Providing Alternate Source For 33/11 Kv S/S Lalbagh From 33 Kv Line Lalbagh Line Emananting From 132 Kv S/S Darshan Nagar Distt Ayodhya, ayodhya-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Providing Alternate Source For 33/11 Kv S/S Lalbagh From 33 Kv Line Lalbagh Line Emananting From 132 Kv S/S Darshan Nagar Distt Ayodhya. Submission Date for this Tender is 04-11-2023. Electrification Work Tenders in ayodhya Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

40214391
Corrigendum : Providing Alternate Source For 33/11 Kv S/S Lalbagh From 33 Kv Line Lalbagh Line Emananting From 132 Kv S/S Darshan Nagar Distt Ayodhya
Open Tender
Indian
Uttar Pradesh
ayodhya
04-11-2023

Tender Details

Providing Alternate Source For 33 / 11 Kv S / S Lalbagh From 33 Kv Line Lalbagh Line Emananting From 132 Kv S / S Darshan Nagar Distt Ayodhya- 1 Safeloading, Carriage And Then Safeunloading Of The Following Material From Store Centres Under The Jurisdiction Of Eeesd Ayodhaya To Dump Site Proper Stacking. 2 33 Kv Post Insulator 3 33 Kv Line Isolator 4 33 Kv Lightening Arrestor 5 Stp 11 Mtr. 6 M.S. Top Channel 125X65mm 3200 Mm 7 M.S. Angle 65X65x6 Mm Bracing, 4300 Mm 8 Gi Wire 6 Swg 9 33 Kv Pin Insulator Polymer Type 10 Stay Wire 7 / 8 Swg 11 Acsr Dog Conductor 12 33 Kv Cable 3X300 Mm Xlpe 13 33 Kv Straight Through Jointing Kit Indoor 3X300 Sq.Mm. Xlpe 14 33 Kv Cable Jointing Kit Outdoor 3X300 Sq.Mm. Xlpe 15 M.S. Channel 125X65 ( For Structures ) 16 M.S. Angle 75X75x6 ( For Structures ) 17 Lineisolator Structurefabrication Of Isolator Structures 3.5Mtr In Height As Per Drawing No. Res 39 Digging Of Two Nos. Pits Of Size 1.075 X 0.9 X0.3 Mtr Providing Stone Pad At The Bottom Of The Pit And Grouting Pad At The Bottom Of The Pit And Grouting Of Two Legs Of The Isolator Structure In Cc ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Of Ratio 1:4:8 In Block Of 1.075 Mtx 0.3 Mtr Including Supply Of All T&P Complete In All Respect. The Work Includes Dragging, Shifting Upto 40 Mtr. Raising And Erecting The Two Legs With Runner Of Isolator In Proper Allingment Level And Plumb. Plinths Of The Isolator Structure Shall Be Properly Finished With Champering Of Edges. ( All The Material Will Be Supplied By The Contractor Like M.S Flat Etc. Except Steel ) 18 Post Insulator Structurefabrication Of Of Post Insulatorstructure Per Drawing No. Res 39 Digging Of Two Nos. Pits Of Size 1.075 X 0.3 X0.3 Mtr Providing Stone Pad At The Bottom Of The Pit And Grouting Of Two Legs Of The Above Structure In Cc ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Of Ratio 1:4:8 In Block Of 1.075 Mtr X 0.3 Mtr X 0.3 Mtr Including Supply Of All T&P Complete In All Respect. The Work Includes Dragging, Shifting Upto 40 Mtr. Raising And Erecting The Two Legs With Top Frame Above StructureS In Properallingment Level And Plumb. Plinths Of All The Structure Shall Be Properly Finished With Champering Of Edges Etc. ( All The Material Will Be Supplied By The Contractor . Except Steel ) 19 Lightening Arrestor Structurefabrication Of 1 No Lightening Arrestor Structure& 2 Set Of Post Insulatorstructure Per Drawing No. Res 39 Digging Of Two Nos. Pits Of Size 1.075 X 0.3 X0.3 Mtr Providing Stone Pad At The Bottom Of The Pit And Grouting Of Two Legs Of The Above Structure In Cc ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Of Ratio 1:4:8 In Block Of 1.075 Mtr X 0.3 Mtr X 0.3 Mtr Including Supply Of All T&P Complete In All Respect. The Work Includes Dragging, Shifting Upto 40 Mtr. Raising And Erecting The Two Legs With Top Frame Above StructureS In Properallingment Level And Plumb. Plinths Of All The Structure Shall Be Properly Finished With Champering Of Edges Etc. ( All The Material Will Be Supplied By The Contractor . Except Steel ) 20 Laying & Dressing Of 3X300 Sq. Mm Xlpe Cable Underground Double Circuit.Laying Of Double Circuit 3X300 Sq .Mm Xlpe Cable In Normal Soil By Digging Of Trench 1050 Mm Deep, 750 Mm Wide Including Supply Of Required Materials, As 1St Class Bricks, Stone Slabs And Fine Sand. Providing 150 Mm Fine Sand Cusion Beneath, And 150 Mm Sand Cusion Above The Cable. The Cable Shall Be Duly Protected By Bricks, Sand And Stone Slab. The Inter Axial Spacing Between Two Cables Should Be In Between 0.25 To 0.04 M. After Laying The Cable Refilling And Ramming Of The Left Out Soil, Closing The Trench And Leveling. 21 Installation Of Line Isolators Assembling And Installation Of Line Isolator On The Isolator Structure , Adjusting Of Opening Mechanism In Proper Alignment So As To Ensured Smooth Operation Of The Same. In Case Of Line Isolator Proper Operation Of Earth Links Shall Also Be Ensured. The Work Includes Fabrication For Proper Fixing If Required. 22 Installation Of Post Insulator Installation Of Post Insulator On The Post Insulator Structure . The Work Includes Fabrication For Proper Fixing If Required. 23 Installation Of Lightening Arrestorsassembling And Installation / Mounting Of Lightening Arrestors On The L.A. Structure / Complete With Making Earth Connection ( Separate ) And Line Connections. The Work Includes Fabrication For Proper Fixing If Required. 24 Installation Of Heat Shrinkable Type Cable Jointing Kits Indoor And O / D End Termination And S / T Joint Suitable For 33Kv Xlpe Cable Confirming To Is Esi-09-13-Is-13573 Of 1992 Amendment I&Ii Vde-0278 Of Latest Version There Of If Any. 25 Safe Dragging / Loading - Unloading From Dump Site To Pit Site And Fabrication & Erection For Exposure Double Pole For 33 Kv Line On 11 Mtr St Pole With Fitting Of Necessary Clamp & Other Acessories Like 1 No. Top Channel Of 125X65x6 Mm Size 3200 Mm, Bracing Angle 1Set. .2 No.33 Kv Dropper Tee-Off Channel And 9 No. Pin Insulator As Per Norms. ( Contractor Shall Provide 2 No.33 Kv Dropper Tee-Off Channel G.I. Pin, E- Bracket 9 No., Necessary Clamps, , Nut - Bolts Washers Etc. ) 26 Grouting Of Following Structure By Digging Of Pit 1.5 Mtr / 1.83 Mtr Deep For 9.0 Mtr Pcc / 11 Mtr Stp Respectively, Placing Stone Pad At Bottom 450X450 Size Foundation Is Provided With Help Of Steel Or Wooden Formers, Groutung With 1:4:8 Ratio Cement, Sand & First Class Brick Ballast 0.268 / 0.285 Cu Mtr For 9.0 Mtr Pcc Pole & 11 Mtr Stp, Plinthing 0.3 Mtr Above G / L And Proper Plastering. 27 11 Mtr St Poles 28 Supply And Fixing Of A Stone Pad Of Size 300X300x75 Mm At Pcc / Stp Bottom Of The Pit ( Contractor Shall Provide All Materials ) 29 Earthing Of Pole By Earthing Rod 20X2500 Mm And 6 Swg Wire. ( Contractor Shall Provide All The Materials Except 6 Swg Wire ) 30 Fixing Of Barbed Wire On Polesupply And Fixing Of Barbed Wire On The Pole Above 2750 Mm Ground Level. Barbed Wirewrapped For A Distance Of 0.9 Mtr. With Apitch Of 13.Mm At A Height. ( All Materials Supplied By The Contractor ) 31 Fixing Of Danger Board .Supply And Fitting Of Danger Board Of Size 250X200x2 Mm 3650 Mm Above Ground Level As Per Respo Norms. Respo Drawing No-55 32 Fixing Of Number Plate .Supply And Fitting Of Number Plate Of Size 250X200x2 Mm 3650 Mm Above Ground Level As Per Respo Norms. Respo Drawing No-55 33 Nozeling And Grouting Of Stay At Sectional Pole At Angle Locations ( All The Civil Material And Stay Set, Stay Clamp Will Be Arranged By The Contractor Except Stay Wire ) 34 Cable Stand Structurefabrication & Erection Of 33 Kv Cable Stand Made Of 02 No. M.S Chanel 125X65x6 Mm 3 Mtr. Jointed To Each Other By M.S Channel Horizontally And Also Jointed To Each Other By Means Of 05 No. M.S Strip ( M.S Flat ) 50X6 Mm Of Size 200 Mm Long Each By Welding At Actual Distance Interval As Per Norms. And Grouting In Block Of 300X300x700 Completely Providing 02 No. Cable Clamps Also And Eathing By G.I Strip 50X6 Mm Size With The Earth Mat Of Switchyard Both Side Of Legs And Provideing Clamps , Post / Pin Insulator For Holding Cable. ( All The Materials Will Be Arranged By The Contractor Such That Clamps Nut Bolts And Civil Materials Except M.S Channel. ) 35 Earthing By Way Of Boring And Lowering The B Class Gi Pipe Of 55 Mm Dia From Ground Upto Water Level Not Less Than 20 Mtr. As Per Standard Practice . The G.I Pipe Which Laid Down Below The Railway Crossing Will Be Connected With G.I Strip 50X6. ( All Material Will Be Supplied By The Contractor ) 36 High Pressure Testing To Which 33 Kv Line & Cable To Be Stand For Duration Of 5 Minutes After Completion Of Laying, Stringing, Sagging, Binding And Jumpering Of Acsr Dog Conductor. ( Testing Equipment Will Be Arranged By The Contractor ) 37 Hoisting Of 33 Kv Cable On Existing / Erected Support With Provision Of Ms Pipe 150 Mm Dia 3 Mtr Long Suitable For 3X300 Sq Mm Cable Fixing Of Proper Support And Its Clamping, Providing Long Barral Lugs 6 Nos And P.G. Clamps & Y Shapejumpering Properly And 02 Nos. Supporting Angle 65X65x6, 2240 Mm Long And Making Connection Including Supply Of Jumpering Cable , Mounting Clamps As Per Resspo Norms. ( All Material Will Be Supplied By The Contractor Like M.S Pipe , P.G. Clamps, Al. Lug And Supporting Angle 65X65x6, 2240 Mm And Jumpering Cable Suitable For 33Kv Jumper ) . 38 33 Kv Bay Bus Bar & Stringing.Stringing Of 33Kv Bay Bus Bar By Using And Laying Of Acsr Dog Conductor Including Making Vertical / Horizontal ( Y-Shape ) Jumperconnection Through Pg Clamps And Connecting All The Equipments ( Bus Isolator, P.I. , C.T. , Vcb, L.A & T / F ) With Each Other Through Connecting Clamps. ( All The Material Will Be Supplied By The Contractor ) 39 Fabrication, Erection And Grouting Of Route Marker And Marking 33 Kv Line By Painting After Grooving On The Stone. ( Contractor Shall Provide Allmaterials ) 40 Providing Of G.I6Dia Pipe Pn-6 Specification 41 Laying Of Cable & G.I Pipelaying Of Double Circuit 33 Kv 3X300 Sq Mm Xlpe Cable And G.I Pipe By Drilling Method Below Railway Line. The Cable Be Laid At The Depth Of 3 Mtr From The Under Surface In G.I. Pipe ( 200 Mm. Dia. ) Casing. 42 Providing And Fixing Of G.I Strip50x6 With Its Proper Connection 43 Providing Of Hdpe 6Dia Pipe Pn-6 Specification 44 Laying Of Cable & Hdpe Pipelaying Of Double Circuit 33 Kv 3X300 Sq Mm Xlpe Cable And Hdpe Pipe By Drilling Method Below Nhai Road Crossing. The Cable Be Laid At The Depth Of 3 Mtr From The Under Surface In Hdpe Pipe ( 200 Mm. Dia. ) Casing. 45 Laying D / C And Hanging Of Cable Through 3X300 Xlpecable Inside The Trench At Proper Depth By Using Proper Size Of Clamps And The Clamping Must Be At A Distance Of 1 Mtr. Insure The Proper Separation Between Two Circuits. All The Material Shall Be Provided By The Contractor 46 Permission Of Railway Crossingpermission Must Be Granted From Railway Authority For Laying Of 33 Kv Cable And Pipe Under The Railway Crossing ( Final Settlement Of Payment Will Be On The Basis Of After Provindg Receipt And Agreement Of Permission Of Railway Crossing ) ( Estimate Value -500000 ) 47 Noc Will Be Granted From Central / State Electrical Safety Department. ( Final Settlement Of The Payment Will Be Done After Providing Receipt, Agreement And Permission Paper ) . ( Estimated Amount 150000 / - ) 48 Restoring The Road As It Is Before After Completion Of Work. ( Estimate Value Rs.500000 ) 49 Permission Of Nhai / Pwd Etc. For Road Crossing.. ( Final Settlement Of The Payment Will Be Done After Providing Receipt, Agreement And Permission Paper ) ( Estimate Value Rs.300000 )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Oct-2023 Date E Date 20-10-2023
2 20-Oct-2023 Dateest Date 25-10-2023
3 25-Oct-2023 Dateeste Date 27-10-2023
4 28-Oct-2023 Dateesten Date 28-10-2023
5 30-Oct-2023 Dateestend Date 01-11-2023
6 01-Nov-2023 Dateestende Date 03-11-2023
7 03-Nov-2023 Dateestenden Date 04-11-2023

Key Value

Document Fees
INR 5900 /-
EMD
INR 151000.0 /-
Tender Value
INR 1.50 Crore /-

BOQ Items

Name of Work: PROVIDING ALTERNATE SOURCE FOR 33/11 KV S/S LALBAGH FROM 33 KV LINE LALBAGH LINE EMANANTING FROM 132 KV S/S DARSHAN NAGAR DISTT AYODHYA
Sl. No. Item Description
1SafeLoading, Carriage and then safeunloading of the following material from Store Centres Under the jurisdiction of EEESD Ayodhaya to dump site proper stacking.
233 KV Post Insulator
333 KV line Isolator
433 KV Lightening Arrestor
5STP 11 Mtr.
6M.S. Top Channel 125x65mm 3200 mm
7M.S. Angle 65x65x6 mm Bracing, 4300 mm
8GI Wire 6 SWG
933 KV Pin Insulator polymer type
10Stay Wire 7/8 SWG
11ACSR Dog Conductor
1233 KV Cable 3x300 mm XLPE
1333 KV Straight through jointing kit indoor 3x300 sq.mm. XLPE
1433 KV cable jointing kit outdoor 3x300 sq.mm. XLPE
15M.S. Channel 125x65 (for Structures)
16M.S. Angle 75x75x6 (for Structures)
17LineIsolator Structure Fabrication of isolator structures 3.5mtr in height as per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.9 x0.3 Mtr providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 mtX 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with runner of isolator in proper allingment level and plumb. Plinths of the Isolator structure shall be properly finished with champering of edges.(All the material will be supplied by the Contractor like M.S Flat etc. except steel)
18Post Insulator Structure Fabrication of of Post Insulatorstructure per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure"s in properallingment level and plumb. Plinths of all the structure shall be properly finished with champering of edges etc.(All the material will be supplied by the Contractor . except steel)
19Lightening Arrestor Structure Fabrication of 1 No Lightening Arrestor structure& 2 set of Post Insulatorstructure per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure"s in properallingment level and plumb. Plinths of all the structure shall be properly finished with champering of edges etc.(All the material will be supplied by the Contractor . except steel)
20Laying & Dressing of 3x300 sq. mm XLPE Cable underground Double Circuit. Laying of Double circuit 3x300 sq .mm XLPE Cable in normal soil by digging of trench 1050 mm deep, 750 mm wide including supply of required materials, as 1st class Bricks, Stone slabs and fine sand. Providing 150 mm fine sand cusion beneath, and 150 mm sand cusion above the cable. The cable shall be duly protected by Bricks, sand and stone slab. The inter axial spacing between two cables should be in between 0.25 to 0.04 M. After laying the cable refilling and ramming of the left out soil,closing the trench and leveling.
21Installation of Line Isolators Assembling and installation of Line isolator on the Isolator structure , adjusting of opening mechanism in proper alignment so as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
22Installation of Post Insulator Installation of post insulator on the post insulator structure . The work includes fabrication for proper fixing if required.
23Installation of Lightening Arrestors Assembling and installation/ mounting of Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
24Installation of Heat Shrinkable Type cable jointing kits indoor and O/D end Termination and S/T Joint suitable for 33KV XLPE cable confirming to IS ESI-09-13-IS-13573 of 1992 amendment I&II VDE-0278 of latest version there of if any.
25Safe Dragging/ Loading - unloading from dump site to pit site and Fabrication & erection for Exposure Double pole for 33 KV Line on 11 Mtr ST Pole with fitting of necessary clamp & other acessories like 1 No. Top channel of 125x65x6 mm size 3200 mm, Bracing angle 1set. .2 No.33 Kv dropper tee-off channel and 9 No. Pin insulator as per norms. (Contractor shall provide 2 No.33 Kv dropper tee-off channel G.I. Pin, E- Bracket 9 No.,necessary clamps, , Nut - Bolts washers etc.)
26Grouting of following structure by digging of pit 1.5 Mtr/1.83 Mtr deep for 9.0 Mtr PCC / 11 Mtr STP respectively, placing stone pad at bottom 450x450 size foundation is provided with help of steel or wooden formers, groutung with 1:4:8 Ratio cement, sand & first class brick ballast 0.268/0.285 cu mtr for 9.0 mtr PCC Pole & 11 mtr STP, plinthing 0.3 Mtr above G/L and proper plastering.
2711 Mtr ST Poles
28Supply and fixing of a stone pad of size 300x300x75 mm at PCC/STP Bottom of the pit ( Contractor shall provide all materials)
29Earthing of pole by Earthing rod 20x2500 mm and 6 Swg wire. (Contractor shall provide all the materials except 6 swg wire)
30Fixing of barbed wire on pole Supply and fixing of barbed wire on the pole above 2750 mm ground level. Barbed wirewrapped for a distance of 0.9 mtr. with apitch of 13.mm at a height. (All materials supplied by the contractor)
31Fixing of Danger board . Supply and fitting of Danger board of size 250x200x2 mm 3650 mm above ground level as per Respo norms. RESPO Drawing No-55
32Fixing of Number plate . Supply and fitting of Number plate of size 250x200x2 mm 3650 mm above ground level as per Respo norms. RESPO Drawing No-55
33Nozeling and grouting of stay at sectional pole at angle locations (All the civil material and stay set, stay clamp will be arranged by the contractor except stay wire)
34Cable stand Structure Fabrication & erection of 33 KV Cable Stand made of 02 No. M.S chanel 125x65x6 mm 3 Mtr. Jointed to each other by M.S Channel horizontally and also jointed to each other by means of 05 No. M.S Strip (m.s flat) 50x6 mm of size 200 mm long each by welding at actual distance interval as per norms. And grouting in block of 300x300x700 completely providing 02 no. cable clamps also and eathing by G.I strip 50x6 mm size with the earth mat of switchyard both side of legs and provideing clamps , post/ pin insulator for holding cable. (All the materials will be arranged by the contractor such that clamps nut bolts and civil materials except M.S channel.)
35Earthing by way of boring and lowering the "B" class GI pipe of 55 mm dia from ground upto water level not less than 20 mtr. As per standard practice . The G.I pipe which laid down below the railway crossing will be connected with G.I strip 50x6. (All material will be supplied by the contractor)
36High Pressure testing to which 33 KV Line & cable to be stand for duration of 5 minutes after completion of Laying, Stringing, sagging, binding and Jumpering of ACSR Dog conductor. ( Testing equipment will be arranged by the contractor)
37Hoisting of 33 KV Cable on existing/erected support with provision of MS Pipe 150 mm dia 3 mtr long suitable for 3x300 sq mm cable fixing of proper support and its clamping, providing long barral lugs 6 nos and P.G. Clamps & "Y" shapejumpering properly and 02 nos. supporting angle 65X65X6, 2240 mm long and making connection including supply of jumpering cable ,mounting clamps as per RESSPO Norms. (All material will be supplied by the contractor like M.S Pipe , P.G. Clamps, Al. Lug And Supporting Angle 65X65X6, 2240 mm and jumpering cable suitable for 33KV jumper).
3833 KV Bay Bus Bar & Stringing. Stringing of 33KV Bay Bus Bar by using and laying of ACSR Dog Conductor including making Vertical/Horizontal (Y-shape) jumperconnection through PG clamps and connecting all the equipments ( Bus isolator, P.I. , C.T. , VCB, L.A & T/F) with each other through connecting clamps.(All the material will be supplied by the contractor)
39Fabrication, Erection and grouting of route marker and marking 33 KV line by painting after grooving on the stone. (Contractor shall provide allmaterials)
40Providing of G.I6"Dia Pipe PN-6 Specification
41Laying of cable & G.I Pipe Laying of Double circuit 33 KV 3x300 Sq mm XLPE cable and G.I Pipe by drilling method below Railway line. The cable be laid at the depth of 3 mtr from the under surface in G.I. pipe (200 mm. dia.) casing.
42Providing and fixing of G.I strip50x6 with its proper connection
43Providing of HDPE 6"Dia Pipe PN-6 Specification
44Laying of cable & HDPE Pipe Laying of Double circuit 33 KV 3x300 Sq mm XLPE cable and HDPE Pipe by drilling method below NHAI road crossing. The cable be laid at the depth of 3 mtr from the under surface in HDPE pipe (200 mm. dia.) casing.
45laying D/C and hanging of cable through 3x300 XLPEcable inside the trench at proper depth by using proper size of clamps and the clamping must be at a distance of 1 mtr. insure the proper separation between two circuits. All the material shall be provided by the contractor
46Permission of railway crossing permission must be granted from railway authority for laying of 33 kv cable and pipe under the railway crossing ( final settlement of payment will be on the basis of after provindg receipt and agreement of permission of railway crossing)(Estimate value -500000)
47NOC will be granted from Central/ state Electrical safety department.( Final settlement of the payment will be done after providing receipt, agreement and permission paper). (estimated amount 150000/-)
48restoring the road as it is before after completion of work.(estimate value Rs.500000)
49Permission of NHAI/PWD etc. for road crossing..( Final settlement of the payment will be done after providing receipt, agreement and permission paper) (estimate value Rs.300000)
Disclaimer :