Tender For Special Repair For Replacement Of Lt Panels And Apfc Panels Near P-94 And P-26 And Flood Lights, Street Lights And Garden Lights At Ins Hamla Under Ge(Nw) Bhandup, hamla-Maharashtra

Military Engineer Services-MES has published Tender For Special Repair For Replacement Of Lt Panels And Apfc Panels Near P-94 And P-26 And Flood Lights, Street Lights And Garden Lights At Ins Hamla Under Ge(Nw) Bhandup. Submission Date for this Tender is 01-12-2023. Halogen Light Tenders in hamla Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

40318904
Corrigendum : Tender For Special Repair For Replacement Of Lt Panels And Apfc Panels Near P-94 And P-26 And Flood Lights, Street Lights And Garden Lights At Ins Hamla Under Ge(Nw) Bhandup
Open Tender
Indian
Maharashtra
hamla
01-12-2023

Tender Details

Special Repair For Replacement Of Lt Panels And Apfc Panels Near P-94 And P-26 And Flood Lights, Street Lights And Garden Lights At Ins Hamla Under Ge ( Nw ) Bhandup

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 03-Nov-2023 DATE EXTENSION Date 17-11-2023
2 10-Nov-2023 DATE EXTENSION 2 Date 24-11-2023
3 13-Nov-2023 REVISED BOQ BOQ 24-11-2023
4 24-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-12-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 97000.0 /-
Tender Value
INR 48.50 Lakhs /-

BOQ Items

Name of Work : SPECIAL REPAIR FOR REPLACEMENT OF LT PANELS AND APFC PANELS NEAR P-94 AND P-26 AND FLOOD LIGHTS, STREET LIGHTS AND GARDEN LIGHTS AT INS HAMLA UNDER GE(NW) BHANDUP
Sl. No. Item Description
1Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 and it shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections with Aluminium Bus bars only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Location:- "P-26 Garden. Make:- Universal Switch Gear Control/HPL/Schnider/L&T
2The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 150 Amp 3 Strips, & Neutral 75Amp Aluminium conductors, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Blue Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).(iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three).(iv) CT 100/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos, OUTGOING SUPPLY :- (i) MCCB 63 Amps 16 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 02 Nos, (ii) MCB SPN 40 Amps 10 KA = 03 Nos, Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
3Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 and it shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections with Aluminium Bus bars only of adequate size complete.if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Location:- "P-94 Building. Make:- Universal Switch Gear Control/HPL/Schnider/L&T
4The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 300 Amp 3 Strips, & Neutral 150Amp Aluminium conductors, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Blue Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).(iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three).(iv) CT 200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 200 Amps 36 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 01 Nos, OUTGOING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 02 Nos, (ii) MCCB 63 Amps 25 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 04 Nos, (iii) MCB SPN 40 Amps 10 KA = 02 Nos, Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
5Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type,platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections Shall be Aluminium Bus bar only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed (Location P-136 Opposite) Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
6The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 600 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) R,Y,B,Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 400/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 400 Amps breaking capacity 36 KA, 4 Pole, 50Hz at 415 Volts, Thermal and Magnetic release with adjustable overload. OUTGOING SUPPLY :- (i) MCCB 160 Amps 25 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 01 Nos, (ii) MCCB 100 Amps 25 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 01 Nos, (iii) MCCB 63 Amps 25 KA, 4 Pole with Adjustable thermal & magnetic release 415 volts , 50Hz = 07 Nos, (vi) MCB SPN 40 Amps 10 KA = 02 Nos, Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
7Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections Shall be Aluminium Bus bar only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed. Location : Sea Shore Childernpark Panel Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
8The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 200 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) R,Y,B,Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 150/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 125 Amps breaking capacity 25 KA, 4 Pole, 50Hz at 415 Volts,FixedThermal and Magnetic release OUTGOING SUPPLY :- (i) MCCB 63 Amps 16 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 04 Nos. (ii) MCB 63 Amps 16 KA,TPN 415 volts ,50Hz = 01 Nos. (iii) MCB SPN 40 Amps 10 KA,50Hz = 02 Nos. Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
9Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type,platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections Shall be Aluminium Bus bar only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed. Location : Officers Mess Panel Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
10The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 300 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) R,Y,B,Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 200 Amps breaking capacity 35 KA, 4 Pole, 50Hz at 415 Volts, Thermal and Magnetic release with adjustable overload. OUTGOING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 03 Nos. (ii) MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 02 Nos. (iii) MCB SPN 40 Amps 10 KA,50Hz = 02 Nos. Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
11Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections Shall be Aluminium Bus bar only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed. (Location NSB Childern Park) Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
12The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 400 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) R,Y,B,Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 200 Amps breaking capacity 35 KA, 4 Pole, 50Hz at 415 Volts, Thermal and Magnetic release with adjustable overload. OUTGOING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. (i) MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 05 Nos. (iii) MCB SPN 40A ,10 KA -02 Nos. Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
13Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type,platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections Shall be Aluminium Bus bar only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed. Location : Near Cat School Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
14The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 300 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) R,Y,B,Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 400/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- (i) MCCB 200 Amps breaking capacity 35 KA, 4 Pole, 50Hz at 415 Volts, Thermal and Magnetic release with adjustable overload. OUTGOING SUPPLY :- (i) MCCB 125 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 03 Nos. (ii) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts ,50Hz = 01 Nos. (iii) MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
15Supply, installing, testing and commissioning factory made and tested 10 KVA Rated AMF Panel Indoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connectionscomplete all as specified and directed. The scope of work also comprising of the following:- (i) R,Y,B,Phase indicating Lights, Auto and Mains indicating LightsLED type 220V AC- 1 Set. (iii) Protection MCB 6 A SP C Series- 1 Set. (ii) Suitable size MCB"s and Contactors for Mians and 10 KVA DG Output Supply (iii)Auto and Mains Manual selector Switch Note : All MCCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes Location : MAP Pump house DG Panel Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
16Supply, installing, testing and commissioning factory made and tested APFC Panel Indoor type, 60 KVAR Capacity platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,and made of 2.00 mm thick Stainless Steel Sheet SS316 grade & suitable frame made out of MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal Connections Shall be Aluminium Bus bar only if MCCBrating is 100 Amps and above sizes, Copper wiring with PVC FRLS insulated multistranded copper conductor FRLS cable can be done of adequate size for MCCB rated below or equal 63 Amps complete all as specified and directed. Location : C Zone Sub Station Note :The contractor duly shall submit the Manufacturer"S Design and drawings of LT panels for approval of GE before placing the order. Make : Universal Switch Gear Control/HPL/Schnider/L&T
17BUS BAR CHAMBER :- (a) 300 Amp 3 Strips & Neutral Strip 200 Amp Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter ( VAF+PF ) 3 Phase- 01 Set. (ii) Red,Yellow,Blue Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).(iii) CT"s 160/5A, Make: L&T/ Trinity/ AE - 1 Set of 03 Nos.(iv) Protection MCB 6 A SP C Series- 5 Nos. (v) Auto/Manual Selector Switch 6A -08 Nos Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. INCOMING SUPPLY :- 1. MCCB 160 Amps 25 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., 2. Power Factor Correction relay 8 Stage 3 Phase, Make: L&T/ Epcos/ Trinity - 1 No. 3. Capacitor duty contactor & Standard Duty Power Capacitor for 20 KVAR, - 1 Nos. 4. Capacitor duty contactor & Standard Duty Power Capacitor for 10 KVAR, - 3 Nos. 5. Capacitor duty contactor & Standard Duty Power Capacitorfor 5 KVAR,- 1 Nos. 6. Capacitor duty contactor & Standard Duty Power Capacitorfor 9 Amp 3 Pole for 2 & 1 KVAR,-3 Nos. 6. MCB 63 A. 10 KA TP for 20 KVAR, Make: L&T/ Schneider/ HPL/ Legrand - 1 Nos. 8. MCB 25 A. 10 KA TP for 10 KVAR, Make: L&T/ Schneider/ HPL/ Legrand - 3 Nos. 9. MCB 16 A. 10 KA TP for 5 & 2 KVAR, Make: L&T/ Schneider/ HPL/ Legrand - 4 Nos. Note : All MCCB"S/MCB"S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
18Supply & Fixing 100Amps rated Current 3-Phase Onload LT Changeover Panel Indoor type, Wall mounted, suitable for 415 Volts 3 Phase 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-42 as per IS : 2147 shall be dust and vermin proof,with space for cable entry fromwith proper ferrule & cable gland,complete all as specified and directed Location -SE-I Pump House Make : Universal Switch Gear Control/HPL/Schnider/L&T
19Supply, installing ,testing and commissioing factory made and testedLT Outdoor Street Light/ Flood light Control/ Timer Panel withhaving platform mounted,suitable for 415 Volts 3 Phase and neutral 4 wire,50 HZ AC supply system shall be dust and vermin proof,protection class(IP-54) and made of 2.00 mmthick stainless steel sheet 316 L & suitable framework/Support made out of 40x40x5 mm MS Iron angle frame ,front opening type with aprons for cable entry,with proper ferrul and cable gland,internal wiring with PVC insulated multistranded copper conductor FRLS Cable of adequate size but not less than 4 sqmm complete. The scope of work also comprising of the following :- (i) RYB Phase indicating LED type -01 set. (ii) MCB TPN 40Amps 4 polez,10 KA,50 HZ,415 Volts-01 No (iii) Power contactor 3 Pole,40 Amps.50 Hz,415 Volts-01 No. (iv) Time switch Digital Type,one dial daily,240/415 Volts,50 Hz-01 No. (v) Auto/Manual selector switch 6A-01 No.(vi) RED Phase indicating light LED Type -01 No Location : B Zone S/S and High Mast Light Make : Universal Switchgear /HPL/Schnider/L&T
20Material and labour for earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground lavel) with top edge of the plate not less than 1.5mtr below normal ground lavel connected to GI Earth strip 32x6 mm by mean of bolts, nuts, check nuts and washer of brass all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including PCC pit and CI cover fullel with watering pipe, wire mess and copper lugs etc GI protection pipe 40 mm dia medium gradeincluding testing on completion all as specified and directed.
21Material and labour for earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground lavel) with top edge of the plate not less than 1.5mtr below normal ground lavel connected to Galvanised iron earth strip 25x4 mm by mean of bolts, nuts, check nuts and washer of brash all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including PCC pit and CI cover fullel with watering pipe, wire mess and copper lugs etc GI protection pipe 40 mm dia medium gradeincluding testing on completion all as specified and directed.
22Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting outin soft/loose soil for removing/laying of cables complete all as specified and as directed by Engineer-in-charge.
23Returning, filling in including spreading , leveling , watering and well ramming in layers n.exc 25 cm with soil complete all as specified and as directed by the Engineer-in- Charge.
24Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge.
25Supply and laying DWC(Double Wall Corrugate)HDPE pipes of pressure rating 6 Kg/Cm sq of size 40 mm dia IS: 16205(Part 24):2018 laid in trenches complete all as specified and directed.
26Supply and laying GI pipe 50 mm, light grade for the protection of the cable passing through road crossing, etc.
27Supply and Fixing GI pipe 40 mm, light grade for fixing the for Garden Lights include necessary length of cutting as well as reducers for suitable size of garden lights and making holes for entry cable and fixing clamps for placing junction boxes complete all as specified and directed.
28Suppl,Laying,Testing & commissioning of LTXLPE insulated,Screened,PVC bedded galvanised steel strip or wire armoured,electric power cables with aluminium stranded conductor,1100 volts,grade cross sectional area 4 x 16 sqmm confirming to IS : 7098(part-I) -1988 and as specified and directed by the Engr-in-Charge.
29Supply and layingcable LT XLPE insulated and screened PVC bedded, galvanised steel strip armoured electric power cable 10 sq mm 2 core (heavy duty) with Multi stranded aluminium conductor, 1100 Volts grade complete all as specified and directed by Engineer in charge.
30Material and labour for Cement Concrete 1:2:4 type B1 (using 20mm graded stone aggregate) for foundation, filling and mass concrete complete all as specified and directed.
31M&L for reinforced cement concrete 1:2:4, type B-1 (using 20mm graded stone aggregate) including 10 mm size verticle steel rods each having upto 1.5 mtr length and 8 mm rods for stirrups(06 Nos)for foudations, footings,columns, postd, pillarsetc & in any location, complete all as specified and directed.(For Pole Foundation)
32Supply and drawing through the pole for making connections to the light fittings,three core,PVC insulated and sheated, Heavy duty,1100 volts grade,multistranded copper conductor(FRLS) cable 3Cx2.5 sqmm, complete all as specified and directed
33Supply and fix in Replacement of Old U/S LED Garden bollard Light with warm white illumination 10-12 watt powermade in Di cast aluminium spigot housing with decorative opal diffuser and IP 65 protection complete including cable connection with connector complete all as specified and directed. Make: Jaquar Cart part No LBLDCON010XW or any equivalentmodel of Havells/Crompton/Philips/Surya as Approved by the GE.
34Supply and fix in Replacement of Old U/S post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Make : Surya cat part No SLE PT 20W ETPP or any equivalent of Bajaj/Crompton/Havells/Jaquar
35Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Make : Crompton cat part No LPTO-40-CDL-M or any equivalent of Bajaj/Surya/Havells/Jaquar
36S & F in replacement of old U/S PCC Pole with 7 meter long hot dipped galvanized octagonal poles with top A/F 70mm Bottom A/F 130mm, made out of 3 mm Thick HT sheet along with base plate of size 220 x 220 x 12 mm , including 1500mm long single arms,bracket made out of 48mm dia, GI pipe, M20 in PCD 205mm,700mm long and projected 100 "J" Type EN8 grade set of 04 Nos Foundation bolts alongwith templates,also including provision of the following : - (a) MCB SP 6A,230 V "B" series,10 KA Mounted on and including 3mm thick plastic laminated sheet-01 No.(b) 4 Way connector, bolt type having locking arrangement,weather proof and water proof control space -01 No. Notes :- (a) The rate quoted shall also be deemed to include the cost for provision of 50mm bore PVC pipe from cable trench to centre of the pole concrete. (c) The conncrete for foundation,Reinforced and formwork will measured and paid seperately. (e) The excavation and earth work for foundation of pole shall be measured and paid seperately Make :- Bajaj or its equivalent in Crompton/Philips/Wipro as approved by the GE.
37Supply and Fixing in replacement of old detiorated Steel Tubular Swaged Poles Complete wih MS Base plate,final taper plug,bolts,nuts and screws as specified type 410 SP-55 (11.00 meters long) Confirming to IS-2713 including applying Two coats of aluminium paint over a coat of red oxide zinc chrome primer over the exposed surface and applying two coats of bituminious paint over the embeded portion of pole,erecting truly verticle position Complete all as specified and directed.
38M&L fixing Cross arms, bracings, supports,clamps and back plates for above item Steel Tubularpoles fabricated from structural steel sections(all as directed by the Engineer-in-Charge) including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
39Supply and fixing in pole mounting FRP Junction box FRP type IP 55 Protection of size 250mm x 200mm x 100 mm, single phase with locking arrangements, including necessary nut, bolt and clamps of the flat iron of size 20mm x 3 mm comprising of MCB SP 6 Amps, 240 Volts, 10 KA, "B" series with proper fixing arrangements on pole complete all as specified and directed.Make: National/ Sintex
40Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
41Supply and fixing LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.
42Supply and fixing Multi LED flood light 200 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.
43Deduct Credit for Demolished/ Dismantled material Rs. (-) 92,325.00 (Minus) as listed in Schedule of CreditNote1: Tenderers will not quote against this item being a tentative amount to be considered to arrive at the "Contract Sum" Note 2:- The tenderer must keep in mind when quoting rates against items out in multiple store house having height 4 mts to 7 mts. Necessary scaffolding and saftey measures required during execution of work are including in this items.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail