Tender For Replacement Of Asbestos Sheet Along With False Ceiling And Rewiring In The Aor Of Age B/R Dett-Iii Of Ge 862 Ews, Rajouri-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Replacement Of Asbestos Sheet Along With False Ceiling And Rewiring In The Aor Of Age B/R Dett-Iii Of Ge 862 Ews. Submission Date for this Tender is 14-11-2023. Electrification Work Tenders in Rajouri Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

40206054
Corrigendum : Tender For Replacement Of Asbestos Sheet Along With False Ceiling And Rewiring In The Aor Of Age B/R Dett-Iii Of Ge 862 Ews
Open Tender
Indian
Jammu And Kashmir
Rajouri
14-11-2023

Tender Details

Tender For Replacement Of Asbestos Sheet Along With False Ceiling And Rewiring In The Aor Of Age B / R Dett-Iii Of Ge 862 Ews

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 26-Oct-2023 Corrigendum1 Date 07-11-2023
2 27-Oct-2023 Corrigendum2 BOQ 07-11-2023
3 07-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 14-11-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 99980.0 /-
Tender Value
INR 49.99 Lakhs /-

BOQ Items

Name of Work:-REPLACEMENT OF ASBESTOS SHEET ALONGWITH FALSE CEILING AND REWIRING IN THE AOR OF AGE B/R DETT-"III" OF GE 862 EWS
Sl. No. Item Description
1Sch "A" Part-I (B/R works) Dismantling of asbestos cement (corrugated, semi corrugated etc) sheeting, any gauge, thickness in roof covering complete all as specified and directed.
2S&F for Pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mmthick of approved colour having tensile strength 550 MPa as in roof covering/cladding to wall fixed with self tapping screws including side and end lap as per manufacturer’s instructions, complete all as specified and directed.
3S&F for Pre-painted galvalume aluminium zinc coating GI based Plain steel sheet 0.50mmthick of approved colour having tensile strength 550 MPa as in roof covering/cladding to wall fixed with self tapping screws including side and end lap as per manufacturer’s instructions, complete all as specified and directed.
4S&F for Pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mmthick of approved colour having tensile strength 550 MPa as in curve roof (of any radius) covering/cladding to wall fixed with self tapping screws including side and end lap as per manufacturer’s instructions, complete all as specified and directed.
5Dismantling of timber scantling 40 Sqcm and over in section, in any position as in unframed work complete all as specified and directed.
6Dismantling of wrought iron or mild steel work of any description not otherwise provided for, complete all as specified and directed.
7Demolition of cement concrete (unreinforced) in ground floor and paving n exc 15 cm thickness below or above the ground level, complete all as specified and directed.
8S&F for mild steel structural steel work as in roof trusses (framed), trussed, purlins, crane gantries, rails and fastening and heavy brackets framing (beam, tee, angle, channel or flat sections) including distance pieces, cleats, etc. conforming to Fe-410-W (Gde - E-250) quality A complete all as specified and directed.
9M&L for preparation of new or previously untreated steel or iron surfaces of any description over 10 cm width or girth not otherwise described and applying two coats of Synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
10Demolition of Brickwork or stone/boulder masonry, built in cement mortar including all quoins, arches, pillars, etc, but excluding ashlar facings, dressed stone-work and precast concrete articles complete all as specified and directed.
11M&L for stone walling of random rubble masonry, uncoursed, well bonded, bedded and soilidly hearted, built in cement mortar (1:6), complete all as specified and directed.
12All as per item No 11 here-in-before but except stone. Note:- Stone retrieved from item no 10 will be re-used.
13M&L for rendering 20mm thick in cement mortar (1:4)on stone masonry surface at any height, finished even and smooth without using extra cement complete all as specifed and directed.
14M&L for 4mm thick designer cement fibre ceiling boardin ceiling fixed with screw as per manufacturers instructions , laid over and including hot dipped galvanised iron in post grid with 24mm wide T section exposed flanges which shall be powder coated white.The frame work shall comprise of main runner made from 0.33 mm thick galvanised steel sheetof size 24 x 32 x 300 mm spaced at 12 mm centres securely fixed to the structural soffits by approved hangers at 1200mm maximum centres.Hangers of GI wire 4 mm dia to be fixed by approved rawl plug, level adjusters andscrews etc.The last hanger at the end of each main runner shall not be greater than 450 mm from adjacent wall flush fittings of 1200 mm long screws Tee with (double stiching) to interlocked between main runners at 600 mm centre to centre from 1200 x 600 mm modulescross tee longer than 600 mm modules to be formed by fittings 600 mm long cross tee, tee perimeter wall angle shall be of 0.45 mm thick galvanised steel of size 19 x 19 mm and 300 mm long of white colour all as per insturctions including dismantling of existing board etc complete all as specified and directed.
15Taking down cement plaster, any description on any walls etc including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed.
16M&L for rendering 15 mm thick in cement mortar 1:6 on fair faces of brick, stone or concrete surface, finished the surface even and smooth without using extra cement, complete all as specified and directed.
17M&L for preparation of new plastered surfaces of walls and applying two coats of distemper oilemulsion over one coat of 3mm thick wall care putty to make surface smooth and even, complete all as specified and directed.
18M&L for complete removal of existing treament of old plastererd surface of wall including washing rubbing down and stopping and applying two of distemper oil emulsion after preparation of surface, complete all as specified and directed.
19M&L for rendering 15 mm thick in cement mortar 1:4 on other than fair faces of brick, stone or concrete work, finished the surface even and smooth without using extra cement, complete all as specified and directed.
20M&L for preparation of new plastered surfaces of walls and applying two coats of exterior emulsion weather proof paint of apex ultima over and including a coat of primer, complete all as specified and directed.
21M&L for complete removal of existing treament of wall/roof surface including cornice and chajja etc and applying two coats of exterior emulsion weather proof paint of apex ultima after preparation of surface, complete all as specified and directed.
22Sch "A" Part-II (E/M works) Taking down carefully copper/ aluminum point wiring (light, fan, socket or power) complete, including all fittings such as switches, ceiling roses, pendants, regulators sockets etc.) removing material from the site and making good the disturbed surfaces of walls, floor or ceiling etc. to match with existing specifications, keeping aside serviceable items and removing to store for reuse within the same bldg or otherwise removing unserviceable items from site complete all as specified and directed. (Note: The decision of the Engr-in-Charge as to which materials are serviceable or otherwise credit to be afforded by the contractor for the unserviceable material shall be final and binding.
23M&L for point wiring for one light point/fan point controlled by one-one way switchwith 1.5 Sqmm. (nominal area) single core FRLS,PVC insulated 1100 Volts, grade multi stranded unsheathed copper conductor unsheathed in and including non metalic rigid PVCcasing & caping of 25mm width (Medium grade double locking system)complete with all acessories including PVC sunk box ISI marked for mounting of switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet as top cover, and 1.5 Sqmm. (nominal area) single core FRLS, PVC insulated 1100 Volts, grade multi stranded unsheathed copper conductor cable as earth wire upto common earth and connected to earth dolly including making goodthe diturbed surfaces compete all as specified and directed. (Note:- Three run of copper conductor of required size and one run of casing capping measured as one unit and also colour coding of wiring to be followed as red/yellow/blue for phase, black for neutral and green for earth)
24Description all as per srl item No. 23.00 above but for socket outlet 5 Amps on independent board complete all as specified and directed.
25Description all as per srl item No. 23.00 above but for socket out 5 Amps on same board complete all as specified and directed.
26Description all as per Serial item No 23.00 above but for one 3 pin 16 Amp socket outlet independent with2.5 sqmm PVC insulated FRLS multistraind copper cable with 2.5 sqmm single core multistraind FRLS copper cable as earthling lead complete all as specified and directed.
27S&F for switch piano flush type single pole one way 5 amps 240 volts complete all as specified and directed.
28S&F for switch socket combination 2 in 1, 5 pin, 6 amp flush type, 230 volts complete all as specified and directed.
29S&F for socket outlet 2 in 1, 5 pin, 5 amp flush type, 230 volts complete all as specified and directed.
30S&F for switch socket combination 2 in 1, 5 pin, 15 amp flush type, 230 volts complete all as specified and directed.
31S&F for ceiling rose 3 phase/PVC/polycarbonate isolated body surface bakelite2 to 3 terminals complete all as specified and directed.
32S&F for fan regulator electronic, step type hum free suitable to control speed of fan from 0 to 100% and connecting electrically complete all as specified and directed.
33S&F for lamp holder insulated body PVC/ Polycabonate type with back plate suitable for batten/angular/pendent fittings including LED lamp 9 wattcomplete all as specified and directed.
34M&L in repair for LED Tube light fitting, complete with 1x 20 watts, 4feet long, 220V, AC decorative box type with driver, holder in andincluding LED tube light connection complete prewiredand connecting electrically to ceiling rose to fitting using PVC insulated and overall sheathed flexible copper conductor cable of size 0.75 sqmm 3 core and connector block etc and necessary fixing arrangement at any height, complete all as specified and directed.
35S&F in replacement for environmental friendly, ultra modern, energy saving, surface mounted, decorative oval bulk head 10 watt 6000 K inbuilt LED luminaire comprising of high brightness LEDs, IP54 protection including connecting electricaly using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 0.75 sqmm complete as in repair all as specified and directed.
36M&L in repair for sheet metal enclosure MCB distribution board, double door single pole and neutral with IP-66 protection single phase 240 volt 8 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good disturb wall surfaces to match with existing specification, complete all as specified and directed. (Note:-MCBs will be measured and paid separately.)
37M&L in repair for MCB single pole,240 volts any rating from 6 to 32 amps, with rupturing capacity 10 KA, including providing thimble for out going cables, complete all as specified and directed.
38M&L in repair for MCB single pole & neutral 240 volts any rating from 40 to 63 amps, with rupturing capacity 10 KA, including providing thimble for out going cables, complete all as specified and directed.
39M&L for sub main wiring complete with 2 run of 4 sqmm, single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi strandedduly colour coded cable drawn through and including PVC casing and caping of size 25mm width or above as required at site and accessories such as tee, corners,overlaping connector etc of suitable size fixed on surface of walls/roofs/ceiling and including 01 run of 4 sqmm single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded of green colour as earth continuity conductor connected to common earth dolly including removing old unserviceable sub main wiring items complete all as specified and directed. (Note : -02 run of 4 sqmm single core copper conductor cable and 01 run of 4 sqmm single core copper conductor and 01 run of PVC casing and caping shall be measured as one unit and also colour coding of wiring to be followed as red/yellow/blue for phase, black for neutral and green for earth).
40Supply,laying, jointng and testing,XLPE insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 16 Sqmm 2 core laid in trenches, ducts, pipes, on poles and connection with necessary cables lugs, glands , complete after taking down old unserviceable cable all as specified and directed. (Note :- Excavation of earth work, removing, returning filling in, sand cushoining, concrete cable cover and protection GI pipe shall be measured and paid separetly and length of calbe shall be one length unless otherwise as directed by GE).
41Excavating in trenches, n.exc 1.5m wide and n.exc 1.5m in depth in soft loose soil for foundation, laying of cable/pipes/poles etc and getting out, complete all as specified and directed.
42Returning, filling in, trenches including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick ,complete all as specified and as directed.
43Removing excavated material, not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed.
44M&L for dry sand cushioning to underground cable, provided with a layer 8 cm thick before and 15 cm deep after laying and stretching jointing and testing the cable complete all as specified in SSR Part-I and as directed. (Note: Punned thickness of sand shall be measured and paid).
45M&L for brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat,size 230mm x 115mmx 75mm, complete all as specified and as directed.
46M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level, earth plate surrounded by and packed with 15 cm thick layer of char coal dust and common salt, earth lead GI wire 4.00 mm dia by means of bolts, Nuts, Check Nuts and washers of galvanized iron and thimbles and other end of the earth wire connected to main switch board and protected by galvanized iron pipe light grade 15 mm bore and water pipe 20 mm bore GI light grade with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-2 & RCC cover all as specified & shown in elect plate No. 3 of SSR part I of 2009 including testing on completion after dismantling of old unserviceable earthing with material etc. complete all as specified and directed. (Note:-Earthwork, Earth strip and protection pipe upto board is included in the rate quoted)
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail