Military Engineer Services-MES has published Tender For Repairs / Replacement Of Internal Wiring And Connected Items At Duty Coy, Kr Coy, &Square Barrack Area , Trg Shed & Education Bldgs And Certain Other Otm Accn Of Mrc Farm Area, Gorkha Camp Area, Mandir View Area, Lake View Area Centre St. Submission Date for this Tender is 04-11-2023. Electrification Work Tenders in wellington Tamil Nadu. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 28-Oct-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 04-11-2023 |
Sl. No. | Item Description |
1 | Taking down aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting, bell etc, and making good disturbed surfaces with smooth finish matching with the existing surface of walls, floors, etc. all as specified and directed. |
2 | Point wiring complete with 1.5 sqmm (nominal area) FRLS gradePVC insulated, unsheathed stranded copper conductor single core cable 1100 volts grade in and including PVC conduit medium grade complete with conduit fittings/accessories with provn of 1.2 mm thick MS/PVC terminal boxes of suitable size and 3 mm thick plastic laminated sheet top cover for housing of switches, sockets etc including 1.5 sqmmFRLS grade PVC insulated unsheathed stranded copper conductor cable for earth continuity conductor and connected to common earth dolly for One light/Ex-fan point controlled by one switch 5Amps SP all as specified anddirected. |
3 | All as per Item No 2 hereinbefore but One 3 pin5Aswitch socket outleton independent Board all as specified and directed. |
4 | All as per Item No 2 hereinbefore but One 3 pin 5A Socket outlet on same board complete all as specified and directed |
5 | All as per Item No 2 hereinbefore but point wiring complete with 4 sqmm FRLS cablefor 3 pin 15 A socket outleton independent board including 4 sqmmFRLS grade PVC insulated unsheathed stranded copper conductor cable for earth continuity conductor all as specified and directed. |
6 | Point wiring complete with 1.5 sqmm (nominal area) FRLS gradePVC insulated, unsheathed stranded copper conductor single core cable 1100 volts grade in and including PVC casing and caping complete with fittings/ accessories with provn of 1.2 mm thick MS/PVC terminal boxes of suitable size and 3 mm thick plastic laminated sheet top cover for housing of switches, sockets etc including 1.5 sqmmFRLS grade PVC insulated unsheathed stranded copper conductor cable for earth continuity conductor and connected to common earth dolly for One light /Ex-fan point controlled by one switch 5Amps SP all as specified and directed. |
7 | All as per Item No.6 hereinbefore but One 5Aswitch socket outlet on independent Board all as specified and directed. |
8 | All as per Item No 6 hereinbefore but One 5A Socket outlet on same board complete all as specified and directed |
9 | All as per Item No 6 hereinbefore but point wiring complete with 4 sqmm FRLS cable for 3 pin 15 A socket outlet on independent board including 4 sqmmFRLS grade PVC insulated unsheathed stranded copper conductor cable for earth continuity conductor all as specified and directed. |
10 | Material and labour for Point wiring complete with 1.5 sqmm (nominal area) FRLS gradePVC insulated, unsheathed stranded copper conductor single core cable 1100 volts grade in and including PVC conduit medium grade in concealed complete with conduit fittings/ accessories including 1.5 sqmmFRLS grade PVC insulated unsheathed stranded copper conductor cable for earth continuity conductor and connected to common earth dolly for One light/Ex-fan point controlled by one switch 5Amps SP all as specified and directed. Note: 1. Sunken box/ Cover plate for modular plate for modular switches, sockets etc will be measured and paid separately under relevant items and blank plate required if any will be deemed included in the item rate. 2.Cutting chases in stone masonry wall will be measured and paid separately. |
11 | All as per Item No 10 hereinbefore but One 5 Amps socket out let on independent Board all as specified and directed. |
12 | All as per Item No.10hereinbefore but point wiring complete with 4 sqmm FRLS cable for 3 pin 15 A socket outleton independent board including 4 sqmmFRLS grade PVC insulated unsheathed stranded copper conductor cable for earth continuity conductor all as specified and directed. |
13 | All as per item No.10 hereinbefore but point wiring One light point controlled by two 2 - way switches, with cables 1.5 sq.mm FRLS size all as specified and directed. |
14 | All as per Item No.10 hereinbefore but point wiring for each additional light point on the same switch circuit all as specified and directed. |
15 | All as per Item No.10 hereinbefore but point wiring complete One bell/ buzzer point controlled by one push button on the same board with other switches or independent with cables 1.5 sq.mm size FRLS all as specified and directed. |
16 | Switch piano flush type 5 Amps SP, one way all as specified and directed. |
17 | Switch piano flush type 15 Amps, all as specified and directed. |
18 | Switch piano flush type 15 Amps 2 way SP all as specified and directed. |
19 | Lamp holder, PVC/ Polycarbonate type with cord grip cap suitable for pendant fittings all as specified and directed. |
20 | Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings all as specified and directed. |
21 | Switch socket combination 2 in 1 , 5 Amps multipurpose flush type with PVC surface box all as specified and directed. |
22 | Switch socket combination 3pin 5A /15 A flush type, 2 in 1 all as specified and directed. |
23 | Bell Multi Music type 230 volts single pole all as specified and directed. |
24 | Bell push flush type 5 A all as specified and directed. |
25 | Ceiling rose, 3 terminals PVC / polycarbonate, isolated body all as specified and directed. |
26 | Modular switch one way 6A 230V AC 50 HZ SP one module all as specified and directed. |
27 | Modular switch one way 16A 230V AC 50 HZ SP one module all as specified and directed. |
28 | Modular socket 2/3 pin combined 6A 230V AC 50 HZ SP two module all as specified and directed. |
29 | Modular socket 6A/16A2/3 pin combined230V AC 50 HZ SP two module all as specified and directed. |
30 | Modular Bell push 6A 230V, AC 50 Hz SP One module all as specified and directed. |
31 | PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 100mm x 100mm x 50mm deep allas specified and directed. |
32 | PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 175mm x 100mm x 50mm deep allas specified and directed. |
33 | PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 200mm x 150mm x 50mm deep allas specified and directed. |
34 | PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 250mm x 200mm x 50mm deep allas specified and directed. |
35 | PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 350mm x 300mm x 50mm deep allas specified and directed. |
36 | Modular Metal Flush Box 1 or 2 module all as specified and directed. Make: Havells/ Legrand/ L&T. |
37 | Modular Metal Flush Box 3 module all as specified and directed. Make: Havells/ Legrand/ L&T. |
38 | Modular Metal Flush Box 4 module all as specified and directed. Make: Havells/ Legrand/ L&T. |
39 | Modular Metal Flush Box 6 module all as specified and directed. Make: Havells/ Legrand/ L&T. |
40 | Modular White Cover Plate with Frame, 1 module all as specified and directed. |
41 | Modular White Cover Plate with Frame, 2 module all as specified and directed. |
42 | Modular White Cover Plate with Frame, 3 module all as specified and directed. |
43 | Modular White Cover Plate with Frame, 4 module all as specified and directed. |
44 | Modular White Cover Plate with Frame, 6 module all as specified and directed. |
45 | Modular White Cover Plate with Frame, 8 module all as specified and directed. |
46 | Taking down unserviceable DBs with MCBs and Supply and fix MCB DB SPN 4 way 230 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. |
47 | Taking down unserviceable DBs with MCBs and Supply and fix MCB DB SPN 8 way 230 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. |
48 | Taking down unserviceable DBs with MCBs and Supply and fix MCB DB TPN 4 way 415 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. |
49 | Taking down unserviceable DBs with MCBs and Supply and fix MCB DB TPN 8 way 415 volts, double door type with minimum capacity of 200 Amps rated bus bar including necessary dummy plate and necessary civil works all as specified and directed. |
50 | Supply and fix 240V, 10 KA "B" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning all as specified and directed. |
51 | All as per item No. 50. hereinbefore but SPN 230V 32 Ampscapacity all as specified and directed. |
52 | All as per item No. 50. hereinbefore but MCB TPN 415V 40 to 100 Ampscapacity all as specified and directed. |
53 | Emergency LED bulb operating voltage 120-300 V AC IP 20 wattage 9 CCT 6500K lumen output 900 (Main) 350 (Battery) 4hr backupB-22 holder type all as specified and directed. Make: Panasonic Product code- PBUM13097 or equivalent in Philips/Bajaj. |
54 | Taking down old unsv FTL fittings, Supply and fix20W LEDbatten light Lum output 2000 CCT 6500K Size 115x2.5x3.5 cm comprises of thermally conductive material pre-wired with high efficiency electronic driver, high translucentserrated milky white diffuser gets glare free, smooth light distribution lamp colour white all as specified and directed. Make: Panasonic Product Code-. PBTM01207 or equivalent in Philips / Bajaj. |
55 | Taking down old unsv FTL fittings, Supply and fix24W LEDbatten light Lum output 2400 CCT 6500K Size 115x2.5x3.5 cm comprises of thermally conductive material pre-wired with high efficiency electronic driver, high translucentserrated milky white diffuser gets glare free, smooth light distribution lamp colour white all as specified and directed. Make. Panasonic Product Code-. PBTM06247 or equivalent in Philips / Bajaj. |
56 | Taking down old unsv FTL fittings, Supply and fix10W LEDbatten light Lum output 1000 CCT 6500K Size 59x2.2x3.4 cm comprises of thermally conductive material pre-wired with high efficiency electronic driver, high translucentserrated milky white diffuser gets glare free, smooth light distribution lamp colour white all as specified and directed. Make: Panasonic Product Code-. PBTM01107 or equivalent in Philips / Bajaj. |
57 | LED bulk head light fitting 12 W 6500K lumen output 1080 including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size all as specified and directed. Make: Panasonic Cat Part No-PBHM02127 or equivalent in Philips / Bajaj |
58 | Round shape 24 watt 220 volts AC 6500Klumen output 2400, 20 cm dia x 3.1 cm rimless surface panel type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. Make: Panasonic product code- PPAM16247R1 or equivalent in Philips/ Bajaj |
59 | LED luminaire 600mm x 600mm, 30 watt, 6000K, 100 Watts/Luman, 220VAC surface mounted type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, & LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. Make: Panasonic/Philips/ Bajaj |
60 | Taking down old unserviceable post top light fittings and supply and fixing post top lantern LED type 40 watt 230 volts AC out door type with decorative post top for 360 degree in direct light IP 65 protection with impact and corrosuon resistant complete with driver and lamp complete all as specified and directed. Make: Crompton product Cat ref- LPTC - 40 - WW or equivalent in Wipro/ Philips/Surya/Havells |
61 | Taking down unserviceable building security light and Material and labour for LED (street) Security Light fitting of 15 Watt comprising of epoxy powder coated housing enclosed with glass cover in frame with protection IP 66 complete wit all accessories and lamp colour white complete all as specified and directed. Make : Panasonic product code - PSTM23157 or in equivalent of Philips/Bajaj |
62 | Taking down unserviceable building security light and Material and labour for LED (street) Security Light fitting of 25 Watt comprising of epoxy powder coated housing enclosed with glass cover in frame with protection IP 66 complete wit all accessories and lamp colour white complete all as specified and directed. Make : Panasonic product code - PSTM23257 or in equivalent of Philips/Bajaj |
63 | Taking down unserviceable building security light and Material and labour for LED (street) Security Light fitting of 45 Watt comprising of epoxy powder coated housing enclosed with glass cover in frame with protection IP 66 complete wit all accessories and lamp colour white complete all as specified and directed. Make : Panasonic product code - PSTM23457 or in equivalent of Philips/Bajaj |
64 | Taking down old unserviceable geyser any type and capacity for servicing and overhauling of water supply connection, de-scaling, reshaping of inner cell complete including refixing the same after repair/servicing complete all as specified and directed. |
65 | S&F for replacement of heating element cup type 1 kw complete all as specified and and directed. |
66 | S&F for replacement of heating element triangular type 2/3 kw complete all as specified and and directed. |
67 | S&F for replacement of heating element 2/3 kw of solar water heater complete all as specified and and directed. |
68 | S&F for replacement of thermostat for geyser complete all as specified and and directed. |
69 | Supply and replacement of storage type steel body with copper inner tank of geyser of any capacitycomplete all as specified and and directed. |
70 | PVC connections 15mm size with PTMT nuts of length 300mm all as specified and directed. |
71 | Bib tap of size 15mm bore standard of PTMT any colour high pressure screwed for iron pipe and fixed (Minimum weight 15mm-90gms) in repairs all as specified and directed |
72 | PVC insulated copper conductor flexible cable 3 core 1.5 Sqmm including taking down old unserviceable copper conductor complete including testing all as specified and directed. Make : Polycab/Paragon/Gloster |
73 | Takingdown unserviceable Plug and socket and Supply and fix single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one 20A SP MCB all as specified and directed. Make-Legrand/ABB/Havells |
74 | Taking down Submain wiringwith aluminium conductor along with PVC Conduit and Material and Labour for Submain wiring with 2 runs of FRLS gradePVC copper conductor cable4 sqmm, multistranded along with FRLS grade PVC insulated copper earth continuity conductor 4 Sqmm drawn through and includingPVC Conduit pipe 20 mm dia with all fittings all as specified and directed. Note: 3 runs of cable and one run of conduit pipe together measured as one RM |
75 | All as per Item No 74 hereinbefore but in and including casing caping all as specified and directed |
76 | Taking down Submain wiring with aluminium conductor along with PVC Conduit and Material and Labour for Submain wiring with 2 runs of FRLS gradePVC copper conductor cable 6 sqmm, multistranded along with FRLS grade PVC insulated copper earth continuity conductor 6 Sqmm drawn through and includingPVC Conduit pipe 20 mm dia with all fittings all as specified and directed. Note: 3 runs of cable and one run of conduit pipe together measured as one RM |
77 | All as per Item No 76 hereinbefore but in and incl casing caping all as specified and directed |
78 | Earthing complete with galvanized steelearth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground(earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanized earth wire of size 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical platee No 3 connected to earth testing point including necessary excavation, earth work, PCC pit ,RCC cover 1:2:4 type - B1 with 8 mm dia MS bars at 100 c/c, funnel, watering pipe etc. complete all as specified and directed including testing on completion.Note : On testing after completion of earthing, if earth resistance is found achieved below 5 Ohms, then the earthing will be redone completely without any extra cost. |
79 | Supply and fix in repairs Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire all as specified and directed. |
80 | Cutting chases in brick/stone masonry wall/concrete floor/roof for laying PVC conduit and making good to facings where required and pointing in cement mortar 1:3, and making good, cutting not exc 10cm girth all as specified and directed. |
81 | Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as directed for 15 mm bore GI pipe and all as specified and directed. |
82 | 15 mm bore Tubes, "Medium grade" galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors all as specified and directed. |
83 | Taking down carefully unserviceable Exhaust fan of any size from its position dismantling blades, opening the fan motor, removing of defective parts such as ball bearing , bush, shaft, split pin, condenser, condenser holder, shackle, re-assembling after replacement of 3 core 0.75 Sqmm (24/0.2mm) flexible coppper cable from ceiling rose to connector, hanging in its position properly complete all as specified and directed. |
84 | Supply and replacement of exhaust fan condenser upto 4.0 Mfd, 240 Volt, AC complete all as specified and as directed. |
85 | Re-winding the stator complete with super enamelled copper conductor with the same size of the number of turns as that the old one insulating, varnishing and pre-heating for exhaust fan upto 300mm sweep complete all as specified and as directed. |
86 | Re-winding the stator complete with super enamelled copper conductor with the same size of the number of turns as that the old one insulating, varnishing and pre-heating for exhaust fan above 300mm sweep upto 450mm sweep complete all as specified and as directed. |
87 | Supply and fixing in repairs of exhaust fan blade for 300mm sweep exhaust fan complete all as specified and as directed. |
88 | GI Pipe Medium Grade 40 mm bore bracket of suitable size bent to shape of not less than 1.2m long with clamp made of GI flat Iron of size 32 x 6mm for street light fittings, duly painted with one coat of red oxide primer and two coats of aluminium based paint, fixed on poles with bolts, nuts and washers including taking down old brackets complete all as specified and directed. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy