Tender For Repair Maintenance Of Lt Distribution System And Misc Works At Jalipa Mil Stn Under Ge Army Barmer, barmer-Rajasthan

Military Engineer Services-MES has published Tender For Repair Maintenance Of Lt Distribution System And Misc Works At Jalipa Mil Stn Under Ge Army Barmer. Submission Date for this Tender is 02-12-2023. Rough Finishing Tools Tenders in barmer Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

40426696
Corrigendum : Tender For Repair Maintenance Of Lt Distribution System And Misc Works At Jalipa Mil Stn Under Ge Army Barmer
Open Tender
Indian
Rajasthan
barmer
02-12-2023

Tender Details

Tender For Repair Maintenance Of Lt Distribution System And Misc Works At Jalipa Mil Stn Under Ge Army Barmer; 1 Excavating In Trenches Not Exc 1.5M Wide And Not Exc 1.5M In Depth For Foundation Of Poles, Laying Ug Cables, Etc And Getting Out In Soft / Loose Soil Complete All As Specified And Directed. 2 Removing Excavated Material Not Exc. 50 M And Depositing Where Directed At A Level Not Exc 1.5 M Above The Starting Point In Soft / Loose Soil Complete All As Specified And Directed. 3 Returning Filling Including Spreading Levelling, Watering And Well Ramming In Layers Not Exceeding 25Cm In Soft / Loose Soil Complete All As Specified And Directed. 4 M&L For Boring / Drilling By Machines / Manual Horizontally Under The Road In Any Type Of Soil Without Cuttiing / Disturbing The Existing Road And Inserting Gi Pipe Of Any Size For Drawing The Cable Complete All As Specified And Directed. ( Gi Pipe Shall Be Measured And Paid Seperately. 5 Material And Labour For Sand Cushioning For Under Ground Cables, Spread In Trenches, River Sand Including Cleaning, Spreading Levelling, Punning For Laying / Cushioning Of Cable With Layer Of 8 Cm Deep Before Laying Cable And 15 Cm Depth After Laying And Stretching The Cable Complete All As Specified And Directed. Note: For The Purpose Of Payment Punned Thickness Shall Be Measured. 6 Supply And Laying Un-Reinforced Precast Concrete Cable Cover, Class Lv, Type 1 Flat, Size 250 Mm X 150 Mm X 40 Mm As Mechanical Protection To Underground Cables Laying With Length Of The Cable Cover Equal To The Width Of The Trench Complete All As Specified And Directed. 7 M&L For Galvanised Steel Tube 50Mm Bore ( Light Grade ) Laying In Road / Drain Crossingfor Cable Protection Pipe Complete All As Specified And Directed.. 8 M&L For Galvanised Steel Tube 50Mm Bore ( Light Grade ) Fixed To Pole / Wall / Floor For Cable Protection Pipe Includingclamp Of Ms Flat Of Size 50X5mm And Nut, Bolt & Washers Of Size 50X12mm For Clamping Of Cable Protection Pipe With Wall / Pole As Where Required Complete All As Specified And Directed. 9 M&L For Pcc ( 1:4:8 ) Type D-2 Using 40 Mm Graded Stone Aggregate As In Foundation Filling & Mass Concrete For Sub Base Of Poles Complete All As Specified And Directed. 10 M&L Cement Concrete 1:3:6, Type C-2, ( Using 40 Mm Graded Stone Aggregate ) For Foundation Of Poles, Stays, Etc Including Form Work As Required / Ordered Complete All As Specified And Directed. 11 M&L Cement Concrete 1:3:6 Type C1 ( Using 20 Mm Graded Stone Aggregate ) As In Coping Of Poles, Padestal, Etc Including Necessary Form Work Etc Complete All As Specified And Directed. 12 Excavation In Post Holes ( Or Similar Holes ) Each Not Exc 0.5 Cum Getting Out , Returning, Filling In And Ramming Earth Or Broken Rubble Mixed With Earth Around, In Layers Not Exceeding 25 Cm In Hard / Dense Soil Complete All As Specified And Directed. 13 Supply And Laying In Repair Xlpe Insulated, Armoured, Heavy Duty Electric Ug Cables Withaluminium Conductor 1100 Volts Grade Complete Including Porviding Lugs As Required Complete All As Specified And Directed For Cross-Sectional Area 10 Sqmm 2 Core. 14 All As Per Srl Item No 13 Above But Of Size 10 Sqmm, 4 Core 15 All As Per Srl Item No 13 Above But Of Size 16 Sqmm, 2 Core 16 All As Per Srl Item No 13 Above But Of Size 16 Sqmm, 4 Core 17 All As Per Srl Item No 13 Above But Of Size 25 Sqmm, 3 1 / 2 Core 18 All As Per Srl Item No 13 Above But Of Size 35 Sqmm, 3 1 / 2 Core 19 All As Per Srl Item No 13 Above But Of Size 50 Sqmm, 3 1 / 2 Core 20 All As Per Srl Item No 13 Above But Of Size 70 Sqmm, 3 1 / 2 Core 21 All As Per Srl Item No 13 Above But Of Size 95 Sqmm, 3 1 / 2 Core 22 All As Per Srl Item No 13 Above But Of Size 120 Sqmm, 3 1 / 2 Core 23 All As Per Srl Item No 13 Above But Of Size 150 Sqmm, 3 1 / 2 Core 24 All As Per Srl Item No 13 Above But Of Size 185 Sqmm, 3 1 / 2 Core 25 All As Per Srl Item No 13 Above But Of Size 240 Sqmm, 3 1 / 2 Core 26 Dismantling / Uprooting Of Lt Unserviceable Pre-Stressed Concrete / Steel Poles Of Any Size And Length Including Taking Out Dismantled Portion Of Poles Embeded In Concrete After Necessary Demolition Ofconcrete Foundation And Disposal There Of Complete All As Specified And Directed 27 M&L For Prestressed Concrete Pole, 9.0 Metres Long, 102 Mm X 152 Mm At Top And 102Mm X 289 Mm At Bottom, Class 10 Complete All As Specefied And Directed. 28 Dismantling Cross Arms Of Ms Channel Or Angle Sections Etc And Keeping Serviceable Materials In Safe Custody For Re-Use And / Or Unserviceable Materials Removing From The Site Complete All As Specified And Directed. 29 Fixing Only Serviceable Cross Arm, Ms Channel, Angle Section Obtained From Item No 28 Above After Painting With One Coat Of Aluminium Paint Including Preparation Of Old Steel Surfaces Complete All As Specified And Directed. 30 M&L Cross Arms, Bracings, Supports, Clamps And Back Plates Fabricated From Structural Steel Sections, Including Nuts, Bots, Washers, Welding, Bending Cold Or Hot, Drilling Holes For Bolts, In Any Shape Or Size As Indicated Or Directed And Inclusive Of One Primer Coat ( Red Oxide, Zine Chrome Primer ) , One Under Coat And One Finishing Coat Of Aluminium Paint Including Preparation Of Surfaces Complete All As Specified And Directed. 31 Dismantling Of Acsr Conductors Or Disturbed Span Including Line Spacer And Keeping Serviceable Materials In Safe Custody For Re-Use And Unserviceable Materials Removing From The Site Complete All As Specified And Directed. 32 Fixing Only By Re-Straining, Tightening Of Acsr Conductors Of Any Size / Type On Lt Poles Including Necessary New Aluminium Binding Wire For Fixing With Insulator / Pvc Sleeves For Jumper Etc As Required Complete All As Specified And Directed. ( Note:Serviceable Acsr Conductors Shall Be Obtained From Item No. 31 Above ) . 33 M&L For Aluminium Conductor Steel Reinforced ( Acsr ) On Lt Poles Including Straining, Binding With Insulators With Aluminium Binding Wire With Insulator As In Oh Conductor, Providing Pvc Sleeves For Jumpers Complete All Specified And Directed. 34 Dismantling Insulators Of Any Type And Any Size And Keeping Serviceable Materials In Safe Custody For Re-Use And Removing Unserviceable Materials From The Site Complete All As Specified And Directed. 35 Fixing Only Serviceable Pin Type Porcelain, Vitreous, ( White / Brown Or Green ) Insulator For 1100 Volts Grade Of Any Type Obtained From Item No 34 Above. 36 Fixing Only Serviceable Shackle Type Porcelain, Vitreous ( White / Brown Or Green ) Insulator Of Any Size And Shape For 1100 Volts Grade Obtained From Item No 34 Above. 37 S&F Pin Type, Porcelain, Vitreous, White, Brown Or Green Insulator Including One Galvanised Mild Steel Spindle, Two Galvanised Iron Washers And One Galvanised Iron Nut, 100 Mm Height, 65 Mm Dia For 1100 Volts Grade Complete All As Specified And Directed. 38 S&F Shackle Type, Porcelain, Vitreous White, Brown Or Green Insulator Including Galvanised Mild Steel Straps Of Size 31 X 3 Mm, 12 Mm Dia Insulator Bolts, Nuts And Washers For Working Pressure 1100 Volts Of Size 75 Mm Height, 90 Mm Dia Complete All As Specified And Directed. 39 Dismantling Lt Stay Assembly, Of Any Size And Unserviceable Materials Removing From The Site ( S ) , Complete All As Specified And Directed.A ) Unserviceable Stay Assembly Shall Be Taken Off / Dismantled At Ground Level And Making Good Disturbed Ground Surface.B ) Rate Is Inclusive Of Necessary Earthwork For Demolition Of Cement Concrete Complete. 40 M&L Stay Assembly For Lt Complete With Accessories As Shown In Electrical Plate No. 1 Of Mes Schedule Part- I, 16 Mm Dia Stay Rod, 7 / 3.15 Mm Galvanised Stay Strand Complete All As Specified And Directed. ( Note:Loop Insulator, Stay Clamps, Excavation / Earthwork And Cement Concrete Shall Be Measured And Paid For Separately Under Relevant Items Of This Schedule ) . 41 S&F In Repair Loop Type Insulators Vitreous Porcelainwhite / Brown Or Green Small Size With Overall Dimensions 65X90 Mm Clearance Of Hole 16 Mm Dia Complete All As Specified And Directed. 42 Dismantling Earth Wire Of Any Size / Dia, Guarding Cradle Of Disturbed Span And Keepingserviceable Materialsin Safe Custody For Re-Use And Removing Unserviceable Materials From The Site Complete All As Specified And Directed. 43 Fixing Only Serviceable Gi Wire 3.15 Mm Or 4 Mm Dia Obtained From Item No 42 Above Complete All As Specified And Directed. 44 M&L For Cradles, Hexagonal / Rectangular, Fabricated Or Continuous Earth Wire With Galvanised Steel Wire 3.15 Mm Or 4 Mm Dia Complete All As Specified And Directed. 45 S&F In Repair Pvc Fibre Separator For Lt Line 1100 Volt Oh Conductor 3 / 4 Wire System For Maintaining Horizontal Spacing Of Conductor Complete With Nut & Bolt Minimum Two Nos In A Span Complete All As Specified And Directed. 46 Trimming Of Tree Branches Around The Lt / Ht Oh Conductor, Pole & Stay ( Not Less Than 3 Metre ) To Clear The Over Head Lines Including Cleaning Of Birdnest, Creepers On Poles And Stays Etc Complete As Required Including Removing And Disposed Off From The Site Directed. Note : The Quoted Shall Deemed To Be Inclusive Of Provision Of Periodically Cleaning / Cutting Etc Including Disposal There-Off And Span Will Be Measured & Paid Only Once In Entire Contract Period. 47 M & L In Repair Earthing Complete With Galvanised Steel Earth Plate Electrode 600 X 600 X 6Mm Thick, Burried Directly In Ground ( Earth Pit Not Less Then 2.25M Deep Bellow Ground Level ) With Top Edge Of The Plate Not Less Then 1.5M Deep Below Normal Ground Level Connected To Galvanised Iron Strip Of 32 X 6Mm Earth Lead By Means Of Bolt, Nuts, Washers Of Galvanised Steel Earth Strip Protected By And Including Gi Pipe 40Mm Dia Bore ( Light Grade ) And Conncted To Main Test Point Directed And Including Concrete Pit In Pcc ( 1:3:6 ) Type C-1 Precast Rcc ( 1:1.5:3 ) Type A-1 Cover Slab 54 X 5 Cm Reinforced With 4Mm Dia Tmt Bars @ 150 Mm C / C Both Ways With One Handle For Lifting Made Out Of 8Mm Dia Tmt Bar Embedded In Precast Cover Slab Funnel Wire Mens 20Mm Bore Gi Pipe ( Medium Grade ) For Watering Charcoal And Salt In Altemate Layers, Including Necessary Excavation And Earth Work In Any Type Of Soil Complete All As Shown On Electrical Plate No3 Of Ssr Part-I Complete All As Specified And Directed. 48 M & L In Repair Earthing Complete With Galvanised Steel Earth Plate Electrode 600X600x6 Mm Thick Buried Directly In Ground Preferably Vertically In Ground With Top Edge Not Less Than 1.25 Mtr Deep Below Normal Ground Level Connected With And Including Galvanised Iron Wire 4 Mm Dia As Earthing Lead By Means Of Nuts Bolts And Washers Of Galvanized Iron Protected By 15Mm Dia ( Medium Grade ) Gi Tubing, Funnel, Wire Mesh, 20Mm Bore Gi Tubing ( Light Grade ) Watering Pipe, Including Concrete Pit In Pcc ( 1:3:6 ) Type C-1, Precast Rcc ( 1:2:4 ) Type B-1 Cover Slab Of Size 350X350x50mm Reinforced With 8Mm Dia Tmt Bars @ 15Cm C / C In Both Ways And 10Mm Dia Ms Handle ( 01 No ) Of Suitable Size, Charcoal And Salt In Alternate Layers Necessary Excavation And Earth Work In Soft / Loose Soil All As Shown In Electric Plate No. 3 Of Ssr Part-I And Testing On Completion Complete All As Specified And Directed. 49 Supply, Install, Commission And Testing In Repair Cubical Type Lt Panel Board , Outdoor Canopytype, Manufactured By A Cpri Approved Factory, Floor Mounted, Dust & Vermin Proof, Front And Rear Operated Doorwithnecessary Locking Arrangement Made Of 50 X 6Mm Ms Angle Iron Frame Work And Crca Sheetof 3.00 Mm Thick Duly Painted With Two Coats Of Powder Coated Paint Of Approved Shade After Seven Tank Treatment Process Both Internally And Externally. The Panel Shall Be Suitable For 415 Volts, 50 Hz, 3 Phase 4 Wire System And Shall Be Complete With Suitable Capacity Copper Bus Bar ( 1.5 Times The Incoming Switch Gear Current Rating ) With Suitable Size Of Pvc Insulated Copper Conductor, Thimbles Glands Complete All As Specified And Directed With The Following Accessories :- Incoming ( A ) Mccb 4 Pole, 415 Volts, 250 Amps, 25 Ka - 01 No.Outgoing ( A ) Mccb4 Pole, 415 Volts, 125 Amps, 16 Ka -01 No. ( B ) Mccb4 Pole, 415 Volts, 100 Amps, 16 Ka -02 Nos ( C ) Mccb4 Pole, 415 Volts, 100 Amps, 10 Ka -01 Nos ( Spare ) ( D ) Mcbtpn , 415 Volts, 32 Amps, -01 Nos ( E ) Digitalvaf Meter For Basic Electric System Monitoring-01 Nos. ( F ) Indicator Lamp ( Ryb ) ( Set Of Three ) - 01 Set 50 S&F In Repair Tpn Copper Bus Bar Box, Outdoor Type Of 200A Capacity Mounted On Porcelain Bridge Insulator For One Incoming Cable And 4 Out Going Cable, Housing In Sheet Metal Enclosure Of Ms Sheet 3.0 Mm Thick Crca Sheet And Angle Iron 40X40x6 Mm Frame, Painted With Two Coats Including Arrangement For Cable Gland For Incoming And Outgoing Cables, Locking Arrangement, Suitable Foundation / Platform For Mounting The Fpb With Space For And Including The Following Switch Gears: ( A ) Mccb 100 A Fp, 10 Ka ( For Incoming Control ) 51 Preparation Of Old Painted Surface Above The Planting Depth And Pcc Coping Of Steel Tubular Lt Pole Of09.00 Metre Length Including Ms Clamps , Cable Protection Pipe Bracket Fittedwith Street Light Fittings Etc By Scraping With Steel Wire Brush And Applying Two Coats, Of Aluminium Paint To External Surface Of Poles Ms Cross Arms Ms Clamp, Cable Protection Pipe Etc To Give Even Shade Including Zebra Colour Of Painting From 1.5 Mtr Height From The Top Of Coping / Bottom Of Pole As Per Site Condition And Numbering Of Poles Complete All As Specified And Directed.Note: Zebra Colour Will Be Applied By Synthetic Enamel Paint Of Black / Yellow Colour As Approved In Alternate Layer Of 30 Cm Height Of Each Layer. 52 Preparation Of Old Painted Surfaces And Removing Dust And Other Deposited Material By Scraping From Lt Pcc Polesof09.00 Metre Length, Cross Arms Brckets And Applying 2 Coats Of Aluminium Paint To All Steel Surfaces, Including Ms Clamps , Cable Protection Pipe Bracket Fittedwith Street Light Fittings Etcincluding Zebra Colour Of Painting Upto 1.5 Mtr Height From The Top Of Coping / Bottom Of Pole As Per Site Condition And Numbering Of Poles Complete All As Specified And Directed. 53 Supply And Fix In Repair Energy Efficient Led Street Light Fitting Of 45 Watt Made Up Of Pressuredie Castaluminium Housing With Toughened Glass And High Power Leds With Secondary Optics, Efficacy 110 / 120 Lpw, Ip 66 Protection Aerodynamically Designed For All Weather Conditions With Efficient Thermal Management Including 10 Kv Spd Complete All As Specified And Directed .Model: Raptor Neo Cat No: Trp-409-45-57-Sl-Gl-Nsgof Make Cg Or Techno Commercially Equivalent Model Of Havells, Bajaj, Wipro, Halonix 54 Supply And Fix In Repair Energy Efficient Led Street Light Fitting Of 60 Watt Made Up Of Pressuredie Castaluminium Housing With Toughened Glass And High Power Leds With Secondary Optics, Efficacy 110 / 120 Lpw, Ip 66 Protection Aerodynamically Designed For All Weather Conditions With Efficient Thermal Management Including 10 Kv Spd Complete All As Specified And Directed .Model: Raptor Neo Cat No : Trp-409-60-57-Sl-Gl-Nsgof Make Cg Or Techno Commercially Equivalent Model Ofhavells, Bajaj, Wipro, Halonix. 55 Supply And Lay In Repair Lt Service Cable 6 Sqmm 2 Core Inside Pvc Conduit 20 Mm Dia Medium Grade For Landscape Lighting / Garden Lighting Inside Trench Or On Wall / Floor Complete All As Specified And Directed.Note: The Rate Quoted Must Be Inclusive Of Laying The Cables In Trench At Max 10 Cm Depth Or Mounting On Floor / Wall 56 S&F Integral Compact Wide Beam Led Flood Light Luminiaire With Die Cast Aluminium Alloy Housing With Ip 66 Protection, Tampered Protective Toughened Glass 5Mm Thick, Thermal Shock Impact Resistant Cover, Epoxy Black Powder Coated Finish, High Purity Pre-Anodised Specular Aluminium Sheet Reflector, With Silver Painted Contacts Suitable For 1X100 Watts Led And Connection With Two Runs Of 2.5 Sqmm Multi-Stranded, Copper Flexible Wire Including Taking Down Old Unserviceable One And Testing Complete All As Specified And Directed. Make Cat Part No Lhepczu7pa6j100 Havells Or Techno Commercially Equivalent In Wipro And Crompton 57 Supply And Fix In Repair Led Post Top Lantern Of 45 W, Ip 65 Protection With In Builtelectronic Driver And Aluminium Housinginpure Polyster Uv Resistant Powder Coated Black Finish, Top Maintainable Product With Top Opening Die Cast Cover , Anti Corrossive Stainless Steel Screws & Silicon Gasket, Het Pmma Diffuser Conforming To Is 10322 Part 5 / Sec 1: 1987, Suitablefor Pole Diameter Up To 75 Mm , Cable Entrythrough Pole From Bottom, 3 Way 10 Amps Gfp Mains Connector Duly Wiredupto Terminal Block Complete All As Specified And Directed. Make Wipro Cat Part No: Lp07-501-Xxx-57-Cl Or Techno Commercially Equivalent In Bajaj, Crompton, Havells, Halonix. 58 Supply And Fix In Repair Gi Pipe Bracket For Street Light Fittings Made Out Of 32 Mm Dia Gi Pipe Light Grade 1.5 Mtr Long Bent To Required Angle / Shape With And Including Necessary Clamps, Nuts, Bolts, & Washers Of Suitable Size Complete All As Specified And Directed. 59 S & F In Repair Pvc Weather Proof Loop-In Loop-Out Box With 4 Pole Terminal Block Mounted On Porcelain Or Bakelite And Mcb Sp 06 Amps For Controlling Including Necessary Clamps For Mounting On Pole Etc Complete All As Specified And Directed. Make: Sintex Cat Part No-Gsjb 2014 Or Techno Commercially Techno Commercially Equivalent. 60 Supply, Jointing And Testing In Repair Cable Jointing Kit For 1.1 Kv Grade Cable For Outdoor Termination Heat Shrink Type Joint Complete With Jointing Material And Accessories Suitable For 3.5 Core Xlpe Armoured Aluminium Conductor Cable Of Size 25-50 Sqmm Complete All As Specified And Directed. 61 Supply, Jointing And Testing In Repair Cable Jointing Kit For 1.1 Kv Grade Cable For Outdoor Termination Heat Shrink Type Joint Complete With Jointing Material And Accessories Suitable For 3.5 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70-150 Sqmm Complete All As Specified And Directed. 62 Supply, Jointing And Testing In Repair Cable Jointing Kit For 1.1 Kv Grade Cable For Straight Through Heat Shrink Type Joint Complete With Jointing Material And Accessories Suitable For 3.5 Core Xlpe Armoured Aluminium Conductor Cable Of Size 25-50 Sqmm Complete All As Specified And Directed. 63 Supply, Jointing And Testing In Repair Cable Jointing Kit For 1.1 Kv Grade Cable For Straight Through Heat Shrink Type Joint Complete With Jointing Material And Accessories Suitable For 3.5 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70-150 Sqmm Complete All As Specified And Directed. 64 S&F Voltmeter, Digital Type, 0-500 Volt With In-Built Selector Switch Including Taking Down Existing Old / Unserviceable Voltmeter From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 65 S&F Ampere Meter, Digital Type, 0-500 Amps With In-Built Selector Switch, Complete With Suitable Size Of CtS Including Taking Down Existing Old / Unserviceable Ammeter From Lt Panel / Apfc Panelboard After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed. 66 S&F Indicator Lamp, Led Type Of Colour Red, Blue And Yellow Including Taking Down Existing Old / Unserviceable Lamps From Lt Panel / Apfc Panelboard After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed And Asdtrected. 67 S&F Mccb, 415 Volts, 400 Amp, Breaking Capacity 36 Ka, 4 Pole Including Taking Down Existing Old / Unserviceable Mccb From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 68 S&F Mccb, 415 Volts, 250 Amp, Breaking Capacity 25 Ka, 4 Pole, Including Taking Down Existing Old / Unserviceable Mccb From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 69 S&F Mccb, 415 Volts, 200 Amp, Breaking Capacity 25 Ka, 4 Pole, Including Taking Down Existing Old / Unserviceable Mccb From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 70 S&F Mccb, 415 Volts, 160 Amp, Breaking Capacity 16 Ka, 4 Pole Including Taking Down Existing Old / Unserviceable Mccb From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 71 S&F Mccb, 125 Amp, 415 Volts, Breaking Capacity 16 Ka, 4 Pole, Including Taking Down Existing Old / Unserviceable Mccb From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 72 S&F Mccb, 100 Amp, 415 Volts, Breaking Capacity 10 Ka, 4 Pole, Including Taking Down Existing Old / Unserviceable Mccb From Lt Panel / Apfc Panel Board After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 73 S&F In Repair 3 / 4 Pole Contactor For Capacitor Switching Ac 230 / 240 Volt , 50 Hzs Coil Operated Suitable For Iec Rated 400 Volt , 5-100 Amps Max Complete All As Specified And Directed. 74 S&F Contactor 3 / 4 Pole Ml-2.5 To 3.0 Including Taking Down Existing Old / Unserviceable Contactor From Lt Panel / Apfc Panelboard After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 75 S&F Contactor 3 / 4 Pole Ml-4.0 Including Taking Down Existing Old / Unserviceable Contactor From Lt Panel / Apfc Panelboard After Carefully Disconnecting The Electric Connection Complete All As Specified And Directed 76 Taking Down The Unserviceable Capacitor From Apfc Panel And Supply And Fix Cylindrical Capacitorheavy Duty Of Capacity 1 Kvar Complete All As Specified And Directed. 77 Taking Down The Unserviceable Capacitor From Apfc Panel And Supply And Fix Cylindrical Capacitor Heavy Duty Of Capacity 3 Kvar Complete All As Specified And Directed. 78 Taking Down The Unserviceable Capacitor From Apfc Paneland Supply And Fix Cylindrical Capacitor Heavy Duty Of Capacity 5 Kvar Complete All As Specified And Directed. 79 Taking Down The Unserviceable Capacitor From Apfc Paneland Supply And Fix Cylindrical Capacitor Heavy Duty Of Capacity 7.5 Kvar Complete All As Specified And Directed. 80 Taking Down The Unserviceable Capacitor From Apfc Paneland Supply And Fix Cylindrical Capacitor Heavy Duty Of Capacity 10 Kvar Complete All As Specified And Directed. 81 Taking Down The Unserviceable Capacitor From Apfc Panel And Supply And Fix Ylindrical Capacitor Heavy Duty Of Capacity 15 Kvar Complete All As Specified And Directed. 82 Taking Down The Unserviceable Capacitor From Apfc Panel And Supply And Fix Cylindrical Capacitor Heavy Duty Of Capacity 20 Kvar Complete All As Specified And Directed. 83 Taking Down The Unserviceable Capacitor From Apfc Panel And Supply And Fix Cylindrical Capacitor Heavy Duty Of Capacity 25 Kvar Complete All As Specified And Directed. 84 Taking Down The Existing Unserviceable Automatic Power Factor Control Panel And Supply And Fix Automatic Power Factor Control Panel Microprocessor Based Incuding Led Display Input Voltage 415 V Ac, +-15 %, 50 Hzs, Three Phase Delta Connection With Heavy Duty Cylindrical Capacitor And8 Step Controlof Capacity 10 Kvar Copmplete All As Specified And Directed. Make: Havells Cat Part No: Qhktcb5010x0 Or Techno Commercially Equivalent In Abb, Siemens, L&T, Schneider, C&S 85 Taking Down The Existing Unserviceable Ct From The Lt Panel / Apfc Panel And Supply And Fix Lt Ct Ring Type Suitable For Primary Current Ratio 100 / 5 Amps, Burden 5 Va, Class 1.0 Complete All As Specified And Directed.Make: Havells Cat Part No:Qscelfbol001 Or Techno Commercially Equivalent In Abb, Siemens, L&T, Schneider, C&S 86 Taking Down The Unserviceable Dimmer From The Servo Voltage Stabilizer Of 75 Kva Capacity And Supply And Fix Dimmer Or Variable Transformer Of Servo Voltage Stabilizer Of 75 Kva Capacity Complete All As Specified And Directed. 87 Taking Down The Unserviceable Carbon Brush From The Servo Voltage Stabilizer Of 75 Kva Capacity And Supply And Fix New Carbon Brush Of Servo Voltage Stabilizer Of 75 Kva Capacity Complete All As Specified And Directed. 88 Taking Down The Unserviceable Buck Boost Transformer From The Servo Voltage Stabilizer Of 75 Kva Capacity And Supply And Fix New Buck Boost Transformer Of Servo Voltage Stabilizer Of 75 Kva Capacity Including Necessary Wiring Complete All As Specified And Directed. 89 Material And Labour For Servicing Of Servo Voltage Stabilizer Of 75 Kva Capacity Including Replacement Of Necessary Wiring And Copper Lugs, Contactors, Relays Etc Complete All As Specified And Directed. Note: Rate Quoted Must Be Inclusive Of Necessary Wiring And Copper Lugs Required To Be Replaced But The Contactors And Relays If Required To Be Replaced Will Be Measured And Paid Separately.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 27-11-2023
2 27-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 02-12-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work : REPAIR/ MAINTAINANCE OF LT DISTRIBUTION SYSTEM & MISC WORKS AT JALIPA MIL STN UNDER GE (ARMY) BARMER
Sl. No. Item Description
1Excavating in trenches not exc 1.5m wide and not exc 1.5m in depth for foundation of poles, laying UG cables, etc and getting out in soft/loose soil complete all as specified and directed.
2Removing excavated material not exc. 50 m and depositing where directed at a level not exc 1.5 m above the starting point in soft / loose soil complete all as specified and directed.
3Returning filling including spreading levelling, watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed.
4M&L for boring/drilling by machines/manual horizontally under the road in any type of soil without cuttiing/disturbing the existing road and inserting GI pipe of any size for drawing the cable complete all as specified and directed. (GI pipe shall be measured and paid seperately.
5Material and labour for sand cushioning for under ground cables, spread in trenches, river sand including cleaning, spreading levelling, punning for laying/cushioning of cable with layer of 8 cm deep before laying cable and 15 cm depth after laying and stretching the cable complete all as specified and directed. Note: For the Purpose of payment punned thickness shall be measured.
6Supply and laying un-reinforced precast concrete cable cover, class LV, Type 1 flat, size 250 mm x 150 mm x 40 mm as mechanical protection to underground cables laying with length of the cable cover equal to the width of the trench complete all as specified and directed.
7M&L for galvanised steel tube 50mm bore (light grade) laying in road/drain crossingfor cable protection pipe complete all as specified and directed. .
8M&L for galvanised steel tube 50mm bore (light grade) fixed to pole/wall/floor for cable protection pipe includingclamp of MS flat of size 50x5mm and nut, bolt & washers of size 50x12mm for clamping of cable protection pipe with wall/pole as where required complete all as specified and directed.
9M&L for PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation filling & mass concrete for sub base of poles complete all as specified and directed.
10M&L cement concrete 1:3:6, type C-2, (using 40 mm graded stone aggregate) for foundation of poles, stays, etc including form work as required/ordered complete all as specified and directed.
11M&L cement concrete 1:3:6 type C1 (using 20 mm graded stone aggregate) as in coping of poles, padestal, etc including necessary form work etc complete all as specified and directed.
12Excavation in post holes (or similar holes) each not exc 0.5 cum getting out , returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm in hard/dense soil complete all as specified and directed.
13Supply and laying in repair XLPE insulated, armoured, heavy duty electric UG cables withaluminium conductor 1100 volts grade complete including porviding lugs as required complete all as specified and directed for cross-sectional area 10 sqmm 2 core.
14All as per srl item No 13 above but of size 10 Sqmm, 4 core
15All as per srl item No 13 above but of size 16 Sqmm, 2 core
16All as per srl item No 13 above but of size 16 Sqmm, 4 core
17All as per srl item No 13 above but of size 25 Sqmm, 3 1/2 core
18All as per srl item No 13 above but of size 35 Sqmm, 3 1/2 core
19All as per srl item No 13 above but of size 50 sqmm, 3 1/2 core
20All as per srl item No 13 above but of size 70 sqmm, 3 1/2 core
21All as per srl item No 13 above but of size 95 sqmm, 3 1/2 core
22All as per srl item No 13 above but of size 120 sqmm, 3 1/2 core
23All as per srl item No 13 above but of size 150 sqmm, 3 1/2 core
24All as per srl item No 13 above but of size 185 sqmm, 3 1/2 core
25All as per srl item No 13 above but of size 240 sqmm, 3 1/2 core
26Dismantling/uprooting of LT unserviceable pre-stressed concrete/steel poles of any size and length including taking out dismantled portion of poles embeded in concrete after necessary demolition ofconcrete foundation and disposal there of complete all as specified and directed
27M&L for prestressed concrete pole, 9.0 metres long, 102 mm x 152 mm at top and 102mm x 289 mm at bottom,class 10 complete all as specefied and directed.
28Dismantling cross arms of MS channel or angle sections etc and keeping serviceable materials in safe custody for re-use and/or unserviceable materials removing from the site complete all as specified and directed.
29Fixing only serviceable cross arm, MS Channel, angle section obtained from item No 28 above after painting with one coat of aluminium paint including preparation of old steel surfaces complete all as specified and directed.
30M&L cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections, including nuts, bots, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat (red oxide, zine chrome primer), one under coat and one finishing coat of aluminium paint including preparation of surfaces complete all as specified and directed.
31Dismantling of ACSR conductors or disturbed span including line spacer and keeping serviceable materials in safe custody for re-use and unserviceable materials removing from the site complete all as specified and directed.
32Fixing only by re-straining, tightening of ACSR conductors of any size/type on LT poles including necessary new aluminium binding wire for fixing with insulator/PVC sleeves for jumper etc as required complete all as specified and directed. (Note:Serviceable ACSR conductors shall be obtained from item No. 31 above).
33M&L for aluminium conductor steel reinforced (ACSR) on LT poles including straining, binding with insulators with aluminium binding wire with insulator as in OH conductor, providing PVC sleeves for jumpers complete all specified and directed.
34Dismantling insulators of any type and any size and keeping serviceable materials in safe custody for re-use and removing unserviceable materials from the site complete all as specified and directed.
35Fixing only serviceable pin type porcelain, vitreous, (white/brown or green) insulator for 1100 volts grade of any type obtained from item No 34 above.
36Fixing only serviceable shackle type porcelain, vitreous (white / brown or green) insulator of any size and shape for 1100 Volts grade obtained from item No 34 above.
37S&F pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed.
38S&F shackle type, porcelain, vitreous white, brown or green insulator including galvanised mild steel straps of size 31 x 3 mm, 12 mm dia insulator bolts, nuts and washers for working pressure 1100 volts of size 75 mm height, 90 mm dia complete all as specified and directed.
39Dismantling LT Stay assembly, of any size and unserviceable materials removing from the Site(s), complete all as specified and directed. a) Unserviceable Stay assembly shall be taken off/dismantled at Ground Level and making good disturbed ground surface. b) Rate is inclusive of necessary earthwork for demolition of cement concrete complete.
40M&L Stay assembly for LT complete with accessories as shown in Electrical plate No. 1 of MES schedule Part- I, 16 mm dia stay rod, 7/3.15 mm galvanised stay strand complete all as specified and directed. (Note:Loop insulator, stay clamps, excavation/ earthwork and cement concrete shall be measured and paid for separately under relevant items of this Schedule).
41S&F in repair loop type insulators vitreous porcelainwhite / brown or green small size with overall dimensions 65x90 mm clearance of hole 16 mm dia complete all as specified and directed.
42Dismantling earth wire of any size/dia, guarding cradle of disturbed span and keepingserviceable materialsin safe custody for re-use and removing unserviceable materials from the site complete all as specified and directed.
43Fixing only serviceable GI wire 3.15 mm or 4 mm dia obtained from item No 42 above complete all as specified and directed.
44M&L for cradles, hexagonal / rectangular, fabricated or continuous earth wire with galvanised steel wire 3.15 mm or 4 mm dia complete all as specified and directed.
45S&F in repair PVC fibre separator for LT line 1100 volt OH conductor 3/4 wire system for maintaining horizontal spacing of conductor complete with nut & bolt minimum two nos in a span complete all as specified and directed.
46Trimming of tree branches around the LT/HT OH conductor, pole & stay (not less than 3 metre) to clear the over head lines including cleaning of birdnest, creepers on poles and stays etc complete as required including removing and disposed off from the site directed. Note : The quoted shall deemed to be inclusive of provision of periodically cleaning/cutting etc including disposal there-off and "span" will be measured & paid only once in entire contract period.
47M & L in repair earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick, burried directly in ground (earth pit not less then 2.25m deep bellow ground level) with top edge of the plate not less then 1.5m deep below normal ground level connected to galvanised iron strip of 32 x 6mm earth lead by means of bolt, nuts, washers of galvanised steel earth strip protected by and including GI pipe 40mm dia bore (light grade) and conncted to main test point directed and including concrete pit in PCC(1:3:6)type C-1 precast RCC(1:1.5:3)type A-1 cover slab 54 x 5 cm reinforced with 4mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8mm dia TMT bar embedded in precast cover slab funnel wire mens 20mm bore GI pipe (medium grade) for watering charcoal and salt in altemate layers, including necessary excavation and earth work in any type of soil complete all as shown on electrical plate No3 of SSR part-I complete all as specified and directed.
48M & L in repair earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick buried directly in ground preferably vertically in ground with top edge not less than 1.25 mtr deep below normal ground level connected with and including galvanised iron wire 4 mm dia as earthing lead by means of nuts bolts and washers of galvanized iron protected by 15mm dia (medium grade) GI tubing, funnel, wire mesh, 20mm bore GI tubing (light grade) watering pipe, including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:2:4) type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia TMT bars @ 15cm c/c in both ways and 10mm dia MS handle (01 No) of suitable size, charcoal and salt in alternate layers necessary excavation and earth work in soft/loose soil all as shown in Electric plate No. 3 of SSR part-I and testing on completion complete all as specified and directed.
49Supply,install, commission and testing in repair cubical type LT panel board ,outdoor canopytype, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof,front and rear operated doorwithnecessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheetof 3.00 mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity copper bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles glands complete all as specified and directed with the following accessories :- INCOMING (a) MCCB 4 pole, 415 Volts,250 Amps, 25 KA - 01 No. OUTGOING (a) MCCB4 pole, 415 Volts, 125 Amps,16 KA -01 No.(b) MCCB4 pole, 415 Volts, 100 Amps,16 KA -02 Nos (c) MCCB4 pole, 415 Volts, 100 Amps,10 KA -01 Nos (Spare) (d) MCBTPN ,415 Volts, 32 Amps, -01 Nos (e) DigitalVAF meter for basic electric system monitoring-01 Nos. (f) Indicator lamp (RYB) (set of three) - 01 Set
50S&F in repair TPN copper bus bar box, outdoor type of 200A capacity mounted on porcelain bridge insulator for one incoming cable and 4 out going cable, housing in sheet metal enclosure of MS sheet 3.0 mm thick CRCA sheet and angle iron 40x40x6 mm frame, painted with two coats including arrangement for cable gland for incoming and outgoing cables, locking arrangement, suitable foundation/platform for mounting the FPB with space for and including the following switch gears: (a) MCCB 100 A FP, 10 KA (for incoming control)
51Preparation of old painted surface above the planting depth and PCC coping of steel tubular LT pole of09.00 metre length including MS clamps ,cable protection pipe bracket fittedwith street light fittings etc by scraping with steel wire brush and applying two coats, of aluminium paint to external surface of poles MS cross arms MS clamp, cable protection pipe etc to give even shade including Zebra colour of painting from 1.5 mtr height from the top of coping/ bottom of pole as per site condition and numbering of poles complete all as specified and directed. Note: Zebra colour will be applied by synthetic enamel paint of black/yellow colour as approved in alternate layer of 30 cm height of each layer.
52Preparation of old painted surfaces and removing dust and other deposited material by scraping from LT PCC polesof09.00 metre length, cross arms brckets and applying 2 coats of aluminium paint to all steel surfaces, including MS clamps ,cable protection pipe bracket fittedwith street light fittings etcincluding Zebra colour of painting upto 1.5 mtr height from the top of coping/ bottom of pole as per site condition and numbering of poles complete all as specified and directed.
53Supply and fix in repair energy efficient LED street light fitting of 45 watt made up of pressuredie castaluminium housing with toughened glass and high power LEDS with secondary optics, efficacy 110/120 LPW, IP 66 protection aerodynamically designed for all weather conditions with efficient thermal management including 10 KV SPD complete all as specified and directed . Model: RAPTOR NEO Cat No: TRP-409-45-57-SL-GL-NSGof make CG or techno commercially equivalent model of Havells, Bajaj, Wipro, Halonix
54Supply and fix in repair energy efficient LED street light fitting of 60 watt made up of pressuredie castaluminium housing with toughened glass and high power LEDS with secondary optics, efficacy 110/120 LPW, IP 66 protection aerodynamically designed for all weather conditions with efficient thermal management including 10 KV SPD complete all as specified and directed . Model: RAPTOR NEO Cat No : TRP-409-60-57-SL-GL-NSGof make CG or techno commercially equivalent model ofHavells, Bajaj, Wipro, Halonix.
55Supply and lay in repair LT service cable 6 sqmm 2 core inside PVC conduit 20 mm dia medium grade for landscape lighting/ garden lighting inside trench or on wall/floor complete all as specified and directed. Note: The rate quoted must be inclusive of laying the cables in trench at max 10 cm depth or mounting on floor/wall
56S&F integral compact wide beam LED flood light luminiaire with die cast aluminium alloy housing with IP 66 protection, tampered protective toughened glass 5mm thick, thermal shock impact resistant cover, epoxy black powder coated finish, high purity pre-anodised specular aluminium sheet reflector, with silver painted contacts suitable for 1x100 Watts LED and connection with two runs of 2.5 Sqmm multi-stranded, copper flexible wire including taking down old unserviceable one and testing complete all as specified and directed. Make Cat Part No LHEPCZU7PA6J100 Havells or techno commercially equivalent in Wipro and Crompton
57Supply and fix in repair LED post top lantern of 45 W, IP 65 protection with in builtelectronic driver and aluminium housinginpure polyster UV resistant powder coated black finish, top maintainable product with top opening die cast cover , anti corrossive stainless steel screws & silicon gasket, HET PMMA diffuser conforming to IS 10322 Part 5/Sec 1: 1987, suitablefor pole diameter up to 75 mm , cable entrythrough pole from bottom, 3 way 10 Amps GFP mains connector duly wiredupto terminal block complete all as specified and directed. Make Wipro Cat part No: LP07-501-XXX-57-CL or techno commercially equivalent in Bajaj, Crompton, Havells, halonix.
58Supply and fix in repair GI pipe bracket for street light fittings made out of 32 mm dia GI pipe light grade 1.5 mtr long bent to required angle/ shape with and including necessary clamps, nuts, bolts, & washers of suitable size complete all as specified and directed.
59S & F in repair PVC weather proof loop-in loop-out box with 4 pole terminal block mounted on porcelain or bakelite and MCB SP 06 Amps for controlling including necessary clamps for mounting on pole etc complete all as specified and directed. Make: Sintex Cat Part No-GSJB 2014 or techno commercially techno commercially equivalent.
60Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25-50 Sqmm complete all as specified and directed.
61Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70-150 Sqmm complete all as specified and directed.
62Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25-50 Sqmm complete all as specified and directed.
63Supply, jointing and testing in repair cable jointing kit for 1.1 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70-150 Sqmm complete all as specified and directed.
64S&F voltmeter, digital type, 0-500 volt with in-built selector switch including taking down existing old/unserviceable voltmeter from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
65S&F Ampere meter, digital type, 0-500 Amps with in-built selector switch, complete with suitable size of CT"s including taking down existing old/unserviceable Ammeter from LT panel /APFC Panelboard after carefully disconnecting the electric connection complete all as specified and directed.
66S&F Indicator lamp, LED type of colour red, blue and yellow including taking down existing old/unserviceable lamps from LT panel /APFC Panelboard after carefully disconnecting the electric connection complete all as specified and directed and asdtrected.
67S&F MCCB, 415 volts, 400 Amp, breaking capacity 36 KA, 4 pole including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
68S&F MCCB, 415 volts, 250 Amp, breaking capacity 25 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
69S&F MCCB, 415 volts, 200 Amp, breaking capacity 25 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
70S&F MCCB, 415 volts, 160 Amp, breaking capacity 16 KA, 4 pole including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
71S&F MCCB, 125 Amp, 415 volts, breaking capacity 16 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
72S&F MCCB, 100 Amp, 415 volts, breaking capacity 10 KA, 4 pole, including taking down existing old/unserviceable MCCB from LT panel /APFC Panel board after carefully disconnecting the electric connection complete all as specified and directed
73S&F in repair 3/4 pole Contactor for capacitor switching AC 230/240 Volt ,50 Hzs coil operated suitable for IEC rated 400 Volt ,5-100 Amps max complete all as specified and directed.
74S&F contactor 3/4 pole ML-2.5 to 3.0 including taking down existing old/unserviceable contactor from LT panel /APFC Panelboard after carefully disconnecting the electric connection complete all as specified and directed
75S&F contactor 3/4 pole ML-4.0 including taking down existing old/unserviceable contactor from LT panel /APFC Panelboard after carefully disconnecting the electric connection complete all as specified and directed
76Taking down the unserviceable capacitor from APFC panel and supply and fix cylindrical capacitorheavy duty of capacity 1 KVAR complete all as specified and directed.
77Taking down the unserviceable capacitor from APFC panel and supply and fix cylindrical capacitor heavy duty of capacity 3 KVAR complete all as specified and directed.
78Taking down the unserviceable capacitor from APFC paneland supply and fix cylindrical capacitor heavy duty of capacity 5 KVAR complete all as specified and directed.
79Taking down the unserviceable capacitor from APFC paneland supply and fix cylindrical capacitor heavy duty of capacity 7.5 KVAR complete all as specified and directed.
80Taking down the unserviceable capacitor from APFC paneland supply and fix cylindrical capacitor heavy duty of capacity 10 KVAR complete all as specified and directed.
81Taking down the unserviceable capacitor from APFC panel and supply and fix ylindrical capacitor heavy duty of capacity 15 KVAR complete all as specified and directed.
82Taking down the unserviceable capacitor from APFC panel and supply and fix cylindrical capacitor heavy duty of capacity 20 KVAR complete all as specified and directed.
83Taking down the unserviceable capacitor from APFC panel and supply and fix cylindrical capacitor heavy duty of capacity 25 KVAR complete all as specified and directed.
84Taking down the existing unserviceable automatic power factor control panel and supply and fix automatic power factor control panel microprocessor based incuding LED display input voltage 415 V AC,+-15 %,50 Hzs,three phase delta connection with heavy duty cylindrical capacitor and8 step controlof capacity 10 KVAr copmplete all as specified and directed. Make: Havells Cat Part No: QHKTCB5010X0 or techno commercially equivalent in ABB, Siemens, L&T, Schneider, C&S
85Taking down the existing unserviceable CT from the LT panel/APFC panel and supply and fix LT CT ring type suitable for primary current ratio 100/5 Amps, burden 5 VA, class 1.0 complete all as specified and directed.Make: Havells Cat Part No:QSCELFBOL001 or techno commercially equivalent in ABB, Siemens, L&T, Schneider, C&S
86Taking down the unserviceable dimmer from the servo voltage stabilizer of 75 KVA capacity and supply and fix dimmer or variable transformer of servo voltage stabilizer of 75 KVA capacity complete all as specified and directed.
87Taking down the unserviceable carbon brush from the servo voltage stabilizer of 75 KVA capacity and supply and fix new carbon brush of servo voltage stabilizer of 75 KVA capacity complete all as specified and directed.
88Taking down the unserviceable buck boost transformer from the servo voltage stabilizer of 75 KVA capacity and supply and fix new buck boost transformer of servo voltage stabilizer of 75 KVA capacity including necessary wiring complete all as specified and directed.
89Material and labour for servicing of servo voltage stabilizer of 75 KVA capacity including replacement of necessary wiring and copper lugs, contactors, relays etc complete all as specified and directed. Note: Rate quoted must be inclusive of necessary wiring and copper lugs required to be replaced but the contactors and relays if required to be replaced will be measured and paid separately.
Disclaimer :