Power Development Department has published Survey,Supply, Transportation, Carriage, Erection,Testing And Commissioning For Creation Of 63 Kva & 3X250 Kva Sub Stations Alongwith Erection Of 11 Kv Line On 9 Mtr. St Poles, 30Mm Sqacsr Weasel Conductor & Lt Line On 8 Mtr. St Poleat Wss Garnai Under Jj. Submission Date for this Tender is 02-11-2023. Road Cargo Transport Tenders in udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Garnai (Stage Intake) |
2 | 9 mtr. Long ST Pole (ST-410 SP-33) |
3 | GI V Cross -arm with top Bracket including clamps |
4 | GI Channel X-arm including clamps and Angle for braces |
5 | 30mm² ACSR conductor |
6 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
7 | PG Clamps for 30mm² ACSR Conductor |
8 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. |
9 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
10 | Galvanized Nuts and Bolts |
11 | Danger Plates with Clamps |
12 | Anti climbing device with clamps |
13 | Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm |
14 | Painting of 9 mtr ST poles with two coat of Aluminium Paint. |
15 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
16 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
17 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for creation of 63 KVA Sub stn. at WSS Garnai (Stage Intake) |
18 | 11/0.433 KV, 3-phase distribution Transformer 63 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate |
19 | Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type |
20 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
21 | 11 KV Horn gap fuse set 3 phase 200 A |
22 | 120mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type |
23 | 9 mtr. Long ST poles (ST-410 SP33) |
24 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
25 | GI Channel /Angle/flat of sizes including clamps |
26 | Galvanized Nuts and Bolts. |
27 | Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover |
28 | 11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm |
29 | LT distribution box for 100 KVA DTR with MCCB for incomer and SFU"s for outgoing circuits |
30 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
31 | PG Clamps |
32 | Danger Plates with Clamps |
33 | GI Barbed wire for Anticlimbing |
34 | 3-Phase 4 Wire LT Prodigy Meter with Box. |
35 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
36 | Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint. |
37 | Survey,supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Garnai (Stage Intake) |
38 | 8 mtr. Long ST poles (ST-410 SP15) |
39 | GI M Clamps for shackle insulator |
40 | 30mm²ACSR weasel Conductor |
41 | Shackle insulator |
42 | Galvanized Nuts and Bolts. |
43 | Danger Plates with Clamps |
44 | Anti climbing device with clamps |
45 | Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip |
46 | Painting of 8 mtr ST poles with two coat of Aluminium Paint |
47 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
48 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
49 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Garnai (stage Zero). |
50 | 9 mtr. Long ST Pole (ST-410 SP-33) |
51 | GI V Cross -arm with top Bracket including clamps |
52 | GI Channel X-arm including clamps and Angle for braces |
53 | 30mm² ACSR Weasel conductor |
54 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
55 | PG Clamps for 30mm² ACSR Conductor |
56 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. |
57 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
58 | Galvanized Nuts and Bolts |
59 | Danger Plates with Clamps |
60 | Anti climbing device with clamps |
61 | Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm |
62 | Painting of 9 mtr ST poles with two coat of Aluminium Paint. |
63 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
64 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
65 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for creation of 250 KVA Sub stn. at WSSGarnai (Stage Zero) |
66 | 11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 Copper Wound, & with LV Cable box having detachable Aluminium Gland plate |
67 | Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type |
68 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
69 | 11 KV Horn gap fuse set 3 phase 200 A |
70 | 300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type |
71 | 9 mtr. Long ST poles (ST-410 SP33) |
72 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
73 | GI Channel /Angle/flat of sizes including clamps |
74 | Galvanized Nuts and Bolts. |
75 | Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover |
76 | 11 KV Polymer composite pin insulator, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm |
77 | LT distribution box for 250 KVA DTR with MCCB for incomer and SFU"s for outgoing circuits |
78 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
79 | PG Clamps |
80 | Danger Plates with Clamps |
81 | GI Barbed wire for Anticlimbing |
82 | 3-Phase 4 wire Trivector Meter with CT PT Unit |
83 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
84 | Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint. |
85 | Survey,supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Garnai (Stage Zero). |
86 | 8 mtr. Long ST poles (ST-410 SP15) |
87 | GI M Clamps for shackle insulator |
88 | 50mm²ACSR Rabbit Conductor |
89 | LT Shackle insulator |
90 | Galvanized Nuts and Bolts. |
91 | Danger Plates with Clamps |
92 | Anti climbing device with clamps |
93 | Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip |
94 | Painting of 8 mtr ST poles with two coat of Aluminium Paint |
95 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
96 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
97 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Garnai (stage First). |
98 | 9 mtr. Long ST Pole (ST-410 SP-33) |
99 | GI V Cross -arm with top Bracket including clamps |
100 | GI Channel X-arm including clamps and Angle for braces |
101 | 30mm² ACSR Weasel conductor |
102 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
103 | PG Clamps for 30mm² ACSR Conductor |
104 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. |
105 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
106 | Galvanized Nuts and Bolts |
107 | Danger Plates with Clamps |
108 | Anti climbing device with clamps |
109 | Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm |
110 | Painting of 9 mtr ST poles with two coat of Aluminium Paint. |
111 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
112 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
113 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for creation of 250 KVA Sub stn. at WSSGarnai (Stage First) |
114 | 11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 Copper Wound, & with LV Cable box having detachable Aluminium Gland plate |
115 | Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type |
116 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
117 | 11 KV Horn gap fuse set 3 phase 200 A |
118 | 300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type |
119 | 9 mtr. Long ST poles (ST-410 SP33) |
120 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
121 | GI Channel /Angle/flat of sizes including clamps |
122 | Galvanized Nuts and Bolts. |
123 | Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover |
124 | 11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm |
125 | LT distribution box for 250 KVA DTR with MCCB for incomer and SFU"s for outgoing circuits |
126 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
127 | PG Clamps |
128 | Danger Plates with Clamps |
129 | GI Barbed wire for Anticlimbing |
130 | 3-Phase 4 wire Trivector Meter with CT PT Unit |
131 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
132 | Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint. |
133 | Survey,supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Garnai (Stage First). |
134 | 8 mtr. Long ST poles (ST-410 SP15) |
135 | GI M Clamps for shackle insulator |
136 | 50mm²ACSR Rabbit Conductor |
137 | LT Shackle insulator |
138 | Galvanized Nuts and Bolts. |
139 | Danger Plates with Clamps |
140 | Anti climbing device with clamps |
141 | Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip |
142 | Painting of 8 mtr ST poles with two coat of Aluminium Paint |
143 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
144 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
145 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Garnai (stage Second). |
146 | 9 mtr. Long ST Pole (ST-410 SP-33) |
147 | GI V Cross -arm with top Bracket including clamps |
148 | GI Channel X-arm including clamps and Angle for braces |
149 | 30mm² ACSR Weasel conductor |
150 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
151 | PG Clamps for 30mm² ACSR Conductor |
152 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. |
153 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
154 | Galvanized Nuts and Bolts |
155 | Danger Plates with Clamps |
156 | Anti climbing device with clamps |
157 | Earthing complete byGI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm |
158 | Painting of 9 mtr ST poles with two coat of Aluminium Paint. |
159 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
160 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
161 | Survey, Supply, Transportation, Carriage, Erection,Testing and Commissioning for creation of 250 KVA Sub stn. at WSSGarnai (Stage Second) |
162 | 11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 Copper Wound, & with LV Cable box having detachable Aluminium Gland plate |
163 | Gapless surge Arrestor, 9 kv, 10 KA , LA with polymer housing stn. Type |
164 | 11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical |
165 | 11 KV Horn gap fuse set 3 phase 200 A |
166 | 300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type |
167 | 9 mtr. Long ST poles (ST-410 SP33) |
168 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KVPositive and 80 KV Negative, creepage distance 320mm with fitting |
169 | GI Channel /Angle/flat of sizes including clamps |
170 | Galvanized Nuts and Bolts. |
171 | Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mmfor connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover |
172 | 11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm |
173 | LT distribution box for 250 KVA DTR with MCCB for incomer and SFU"s for outgoing circuits |
174 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
175 | PG Clamps |
176 | Danger Plates with Clamps |
177 | GI Barbed wire for Anticlimbing |
178 | 3-Phase 4 Wire Trivector Meter with CT PT Unit |
179 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
180 | Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint. |
181 | Survey,supply, Transportation, Carriage, Erection,Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Garnai (Stage Second). |
182 | 8 mtr. Long ST poles (ST-410 SP15) |
183 | GI M Clamps for shackle insulator |
184 | 50mm²ACSR Rabbit Conductor |
185 | LT Shackle insulator |
186 | Galvanized Nuts and Bolts. |
187 | Danger Plates with Clamps |
188 | Anti climbing device with clamps |
189 | Earthing complete byGI Rod 20mm 2.5 mtr. Long through GI Strip |
190 | Painting of 8 mtr ST poles with two coat of Aluminium Paint |
191 | Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole |
192 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail