| 1 | Supply, installation, testing and commissioning of Submersible pump including lifting/lowering, electric driven 415 V, TP suitable for 150MM dia bore well (Casing pipe size 150/100 mm) head not less than 95 meter and capacity not less than 5 HP stage 10.Outlet pipe should be 50mm dia including necessary clamps, nuts, bolts & washers. Complete all as specified and directed by Engineer-in-Charge (in existing bore well).Make : Kirloskar Code No D12720501054 or equivalent make of CRI, KSB.Note :- Cost of T&P required for lifting/lowering the motor shall be included in quoted rates. |
| 2 | Supply, installation and testing of DOL starter for Submersible pump, 415 V, TP suitable for 5 HP with ON/OFF switch, single phase preventor, motor ON/Trip indicator, MCB TP-32 Amps, Ammeter, Voltmeter with selector switch of pump. Complete all as specified and directed by Engineer-in-Charge.Make : L&T, Havells, C&S. |
| 3 | Supply & fix Submersible flat cable 4 sqmm 3 core multistranded copper conductor cable . Complete all as specified and directed. Make : Havells, Finolex, Polycab |
| 4 | Supply and fix HDPE pipe PN-10, PC-100, 50mm dia ISI mark for connection to submersible pump. Complete all as specified and directed. Make :- Supreme, Sudhakar, Finolex. |
| 5 | Supply & Fix Non Return Sluice Valve 50mm dia, ISI mark, complete all as specified and directed. Make : Zoloto, Leader, Kirloskar |
| 6 | Supply & Fix steel water tubing 50mm dia \"medium\" grade for connection to submersible pump. Complete all as specified and directed. Make : Jindal, Tata, Oswal |
| 7 | Supply & Fix 50mm dia, Gun-metal, globe or gate valves,with iron wheel head, screwed both ends for iron pipe and fixed, complete all as specified and directed.Make : Zoloto, Leader, Kirloskar |
| 8 | Supply & fix stainless steel wire rope of 6 mm dia 97/19 guage with PVC coating to support the lowering portion of the submersible pump, complete all as specified and directed. |
| 9 | Excavation in trenches in any type of soil n, exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables, foundation filling of poles or stays complte all as specified and as directed. |
| 10 | Returnig filling, in including spreading, levelling, watering and well ramming in layers not exec 25 cm each complete all as specified and as directed. |
| 11 | Removing excavated material to a distance not exceeding 50 mtrs and depositing where directed at a level not exc 1.5 mtr above the starting point complete all asspecified and as directed. |
| 12 | Supply, installation,testing and commisionining non clog sewage submersible pump set 3 phase 415 volts 50 Hz AC supply 2900RPM whose head not less than 16 meter and discharge not less than 625 LPM capacity not less than 5 HP max solid handling size 30 mm complete all as specified and directed.Make: Kirloskar Model no. 3700 CW or equivalent of KSB/Crompton. |
| 13 | S & F 6 sqmm multistranded copper conductor, 3 core PVC insulated and sheathed copper screen protected 1100 Volts grade submersible flat cable fixed to non clog submersible pump upto panel/starter with suitable clamps &jointing material complete all as specified and directed.Make: Havells/Polycab/Finolex/RR Cable |
| 14 | S & F PVC suction hose pipe medium grade 65 mm dia complete including hose clip of required size as recommendedby OEM all as specified and directed. |
| 15 | S & F mild steel chain (capacity to handle load is not less than 10 Ton) suitable for grip of non clog pump complete all as specified and directed. |
| 16 | S & F 65 mm dia hose pipe jublee clip with suitable size of nut and bolt for sewage submersible pump including connecting all as specified and directed. |
| 17 | Supply, installing, testing and commissioning factory made, floor mounted indoor type LT panel board, cubicle type, suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having 200 Amps capacity copper bus bar for phase and 200 Amps copperbus bar capacity for neutral , colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 2.00 mm thick CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, provision of connecting earth strip from 2 sides, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 40x40x6 mm, welded on all the four corners, embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories:- |
| 18 | MCCB3 pole motor protection circuit breaker 415 Volts 16 KA63 Amps with extendable terminal-01 Nos(In coming) |
| 19 | Provn ofDOLstarter with 63 amps TP power contactors ,NO/NC Aux contact , O/L relay & SD timer etc for 15 HP submersible pumpset -02 Nos. |
| 20 | Digital multifunction meter of size 96x96 mm to measure current, voltage, frequency and power factor with built in selector switch and programable CT ratio with RS 485 port |
| 21 | Start/Stop push buttons - 02 Nos each |
| 22 | Phase indication -RYB & Motor ON/ OFF/Trip indicating lamps LED type - 09 Nos. |
| 23 | Control fuse with link- -03 Nos Make : Bussmann/ FARAZ/ Seimens |
| 24 | Pump protection relay type S2 CMR1 including connected CTs /current sensors ofMake Minilec or equivalent with following protections :-phase failure, unbalance, negative phase sequence, overloading and dry running (under current). Relay shall have following additional features:- Auto/Manual Reset, adjustable current trip settings, selectable overload characteristics - 02 Nos. |
| 25 | Phase sequence correctorswitch 3 pole, on load type, open execution, 100 AmpsMake: BCH/L&T /Siemens / Schneider / ABB/HPL - 01 No. |
| 26 | Single phasing preventer- 02 No Make : Minilac/L&T |
| 27 | MCB of desired rating -04 Nos& connectors as per requirement |
| 28 | One no. danger notice plate |
| 29 | Make: Universal Switchgear Control/ABB/ITE Gurgaon/ Naptune/Hensl/Indoasian/Shalabh |
| 30 | M&L forProvision of earthingwith 600x600x6.0mm galvanised steel earth plate electrode buried vertically in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of the plate at a depth of not less than 1.5m below ground level, connected to and including G.I. Strip of size 32 X 6 mm by means of bolts,nuts and check nuts and washers of galvanised steel (and 40mm dia GI medium grade pipe for protectionof G.I strip) to the extent of 7.5 metres as earthing lead and connecting to the eqpt, viz transformer, L.T. kiosk, H.T.lightening arrestors etc. including charcoal dust and salt packed all around the earth plate in the earth pit all as per electrical plate No. 3 of SSR Part I (2009) including PCC foundation / chamber in mix 1:2:4 type B1 with M.S. angle iron frame, C.I. Cover with provision of locking arrangement and 20mm dia light grade G.I. Pipe from top edge of the earth plate upto M.S. funnel with wire mesh provided inside the concrete earth pit for watering arrangement, M&L complete including excavation and earthwork in any type of soilstrata and testing complete all as specified and directed. (Note : GI strip and earth protection pipe upto and including 7.5 m length shall deemed to be included in unit rate quoted by contractor) |
| 31 | S & F Earth continuity conductor or main earthing lead/stripfixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc of size 32 x 6mm dia galvanised iron or steel wire |
| 32 | M & L forRolled sections Fe-410-W(Gde E-250) quality B as in framing for cladding, glazing and the like fixed with angle cleats and connecting plates, etc.for fixing of roof to support non clog submersible pump set with mild steel chain including making hole on both side of top of roof and making good isturbed surfaces all as specified and directed. |
| 33 | M & L for Excavating in post holes (or similar holes) each n. exc 0.5 cum getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n. exc 50m and making good surface in hard/dense soil |
| 34 | Plain Cement Concrete Type C2 1:3:6 (using 40 mm gradedstone aggregate) in foundations, filling and mass concrete. |
| 35 | S&F mild steel framed work such as grills gratings / fencing/gate etc with ends of bars shouldered and / or riveted or forged into spiked framed guard bars barred iron doors ladders framed blasters walkways railingsframework of water tanks and similar work conforming to Fe 290 Grade E-165 |
| 36 | M&L for applying two coats of synthetic enamel paint in VIBGOUR pattern over one coat of primer on new or previously untreated steel surfaces exc 10 cm width or girth including preparation of surface complete all as specified and directed. |