Tender For Repairs/ Maint Of Internal Wiring Including Fittings/ Fixtures And Runway Lighting At Airfield Hanger Etc At Army Avn Units Under Ge Missamari.
Tender Overview
Project Description
Repairs/ Maint Of Internal Wiring Including Fittings/ Fixtures And Runway Lighting At Airfield Hanger Etc At Army Avn Units Under Ge Missamari.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-Oct-2023 | BOQ CORRIGENDUM | BOQ | 31-Oct-2023 |
| 2 | 21-Oct-2023 | REVISED SCH OF CREDIT | Other | 31-Oct-2023 |
BOQ
| Sl. No. | Item Description |
| 1 | Taking out Runway/Taxiway/Traffic light carefully from CI Transformer housing boxes by unscrewing nuts bolts and detaching isolating transformer and electrical connection repairing the same by opening Cover, re-wir-ing the Light Fitting with 6.0Sqmm solif Copper Conductor XLPECable, replacing unserviceable Parts as required/ordered,re-fix ing Light Fitting in Original Position after repaired and connecting up, complete all as specified and as directed.NOTE:– (a) Spare Parts such as Lamp, Holder, Isolating transformer, etc. wherever required will be measured and paid under appropriate Item(s) as ‘Supply only’. (b) Labour Element for replacement of unserviceable Parts is deemed to be included in the QUOTED UNIT RATE. |
| 2 | Taking out unsv/burnt UGControl Cable/ Runway lighting cable of any cross sectional area etc laying in trenchesall as specified and directed. |
| 3 | Taking out ATC Beacon from ATC Tower for repair and replacement of unsv component repair/rewinding of Synchronous motor and electrical connection repairing the same by opening Cover, re-wir-ing the Light Fitting with 4 Sqmm Copper Conductor Cablereplacing unserviceable Parts as required/ordered,re-fix ing Beacon in Original Position after repaired and connecting up, complete all as specified and as directed.NOTE:– (a) Spare Parts such as Lamp, Holder, Control cable, etc. wherever required will be measured and paid under appropriate Item(s) as ‘Supply only’. (b) Labour Element for replacement of unserviceable Parts is deemed to be included in the QUOTED UNIT RATE. |
| 4 | Material & labour for Segregation ofall parts of single phase 240 voltsSynchronous Motor of any type, make and capacity obtained from item no 3 above, cutting & removing existing burnt/short circuited winding wire complete, cleaning of core grooves and surfaces, rewinding the motor with superior quality enamelled copper winding wire of as original gauge, numbers of turns and coils including insulating material such as sleeves, cotton/PVC tape varnishing etc, reassembling the motorcomplete all as specified and directed by Engr-In-Charge. |
| 5 | Repair ofConstant current regulator panel at ATC CCR room by carefully opening of panel and removing unsv component and repair of unserviceable remote control desk ,including replacement of unserviceable IC,IGBT , Chip , IC Card, 20KW Transformer with panel control wiring complete all as specified and directed by Engr-in- charge. NOTE:– (a) Spare Parts such as IC,Chip , PCB electronic Card etc. wherever required will be measured and paid under appropriate Item(s) as ‘Supply only’. (b) Labour Element for replacement of unserviceable Parts is deemed to be included in the QUOTED UNIT RATE. |
| 6 | S&F in replacement of unsv IGBT as per sample for Constant current regulator 20 KW complete all as specified and directed. |
| 7 | S&F in replacement ofunsv chip as per sample for Constant current regulator 20KWcomplete all as specified and directed. |
| 8 | S&F in replacement of unsv PCB Electronic card as per sample for Constant current regulator 20 KW complete all as specified and directed. |
| 9 | S&F in replacement of unsv 20 KW output current transformer as per sample complete all as specified and directed. |
| 10 | Repair of unsv Constant current regulator panel at ATC CCR room by carefully opening of panel and removing unsv component and repair of unserviceable remote control desk ,including replacement of unserviceable IC,IGBT , Chip , IC Card, 7.5 KW Transformer with panel control wiring complete all as specified and directed by Engr-in- charge. NOTE:– (a) Spare Parts such as IC,Chip , PCB electronic Card etc. wherever required will be measured and paid under appropriate Item(s) as ‘Supply only’. (b) Labour Element for replacement of unserviceable Parts is deemed to be included in the QUOTED UNIT RATE. |
| 11 | S&F in replacement of unsv IGBT as per sample for Constant current regulator 7.5 KW complete all as specified and directed. |
| 12 | S&F in replacement ofunsv chip as per sample for Constant current regulator 7.5 KW complete all as specified and directed. |
| 13 | S&F in replacement of unsv PCB Electronic card as per sample for Constant current regulator 7.5 KW complete all as specified and directed. |
| 14 | S&F in replacement of unsv 7.5KW output current transformer as per sample complete all as specified and directed. |
| 15 | Supplylaying & testingin replacement LT UG XLPE sheathed PVC insulated, screened PVC bedded, Galvanised Steel Strip of Wire armoured Electric Power Cable heavy duty with stranded Aluminium Conductor 1100 Volt grade, cross-sectional area 16 Sqmm 4 Core, laid in trenches/surface of Wall/in GI Pipe along with Pole for connection to OH Lines including Brass Cable Glands Mild Steel Flat Iron Clamps, etc. and Testing, complete all as specified and directed.NOTE : Earthwork, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. |
| 16 | Supplylaying & testingin replacementLT UG XLPE sheathed PVC insulated, screened PVC bedded, Galvanised Steel Strip of Wire armoured Electric Power Cable heavy duty with stranded Aluminium Conductor 1100 Volt grade, cross-sectional area 25 Sqmm 3.5 Core, laid in trenches/surface of Wall/in GI Pipe along with Pole for connection to OH Lines including Brass Cable Glands Mild Steel Flat Iron Clamps, etc. and Testing, complete all as specified and directed.NOTE : Earthwork, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. |
| 17 | Supplylaying & testingin replacementLT UG XLPE sheathed PVC insulated, screened PVC bedded, Galvanised Steel Strip of Wire armoured Electric Power Cable heavy duty with stranded Aluminium Conductor 1100 Volt grade, cross-sectional area 50 Sqmm 3.5 Core, laid in trenches/surface of Wall/in GI Pipe along with Pole for connection to OH Lines including Brass Cable Glands Mild Steel Flat Iron Clamps, etc. and Testing, complete all as specified and directed.NOTE : Earthwork, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. |
| 18 | Supply,installation,testing and replacement of bidirectional approach light suitable for 200W, 6.6 Amp AC constant current series system with bi pin halogen Lamp complete with all accessories such as base plate ,breakable coupling,mounting assembly ,gasket, Lamp Holder,Lenses,bi pin,Secondary lead of adequate length etc confirming to ICAO Annex 14 complete bidirectional type with following fitments all as specified and as directed by Engr-in-Charge. Make:-AMA/THORN |
| 19 | (i) Clear /Clear |
| 20 | (ii) 180 degree clear /yellow |
| 21 | (iii) 180 degree Green /Red |
| 22 | (iv) 180 degree Amber/yellow |
| 23 | S&F in replacement Omni directional taxi way edge light suitable for use with 45 W 6.6 A AC constant current series system complete with accessories such as base plate breakable coupling mounting assembly gasket lamp holder lenses bi pin secondary lead of adequate length confirming to ICAO Annex 14 complete all as specified and directed by Engr in charge |
| 24 | Supply and replacement for the following Spares for taxiway / Runway light fittings.Make:-Thorn/AMA |
| 25 | (i) Halogen lamp bipin holder 200W ,6.6 Amp. |
| 26 | (ii) Halogen lamp bipin holder 45W ,6.6 Amp. |
| 27 | (iii) 180 deg Colour filters for runway lighting Red/Green/Yellow/Clear |
| 28 | (iv) Clear spreader lens for APN approach light |
| 29 | (v) Green spreader lens for APN threshold light |
| 30 | (vi) Red spreader lens for APN end light |
| 31 | (vii)Base plate without gasket and bolts |
| 32 | (viii) 360 deg outer clear lens for AUN Runway light fittimg. |
| 33 | (ix) AMA connector kits for 6 sqmmcopper conductor cable,5 KV Grade |
| 34 | (x) Breakable coupling for R/W/Taxi fittings |
| 35 | Supply installation testing in replacementof isolating transformer 5KV, 50 H Series type encapsulated in polyster resin for all moulded with neoprene rubber as specified and suitable for Air field lighting System confirming to FAA/ICAO andIS 12290 1987 of capacity200W ,6.6Amp,for runway lighting complete all as specified and directed by engr-in -charge.Make-AMA/THORN(Note:-Excavation,Sand cushioning,protective ,covering and refilling the trenches etc shall be measured and paid Separately) |
| 36 | Supply installation testing in replacementof isolating transformer 5KV, 50 H Series type encapsulated in polyster resin for all moulded with neoprene rubber as specified and suitable for Air field lighting System conforming to FAA/ICAO andIS 12290 1987 of capacity45W ,6.6Amp,for runway lighting complete all as specified and directed by engr-in -charge. Make-AMA/THORN |
| 37 | Supply ,laying ,jointing , testing and commisioning in replacement6 Sqmm Airfield lighting cable single core 5KV Grade solidcopper conductor PVC insulated PVC sheathed unshielded antitermiteand anti rodent treated unarmoured cable generally conforming to IS 1554 part I as amended upto date as specified in particularspecification and all as required |
| 38 | Supply and replacement of cast iron transformer housing boxes water tight cylindrical metal container of size 330 mm dia and 450 mm high all round cast iron moulding except top which will be 15 mm thick having two earth bolts nuts and washers 10 mm dia and one hole with GI nut to suit entry of 50 mm dia pipe .Opening on top with a cover plate to be fixed with neoprene rubber gasket etc ,including painting with one coat of synthetic paint as required including cement concrete/foundationPCC 1:2:4 using 20 mm graded crushed stone aggregate thickness of concrete 150mm in all the sides and 100 mm in bottom including dressing of earth soil and finishing with 12mm thick cement plaster 1:3 on exposed surface incl necessary excavation and earth work in any type of soil all as directed. |
| 39 | M&L for earthing complete with galvanised steel earth plate electrodesize 600x600x6.0mm thick buried directly in groundvertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanised earth lead wire 4.0 mm dia means of bolts, nuts, check nuts and washers of galvanised steel and GI pipe light grade 20mm dia bore for watering funnel with wire mesh refilling with vegetable soil without bolders and stones, gravels and aggregate etc,and CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion. NOTES : The unit rate includes for protection pipe and GI strip dia from top of earth plate up to 5.00 meter above ground level. |
| 40 | Excavationintrenchesnotexceeding1.5 M wideandnotexceeding1.5 Mindepthandgettingoutin soft/loosesoilorhard/densesoilfortakingup orlaying ofcableallasspecifiedanddirected. |
| 41 | Returning, filling inincludingspreading, levelling, wateringandwellramminginlayersnotexceeding25 cms complete all as specified. |
| 42 | Removing excavatedmaterialnotexceeding50 Manddepositingwheredirectedatalevelnotexceeding 1.5 Mabovestartingpoint complete all as specified. |
| 43 | M & L sand cushioning in trenches for cable protection with coarse sand laid dry in trenches with uniform thickness including consolidation complete all as directed. |
| 44 | M/Lfor brickwell burntlocallyavailablesubclass \"B\" laid over sand cushioningtocableintrencheskeepingwidthofbrickparalleltothelengthofcableall asdirected. |
| 45 | S & F in replacement GI Tubing light grade of size 50mm dia in protection of cable at road crossing /hard standing/pole protection fixed with clamp as per site requirement etc all as specified and directed. |
| 46 | S & F GI in replacement Tubing light grade of size 80mm dia in protection of cable at road crossing /hard standing/pole protection fixed with clamp as per site requirement etc all as specified and directed. |
| 47 | Repair and Maintenance of \"H\" & \"T\" indicator lampsincluding replacement of control wiring , painting of H/T indicator with existing yellow paint complete all as specified and all as directed. NOTE:– (a) Spare Parts such as Lamp, Holder, Control cable, etc. wherever required will be measured and paid under appropriate Item(s) as ‘Supply only’. (b) Labour Element for replacement of unserviceable Parts is deemed to be included in the QUOTED UNIT RATE. |
| 48 | Supply and fixing in replacementof Lamp of Higher suitable intensity as per aviation standard and as per sample obtained from item No 33here in before suitable for H/T indicator complete all as specified and directed by Engr in charge. |
| 49 | Supply and fixing in replacementof Lamp holderas per sample obtained from item No 33 here in before suitable for H/T indicator complete all as specified and directed by Engr in charge. |
| 50 | Supply of Beacon halogen 500W light as per sample obtained from item No 3 here in before suitable for ATC Beacon complete all as specified and directed by Engr in charge. |
| 51 | Supply and fix in replacementof LED Traffic lightsfitting Green / Red in Colour of 200mm dia with poly carbonate moulded body Red / Green in colour alongwith control box complete all as specified and directed . |
| 52 | Servicing/Overhauling of 3 Phase, 3HP capacity Induction Motoralongwith movable housing with following others repairs :-(a)Taking out Motor and movable housing from its Position and disconnecting all Cable Connections.(b)Dismantaling of induction Motor complete Part by Part carefully, testing all Coils, degreasing bearing and display all the Parts without damaging any portion for inspection of Engineer-in-Charge to ascertain the Serviceability of existing Parts.(c)Heating & Varnishing to Stator with super quality varnish and dried out properely with external heat as ordered and as directed.(d)Reassembeling the Motor complete with all existingServiceable Parts obtained against Item 1(b), greasing the Bearing with bearing grease and new Parts as ordered by Engineer-in-Charge (New Parts shall be measured and paid separately under relevant Itemhere-in after) (e)Reinstall the Motor at its existing Position, connecting all Cable connections and testing on completion complete all as specified and as directed. NOTE: i)Any unforeseen Minor Repairs and Minor Parts which are required to complete the repair work for smooth functioning of Motor are deemed to be included with the Unit Rate andlabour element involved in replacementis included in unit rate quoated against this Item.(ii)Transportation of motorparts for machining, rewinding from work site to lathe shop (Work shop) are deemed to be included with the Unit Rate.(iii)Rewinding ofMotor, any machine workwhere involved shall be measured and paid separetely against relevant Item of this Schedule. |
| 53 | Rewinding burnt coilsof Induction Motor of any make and type of capacity, 3Phase, 3HP, 415Volts with super enamelled copper winding wire as per existing size and guage to achieve therequired /specifiedRPM including taking out old unserviceable winding, cleaning/ repairing damaged slots, complete all as specified and as directed. |
| 54 | S & F in replacement3 phase ,32A/415 V plastic handle Reverse Forward Switch for 3 HP induction motor complete all as specified and directed. Make:- Fybross or equivalent in reputed supplier. |
| 55 | S & F in replacement3 phase,DOL Reversing Starters,complete with combination of 2 AC Electro Mechanical Contactor,with protection relay, Overload protection, Phase Loss, Phase Unbalance ,Suitable for 3 HP induction motor complete all as specified and directed.Make- L&T / Schneider / Seimens / Legrand |
| 56 | Greasing and overhauling of Hanger door guiding rail wheel , inclreplacement of unsv shaft bearings , replacement of unsv GI wire rope, replacement of broken shaft of door mechanismfor smooth movement ofthe hanger door leaves complete all as specified and directed by Engr-in- Charge .NOTE:– (a) Spare Parts such as Bearing, Wheel shaft, Wheel etc. wherever required to be included in the QUOTED UNIT RATE. (b) Labour Element for replacement of unserviceable Parts is deemed to be included in the QUOTED UNIT RATE. |
| 57 | S & F in replacement of \"V\"/ Chain belt drive for Transfer of power to hanger gate lower wheel, complete all as specified and as directed. |
| 58 | S & F in replacement of MCCB 4 Pole 250 Amps, thermal magnetic type DN2-250D with breaking capacity 36 KA with thermal magnetic release at 415 volts, including spreader terminal, Make:L&T / Legrand/ Schneider/Seimens complete all as specified. |
| 59 | Supplylaying & testingin replacementLT UG XLPE sheathed PVC insulated, screened PVC bedded, Galvanised Steel Strip of Wire armoured Electric Power Cable heavy duty with stranded Aluminium Conductor 1100 Volt grade, cross-sectional area 120 Sqmm 3.5 Core, laid in trenches/surface of Wall/in GI Pipe along with Pole for connec-tion to OH Lines including Brass Cable Glands Mild Steel Flat Iron Clamps, etc. and Testing, complete all as specified and as directed.Make - Polycab/ KEI/HavellsNOTE : Earthwork, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. |
| 60 | Taking down existing unserviceable Highbay light /Flood Light of any description/type/ size ,carefully from hanger Ceiling height of 18 mtr, batten/conduitincludingremovalof batten/ conduit/ gutties/ wooden boardscomplete all as specified and directed by Engr-in-charge. |
| 61 | Taking down the existing unserviceable main switch/ cut out/ DBs/ MCCB of any type/ capacity/ description as existing at site including making good the disturbed surfaces to match with the existing finishes all as specified. |
| 62 | Taking down the existing unservicable sub main wiring of any type / description as existing at site including making good the disturbed surfaces to match with the existing finishes all as specified. |
| 63 | M & L Submain wiring with 2 runs of single core 4 sqmm PVC insulated unsheated (FRLSH) multistranded 1100 volts grade with copper conductor drawn through and including non-metalic Rigid PVC Conduit ISI marked and itsaccessoriesincluding one run of single core 4.0 sqmm PVC insulatedunsheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductor for Highway / Flood Lights etc complete all as specified and directed. |
| 64 | M & L Submain wiring with 2 runs of single core 6 sqmm PVC insulated unsheated (FRLSH) multistranded 1100 volts grade with copper conductor drawn through and including non-metalic Rigid PVC Conduit ISI marked and itsaccessoriesincluding one run of single core 6.0 sqmm PVC insulatedunsheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductorcomplete all as specified and directed. |
| 65 | M & L Submain wiring with 4 runs of single core 6 sqmm PVC insulated unsheated (FRLSH) multistranded 1100 volts grade with copper conductor drawn through and including non-metalic Rigid PVC Conduit ISI marked and itsaccessoriesincluding one run of single core 6.0 sqmm PVC insulatedunsheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductorcomplete all as specified and directed. |
| 66 | M & L Submain wiring with 4 runs of single core 10 sqmm PVC insulated unsheated multistranded 1100 volts grade with copper conductor drawn through and including non-metalic rigid PVC concealled conduit ISI marked and itsaccessoriesincluding two run of single core 10 sqmm PVC insulatedunsheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductorcomplete all as specified and directed. |
| 67 | S & F in replacementEnergy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 Flood light fitting luminaire, with system efficiency =110 lumen/W,AC120-300 V with high power LEDs as light source and Secondary lenses 10KV SPD included with high efficiciency electronic driver of capacity 120 watts, with pre wired andnecessary mounting arrangement and provision of 4.00 sq mm three core flexable copper conductor cable multi stranded ,connected to existing points in Hanger beam angle of any description complete all as directed by Engineer- in-charge.Make: Make:Crompton, Cat NoLFLN-120-CDL/60-M, Model- PLUTO NEO, Make-Crompton or eqv in Havells/Philips |
| 68 | S & F in replacementEnergy saving new generation environmental friendly long life with high luminious efficacy upto = 150 LPW versatile presure die cast aluminium IP 66 protectedHighbay light fitting luminaire with descrete high lumen LEDs as light source and electronic driver of capacity 150 watts with pre wired andnecessary mounting arrangement and provision of 4.00 sq mm three core flexable copper conductor cable multi stranded ,connected to existing points in Hanger beam angle of any description complete all as directed by Engineer- in-charge.Cat NoCIP-320-150-57-60D-HL4-GL-NSR, Model- SURROUND HYPERION, Make- CROMPTON or eqv in Havells/Philips. |
| 69 | S&F in replacement LEDs aviation light energy saving new generation environmental friendly long life versatile presure die cast aluminium housing with polycarbonate enclosure with pre wired andnecessary mounting arrangements, provision of new 3 core multistrandedcopper conductor of size 23/0.193 and for fixing taking GI pipe pipe medium grade 40 mm dia 1.5 mtr long, complete all as specified and as directed. (Make :- BAJAJ, Cat Part No-110731 or equivalent in Havells/Phillips as approved by GE). |
| 70 | S&F in replacementElectronic LED Driver of suitable Capacity 150/200 Watt for Highbay/Flood Light, suitable for 220/230/240 Volt, complete all as specified and as directed. |
| 71 | S&F in replacementOctane LED 2X2PANEL ultra slim recess mounted edgelit LED 40Wattmodule with high brightness LED package and unique pattern de-glaring PP diffuser and PS LGP de-glaring diffuser sheet for glare free uniform light distribution suitable for armstrong / grid ceiling complete incl removal of old unsv fitting all as specified and as directed. Model No. LHEBAEP7PV1W040 of Havells or Equivalent in Crompton /Philps / Surya |
| 72 | S & F in replacement sheet metal enclosure MCB DBTPN 4 way with 200 amps rated bus bar 415 volts double door with magnetic locking system complete including removal of old unsv sheet metal enclosure complete all as specified and directed Make -L&T/Schneider/Seimens/Legrand |
| 73 | S&F Triple pole and earth encolsure with a threepin and earth plug with socket complete with one triple pole MCB 63 A ,5 Pin (3 P+N+E) Metal Plug & Socket Enclosure for Three Phase connection all as specified and directed. Model:- DBMPS463SD, Make :-L&T/Schneider/Seimens/Legrand |
| 74 | S & F MCB FP415 volts suitable for fixing in TPN DB of capacity 63 amps complete all as specified and directed.Model:-BB40630D Make :-L&T or equivalent in Schinider and Legrand/Indo Asian/Havells |
| 75 | Supply and fixing for single pole and neutral enclosure with a two pin and earth plug and socket complete with on one single pole MCB 20 Amp, 240 volts.Make:- L&T/Havells/Legrand |
| 76 | S & F MCBSPN230volts suitable for fixing on MCB DB of capacity 32 TO 40Ampscomplete all as specified. |
| 77 | S & F MCB SP 6 to 40 Amps 240 volts for fixing on MCB DB\"sall as specified. |
| 78 | S & F in replacementMCCB 4 Pole 200 Amps, thermal magnetic type DN2-250D with breaking capacity 36 KA with thermal magnetic release at 415 volts,including spreader terminal complete all as specified and directed. make: L&T Cat part No. CM92109OON1OGand equivalent in legrand and Indo Asian |
| 79 | S & F in replacement sheet metal enclosure MCBVTPN 12 wayDouble door Ready to use DBs - Provided with insulated vertical phase bus-bars |neutral bar/s with shroud/s | earth bar/s | sticking saddles | cement spill protector | color-coded interconnecting wire set | cable ties | blanking plates and circuit identification labels With provision for4 Pole MCCB 200 A as incomer and SP/SPN MCBs as outgoing complete all as specified and directed.Model:- DBVTM012DD, Make L&T and equivalent in legrand /Schneider / Seimens |
| 80 | Taking down existing unserviceable point wiring of any description/type/ size of light/fan/tube/power/two way/bell etc on TW batten/conduit includingremovalof batten/ conduit/ gutties/ wooden boards/ switches/ sockets/ regulators/ light fittings etc and seperating the serviceable items like fan regulators and light fittings for re-use under respective items and removal of unserviceable material out of site and making good the disturbed surfaces of wall/ceiling so as to match with the existing finishes all as specified. |
| 81 | M&L Point Wiring with 1.5 Sqmm Copper Conductor single core PVC insulated Flame Retardant Low Smoke (FRLSH) Unsheathed 1100 Volt grade multi-stranded Cable drawn through and including PVC Casing and Caping medium grade of suitable size and its Accessories as required at Site, fixing on surface of Wall, Roof, mounted on Sunk Mild Steel Pressed Terminal Box 1.22mm thick of suitable size duly painted with red oxide metal primer with 3.0mm thick Plastic Laminated Sheet Top Cover for mounting Switches, Sockets, etc. including PVC insulated and unsheathed Single Core multi-stranded Copper Conductor Cable of size 1.5 Sqmm (FRLSH) Green in Colour as Earth Continuity Conductor connected to Common Earth and Earth dolly for One Light Point controlled by One 1-Way Switch 5 Amp, complete all as specified and as directed.Make : KEI/Polycab/Havells |
| 82 | Description all as per item No 67here in before but for one Ceiling Fan / exhaust fan point controlled by one, one way switch and regulator.Make : KEI/Polycab/Havells |
| 83 | Description all as per item No 67here in before but for one 3 point 5 Amps switch socket outlet point controlled by one switch on the same board.Make : KEI/Polycab/Havells |
| 84 | Description all as per item No 67 here in before but for one 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board .Make : KEI/Polycab/Havells |
| 85 | Description all as per item No 67here in before but for one bell point controlled by one, one way bell switch 5 Amps.Make : KEI/Polycab/Havells |
| 86 | Description all as per item No 67here in before but for one light point controlled by one, two way switch 5 Amps.Make : KEI/Polycab/Havells |
| 87 | Description all as per item No 67here in before butusing 2.5 sq mm single core copper conductor cable of multistranded flame retardant Low smoke (FRLSH) PVC insulated unsheathed 1100 volts grade for 5/15 amps switch socket cobmination point incl running of2.5 sq mm copper conductor flame retardant PVC wire as earth continuity conductor along with wiring and connecting to the common eath dolly.Make : KEI/Polycab/Havells |
| 88 | Description all as per item No 67 here in before butusing 4 sq mm single core copper conductor cable of multistranded flame retardant Low smoke (FRLSH) PVC insulated unsheathed 1100 volts grade for AC DB point incl running of4 sq mm copper conductor flame retardant PVC wire as earth continuity conductor along with wiring and connecting to the common eath dolly.Make : KEI/Polycab/Havells |
| 89 | S & Fin replacementswitch piano (White) single pole flush type 5 amps, 230 volts.complete all as specified and directed.Make:- Havells REO/Legrand/L&T |
| 90 | S & F in replacement switch piano (White) single pole flush type, two way, 5 amps, 230 volts.complete all as specified and directed..Make:- Havells REO/Legrand/L&T |
| 91 | S & F in replacement bell push (White) flush type 5 amps, 230 volts.complete all as specified and directed..Make:- Havells REO/Legrand/L&T |
| 92 | S & F in replacement socket (White)flush type multipurpose 2/3 pin 5 amps 2 in 1, 230 Volts all as specified. .Make:- Havells REO/Legrand/L&T |
| 93 | S & F in replacement switch socket combination (White) flush type multipurpose 2/3 pin 5 amps 2 in 1230 Volts complete all as specified and directed. .Make:- Havells REO/Legrand/L&T |
| 94 | S & F in replacement switch socket combination (White) 2 in 1 multipurpose 3/5 pin 5/15 amps flush type complete all as specified and directed. .Make:- Havells REO/Legrand/L&T |
| 95 | S & F in replacement ceiling rose (White) three terminal surface bakelite type AC 50 Hz 230 volts of size 65 x 50 mm complete all as specified and directed..Make:- Havells REO/Legrand/L&T |
| 96 | S & F in replacement ceiling fan regulator (White) step type, flush type heavy duty suitable to work on 230 volts Ac supply complete all as specified and directed. .Make:- Havells REO/Legrand/L&T |
| 97 | S & F in replacementlamp holder (White) insulated body surface bakelite with back plate suitable for angle / batten fittings fixed with PVC round/squareblockscomplete all as specified and directed. Make:- Havells REO/Legrand/L&T |
| 98 | S & F in replacement call bell suitable to work on 230 volts Ac supply including removal of old unsv call bell complete all as specified..Make:- Havells REO/Anchor/L&T |
| 99 | S & F in replacement sheet metal enclosure MCBDBSPN8 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system complete including removal of old unsv sheet metal enclosure all as specified. Model:-DBSPN008DD Make -L&T/Schneider/Indo asian/Legrand |
| 100 | Servicing/Overhauling of 3 Phase, Pressure 12 Kgf/Cm2 capacity 500 Ltr Compressoralongwith movable housing with following others repairs and underlaying points:-(a)Taking out Motor and movable housing from its Position and disconnecting all Cable Connections.(b)Dismantaling of induction Motor complete Part by Part carefully, testing all Coils, degreasing bearing and display all the Parts without damaging any portion for inspection of Engineer-in-Charge to ascertain the Serviceability of existing Parts.(c)Heating & Varnishing to Stator with super quality varnish and dried out properely with external heat as ordered and as directed.(d)Reassembeling the Motor complete with all existingServiceable Parts obtained against Item 39(b), greasing the Bearing with bearing grease and new Parts as ordered by Engineer-in-Charge (New Parts shall be measured and paid separately under relevant Itemhere-in after) (e)Reinstall the Motor at its existing Position, connecting all Cable connections and testing on completion complete all as specified and as directed.(f) Refilling of compressor oil as required at site and as directed.(g) Taking out unsv Automatic Cut off Relay and limit switches refixing the same as required at site.(h) Taking out unsv Pressure Release valve refixing the same as required at site. (j)Taking out unsv Star Delta starter refixing the same as required at site. NOTE: i)Any unforeseen Minor Repairs and Minor Parts which are required to complete the repair work for smooth functioning of Motor are deemed to be included with the Unit Rate andlabour element involved in replacementis included in unit rate quoated against this Item.(ii)Transportation of motorparts for machining, rewinding from work site to lathe shop (Work shop) are deemed to be included with the Unit Rate.(iii)Rewinding ofMotor, any machine workwhere involved shall be measured and paid separetely against relevant Item of this Schedule.(iv) Replacement of Automatic Cut off Relay , limit switches, Pressure Release valve and Star Delta starter wil be paid under supply only. |
| 101 | Rewinding burnt coilsof Induction Motor of any make and type of capacity, 3Phase, upto 20HP, 415Volts with super enamelled copper winding wire as per existing size and guage to achieve therequired /specifiedRPM including taking out old unserviceable winding, cleaning/ repairing damaged slots, complete all as specified and as directed. |
| 102 | Supply and topping upCompressor oil as per sample req and directed by Engr-in - Charge. |
| 103 | Supply and Fixing in replacementLimit Air Switch as per sample and directed by Engr-in - Charge. |
| 104 | Supply and fixing in replacementAutomatic cut off relay as persample and directed by Engr-in- Charge. |
| 105 | Supply and fixing in replacementAutomatic timer as persample and directed by Engr-in- Charge. |
| 106 | Supply and fixingin replacement Automatic Star Delta starter for motor ofcapacity 30 HP andas persample and directed by Engr-in- Charge.Make-MN25FASD Cat No- SS94364 ,L&T |
| 107 | Supply and fixing in replacementAir Outlet Nozzle and regulator as persample and directed by Engr-in- Charge. |
| 108 | Servicing/Overhauling of 3 Phase, 40KVA UPSalongwith with following others repairs and underlaying points:-(a)Taking out Vertiv Make UPS from its Position and disconnecting all Cable Connections.(b)Dismantaling of Vertiv make UPSand removing unsv Part carefully, testing all Connection for inspection of Engineer-in-Charge to ascertain the Serviceability of existing Parts.(c)Replacement of unsv Rectifier / Inverter / static bypass switch /Chip/relay/Semiconductor devices/diode and other Power electronics parts(d)Reassembeling the UPS complete with all existingServiceable Parts obtained as ordered by Engineer-in-Charge(g) Taking out unsv Automatic Cut off Relay andrefixing the same as required at site. NOTE: i)Any unforeseen Minor Repairs and Minor Parts which are required to complete the repair work for smooth functioning of UPS are deemed to be included with the Unit Rate andlabour element involved in replacementis included in unit rate quoated against this Item.(ii)Transportation of Unsvparts for machining incl workshop charges are deemed to be included with the Unit Rate.(iii) New Chip/relay/Semiconductor devices/diode and other Power electronics parts for UPS will be included in quoted unit rate.Also Enginnering /consultancy charge from the company Rep will be bourne by contractor self. |
| 109 | S&F in replacement maintenance free chemical Earthing system complete with 03 Nos ofCopper pipe of 100 mm dia with UL 467 approved copper bonded earth rods 17 mm dia 3000mm long electrode dipped fully in earth enhancing chemical compoundburied in groundto bore holes 100 mm dia vertically to a depth not less 3.5 mtr deep below ground level with top edge of earth electrode at a depth not less than 500 mm below normal ground level, interconnected each other parallelely in Triangle Shape horizontally,With provision of copper busbar of size32 mm x 6mm for inter connection with copper earth lead strip 32mm x 6mm for further connected to test point terminal block of size 120mm x 120mm x 25mmmade of copper as directed including 45 x3 kg (Minimum) NABL Lab certified back fill earth enhancing compound for filling 3 x bore holes with soil mixed ,so as to achieve earth resistance below 1 Ohms including necessary excavation and earth workand Provn of PCC Chamber in PCC (1.3:6) type C1 (using 20 mm graded stone aggregate) with pit cover of 300 mm x 300 mm made of Cast Iron for each earthing complete all as Specified and directed. |
| 110 | S& F in replacement of earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit /pipe or fixed to poles duly fixed over insulatorsor any other indicatedsituation for loop earthing etc as required with 32 x 6mm copper strip duly brazedcomplete all as specified and directed. |
| 111 | S & F in replacementTest point terminal block made of gun metal or Phosphorus bronze size 75 x 75 x 25 mm, drilled and screwed including 3 Nos 8 mm dia 25 mm long hex head screw in a test point boxcomplete all as specified and as directed. |
| 112 | S&F in replacementGI Pipe of 40 mm Dia, ISI Marked , light grade to cover the copper strip (32 mm x 6mm) Complete all as Specified and directed |
| 113 | M&L for earthing complete with galvanized steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground to a depth not less than 2.25 mtr below the normal ground level with top edge of earth plate not less than 1.50 mtr below the normal ground level and connected to GI strips 32 x 6 mm by means of nut, bolt & washer and protected by 40mm dia GI pipe light grade and watering pipe of 20mm dia GI pipes light grade and connected to earth test point including necessary excavation, earth work, PCC chamber (1:3:6) type C-1 and 40 mm thick RCC pit cover in RCC (1:2:4) type B-1 using 6 mm dia MS round bars @ 150 mm C/C both waysall as shown in electrical plate No. 5 of SSR Part-I all as specified and directed. |
| 114 | Supply and fixing of GI strip 32 x 6 mmfixed in ducts / on wall / in trenches / floors etc for earthing complete fixed to equipment / test point / earth electrode duly brazedcomplete all as specified and directed |
| 115 | M&Lin replacementfor earthing complete with copper earth plate electrode of size 600 x 600 x 3.15 mm thick buried directly in ground to a depth not less than 2.25 mtr below the normal ground level with top edge of earth plate not less than 1.50 mtr below the normal ground level and connected to Copper strips 20X3 mm by means of coppernut, bolt & washer and protected by 40mm dia GI pipe light grade and watering pipe of 20mm dia GI pipes light grade and connected to earth test point including necessary excavation, earth work, PCC chamber (1:3:6) type C-1 and 40 mm thick RCC pit cover in RCC (1:2:4) type B-1 using 6 mm dia MS round bars @ 150 mm C/C both waysall as shown in electrical plate No. 5 of SSR Part-Icomplete all as specified and directed. |
| 116 | Supply and Fix in replacement of Copper wire 1.0 Sqmm 2 Core complete all as specified and directed. |
| 117 | Supply and Fix in replacement of Copper wire 1.5 Sqmm 3 Core complete all as specified and directed. |
| 118 | Supply and Fix in replacement of Copper wire 2.5 Sqmm 3 Core complete all as specified and directed. |
| 119 | S & FPVC Square Box of Size 4\"\" x 4\"\" including replacement of old UNSV one and refixing of old switch sockets as per existing at sitecomplete all as specified and directed. Make Presto plast / Harsh /Plaza / AKG |
| 120 | S & FPVC Square Box of Size 7\"\" x 4\"\" including replacement of old UNSV one and refixing of old switch sockets as per existing at sitecomplete all as specified and directed. Make Presto plast / Harsh /Plaza / AKG |
| 121 | S & FPVC Square Box of Size 8\"\" x 6\"\" including replacement of old UNSV one and refixing of old switch sockets as per existing at site complete all as specified and directed. Make Presto plast / Harsh /Plaza / AKG |
| 122 | S & FPVC Square Box of Size 12\"\" x 10\"\" including replacement of old UNSV one and refixing of old switch sockets as per existing at site complete all as specified and directed. Make Presto plast / Harsh /Plaza / AKG |
| 123 | Supply onlyPVC wide 25mmInsulation Tapeof length25 meter complete all as specified and directed. Make :- Anchor Grip /MS-seal / Havells |
| 124 | Supply and Fixfor PVC casing and capping of width 25mm and length 3 metersin repairs duly fixed with casing pins and connecting accessories like Tee , Bends , elbow etc required as per site complete all as specified and direced. Make :- Presto Plast / Plaza / AKG / Harsh |
| 125 | Supply and Fixfor PVC Conduitof length 3 meters of dia 25mm in repairs duly fixed with Clamps on wall surfacesand connecting accessories like Tee , Bends , elbow etc required as per site complete all as specified and direced. Make:-Presto plast / Harsh /Plaza / AKG |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender