Tender For Repair/Replacement Of Low Voltage Panels, Kiosk Box, Air Breaker Etc Electrification System And Repair/Maintenance Of Dg Sets, Amf Panels Installed At Different Location At Af Stn Faridabad In Aor Of Ge(Af) Faridabad, faridabad-Haryana

Military Engineer Services-MES has published Tender For Repair/Replacement Of Low Voltage Panels, Kiosk Box, Air Breaker Etc Electrification System And Repair/Maintenance Of Dg Sets, Amf Panels Installed At Different Location At Af Stn Faridabad In Aor Of Ge(Af) Faridabad. Submission Date for this Tender is 10-11-2023. Electrification Work Tenders in faridabad Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

40193242
Corrigendum : Tender For Repair/Replacement Of Low Voltage Panels, Kiosk Box, Air Breaker Etc Electrification System And Repair/Maintenance Of Dg Sets, Amf Panels Installed At Different Location At Af Stn Faridabad In Aor Of Ge(Af) Faridabad
Open Tender
Indian
Haryana
faridabad
10-11-2023

Tender Details

Repair/Replacement Of Low Voltage Panels, Kiosk Box, Air Breaker Etc Electrification System And Repair/Maintenance Of Dg Sets, Amf Panels Installed At Different Location At Af Stn Faridabad In Aor Of Ge(Af) Faridabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 03-Nov-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 10-11-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work: REPAIR/REPLACEMENT OF LOW VOLTAGE PANELS, KIOSK BOX, AIR BREAKER ETCR ELECTRIFICATION SYSTEM AND REPAIR/MAINTENANCE OF DG SETS, AMF PANELS INSTALLED AT DIFFERENT LOCATION AT AF STN FARIDABAD IN AOR OF GE(AF) FARIDABAD
Sl. No. Item Description
1Excavation in trenches in soft / loose soil not exceeding 1.5 Mtr wide and not exceeding 1.5 mtr depth for laying of cables/poles or foundation etc and getting outcomplete all as specified and directed by Engineer-in-Charge.
2Returning, filling, including spreeding leveling watering and well ramming in layers not exceeding 25 cmapart complete all as specified and directed by Engineer-in-Charge
3Removing of surplus excavated soil to distance not exceeding 50 Mtr from starting point and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed by Engineer-in-Charge
4Material and labor for sand cushioning to XLPE cable with using clean dry and natural river sand with a layer of 8 cm thick before laying the cable and 15 cm thick layer after laying the cable and this then gently punned down to a thick of 10 cm above the top the upper most cable complete all as specified and directed by Engineer-in-Charge
5Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer-in-Charge
6Supply,Laying,Connecting and testing in repairs cable XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volt grade cross sectional area 185 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge
7All as per item No 6 but Size 70 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge
8All as per item No 6 but Size 50 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge
9All as per item No 6 But Size 35 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge
10All as per item No 6 but Size 25 sqmm 4 core complete.All as specified and directed by Engr-In-Charge.
11All as per item No 6but Size 16 sqmm 4 core complete all as specified and directed by Engineer-in-Charge
12All as per item No 6but Size 10 sqmm 4 core complete all as specified and directed by Engineer-in-Charge
13Supply and Fix cable jointing kit,heat shrink type for 1100 volts grade,XLPE insulated armoured heavy duty electric cable with aluminium conductor,cross sectional area 6-16 Sqmm 4 core complete with jointing material and accessories including testing complete all as specified and directed by Engineer-in-Charge
14All as per item No 13 but Size 25-35 sqmm 4 core complete all as specified and directed by Engineer-in-Charge
15All as per item No 13 but Size 50-95 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge
16All as per item No 13 but Size 120 - 185 qmm 3.5 core complete all as specified and directed by Engineer-in-Charge
17S & F in repairs Earth test box made of powder coated, 3.15 mm thick, CRCA sheet,20 cm x 20 cm x 10 cm size conforming to CPRI approved and IP-65 protection class,right hinge openable type including mounting arrangement such as making hole in wall,providing MS clamp,nut,bolt etc complete manufactured through approved manufacturers complete all as specified and directed by Engineer-in-Charge
18S&F in repairs MCCB 3 pole 415 volts fixed type 160 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed by Engineer-in-Charge
19S&FMCCB 3 pole 415 volts in repairs,fixed type 63 Amps to 100 Amps with braking capacity 16 KA.after taking out old U/S one complete all as specified and directed by Engineer-in-Charge
20S&F in repairs MCCB 3 pole 415 volts fixed type 200Ampswith braking capacity 36KA after taking out old U/S one complete all as specified and directed by Engineer-in-Charge
21S&F in repairs MCCB 3 pole 415 volts fixed type 250Ampswith braking capacity 36KA after taking out old U/S one complete all as specified and directed by Engineer-in-Charge
22S&FMCCB 3 pole 415 volts in repairs,fixed type 32 Amps with braking capacity 16 KA.after taking out old U/S one complete all as specified and directed by Engineer-in-Charge
23S&F in Repairs Contactor, (4 Pole AC & DC Control) operational current AC1,160 Amps,poles composition- 4NO,DC control ref-LP1D80004 of TC complete all as specified and directed by Engineer-in-Charge
24S&F in Repairs Contactor, (4 Pole AC & DC Control) operational current AC1,125 Amps,poles composition- 4NO,DC control ref-LC1DT125A of TC complete all as specified and directed by Engineer-in-Charge
25S&F MNX 18, 3 pole contractor,2 NO+ 2 NC,415 volts AC, confirms to IS/IEC 60947 -4-1, in existing model and make including after taking out old unserviceable one, complete all as specified and directed by Engineer-in-Charge
26S&F MNX 95, 3 pole contractor,2 NO+ 2 NC,415 volts AC, confirms to IS/IEC 60947 -4-1, in existing model and make including after taking out old unserviceable one, complete all as specified and directed by Engineer-in-Charge
27S&F MNX 70, 3 pole contractor,2 NO+ 2 NC,415 volts AC, confirms to IS/IEC 60947 -4-1, in existing model and make including after taking out old unserviceable one, complete all as specified and directed by Engineer-in-Charge
28S&F MN contactor 18 Amps in existing model and make including after taking out old unserviceable one, complete all as specified and directed by Engineer-in-Charge
29S& F Panel LED indication lamps (R/Y/B) complete all as specified and directed by Engineer-in-Charge
30S&F Rotary switch of existing make L&T complete all as specified and directed by Engineer-in-Charge
31S&F in repairs digital volt meter ,415 volts,including after taking out old unserviceable one complete all as specified and directed by Engineer-in-Charge
32S&F in repairs digital Ammeter,415 volts grade,100 Amps rating,including and after taking out old unserviceable one complete all as specified and directed by Engineer-in-Charge
33S& F in capacitor 3 phase, 5 KVAR complete all as specified and directed by Engineer-in-Charge
34S& F in capacitor 3 phase, 10 KVAR complete all as specified and directed by Engineer-in-Charge
35S& F in capacitor 3 phase, 25 KVAR complete all as specified and directed by Engineer-in-Charge
36S& F in capacitor 3 phase, 2 KVAR complete all as specified and directed by Engineer-in-Charge
37S& F in capacitor 3 phase, 3 KVAR complete all as specified and directed by Engineer-in-Charge
38Supply and install reactive power manager in existing APFC panelcomplete all as specified and directed by Engineer-in-Charge
39M&L for servicing/testing of APFC(Automatic Power Factor Control) panel including checking of all internal connetions and replacement of spares if required complete all as specified and directed by Engineer-in-Charge Note - Spares to be measured and paid separately
40M & L for High quality powder coating on electric panels (Cubicle) installed at different places with synthetic enamel paint of suitable colour including and after scrubbing all body surface to get all foreign particles removed off,applying one coat of metal primer by disconnecting,removal of all accessories like bas bar, CTs,MCCBs and all wirings,equipments and refix with new Gun metal nut,bolt and washer complete with new copper lead wiring complete all as specified and directed by Engineer-in-Charge
41Boring of Holes under road, Pavement, hard Standing by trenchless technology using ultra Sound technique and necessary machine withHDPE Pipe, PN 10,100 mm dia complete all as specified and directed by Engineer-in-Charge
42M&L for earthing complete for pole with galvanized mild steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtr below ground level connected by using galvanised iron strip 25 X 4mm as earthing lead size by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, PCC (concrete chamber) 1:2:4 type B-1 using 20mm graded stone aggregate copy shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4 funnel wiht wire gauge of 22 gauge (0.68mm) 8 mesh per liner inch, 50 mm thick cover of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with 8 mm four MS bars @ 80mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of earth wire protected by 40mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, all excavation and earth work & connectiing the earthing to an earthing test point as specified and testing on complete all as specified and directed by Engineer-in-Charge
43Supply, laying and fixing in position in repairs galvanized iron pipe 80 mm bore light grade fixed to pole with mild steel clamps of required size or laid through wall/under floor/under road/in trenchesduly painted with two coat of black metallic paint after aprimer coat of red oxide complete all as specified and directed by Engineer-in-Charge
44All as per item No. 43 here in above but 50 mm dia complete all as specified and directed by Engineer-in-Charge
45All as per item No 43 here in above but 40 mm dia complete all as specified and directed by Engineer-in-Charge
46Design, fabrication, assembly, wiring and supply, installation, testing and commissioning of front operated cubicle type compartmentalised, front access free standing/Wall mounted, dust and vermin proof (IP 65 ingress protection) main LT Panel(Out door type) suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for fault level of 50 KA for 1 sec , fabricated from 3.15 mm thick CRCA sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement mounted on angle iron frame made out of 50x50x6 mm frame with 6 nos legs not less than 45 cm fixed with nuts bolts of suitable size,including 3 mm thick gland plates on top and bottom and including lifting hooks and including GI earth strip of required size with 2 nos earthing terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below LT Panel shall have provision for entry of cables from the top or bottom as requiredAll live accessible parts shall be shrouded and all equipment shall be finger touch proof. The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position Suitable arrangement shall be made for termination of multiple incoming cables. All kA values indicated shall be Ics breaking capacity. General Arangement drawings shall be got approved by GE before fabrication
47All as per item No 46 Contd....../- INCOMER : (i) MCCB 160 Amp, 35 KA, 4 pole 415 volts.1 Nos (incoming), (II) Digital Volt Meter (0-500V) =01 No., (iii) Digital Amps Mtr (0-200)=01 No.with suitable CT rating (iv) Selector Switches-02 Nos (3 phase volt meter,3 phase Ammeter), (v) Lamp LED,220 Volt, - 03Nos OUTGOING : (i) MCCB 125 Amp, 25 KA, 4 pole 415 volts - 02 Nos (ii) MCCB 63 Amp, 16 KA, 4 pole 415 volts - 03 Nos Note :MCCBs shall have adjustable thermal setting
48Design, fabrication, assembly, wiring and supply, installation, testing and commissioning of front operated cubicle type compartmentalised, front access free standing/Wall mounted, dust and vermin proof (IP 65 ingress protection) main LT Panel(Out door type) suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for fault level of 50 KA for 1 sec , fabricated from 3.15 mm thick CRCA sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement mounted on angle iron frame made out of 50x50x6 mm frame with 6 nos legs not less than 45 cm fixed with nuts bolts of suitable size,including 3 mm thick gland plates on top and bottom and including lifting hooks and including GI earth strip of required size with 2 nos earthing terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below LT Panel shall have provision for entry of cables from the top or bottom as required. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position. Suitable arrangement shall be made for termination of multiple incoming cables. All kA values indicated shall be Ics breaking capacity. General Arangement drawings shall be got approved by GE before fabrication
49All as per item No 48 Contd..../- Pre - dispatch inspection of panel shall be carried out by Rep. of accepting officer within overall cost quoted. INCOMER : (i) MCCB 315 Amp, 35 KA, 4 pole 415 volts.1 Nos (incoming), (II) Digital Volt Meter (0-500V) =01 No., (iii) Digital Amps Mtr (0-400A)=01 No.with suitable CT rating (iv) Selector Switches-02 Nos (3 phase volt meter,3 phase Ammeter), (v) Lamp LED,220 Volt, - 03Nos OUTGOING : (i) MCCB 160 Amp, 25 KA, 4 pole 415 volts - 02 Nos (i) MCCB 125 Amp, 16 KA, 4 pole 415 volts - 02 Nos (i) MCCB 100 Amp, 16 KA, 4 pole 415 volts - 01 No. Note :MCCBs shall have adjustable thermal setting
50Design, fabrication, assembly, wiring and supply, installation, testing and commissioning of front operated cubicle type compartmentalised, front access free standing/Wall mounted, dust and vermin proof (IP 65 ingress protection) main LT Panel(Out door type) suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for fault level of 50 KA for 1 sec , fabricated from 3.15 mm thick CRCA sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement mounted on angle iron frame made out of 50x50x6 mm frame with 6 nos legs not less than 45 cm fixed with nuts bolts of suitable size,including 3 mm thick gland plates on top and bottom and including lifting hooks and including GI earth strip of required size with 2 nos earthing terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below LT Panel shall have provision for entry of cables from the top or bottom as required. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position.Suitable arrangement shall be made for termination of multiple incoming cables. All kA values indicated shall be Ics breaking capacity. General Arangement drawings shall be got approved by GE before fabrication
51All as per item No 50 Contd......./- Pre - dispatch inspection of panel shall be carried out by Rep. of accepting officer within overall cost quoted. INCOMER : (i) MCCB 315 Amp, 35 KA, 4 pole 415 volts.1 Nos (incoming), (II) Digital Volt Meter (0-500V) =01 No., (iii) Digital Amps Mtr (0-400A)=01 No.with suitable CT rating (iv) Selector Switches-02 Nos (3 phase volt meter,3 phase Ammeter), (v) Lamp LED,220 Volt, - 03Nos OUTGOING : (i) MCCB 160 Amp, 25 KA, 4 pole 415 volts - 03 Nos (i) MCCB 125 Amp, 16 KA, 4 pole 415 volts - 3 Nos (i) MCCB 100 Amp, 16 KA, 4 pole 415 volts - 01 No. Note :MCCBs shall have adjustable thermal setting
52Supply and install and commmissionng of LT bus bar chamber CPRI approved out door type with sloping canopy of size 600x600x600mm made out of 3.15 mm thick CRCA sheet, panel shall be powder coated siemens grey shade mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4:8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200 mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 63 Amps,3 pole ,415 mps, 50 Hz of breaking capacity 25 KA as incomer complete all as specified and directed by Engineer-in-Charge
53Supply & fix porcelain vitreous LT 1.1 KV bushings withcopper/brass studs suitable for out door distribution transformers of capacity upto 400 KVAafter removing the oldunserviceable studs / bushings and draining out the transformer oil from the top level up to conservator of the transformer and removing the top cover of thecarefully and refixing and refilling the oil complete all as specified and directed by Engineer-in-Charge
54M&L forstone aggregate of size not exceeding 40 mm deposited spread and leveled in layers not exceeding 15 cm to a true surface of broken stones for transformer yard andpole structure area complete all as specified and directed by Engineer-in-Charge
55Surface dressing in hard / dense soilnot exceeding 15 cm deepand clearing all the grass weeds etc in the sub station yards after removing stone aggregate asideall as directed at site including setting / spreading back the aggregate including filling of river sand/ stone dust upto 15 cm complete all as specified and directed by Engineer-in-Charge Note:- (i)Stone dust/river sand shall be measured and paid separately under relevant items of this schedule. (ii)The rate also deemed to be included for labour (iii) All the sub station yards shall be kept cleanthrough out the contract period by removing the grass/weeds as many as times required depending on the growth of the grass.
56M&L for General Servicing ofDG sets upto 160 KVA , at run of 500 hours or 5 months which ever comes first(twice in Contract period based on condition ) comprising of Cleaning & greasing of the parts, Tappet setting as per standard, Fan belt, tensioner pulley and lever adjustments, Tightening of all the nuts, bolts and clamps, Testing & checking of AC & DC Wiring, Self & Charging Alternator cleaning and testing, checking of working & minor fault removal, Checking of Supply & return fuel pipes from fuel tank to engine. Checking of FIP timing by Fuel cut off method including Transportation, Labour charges & minor material required for servicing etc. as reqd complete all as specified and directed by Engineer-in-Charge Note - Servicing through OEM authorised rep or service engineer from the manufacturer only. (a) S&Flubrication of oil filter (b) S&Fby pass filter (c) Cleaning of hydraulic governer (d) S&F Checking and toping up of coolant (e) S&F fuel filter (f) S&F air cleaner element (g)S&F in Air filter (h) Cleaning of radiator complete set (j) Engine oil as per manufacturer specification and any other checking as per manufacturer instruction Note: Cost of unserviceable items will be measured and paid seperately under relevant items.
57All as mentioned item No.56 here in above but capacity ofDG set 100 KVA complete all as specified and directed by Engineer-in-Charge
58All as mentioned item No.56 here in above but capacity ofDG set 82.5 KVA complete all as specified and directed by Engineer-in-Charge
59All as mentioned item No.56 here in above but capacity ofDG set 62.5 KVA complete all as specified and directed by Engineer-in-Charge
60All as mentioned item No.56 here in above but capacity ofDG set 25 to 40 KVA complete all as specified and directed by Engineer-in-Charge
61Supply only the following items of DG Set of various capacity complete all as specified and directed by Engineer-in-Charge :-
62(a) Battery terminal, lug, bolts type suitable for heavy duty battery 12/24 V.
63(b) Battery leads copper conductor multi wired 35 Sqmm.
64(c) Hinges for DG set door of any size, any type as required on site.
65(d) Servo cool plus Radiator coolent
66(e) Low viscosity synthetic Engine oil 15W40
67M&L for Dismantling the radiator and fan from the engine for cleaning of copper tubes and cooling fins bydescaling solution andusing air compressor ,soldering on leakage, patch work and re-assembling the radiator and fitted with DG set properly including replacement of radiator hose pipe with clamps and bolt/nut with washer, leak check andpressure testing including transporting to repair workshop and bringing back for upto 62.5 KVA complete all as specified and directed by Engineer-in-Charge
68All as per item No 67 but capacity from 82.5 KVA upto 200 KVA complete all as specified and directed by Engineer-in-Charge
69Supply, replacment and testing of radiator assembly of DG Set 62.5 KVA complete all as specified and directed by Engineer-in-Charge
70Supply, replacment and testing of radiator assembly of DG Set 82.5 KVA complete all as specified and directed by Engineer-in-Charge
71Supply and replacement of low lube oil pressure sensor upto 160 KVA DG Set complete all as specified and directed by Engineer-in-Charge
72Supply and fixing in repair of Water Pumpof Radiatorsuitable for DG set Radiator up to 62.5 KVA complete all as specified and directed by Engineer-in-Charge
73All as per item No 72 but capacity from 82.5 KVA upto 200 KVA complete all as specified and directed by Engineer-in-Charge
74M&L for Removal & replacement offly wheel gear ring suitable for upto 62.5 KVA DG set connection & testing complete all as specified and directed by Engineer-in-Charge
75All as per item No 74 but capacity from 82.5 KVA upto 200 KVA complete all as specified and directed by Engineer-in-Charge
76M&L for Removal & replacement of thermostat suitable for upto 62.5 KVA DG set connection & testing complete all as specified and directed by Engineer-in-Charge.
77All as per item No 76 but capacity from 82.5 KVA upto 200 KVA complete all as specified and directed by Engineer-in-Charge
78Supply and fixing in repair of AVR for DG set having capacity 62.5 KVA complete all as specified and directed by Engineer-in-Charge
79All as per item No 78 but capacity from 82.5 KVA upto 200 KVAcomplete all as specified and directed by Engineer-in-Charge
80Supply and fixing in all type of hose pipe with clamps , over flow pipe, copper tube fuel supply pipe, etc with clip and complete fittingssuitable for DG set upto 62.5 KVA complete all as specified and directed by Engineer-in-Charge
81All as per item No 80 but capacity from 82.5 KVA upto 200 KVA complete all as specified and directed by Engineer-in-Charge
82S&F of under/over voltage relay 3 phase 415V for DG set of capacity upto 100 KVA complete all as specified and directed by Engineer-in-Charge
83Supply & Fixing in repair of Battary Charger 12V DC, 5 Amp of Autocut Electrical Battery Charger Unit SMPS with Constant Voltage Output with Battery Charging Transformer and Moulded Rectifier Unit etcsuitablefor smoothing functioning of DG set asrequired on site complete all as specified and directed by Engineer-in-Charge
84All as per item No 83 but capacity Battary Charger 24V DC, 10 Amp ccomplete all as specified and directed by Engineer-in-Charge
85Supply only distilled water for top up inBatteries complete all as specified and directed by Engineer-in-Charge
86Supply only electrolyte battery solution (Dilute sulphuric acid have specific gravity 1210 degree) in 10 litrs sealed gallon packing complete all as specified and directed by Engineer-in-Charge
87Supply & Fixing in DC 12V Stop Solenoid Coil suitable for DG Setcomplete all as specified and directed by Engineer-in-Charge
88Supply & Fixing in DC 24V Self Solenoid Coil suitable for DG Setcomplete all as specified and directed by Engineer-in-Charge
89Supply and replacement of Bty 12 Volt 100 AHsuitableDG set complete all as specified and directed by Engineer-in-Charge.
90Supply and replacement of Bty 12 Volt 180 AHsuitableDG set complete all as specified and directed by Engineer-in-Charge
91M&L for repairing of self starter of DG setcapacity 12 Volts including transporting upto workshop to carry out necessary replacement of burnt copper winding with new copper winding/ coil of existing gauge from rotor and stator coil, cleaning of slots, dryings varnishing and proper insulating to winding complete all as specified and directed by Engineer-in-Charge
92All as per item No 91 but capacity 24 Volts complete all as specified and directed by Engineer-in-Charge
93S&FCopper Battery leds suitable for Bty 12V complete all as specified and directed by Engineer-in-Charge
94Supply, fixing and testing for smoothing fuctioning Fan Belt suitable for DG set up to 62.5 KVA complete all as specified and directed by Engineer-in-Charge
95All as per item No 94 but capacity from 82.5 KVA upto 200 KVA complete all as specified and directed by Engineer-in-Charge
96M&L for carrying out complete over hauling/servicing of DG set panel /AMF panel/control panel including checking and rewiring of faulty electrical circuit using 1.5 Sqmm FRLS copper conductor for DG set of any type/make /capacity and making all electric connection and testing for smooth operation complete all as specified and directed by Engineer-in-Charge
97Supply and fixing in repair IOPS Module digital display controller unit suitable for exisitng DG Set complete all as specified and directed by Engineer-in-Charge
98S&F for fuel hose pipe from fuel filter to fuel pump for DG set upto 62.5 KVA complete all as specified and directed by Engineer-in-Charge
99S&F for fuel pipe from fuel tank to fuel filter for DG Set 82.5 KVA to 200 KVA complete all as specified and directed by Engineer-in-Charge
100Supply, fixing andtesting of charging alternator 12 V/24V complete all as specified and directed by Engineer-in-Charge
101Supply and fixing mounting rubber bushing set of 6 for existing generator complete all as specified and directed by Engineer-in-Charge
102M&L for attending of any breakdown of standby power supply in any location, whenever required round the clock, rectify the fault and restore the standby supply within three hours after receipt of complaint of any nature ie engine, alternator, control panel/AMF pael etc complete all as specified and directed by Engineer-in-Charge. Note- (i) The cost of replaced spare parts will be paid and measure seperatly. (ii) If complaint is not attended by contractor with in five hours the penaltyof Rs 500/- per hour to be imposed and amount of penalty will be deducted from RAR. (iii) The cost of transportation (to and from) for all kind of necessary equipment /T&P shall be arranged/brought by contractor to complete the job at site or at E/M Yard and no extra cost shall be paid to the contractor to this effect. (iv) Complaint shall be lodged by telephonically so contractor to specify the telephone/mobile No who will receive the complaint round the clock.
103Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of 62.5 KVA capacity three phase 415 Volts, 50 HZ AC including internal wiring with suitable copper conductor with thimbles, timer, relay, MCB 6 Nos- 10 Amps, VMR 3 pole - 02 Nos, battery charger 12 V - 01 No, Motorised changeover switch CX3 160 Amps, Volt meter/Ammeter, RYB phase indicators(DG and Mains), selector switchs etc including fixing with PCC work in floor alongwith suitable angle iron frame for AMF panel complete with all standard features, safeties etc., complete all as specified and directed by Engineer-in-Charge
104Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of 82.5 KVA capacity three phase 415 Volts, 50 HZ ACincluding internal wiring with suitable copper conductor with thimbles, timer, relay, MCB 6 Nos- 10 Amps, VMR 3 pole - 02 Nos, battery charger 12 V - 01 No, Motorised changeover switch CX3 160 Amps, Volt meter/Ammeter, RYB phase indicators(DG and Mains) and selector switchs etcincluding fixing with PCC work in floor alongwith suitable angle iron frame for AMF panel complete with all standard features, safeties etc. complete all as specified and directed by Engineer-in-Charge
105Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for diesel generating set of 100 KVA capacity three phase 415 Volts, 50 HZ AC including internal wiring with suitable copper conductor with thimbles, timer, relay, MCB 6 Nos- 10 Amps, VMR 3 pole - 02 Nos, battery charger 12 V - 01 No, Motorised changeover switch CX3 200 Amps, Volt meter/Ammeter, RYB phase indicators(DG and Mains) and selector switchs etcincluding fixing with PCC work in floor alongwith suitable angle iron frame for AMF panel complete with all standard features, safeties etc., complete all as specified and directed by Engineer-in-Charge
106M&L spray gun painting of generator upto 62.5 KVA in existing colour with smooth finishing complete all as specified and directed by Engineer-in-Charge
107M&L spray gun painting of generator 82.5 KVA upto 160 KVA in existing colour with smooth finishing complete all as specified and directed by Engineer-in-Charge
108Supply and fix Ventilation fan PVC (250 mm Sweep) with louvers and acessories complete all as specified and directed by Engineer-in-Charge
109Material and Labour for fixing white boards 5" x 4" as per site details ofLine digram / Machine History /Distribution boards complete all as specified and directed by Engineer-in-Charge
110M&L for repair maintenance of Steel rolling shutters greasing and sythetic enemal paint blue / black colour, includingball bearing,anchoring rod, hasp and staple push pull or manual type as per site requirement complete all as specified and directed by Engineer-in-Charge
111S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed by Engineer-in-Charge