| 1 | (B&R PORTION)Taking down door/window chowkhats with shutters exc 1.50 sqm and n exc 4.00 sqm each complete all as specified and as directed. |
| 2 | Dismantling floor, hearth or wall tiling including cement mortar bedding,removingrubbish off the premises complete all as specified and as directed. |
| 3 | M & L 25mm thick PCC 1:2:4 type B-0 (using 12.5 mm graded stone aggregate) as in floor sub base or levelling etccomplete all as specified and directed. |
| 4 | S & F 35 mm thick II nd class HW plain solid shutter chamfered or rounded fitted with cut and mitred, framing moulded into squares provide 0.9 mm thick both side decorative laminate type-I ofteak woodentexture of surface etc complete fitted to chowkhats all as specified and directed. |
| 5 | Taking down shutters of any description exc. 1 Sqm and n exc. 2 Sqm each and removing to store etc complete all as specified and directed. |
| 6 | S & F 150 mm long brass tower bolts with cast bolts etccomplete all as specificied and as directed. |
| 7 | M&L applying two coats of synthetic enamel paint over a coat ofred oxide or zinc chromate primer includingpreparation of new steel or iron surfaces exc 10 cm width or girth complete all as specified and directed. |
| 8 | Taking down cement plaster from brick / stone masonrysurface of wall including racking out joint , hacking for key and scrubing down with water etccomplete all as specified and directed. |
| 9 | M & L for 15mm thick plastering in cement morter 1:6 onbrick / concrete masonry surface finishedeven and smooth w/o using extra cement on internal surface ofwalls etc complete all as specified and as directed. |
| 10 | S & F 250 mm long brass sliding door bolts, with sand or die cast brasshasp staple and fixing bolts with rolled or dran brass etc complete all as specified & directed. |
| 11 | M&L for Rendring 20 mm thick, in two layers (each 10mm thick) in cm 1:4 on brick / concrete masonry surface, with using water proof compound Dr fixit or pedilite @ 3% by weight of cement in 2nd layer as per manufacturer\"s instructions & finishing the external surface of wall even & smooth withoug using extra cement all as specified and directed.Note : Water Proofing compound shall be measured and paid for seprately as \"Supply Only\" |
| 12 | S&F 100 mm long medium weightcold rolled mild steel butt hinges etc complete all as specified and directed. |
| 13 | S&F 150 mm brass handlescast type polished bright etc complete all as specified and directed. |
| 14 | S&F 140mmsizefloor door stopper of brass body and tongue with hard drawn steel spring complete all as specified and directed. |
| 15 | M&L for vitrified ceramic tiles 10 mm thick light coloured(square/rectangular) area of each tile exceeding 0.36 sqm but not exceeding 0.42 sqm, in floors etc.and jset & joineted neat in cement slurry and pointed in white or colour cement to match the tiles shade with & over 15mm thick screed bed in CM 1:6 complete all as specified and directed. |
| 16 | All as per item no15.00 above but as in skirting with and over 10 mm thick rendering in CM 1:6 on stone masonry surfaces or surfaces other than fair face of brick work / concrete surfaces complete all as specified and directed. |
| 17 | M&L for 20 mm thick machine cut Granite work as in steps, pillars,window cills, cooking plateforms and like with and incl 15 mm thick (avg thickness) cement mortar 1:4 screeding including pointing in white cement 1:2 using marble dust and admixture of pigment to match shade of granite including cutting, waste, rubbing andpolshing & moulding of edgesetc complete all as specified and directed. |
| 18 | Supply only integral water proofing compound of approved make all as specified & directed. |
| 19 | M&L forcompete removal of existing treatment on new/old wall surfaces and applying twocoats of 100% Premium acrylic emulsion paint having VOC less than 50gm/litre and UV resistance as per IS 15489 : 2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade over a coat of exterior primer@ 0.90litre/10Sqmover coat of 2 mm thick wall care putty includingpreparation of surfaces &necessary scaffolding required for painting work, safety measures etc complete all as specified and directed. |
| 20 | S & F powder coated aluminium (powder coating50 micron) for door,fxed partitions with extruded built up appropriatesections of approvedmake onfirming to IS : 733 & IS: 1285 ,incl the cost of EPDM rubber/neoprene gasket, cleat angle, aluminium snap beading for glazing /paneling ,stainless steel screws, etc complete all as specified and directed. |
| 21 | S & F powder coatedaluminium(powder coating50 micron) for three trac sliding windows with two glass shutters and one fly proof shutter with stainless steel wire mesh extruded built up appropriate section of approved make confirming to IS:733 & IS;1285incl the cost of EPDM rubber/neoprene gasket, cleat angle, aluminium snap beading of following sections a) three trac top and bottom sec 20957 b) shutters top, verticle and bottom sec 20605 c) three trac verticle sec 20958complete all as specified and directed. |
| 22 | S & F anodised aluminium powder coated sections weighing 0.55 kg /m framework with fixed glass ventillators using 4 mm thick plain glass andfollowingaluminium powder coated sections confiming to catalogue of \" JINDAL\" or of equvalent make and rubber beading etc all as directeda) SP-20048 b) 19352 complete all as specified and directed. |
| 23 | S & F 4 mm thick sheet glass ordinary quality plain/tinted glass for sliding shutter exc 0.50 sqm ineach pane etccomplete all as specified and directed. |
| 24 | M & L for preparation of new plastered surface of wall with premium acryllic smooth exterior paint with silicon additives of required shade two coats applied 1.43 litrs/10 Sqm over coat of exterior primer @2.20 kg /sqm etccomplete all as specified and directed. |
| 25 | S&Fgalvanised mild steel wire cloth, 0.36 mm nominal dia of wire and average width of aperture 1.40 mm and fixed with stainless steel wite staples complete all as specified and directed. |
| 26 | S & F suncontrol film of 50 micron reflective type to shutters complete all as directed by EIC.Make :- Garware or equivalent & approved) |
| 27 | S&F of mineral fibre acoustic suspended ceiling system with prima fine fissured tile( K2C2) with semi concealed grid , the tile should have humidity resistance (RH) of 99% , NRC upto 0.6, light reflectance> 83%, thermal conductivity K= 0.052 to 0.057 w/m, colour white fire performance class O/class 1 (BS476 part6 &7) in module sizeof 600x 600x16 mm with Bio block coating on the face of the tile, impact resistant and suitable for green bldg application, eith recycled content of 63 %. The tile shall be laid on semi concealed grid system with 15 mm white flange incorporating 6 mm central reveal in white/black colour and with web height of 38 mm and load carring capacity of minimum 11.68 kg/sqm.Silhouette. main runner and cross tees to have mitred ends & birdmouth notches to provide mitred cruciform junction. The T sections have galvanising of 120 gms/sqm and passed through 500 hrs of salt test. all as per manufacutrer\"s instructions Complete all as specified and as directed.(Make : Armstrong, saint Gobain or equivalentand approved make) |
| 28 | S & F for door closer hydraulically regulated cast iron body, designation No 1, universal type, suitable for door shutters upto 851 to 1000 mm width and weight betweenbetween 61 to 80 Kg of aluminium (Die cast) body complete all as specified and directed. |
| 29 | M&L forframed work such as grill, grating etc. with ends of bars shouldered or rebated or forged into spike framed guard bars barred iron doors, ladders, framed baluster, walk way, railing;frame work, including pintle hinges, stops, hand-made sliding bolts etc,sliding channels for sliding of gate and similar work conforming to Fe 290 Gde-E-165 complete all as specified & as directed. |
| 30 | (E&M PORTION)Installation, testing and commissioning of Diesel Engine driven Gen Set with sound proof acoustic enclosure cover to control the noise level as per limit of central pollution control board (CPCB) suitable for outdoor of capacity 40 KVA, water cooled with Automatic of Mains Failure Panel (AMF) and switch gears for automatic starting on main failure, 3 Phase 415 Volts, 1500 RPM, 4 wire 50 Cycles with two years maintenance spares and set of tools as recommeded by manufacturer\"s including the foundation for mounting of the DG set and comprising of the following:- (a) Desiel Engine :- Diesel engine developing power @ 1500 RPM. Our diesel engines are Vertical, electric start, compression ignition, 4 stroke, designed to run continuously at 1500 RPM confirming to IS 10002, ISO-3046, BS 5514 standard with an overload capacity of 10 % for one hour in every 12 hrs operation. Diesel Engine will comply with present CPCB norms. The diesel engine will comprise of following :-(i) Fuel pump with Mechanical Governor(ii) Dry type air cleaner(iii) Exhaust Silencer(iv) 12V Electric starting system (v)Lub Oil filter (Spin On Type)(vi)Fuel Oil filter (Spin On Type)(vii) Battery charging alternator(viii)First Fill of Lube oil |
| 31 | (b) Alternator. 40 KVA/32 KW suitable for continuous operation rated at 1500 rpm 415V 0.8 PF, 50Hz, 3Ph. In SPDP enclosure, self- excited & self- regulated, Brush less, floor mounted with Ball or Bearings on end shields. The alternator conforms to IS: 4722, BS EN 60034-1 & will be suitable for tropical condition. |
| 32 | (c)Base Frame : Suitable to couple above Engine & Alternator made from steel sheet metal. |
| 33 | (d) Fuel Tank : 8 Hrs Capacity, with Inlet & Outlet arrangement, air vent & drain plug arrangement. |
| 34 | (e) Battries : 1 No.12 V batteries with Leads and Battery Cable. |
| 35 | Supply and fix UPS 10 KVA/360V (3 Ph-3 ph), online UPS with isolation transfer, acceptable voltage range - 285 VAC - 475 VAC, frequency range - 50 Hz + 10% overall efficency - 91 %, Efficency (Battery mode) 91 %, Battery Type - SMF, 12 Volts 42 AH - 30 Nos of battery including fabricated open rack in black shade with link-set for batteries inter-connection, operating temperature - 0 - 50°C, Humudity : 0 - 90 % (Non Condensing) Noise level - less than 60dBA @ 1 meter. Output : 3 x 380/400 VAC + 1% (3 ph + N), 415 VAC (Adjustable), Frequency range - 50 Hz + 1%, Power Factor - 0.8, Overload capacity 110% for 10 mins including suitable size 3 phase wiring as required length for connecting battery, UPS and existing DB in bldg. Make : Microtek / Luminous / APC as approved. |
| 36 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with copper conductor of size 25 sq mm 4 core cable connecting lugs, glands, jointing materials etc., laid on wall, floors, roof, ducts and fixing using clamps, saddle complete all as directed by Eng-in-charge. |
| 37 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 Core cable connecting lugs, glands, jointing materials etc., laid on wall, floors, roof, ducts and fixing using clamps, saddle complete all as directed by Eng-in-charge. |
| 38 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth and getting out in any type of soil including forming bottom surface etc, complete all as directed by Eng-in-charge. |
| 39 | Returning, fillingin including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete complete all as directed by Eng-in-charge.. |
| 40 | Removing excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 50 mtr above the starting point complete all as directed by Eng-in-charge. |
| 41 | Supply & Laying 40 mm outside dia double wall corrugated pipe (DWC) ISI Mark for enclosing cable below ground / road surface, to a required depth, including suitable size coplers for jointing of pipe all as per site requirement complete all as directed by Eng-in-charge. |
| 42 | Material and labour for cutting of bituminous road / floor for laying of pipe / cables not exceeding 30cm wide and not exceeding 60 cm deep including refilling / with material and watering well ramming / compacting and making good with PCC 1:2:4, type B-1, 100 mm thick complete all as specified anddirected by Engr-in-Charge. |
| 43 | M &Lfor GI pipe 40mm dia \"\"light grade\"\"for road crossing / on wall / on pole for cable protection complete all as specified and directed by Engr-in-Charge. |
| 44 | Supply Fabricate, install, connect, test and commission Outdoor type dust & Vermin proof LT electrical panel board, 1100 volts, 50 Hz AC supply, fully compartmentalised for cable chamber and busbar chambers with adequate space made out of 3.15 mm thick CRCA sheet for load bearing like all over body, front and back cover with hinges and aldrops with DC locks CRCA poweder coated and 2.0 mm thick MS Sheet for non load bearing and portions, complete with one coat of powder coating including suitable angle iron/ flat iron frame work/ supports bottom 50x50x6 mm MS channel as base and chamber for metering equipment complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated and connection wirings with FRLS copper conductor complete mounted on PCC pillars foundation, cable connection using new lugs complete with danger notice all as specified and comprising of the followings:-(i) Existing cables which removed from old panel board will be fixed with new lugs during fixing in new panel board (if required) (ii) Getting of approval for Panel board drawing from Engr-in-Charge is necessary before fabrication. (iii) All swith gears should be fixed with 06 mm thick Fibre sheet Make: MES & CPRI approved make(iv) All MCCBs fixed with extended rotary handles ROM(v) Adequate space and independent compartment given to MCCBs & switch gears as directed(vi) Adequate space given to Each MCBs for easy cable connection and working. |
| 45 | a) LED/Neon indicator bulb in RYB Colour - 1 Set. |
| 46 | b) 4 No aluminium Bus bar 400 amps with chamber |
| 47 | c) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT |
| 48 | d) MCCB 4 Pole, 415 V, Adjustable thermal & adjustable magnetic type, 200A with breaking capacity 36 KA - 01 Nos |
| 49 | Out going: |
| 50 | e) MCCB 4 Pole, 415 V,adjustable type, 100 A with breaking capacity 16 KA - 02 Nos |
| 51 | f) MCCB 4 Pole 63 Amps - 02 Nos |
| 52 | g) suitable cable gland for incoming and outgoing cable |
| 53 | M & L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to using galvanised iron strip 25×4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including earth work , GI tube for watering, funnel with wire mesh, PCC pit with RCC cover and earth test point on completion complete all as specified and directed.Note :- Cost of earth lead & protection pipe upto 7.5m shall deemed to be included in quoted rate. |
| 54 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators sockets etc. to be measured separately), removing materials to store for keeping in safe custody for reuse at site and making good disturbed surfaces of walls, floors, etc. complete all as directed by Engineer-in-Charge |
| 55 | Taking down of old unserviceable sub main wiring of any type complete all as specified and as directed. |
| 56 | Taking down the existing unserviceable main switch / cut out / DBs of any type /metal plug & socket capacity / description as existing at site including necessary making good the disturbed surfaces to match with the existing finishes all as specified. |
| 57 | M&L Point wiring complete with 1.5 sqmm single core PVC insulated andunsheathed cable 1100 volts, FRLS grade with multistranded copper conductor ISI marked drawn throughPVC concealed conduit fixed to walls / roofs / floors / ceiling etc. and including provision of 1.5 sqmm stranded copper conductor cable as earth continuity conductor connected to common earth dolly with suitable size of PVC conduit and including cutting & chasing, modular cover plates and modular flush boxes, Plate for mounting for housing the switches, socket outlets, fan regulators etc, all as specified and as directed. |
| 58 | (a) One light point controlled by one way switch. |
| 59 | (b) One fan/exhaust fan point controlled by one switch and one regulator. |
| 60 | (c) One 3 pin switch socket outlet point 5 Amps on independent board. |
| 61 | (d) One 3 pin switch socket outlet point 5 Amps on same board with other switch. |
| 62 | All as per item above here in before but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 sqmm size complete all as specified and as directed. |
| 63 | S & Fix modular switch 1 way 6A, 1 module complete all as specified and as directed. |
| 64 | S & Fix modular switch1 way 16A, 1 module complete all as specified and as directed. |
| 65 | S & Fixmodular socketout let 6A 2/3 on combined 2 module complete all as specified and as directed. |
| 66 | S & Fix modular socket out let 6A/16A-2/3 pin combined 2 module complete all as specified and as directed. |
| 67 | S & Fix Ceiling rose surface backlite 65x50mm 3 terminals complete all as specified and as directed. |
| 68 | S&Fixfan regulator electronic 2 modular type volts AC 50 HZ, 4 step complete all as specified and directed. |
| 69 | S & Fix Batten General purpose industrial compact batten suitable for single or twin LED Tubelight with integral LED driver, available in single / double side connection CRCA batten suitable for mount LED tube rod 1 x 18 watts including necessary electric connections 3 core 1 sqmm insulated copper wire from ceiling rose to tube light fitting complete all as specifed and directed by Engineer-in-charge.Make - Havells or equivalent in Crompton/Wipro/Philips as approved. |
| 70 | S & Fix LED Tubelight (single side connection) for installation in existing tubelight luminaire with G13 lamp holders to give glare free light with necessary fixing arrangement etc complete all as specifed and directed by Engineer-in-charge. Make-Havells or equivalent in Crompton/Wipro/Philips as approved. |
| 71 | S & Fix of recess mounted 2\" x 2\" square LED panel 36 watts,Ultra modern recess mounting luminaire with high performance LEDs, suitable for mounting with Armstrong/Grid ceiling. Make : Havells or equivalent in Wipro/Philips/ Crompton as approved. |
| 72 | Taking down the defective ceiling fan / Exhaust fanof any sweep andmake after disconnecting electrically & mechanically and examine & carry out the servicing/overhauling the ceiling fan by thoroughly cleaning the bearing, shaft, stator, rotor & applying the lubricant / grease to the bearing including applying one coat of painting re-fixing, testing in all respect for smooth running complete all as specified and directed. |
| 73 | Supply and fixing ceiling fans complete with blades, down rods and accessories, 230 V, 1200 mm sweep with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) including taking down old U/s ceiling fan & depositing to MES store all as specified and directed. |
| 74 | M&L for submain wiring alongwith earth wire with the following sizes of FRLSPVC insulatedcopper conductor single core cable, multistrandedon the surface through and including suitable size of PVC conduit with its accessories all as specified and directed by Engr-in -charge for the following :- |
| 75 | (a) 2 x 6.0 sq mm and 1 x 6.0 sq mm as earth wire. |
| 76 | (b) 2 x 4.0 sq mm and 1 x 4.0 sq mm as earth wire. |
| 77 | S&Fix MCB DB VTPN4 ways,with metal double door ,IP -43 protection suitable for MCCB as incommer and MCB as out going,VTPN DB\"s 415 volt 3 phase complete with appropriate size copper bus bar and neutral link as required at site and including cutting chases to wall for fixing of DB and making good distrubed wall/surface all as required at site i.e directed by Engr-in charge.Make : Legrand or eqvt make in ABB/Siemens as approved. |
| 78 | S & Fix of MCCB TP, 415 volts, 63Ampere, rupturing capacity 16 KA, complete all as specified and directed. |
| 79 | S & Fix of MCB TP, 240 volts, 25 to 63 Ampere, rupturing capacity 10 KA, ‘C’ series complete all as specified and directed. |
| 80 | S & Fix sheet metal enclosure distribution board SPN, 12 ways 240 volts, with 200 amps rated bus bar, with IP 43 protection and double door, suitable for mounting MCBs including taking down old MCB DB complete all as specified and as directed. |
| 81 | S & Fix of MCB single pole and neutral, 240 volts, 6 to 40 Ampere, rupturing capacity 10 KA, ‘C’ series complete all as specified and directed. |
| 82 | S & Fix of MCB single pole, 240 volts, 6 to 40 Ampere, rupturing capacity 10 KA, ‘C’ series complete all as specified and directed. |
| 83 | S & Fix sheet metal enclosure MCCB DB suitable for DPX3 160 Amps, 4 pole, 415 V, including flushed on walls and making good disturbed surfaces including taking down the old DB suitable for MCCB complete all as specified and as directed. |
| 84 | S & Fix MCCB Tripple pole and neutral, 415 volts, 100 Amps, 4 pole all as specified and as directed. Make : Legrand or equivalent in AAB/Schneider/L&T as approved. |
| 85 | S & Fix Metal plug and socket DB\"s with MCB 20A SPN for AC complete all as specified and as directed. |
| 86 | Taking down split AC any capacity, make, model from exisitng position and carry out the servicing by cleaning indoor and outdoor unit with the terminal loose connections, applying the oiling/greasing to fan motor bearing all and in the locaiton as directed including shifting of the indoor/outdoor unit and existing voltage stablizer all as specified and directed by Engr-in-Charge. |
| 87 | Supply and install hi wall split units indoor/outdoorcomplete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality,with 5 star rating and with inverter technology of capacity 1.5 TR complete all as specified and as directed. |
| 88 | Supply and fix suction and discharge copper tubing pipe 3/8\" and 5/8\" for split type AC including provision of insulation on tubing, PVC insulated flexible multistranded copper cable 3 core 2.5 sqmm all as directed by Engr-in-charge. |
| 89 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4 KVA complete all as specified and as directed. |
| 90 | M & L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and as directed. |