and screened dry sand for filling in trenches below and around the cable for cushioning including punning down as specified in relevant clause of SSR Part I complete all as specified and directed. Note: Punned thickness shall only be measured for payment.
7Supplying and laying class LV, type I, flat, size 250mm x 150mm x 40mm for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed.
8M&L for cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) in foundations, filling and mass concrete including filling at road cuttings or making pillars for supporting pipe including necessary form work complete all as specified and directed.
9M&L for cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed. including necessary form work complete all as specified and directed.
10Dismantling of LT insulator of any type any size complete all as specified and directed.
11M&L for shackle type, porcelain vitreous white or brown insulator (for LT) working pressure in 1100 volts including galvnised mild steel straps of size 31X 3 mm and 12 mm dia insulator bolts, washers and nuts etc including dismantling unserviceable insulator of any size complete all as specified and directed.
12M&L for pin type, insulator of size 100 mm height, 65 mm dia porcelain vitreous white or brown/green insulator (for LT) for working pressure in 1100 volts with one galvanised spindle and two galvanised iron washers and nut including dismantling unserviceable insulator of any size complete all as specified and directed.
13M&L for loop type insulator of size 60x90 mm, clearence of hole 16 mm porcelain vitreous white or brown/green insulator (for LT) for working pressure 1100 volts including dismantling of unserviceable insulator of any size complete all as specified and directed.
14M&L for errection in position including steel tubular swaged poles type 410 SP-31 (09.00 metres long) complete with cast iron base plate, final taper plug, bolts, nuts, screws and top cover all as specified and including the following:- (a) Excavation, PCC for foundation, returning filling and removing exevated shall be measured and paid seperately. (b) Painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block/concrete collar with two coat of aluminium paint over a coat of red oxide steel primer including preparation of surface including painting of 30cm wide blue bands 3 Nos. with synthetic enamel paint in alternate layer upto the height of 1.5m above plinth block. (c) M&L for writing letter or figures (Block, Roman, italic as Indian) with thick synthetic enamel paint of approved shade not exc height in numbering of pole all as directed.
15S&F in replacement of stay assembly comprising of galvanised iron stay bow of size 40 cm X14 cm, 20 mm dia and 1800 mm long GI stay rod including excavation, PCC, GI nuts mild steel stay plate 300 mm X 300 mm X 6 mm, 2 No thimble, 50X6 mm flat iron stay clamp, steel stay wire 16 mm dia bolts, nuts and washers etc including taking down unserviceablestay assembly of any size complete all as shown in electrical plate No 1 of MES SSR 1991 Part 1 all as specified and directed.
16Dismantling cross arms, bracings, supports, clamps and back plates from existing poles (other than dismantled poles) and pole structures complete all as specified and directed.
17Fixing only cross arms, bracing, supports, clamps and back plate, obtained from demolition with and including new nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
18M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers etc, welding, bending cold or hot,drilling holes for bolts, in any shape or size as directed and inclusive of applying one priming coat and two coats of synthetic enamel paint/aluminium paint including taking down corroded items of any type and size all as specified and directed.
19S&F and stringing of OH electric ACSR conductor of any size fixing to insulator with necessary binding wire of suitable size including taking down unserviceable ACSR conductor of any type and sizecomplete all as specified and directed. Note:- (i) 3% extra will be added to the weight for sagging. (ii) Binding and jointing will not be considered for measurement and all the jumper shall be fixed with minimum 6 pg clamps and the quoted rate shall deemed to be include in the unit rate quoted.
20M&L for replacement of GI cradle guard hexagonal / rectangular with galvanised steel wire of 3.15 mm to 4 mm dia including taking down unserviceable GI craddle of any size and type complete all as specified and directed.
21S&F of galvanised steel continuous earth wire of size4.00 mm including taking down unserviceable GI earth wire of any size and type complete all as specified and directed.
22S&F of galvanised stay strand wire of size 7/ 4 mm including taking down unserviceable stay wireof any size and type complete all as specified and directed.
23Restringing of LT over head line conductor comprising of any size ACSR conductor / GI wire on existing pole after opening from insulator by taking out of binding wire and refixing the same with suitable size of binding wire upto permissible sag after restringing including cutting of tree branches and trimming of smaller branches of any size up to 2 metre each side of OH line which touch/ falling on the OH line without damaging of 4 wire (3 phase and neutral) span exc 25.00m but n. exc 35.00m complete all as specified and directed.
24All as per Sl. item No. 22.00 here-in-before but 6 wire (3 phase, neutral and street light) span exc 25.00m but n. exc 35.00m.
25M&L for GI tubing, light grade, 50mm dia with all necessary fittings, laid in trenches, under floor/road crossing, fixed on poles for cable protection fixed with the clamps made out of FI 25 x 3mm duly painted with two coats of aluminium paint over a coat of approved primer etc. including taking down old unserviceable any size and capacity of GI pipe complete all as specified and directed.
26M&L for GI tubing, light grade, 80mm dia with all necessary fittings, laid in trenches, under floor/road crossing, fixed on poles for cable protection fixed with the clamps made out of FI 25 x 3mm duly painted with two coats of aluminium paint over a coat of approved primer etc. including taking down old unserviceable any size and capacity of GI pipe complete all as specified and directed.
27M&L for PVC line spacer for LT over head line complete all as specified and directed. Note- Required T&P will be arranged by contractor no extra cost shall be paid.
28M&L for replacement of GI cradle guard hexagonal / rectangular with galvanised steel wire of 3.15mm to 4 mm dia including taking down unserviceable GI craddle of any size and type complete all as specified and directed.
29M&L for painting to steel tubular pole with aluminium enamel paint of 9.00 Mtr including cross arms, clamps any size and nuts, bolts etc with one coat of aluminium synthetic enamel paintincluding preparing the surfacesfree from finish particalsand making the smooth surface and numbering on pole with black ground such as pole number and source of supply, painting withradium paint around the pole at width of 10cm, similar three rounds from 1.5 m GL top on circumferance of polecomplete all as specified and directed.
30Cutting and trimming of trees and branches to clear the over head line in the arc of HT/LT over head line feeders and removal of the trimmed branches of trees complete all as specified and directed. Notes : 1. Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account what-so-ever. 2. The cutting / trimming of tree branches shall be done to atleast 2.00 metre radius of OH line. 3. The unit of measurement is "SPAN" i.e. distance covered between two poles.
31S&F in repairs on load change over switch 63 Amps 4 pole415 volts50 Hzwith SS enclosure including taking down unserviceable one complete all as specified and directed.
32S&F in repairs on load change over switch 100 Amps 4 pole415 volts50 Hz . with SS enclosure including taking down unserviceable one complete all as specified and directed.
33S&F of offload change over switch in sheet metal enclosure, heavy duty, 200 Amps, four pole, 415 Volts AC, 50 Hz with side handle including connectins complete all as specified and directed.
34S&F of off load change over switch in sheet metal enclosure, heavy duty, 320 Amps, four pole, 415 Volts AC, 50 Hz with side handle including connectins complete all as specified and directed.
35M&L for earth continuity conductor or main earthing lead of 32x6 mm galvanised iron strip buried in ground or fixed to wall complete all as specified and diirected.
36M&L for replacement of MCCB of follwoing sizes fixed with thermal & magnetic setting with extended terminals, replacemenr to LT panel/ Feeder piller box including connecting lugs with busbar and including mounting arrengments i.e. screws, bolt, nut, washers including taking out old unserviceable complete all as specified and directed. Make-Legrand/Siemens/Schneider
37(a) 400 Amp, 4 pole, 415 volts, adjustable type with breaking capacity 36 KA
38(b) 350 Amp, 4 pole, 415 volts, adjustable type with breaking capacity 36 KA
39(c) 200 Amp, 4 pole, 415 volts, adjustable type with breaking capacity 36 KA
40(d) 160 Amp, 4 pole, 415 volts, adjustable type with breaking capacity 36 KA
41(e) 100 Amp, 4 pole, 415 volts, adjustable type with breaking capacity 16 KA
42(f) 63 Amp, 4 pole, 415 volts, adjustable type with breaking capacity 16 KA
43Supply, laying, jointing with suitable thimble and cable gland, testing and commissioning or fixing in wall or passing through pipe, 1100 volts grade with XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor including making input and output connections with using suitable size of thimbles, lugs, and glands complete of following cross sectional area as under including taking down old unserviceable cable all as specified and directed.
44(a) 120 Sqmm 3.5 Core
45(b) 70 Sqmm 3.5 Core
46(c ) 50 Sqmm 3.5 Core
47(d) 35 Sqmm 3.5 Core
48(e) 25 Sqmm 3.5 Core
49(f) 16 Sqmm 4 Core
50(g) 16 Sqmm 2 Core
51(h) 10 Sqmm 2 Core
52S&F in replacement of 1100 volts grade heavy duty cable of size 10 SqmmPVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable flat or circular complete all as specified and directed.
53M&L in replacment of 1100 Volts grade, heavy duty cable, PVC insulated copper cable, served with inner sheathing of PVC tape and overall PVC sheathed for hight mast light connection cicrular of size 4 Sqmm three core cable round type stranded conductorincluding taking down old unserviceable complete all as specified and directed.
54M&L in replacment of 1100 Volts grade, heavy duty cable, PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed for street light connections cable flat or cicrular of size 6 Sqmm twin core cable stranded conductor including taking down old unserviceable complete all as specified and directed.
55Supplying, jointing, testing straight through jointing kit heat shrinkable, out door type, suitable for LT 1100 Volts grade cable of size 95 Sqmm to 120 Sqmm 3.5 core complete all as specified and directed.
56Supplying, jointing, testing straight through jointing kit heatshrinkable out door type, suitable for LT 1100 Volts grade cable of size 50 Sqmm to 70 Sqmm 3.5 core complete all as specified and directed.
57Supplying, jointing, testing straight through jointing kit heatshrinkable out door type, suitable for LT 1100 Volts grade cable of size 25 Sqmm to 35 Sqmm 3.5 core complete all as specified and directed.
58Supplying, jointing, testing end termination jointing kit heatshrinkable out door type, suitable for LT 1100 Volts grade cable of size 70 Sqmm to120 Sqmm 3.5 core complete all as specified and directed.
59Supplying, jointing, testing end termination jointing kit heatshrinkable out door type, suitable for LT1100 Volts grade cable of size 25 Sqmm to 50 Sqmm 3.5 core complete all as specified and directed.
60S&Fmild steel sliding locking door bolt of size not less then 12 mm dia, 250 mm length bolt, stove enameled black with bright boltwith staple plate on LT panel doors (forlocking of doors) with min six nuts, bolts and washersincluding drilling and fixing on site complete all as specified and directed.
61S&F of butt hinges, heavy weight, cold rolled, mild steel, 100mm size duly welded to doors of LT panel board, etc complete all as specified and directed.
62S&F in repairs LED indication lamps (RGY) (set of three) complete all as specified and directed.
63Cutting and trimming of trees and branches to clear the over head line in the arc of HT/LT over head line feeders and removal of the trimmed branches of trees complete all as specified and directed. Notes : 1. Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account whatsoever. 2. The cutting / trimming of tree branches shall be done min 2.00 metre radius of OH line. 3. The unit of measurement is "SPAN" i.e. distance covered between two poles.
64Supplying and spreading grass killer chemical all around to kill unwanted grass near or below the feeder panel and any E/M installation of cap 1 Litre bottle complete all as specified and directed.
65Cutting of bituminous road/PCC hard standing/road/floor for laying of GI pipe upto 80mm dia (trench not more than 0.3m x 0.3m) for passing of cable including making good the disturbed surfaces all as per existing complete all as specified and directed. Note:-GI pipe shall be measured & paid separately under relevant items of this schedule.
66M&L for servicing/repairing of APFCpanel, any type and size upto 150 KVAR for making them functional, removing and cleaning of dusts, checking control wiring and connections, replacement of any damaged control wire, checkingcapacitors, tightening of all electrical connections and hardware, checking of metering devices, relays, etc, replacement of defective unserviceable parts to make the panel fuly functional complete all as specified and directed. Note:- Spares required shall be paid separately as supply only.
67S&F in repairs and replacement of capacitor, metalized poly propylene heavy duty (MPPH), three phase, 415 volts and 50 Hz system for permissible non-linear load 15 % of 10 KVAR capacity to maintain power factor complete all as specified and directed.
68S&F in repairs and replacement of capacitor, metalized poly propylene heavy duty (MPPH) three phase, 415 volts and 50 Hz system for permissible non-linear load 15% of 15 KVA,R capacity to maintain power factor complete all as specified and directed.
69S&F of capacitor, metalized poly propylene heavy duty (MPPH), three phase, 415 volts and 50 Hz system for permissible non-linear load 15 % of 25 KVAR capacity to maintain power factor complete all as specified and directed.
70Supply, replacement, installation, testing and commissioning ofLT distribution control panel,Kiosk type, 415 Volt, 4 wire AC 50 Hz, factory made, out door type double door, both side opening, (frount and rear side) weather and vermin proofpanel, with canopy of panel having 06 inch outside the main box with both side having degree of protection IP-43& made out of CRCAfabricated out of sheet of 3.15 mm outer structure and 1.6mm for internal structure with duly powder coated, CPRI approved, factory made fabricated , 415 volts, with locking arrangement, powder coated mild steel angle iron base frame with legs of size 40 X 40 X 60mm and 60cm long grountedwith PCC 1:3:6 type C-1for foundation fillingwith platform 100 X 75 X 15 cm above ground level floor incuding cable entries with glandfor incoming and out going cable connection, aluminium bus bar 4 strip rating 400 amps, including colring with RYB & Black including letter writen of pattern and description as directed with supply and fixing the following accessories pre-wired and connected alongwith suitable cable gland, lugs etc. all as specified and directed including taking out of unserviceable existing LT panel board and consisting of following items in panel:- (i) Incoming - MCCB 350 Amp rating with thermal seting, 36 KA, 3 Pole-01 No. (ii) Change over switch (on load) - 250 Amps 4 Pole415 volts50 Hz -01 No (iii) Outgoing - MCCB 200 Amp with thermal seting,36 KA, 4 pole - 01 Nos (iv) MCCB 160 Amp, 36 KA, 4 Pole -01 Nos (v) MCCB 125 Amp,16 KA, 4 Pole- 02 Nos (vi) Digital Voltmeter & Ammeter with selector switches, ON and OFF push button, Indication lamps of 3 Nos for RYB - 01 Set (vii)MCB DP 40 Amps- 02 Nos (viii)Digital Ammeter (0-300) Amps withCTs 250/5 and selector switch, Voltmeter (0-500) Volts with selector switch, Indicating lampset (RYB) LED type.
71M&L for repair of earthing pit cover with fixing of funnel of required size in PCC 1:2:4 type B1 (using 20mm graded stone aggregate) and RCC cover with frame as shown in electrical plate No-03 of SSR Part-I 2020 complete all as specified and directed.
72M&L for earthing galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr depth below normal ground level) with top edge of earth not less than 1.5 mtr below normal ground level connected to and including galvanized steel strip 32 mm x 6 mm as earth lead upto equipment by means of steel bolts, nuts, check nuts and washers, test point made of GI strip 40x8mm, 10cm long PCC 1:2:4, type B-1 in pit with precast RCC 1:2:4 type B-1 in cover reinforced with XPM not less than 4 Kg per Sqm with 40mm bore GI light grade protection pipe, 20mm bore GI medium grade watering pipe with funnel including charcoal, dust, salt, all as shown in electric plate No 3 of SSR Part-I (2009) specifications, complete with necessary earth work in any type of soil, removal to a distance not exceeding 50 mtr including testing on completion and dismantling of existing earthing, complete all as specified and directed.
73Labour only for attending day to day complaints for repairing of street light, security light, post top lantern of any size/ wattage including tighting loose electric connection, carbon deposition and any other minor defacts required for its smooth functioning at Taku area CPE Itarshi by deputing skilled and qualified electrician alongwith helper at any time of the day as per requirement complete all as specified and directed. Note:- (i) Complaint shall be done within 24 hrs after intimation or receiving reciept of complain slip by JE/ AGE otherwise penalty of Rs 250.00 per day per complaint will be levied on contractor. (ii) Complaints will be reported on daily basis with complaint register. (iii) Other minor items such as insulating tape, screws, small pieces of electrical cables PVC insulated copper multistranded conductor of size 2.5 Sqmm three core upto length of 1.5 m etc as required to attend the complaintis included in quoted rates.
74S&F in repairs LED driver suitable for 45-60 Watt existing LED security/street lights of any make and model complete all as specified and directed.
75S&F in repairs LED driver suitable for 70-100 watt existing LED security/street lights of any make and model complete all as specified and directed.
76S&F in repairs LED driver suitable for 120-200 watt existing LED flood lightof any make and model complete all as specified and directed.
77S&F of integral LED street light fitting of 45 watt, lumen notless than 5000 or 110 lm per watt, auto start efficiency not less than 85 % impact residence not less than IK -08, as per IS-10322 comprising of high pressure die cast aluminum hosing, heat resistant enclosed with glass cover in frame, IP-66 degree protection suitable for high efficient moulded lens operating voltage should be 170 Volt to 230 volts complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto required length on pole, testing all as specified and directed.
78S&F of integral LED street light fitting of 60 watt, lumen notless than 9000 or 125lm per watt , auto start efficiency not less than 85 % impact residence not less than IK 08, as per IS 10322 comprising of high pressure die cast aluminum hosing, heat resistant enclosed with glass cover in frame, IP-66 degree protection suitable for high efficient moulded lens operating voltage should be 170 Volt to 230 Volts complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto require length on pole, testing all as specified and directed.
79S&F of integral LED street light fitting of 70/72 watt, lumen notless than 7500 or 125lm per watt, auto start efficiency not less than 85 % impact residence not less than IK 08, as per IS 10322 comprising of high pressure die cast aluminum hosing, heat resistant enclosed with glass cover in frame, IP-66 degree protection suitable for high efficient moulded lens operating voltage should be 170 Volt to 230 volts complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto require length on pole, testing all as specified and directed.
80S&F of integral LED street light fitting of 90 watt, lumen notless than 11300or 125lm per watt, auto start efficiency not less than 85 % impact residence not less than IK 08, as per IS 10322 comprising of high pressure die cast aluminum hosing, heat resistant enclosed with glass cover in frame, IP-66 degree protection suitable for high efficient moulded lens operating voltage should be 170 Volt to 230 Volts complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto required length on pole, testing all as specified and directed.
81S&F of integralLED flood light following 100 Watt, 230 V AC high efficiency as per IS- 16107, IP-66 degree of protection comprising of epoxy powder coated housing enclosed with glass cover in frame, with impact and corrosion resistant complete with driver and lamp complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto required length on pole, testing all as specified and directed.
82S&F of integralLED flood light following 120 watt, 230 V AC high efficiency as per IS- 16107, IP-66 degree of protection comprising of epoxy powder coated housing enclosed with glass cover in frame, with impact and corrosion resistant complete with driver and lamp complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto required length on pole, testing all as specified and directed.
83S&F of integral LED flood light following 150 watt, 230 V AC high efficiency as per IS- 16107, IP-66 degree of protection comprising of epoxy powder coated housing enclosed with glass cover in frame, with impact and corrosion resistant complete with driver and lamp complete with fixing arrangement, nuts, washers, bolts, clamps including electric connection with 2.5 Sqmm PVC aluminium stranded conductor 3 core upto required length on pole, testing all as specified and directed. Note for item no 62 to 68:- Contractor shall produced manufacture test certificate and warrenty card for repair/replacement for 3 Years.
84S&F in replacement for GFS polycarbonate thermoplastic oval shape weather proofjunction boxes IP-65, with internal embedded polyurethane material gasket, IK-09 as per IEC 60695-2-11 for street lightssize not less than 210 mmx155mmx102 mm with metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating of rating 32 Amps for three phase and neutral mounted with locking arrangementand fixed to the PCC/Steel Poles by means of suitable size of clamps with nut and boltsandincluding provn for fixing 01 nos of single pole MCBs 6-32 amps,10KAall as specified and directed.
85S&F in GI pipe 50 mm dia, medium grade, for mounting bracket bent to shape 1.75 meter length and fixing arrangement with two Nos of MS clamps set, nut, bolts, washers, and applying two coats of aluminium paints over one coat of zinc oxide primerincluding taking down old unserviceable complete all as specified and directed.
86S&F of aluminum lugs suitable for aluminum cable of size 16 Sqmm complete all as specified and directed.
87S&F of aluminum lugs suitable for aluminum cable of size 35 Sqmm complete all as specified and directed.
88S&F of aluminum lugs suitable for aluminum cable of size 50 Sqmm complete all as specified and directed.
89S&F of aluminum lugs suitable for aluminum cable of size 70 Sqmm complete all as specified and directed.
90S&F of aluminum lugs suitable for aluminum cable of size 95 Sqmm complete all as specified and directed.
91S&F of aluminum lugs suitable for aluminum cable of size 120 Sqmm complete all as specified and directed.
92S&F of timer switch (light sensor type nature switches), three phase plastic body degree of protection conforms to IP-54, operating illumination level for switching ON should be less than 60 lux for 30 seconds and for switching off must be greater than 10 lux for 30 seconds, multiple option switch for automatic and manual operations, capable to handle lightning load up to 8 KW, including MCB capacity 63 Amp conforms to IEC-60898 and IS-8828, power contactor capacity 40 Amp conforms to IEC 60947-4-1, IS 13947-4-1 completely enclosed with plastic body panel conforms to IP-54 degree of protection, after taking down the burned control gears and cleaning the existing mild steel panel board, duly painted with two coats of epoxy coloured spray paint including taking down the existing unserviceable timer switch of any capacity and removing the site complete all as specified and directed. Make : Model NoSWADEEP- 02EC8KW1P of Kakatiya Energy systems Pvt Ltd,or equivalent make in Havells/ Legrand / ABB / Schneider
93S&F in repairs synthetic rubber insulation mats for insulation for LT panels, transformer or DG Set of size 2mtr x1mtr x 2.5mm thick complete all as specified and directed. Make : Jyoti or equivalent make.
94M&L for MCB, SP 6 A -32 Amp, Curve C,240 V, 10 KA complete all as specified and directed.
95S&F in repairs contactor 25 Amp,3 Phase , 415 V, as per IS 13947-4-1, suitable for nature time switch model swadeep -02complete all as specified and directed.
96S&F in repairs contactor 16 Ampsingle Phase, 240 V, as per IS 13947-4-1, suitable for nature time switch model swadeep -02complete all as specified and directed.
97M&L for repairs of sensor of automatic street light control panel, single phase as per existing make on groundincluding testing for automatic functioning of street light on timer complete all as specified and directed.
98M&L for repairs of sensor of automatic street light control panel, threephase as per existing make on groundincluding testing for automatic functioning of street light on timer complete all as specified and directed.
99Dismantling and taking down solar light fitting of wattage 11 to 25watt comple with solar panel assembly, solar battery assembly, light controller, fixture mounting bracket for checking serviveablity, repair of solar lights and testing including minor repair and painting of pole with 2 coats of existing paint to make fully serviceable complete all as specified and directed.
100M&L for replacement of solar panel assembly with Light controller and MPPT charge controller suitable for 11 to 25 watt solar street light as per existing make including electric connection complete all as specified and directed.
101M&L for replacement of solar light assembly suitable for 11 to 25 watt solar street light as per existing makeincluding electric connection and GI bracket if required complete all as specified and directed.
102M&L for replacement of solar light lithium ferro phosphate battery suitable for 11 to 25 watt solar street light as per existing make including electric connection complete all as specified and directed.
103S&F of 12 volt battery Lead with thimbles
104S&F in replacement cable pvc insulated, sheathed of size 2.5 Sqmm three core stranded aluminium conductor complete all as specified and directed.
105M&L for maintenance freebattery 12 V 180 AHtubular type initial charged complete all as specified and directed. Make- Exide/Tata
106S&F of integral solar light 20 watt, highly efficient not less than 90 %, degree of protection IP-65 with built in high efficiency solar panel approved by MNRE, LED highly brightness high power light and long life lithium iron battery including BIS certified rechargeable cell with display showing for battery charging full charge, low voltage with different colour LED lamp with high efficiency microprocessor based charge controller and motion sensor. The has automatic dusk to down operation. The luminaire shall have specially designed pole mounting piece that enabled lateral as well as post top mounting and installation at varying tilts from 0 to 15 degree for optimal light distribution, including mounting pole of size 6 mtr long and earth, PCC work and electric cable for electric connection and any other parts for smooth functioning of solar lights testing complete all as specified and directed.
107Annual/comprehensive maintenance forpreventive and periodically maint including attending breakdown for electrically over head travelling crane (EOT crane) of capacity 5 Ton hand operated single girder make M/s Cranex Ltd located bldg No 211 of Bofors Shed at Tech area Taku. Servicing routine maint of longitutinal travel/cross travel/ assembly system and checking/ lubricating of gear pully/brake system for proper tightness, checking of housing pulley/hock and lubricaing there of, hoist steel wire rope for cut abberation, cleaning up all grease/clipping materials for its safe operation, checking functioning of limit switches, function of motor with cupling and bracks, functioning of control panel, checking and inspection all foundation structure, Load test of hooks, snatch and rope, checking level of gear boxoil. The following minor spare parts if reqd to be replaced i.e gasket, nuts, bolts, washer & Oiling/Greasing, etc, the contractor to apply two coat of painting for complete system and written onSM No, machine No, make, date of installation & capacity, the rates are deemed to be included in the quoted rate.All other remaining items to be checked if necessary to replace the worm out parts complete time to time for safe and satisfactory run of crane.Spares parts crane will be measured and paid seperatlyall as specified and directed. Note :-i) Contractor will carry out comprehensive maint once in a month in addition he will also attend to any type of break down on emergency basis as and when intimated byJE E/M or Engr-inCharge. ii)Contractor will ensure serviceability and safty of crane during his each visit by way of maintaining job card duly signed by JE E/M, in addition contractor will provide safety certificate once in entire contract period from a competent auth, i.e Safety Offr deputed by State Govt or Central Govt iii)Contractor to maintain records for replacement of spares parts. (iv) If contractor is failed to attend breakdown or complain with in 2 days from date of receipt of complain then a penalty will be imposed @350 Per day will be reocovered from next due RAR.
108All as per item No 92.00 here-in-before but hot crane 3 ton capacity bldg No 92 mortor shed at Tech area Taku of CPE Itarsi Make:- M/s Morris Engg Co Ltd.
109Annual/comprehensive maintenance for preventive and periodicallymaint including attending breakdownfor Electrically over head travelling crane (EOT Crane) of capacity7.5 ton capacity make M/s Vishal Cranex (P) Ltdlocated at Bofors Shed bldg No 211 at Tech area Taku. Preventive maint/servicing and routine maint of the following : longitutinal travel/cross travel for frequent reversing frequent acceleration as well as break, power panel, fuse switches for electric control system,limit switches for hoisting lowering trolley.and coupling unit travel track, base plate,Gear wheel/ housing assembly system. Checking/ lubricating servicing setting and testing of gear box assembly/braek pully system for proper tightness. Hoist steel wire rope for cut abberation, cleaning up all grease/clipping materials for its safe operation, setting right and replacement of damaged wiring of electrical system in PVC trolly cable outside cabin & main switches to control panel, inspect/checking, decarbonizing and tightening of electrical connection in total system, setting and tightening the same as per their capacity. Checking, functioning of limit switches, function of motor with cupling and bracks, functioning of control panel, checking and inspection all foundation structure. Load test of hooks, snatch and rope.Checking level of gear box oil.The following minor spare parts if reqd to be replaced i.e gasket, nuts, bolts, washer, & Oiling/Greasing etc, the contractor to applytwo coat of painting for complete system once in entire contract and written onSM No, Machine No, Make, Date of installation & capacity the rates are deemed to be includedin the quoted rate.All other remaining items to be checked if necessary to replace the worm out parts complete time to time for safe and satisfactory run of crane. Spares parts will be measured and paid seperatly. Note :- (i) Contractor will carry out comprehensive maint once in a month in addition he will also attend to any type of break down on emergency basis as and when intimated by JE E/M or Engr-in Charge. (ii)Contractor will ensure serviceability and safty of crane during his each visit by way of maintaining job card duly signed by JE E/M, in addition contractor will provide safety certificate once in entire contract period from a competent auth, i.e Safety Offr deputed by State Govt or Central Govt (iii)Contractor to maintain records for replacement of spares parts. (iv) If contractor is failed to attend breakdown or complain with in 2 days from date of receipt of complain then a penalty will be imposed @350 Per day will be reocovered from next due RAR.
110All as per item No 94.00 here-in-before but HOT/EOT hoist crane5 Ton capacity (02Nos) ofbldg No 61, Barrel shed& Eqpt store at Tech area Taku of CPE Itarsi Make M/s Morris SWL Safex.
111All as per item No 94.00 here-in-before but HOT/EOT hoist crane 3 Ton capacity (02Nos) of bldg No 64 Barrel cleaning shed bldg No 65, Gun shed at Tech area Taku of CPE Itarsi Make M/s Morris SWL Reva.
112S&F of gear pully complete setof ISI marked suitable for EOT Crane 7.5 Ton capacity complete all as specified and directed.
113S&F of gear pully complete setof ISI marked suitable for HOT HoistCrane 5/3 Ton capacity all as specified and directed.
114(a) HOT host crane capacity 5 Ton
115(b) HOT host crane capacity 3 Ton
116S&F of bearing set of ISI marked suitable for HOT hoist crane 5/3 Ton capacity complete all as specified and directed.
117(a) Capacity 5 Ton
118(b) Capacity 3 Ton
119S&F of bearing setof ISI marked suitable for EOT crane 7.5 Ton capacity complete all as specified and directed.
120M&L for removing/servicing/rewinding and refixing the motor for EOT Crane 7.5 Ton capacity all as specified and directed.
121M&L for removing/servicing/rewinding and refixing the Motor for HOT Hoist Crane 3/5 Ton capacity all as specified and directed.
122(a) Capacity 3 Ton
123(b) Capacity 5 Ton
124M&L for limit switches of existing make HOT Hoist Crane 3/5 Toncapacity all as specified and directed.
125(a) Capasity 3 Ton
126(b) Capasity 5 Ton
127M&L for limit switches of existing makeEOT Crane 7.5 Ton capacity all as specified and directed.
128M&L for replace existing damaged Gear wheel for full set EOT 7.5 Ton capacity all as specified and directed.
129M&L for replace existing damaged Gear wheel for full set HOT Hoist Crane 3Ton capacity all as specified and directed.
130M&L for push button HOT Hoist Crane 3/5 Toncapacity all as specified and directed.
131M&L for Push buttonEOT Crane 7.5 Ton capacity all as specified and directed.
132M&L for replace the damaged base plateof HOT Hoist Crane 3 Ton capacity all as specified and directed.
133M&L for replace the damaged base plateof EOT Crane 7.5 Ton capacity all as specified and directed.
134Supply & replace hoist steel wire rope 10 mm dia for 3 to 7.5 Ton capacity Hoist/ EOT/HOT Craneall as specified and directed.
135M&L for replace the damaged fuse switches for 3 to 7.5 Ton cap of HOT Hoist Crane & EOT Crane all as specified and directed.
136(a) Capacity 3 Ton
137(b) Capacity 5 Ton
138(c) Capacity 7.5 Ton
139Comprehensive preventive maint for operationaly fit to run DG set 30 KVA , three phase , 415 volt, 50 HZ , AC supply alternator of Kirloskar make coupled with diesel engine set, at CPE 2 No pump house by Servicing and routine maint of the following:- checking/ lubricating system, toping up of lubricant of its desired level, replacement of gasket insulation paper sheet glass sleeve of connecting leads, binding the loose coils with binding cloth, nuts, bolts and washers, split pins for proper tightness, cleaning up all filter, if reqd to be replace Air filter, fuel filter, Oil filter,grease/clipping materials for its safe operation, cleaning the startor, excitor coil and cleaning the complete assemblies by taking out perished glass sleeve, insulation paper,binding cloth and washing with carbon tetra chloride, decarbonising and cleaningthe rotorThe following minor spare parts if reqd to be replaced i.e gasket, nuts, bolts, washer, Rod push, clamp hose, control safety, control vernier Oiling/Greasing etc, All other remaining items to be checked if necessary to replace the worm out parts complete time to time for safe and satisfactory run of DG Set. Note :- Spares for DG Set/Alternator will be measured and paid seperatly ii) Contractor will carry out comprehensive maint once in a month in addition he will also attend to any type of break down on emergency basis as and when intimated by JE E/M or Engr-inCharge.iii)Contractor will ensure serviceability and safty of system complete all as specified and directed.
140All as per item No 113.00 here-in-before but capacity 30KVA at Pump house taku area CPE, Itarsi
141All as per item No 113.00 here-in-before but capacity 62.5 KVA at main substation CPE, Itarsi
142All as per item No 113.00 here-in-before but capacity 62.5 KVA at Pump house TakuCPE, Itarsi
143Comprehensive preventive maint for operationaly fit to run DG set 82.5 KVA makeKala Gen set , three phase , 415 volt, 50 HZ , AC supply alternator of Kirloskar makecoupled with diesel engine set at Proof House, by Servicing and routine maint of the following:- checking/ lubricating system, toping up of lubricant of its desired level, replacement of gasket insulation paper sheet glass sleeve of connecting leads, binding the loose coils with binding cloth, nuts, bolts and washers, split pins for proper tightness, cleaning up all filter,if reqd to be replace Air filter, fuel filter, Oil filter,grease/clipping materials for its safe operation, cleaning the startor, excitor coil and cleaning the complete assemblies by taking out perished glass sleeve, insulation paper,binding cloth and washing with carbon tetra chloride, decarbonising and cleaningthe rotorThe following minor spare parts if reqd to be replaced i.e gasket, nuts, bolts, washer, Rod push, clamp hose, control safety, control vernier, Oiling/Greasing,All other remaining items to be checked if necessary to replace the worm out parts complete time to time for safe and satisfactory run of DG Set. Note :- Spares for DG Set/Alternator will be measured and paid seperatly ii) Contractor will carry out comprehensive maint once in a month in addition he will also attend to any type of break down on emergency basis as and when intimated by JE E/M or Engr-inCharge.iii)Contractor will ensure serviceability and safty of system complete all as specified and directed.
144S&F of seal thermostat suitable for 30 to 82.5 KVA
145S&F of thermostat suitable for 30 to 82.5 KVA
146S&F of coolant
147S&F of horse pipe set for any capacity & size
148S&F of engine Oil
149S&F of belt - V for any size/capacity.
150S&F and cleaning for Air cleaner kit suitable for 30 to 82.5 KVA
151Deduct Schedule of credit (calculation will be done off line) Rs. 65530.00