Tender For Repair Maint Of Internal Electrification Work Service Incl Replacement Of Unserviceable Distribution Main Switch Boards Submain Wiring Bldg Security Lights Various Light Fittings And Fixtures Including Maint Of All Type Of Fan Summer Winte, delhi-Delhi

Military Engineer Services-MES has published Tender For Repair Maint Of Internal Electrification Work Service Incl Replacement Of Unserviceable Distribution Main Switch Boards Submain Wiring Bldg Security Lights Various Light Fittings And Fixtures Including Maint Of All Type Of Fan Summer Winte. Submission Date for this Tender is 30-10-2023. Electrification Work Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

40114416
Tender For Repair Maint Of Internal Electrification Work Service Incl Replacement Of Unserviceable Distribution Main Switch Boards Submain Wiring Bldg Security Lights Various Light Fittings And Fixtures Including Maint Of All Type Of Fan Summer Winte
Open Tender
Indian
Delhi
delhi
30-10-2023

Tender Details

Repair Maint Of Internal Electrification Work Service Incl Replacement Of Unserviceable Distribution Main Switch Boards Submain Wiring Bldg Security Lights Various Light Fittings And Fixtures Including Maint Of All Type Of Fan Summer Winter Appliance

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work: CA NO GE/NORTH- 69/2023-24: REPAIR/ MAINT OF INTERNAL ELECTRIFICATION WORK SERVICE including REPLACEMENT OF UNSV DISTRIBUTION MAIN SWITCH BOARDS, SUBMAIN WIRING, BLDG SECURITY LIGHTS, VARIOUS LIGHT FITTINGS & FIXTURES INCLUDING MAINT OF ALL TYPE OF FAN/ SUMMER/ WINTER APPLIANCE ETC OF OTM ACCN AND REPAIR/ MAINT OF EXTERNAL ELECTRIC SUPPLY SYSTEM INCLUDING STREET/ SECURITY LIGHT, REPLACEMENT OF FAULTY UNDERGROUND CABLE WITH CONNECTED ITEMS AT OD SHAKURBASTI & HIRANKUNDNA UNDER GE (NORTH) DELHI CANTT-10
Sl. No. Item Description
1Taking down carefully copper/aluminium point wiring (light/fan/socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets etc including making good the disturbed surfaces to match with the existing complete all as specified & directed
2Taking down unserviceable main switches, DBs including MCBs, bus bars chambers etc from wall/existing main boards and removing from site complete all as specified & directed
3M&L for point wiring with single core FRLS, PVC insulated, unsheathed multi stranded copper conductor of size 1.5 sqmm alongwith 1.5 sqmm earth wire of multi strand copper conductor (with same specification) drawing through existing conduit pipe including replacement of sunk zinc coated pressed steel terminal box of 1.60mm thick withGI metal flush box of 1.60 mm thick suitable for modular/conventional switches/sockets/fan regulators with cover plates (modular/ conventional type as required), blanking plates, brass screws, cup washers etc and making good to the disturbed surfaces to match the existing complete for the following :-
4One light point controlled by one switch
5Oneceiling/exhaust fan point controlled by one switch
6One socket outlet 5 Amps controlled by one switch on same board
7One socket outlet 5 amps controlled by one switch on independent board
8One bell point controlled by one bell push switch
9All as per the description of srl item No 3.00 above but wiring with 2.5sqmm copper wire and 2.5 sqmm earth wire for socket out let 16 Amps on independent board
10All as per the description of srl item No 3.00 above but wiring with 4 sqmm PVC insulated multi-stranded copper conductor for industrial socket outlet 3 pin 16 / 20 Amps point and one single core 4 sqmm PVC insulated unsheathed copper cable as earth continuity conductor
11M&L for point wiring concealed type with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable connected to common earth and earth dolly with suitable copper lugs drawing into and including rigid non-metallic PVC surface conduit of 20mm dia or higher, medium grade complete with all PVC conduit accessories, GI metal flush box of 1.60 mm thick suitable for modular/conventional switches/sockets/fan regulators with cover plates (modular/ conventional type as required), blanking plates, brass screws, cup washers etc including all cutting / chases etc in walls and making good to the disturbed surfaces to match the existing complete all as specified and directed for the followings :-
12One light point controlled by one switch
13Oneceiling/exhaust fan point controlled by one switch
14One socket outlet 5 Amps controlled by one switch on same board
15One socket outlet 5 amps controlled by one switch on independent board
16One bell point controlled by one bell push switch
17All as per the description of srl item No 6 above but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 16 Amps socket outlet point on independent board with 2.5 Sqmm nominal cross sectional area copper conductor cable as continuous earth wire.
18All as per description of srl item No 6 above but wiring with 4 sq mm PVC insulated multi-stranded copper conductor for industrial socket outlet 3 pin 16/20 Amps point and one single core 4 sqmm PVC insulated unsheathed copper cable as earth continuity conductor
19S&F switch piano flush type 5/6 Amps single pole one way230 Volts complete all as specified & directed
20S&F switch piano flush type 15/16 A single pole one way 230 Volts complete all as specified & directed
21S&F socket outlet 2 in 1, 3 pin 5 Ampsflush type 230 Volt complete all as specified & directed
22S&F socket outlet 2 in 1,3/6 pin 5 and 15 Amp flush type 230 Volts complete all as specified & directed
23S/F bell push, flush type 5 Amps 230 Volts complete all as specified & directed
24S&F electronic fan step regulator flush switch type 100/120 watt, 230 Volt complete all as specified & directed
25S&F ding dong bell, AC, 230 volts, single pole complete all as specified & directed
26S&F lamp holder, 230 volt AC, PVC / Polycarbonate type with back plate suitable for batten fitting including 9 watt LED bulb, 6500 K complete all as specified & directed
27S&F ceiling rose, 6 Amps, 250 volts, ACwith three terminals and PVC / Polycarbonate insulated body of 50 x 25mm sizecomplete all as specified & directed
28S&F modular switch 6/10 Amps, one way, one module 240 volts complete all as specified & directed
29S&F modular socket, 3 pin 6 Amps,240 volts, 2 module complete all as specified & directed
30S&F modular switch 16 A, 1 module,240 volts complete all as specified & directed
31S&F modular socket 6/16 A, 5 pin, 2 module, 240 volts complete all as specified & directed
32S&F modular bell push 6 Amps, one module 240 volts complete all as specified & directed
33S&F modular fan regulator, step type, 120 W, humfree, AC, 230 volts, 2 module complete all as specified & directed
34S&F sheet metal enclosure with single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps "C" curve, 240 Volt complete all as specified & directed
35M&L in repair for two single core (submain) PVC insulated cable with 4 sqmm nominal cross sectional area stranded copper conductor and one single core green PVC insulated 4 sqmm stranded copper conductor earth continuity cable drawn through non metallic rigid PVC conduit 20 mm dia or higher size, concealed in wall including all conduit and fixing accessories including cutting chases & making disturbed surfaces complete all as specified & directed. Note:- Two run for neutral and phase and one run for continous earth wire alongwith PVC conduit shall be measured as one unit length.
36All as per the description of srl item No 25 above but with 6 sqmm and 6 sqmm as earth wire
37S&F MCB DB, single pole and neutralwith 200 Amps rated bus bar, 230 volts, glazed,double door type, IP-43,including connecting all connections of wire to MCBs with proper lugs & making good to the disturbed surface complete for the following no of way :-
384 way
398 way
4012 way
41S&F loadline distribution box 4 way, AC, TP & neutral metal enclosure, Glazed double dooor, 415 V, AC, IP-43, concealed type with suitable bus bar, neutral link, earth link suitable for MCCB63/100 Amps as incomer and MCB SP as out going complete all as specified & directed
42S&F MCB DP/SPN, 240 Volts, AC of breaking capacity 10 KA,"C" curve and connections by using suitable copper lugs complete of following rating :-
4363 Amps
4440 Amps
45S&F MCB SP, 240 Volts, AC, 6 to 32 amps, breaking capacity 10 KA, "C" curve and connection by using suitable copper lugs complete all as specified & directed
46S&F MCCB 3 Pole, 415 volt, AC, fixed type, with breaking capacity 16 KA suitable for load line DB & connection complete of following rating :-
4763 amps rating
48100 amps rating
49Supplying and laying in replacement or fixing or passing through pipe, 1100 volts gradePVC insulated aluminium stranded conductor cable served with inner sheathing of PVC tape and overall PVC sheathed in service connections one twin core cable flat or circuler for the following size of cables :-
5016 Sqmm
5110 Sqmm
52S&F in repairs of switch piano, flush type, 5/6 Amp, single pole, one way, 230 volts complete all as specified & directed
53S&F in repairs of socket outlet 2 in 1, 3 pin, 5/6 Amp, flush type, 230 volts complete all as specified & directed
54S&F in repairs of switch piano flush type 15/16 Amp, single pole, one way, 230 volts complete all as specified & directed
55S&F in repairs of socket outlet 2 in 1, 3/6 pin 5 and 15 Amp, flush type, 230 volts complete all as specified & directed
56S&F in repairs of Bell Push, flush type, 6 Amp, 230 Volts complete all as specified & directed
57S&F in repairs electronic fan step regulatorswitch fiush type 120 watt, 230 Volt complete all as specified & directed
58S&F in repairs of modular switch 10 amps single pole one module, 230 volts complete all as specified & directed
59S&F in repairs of universal moudlar socket,10 Amps, 5 pin, 2 module, 230 volts complete all as specified & directed
60S&F in repairs of modular switch 16/20 amps single pole one module, 230 volts complete all as specified & directed
61S&F in repairs of modular socket 16/20 amps, 2 module, 230 volts complete all as specified & directed
62S&F in repairs of modular bell push with indicator 6 amps, one module complete all as specified & directed
63S&F in repairs of modular fan step regulator 120 watt 2 module , 230 voltscomplete all as specified & directed
64S&F in repairs LED Bulkhead luminaire 10 watt of polycarbonate housing and enclosed with acrylic diffuser IP-65 protection including connection complete all as specified & directed
65S&F in repairs LED Post top lantern luminaire with die cast aluminium spigot, lid cover and clear acrylic cover 40 watt, 5700 K with IP-65 protection including connection complete all as specified & directed
66S&F in repairswall mountedLED batten with aluminium housing and integrated electronic drive18/20 watt fixture 4 feet provided for efficient heat dissipation with polycorbonate diffuser and integrated electronic driver and all accessories pre-wired including connecting up with twin core flat flexible copper conductor cable of suitable size complete all as specified & directed
67S&F in repairs surface and wall mounted LED batten 10 watt 2 feet longextruded aluminium housing provided for efficient heat dessipation with polycarbonate diffusser and integrated electronic drive, pre-wired including connecting up with twin core flat flexible copper conductor cable of suitable size complete all as specified & directed
68S&F in repairs wall mounting bracket decorative luminaire powder coated housing, SS finish fixture with opal glass diffuser suitable for GLS, B-22 lamp including connection complete all as specified & directed
69S&F in repairs highly efficient round shape downlighter 25 watt, 240 volt, CCT 5700 K with driver suitable for ceiling cutout 225 mm dia including connection complete all as specified & directed
70S&F in replacement LED landscape bollard light 10 watt, 230 volt, inverted pyramid tripod type with soft 360 degree distribution, IP-65 protection, including necessary civil work for grouting & foundation work of suitable size with PCC work complete all as specified and directed.
71S&F in repairs 5 W LED T5 TL fitting (1ft) attractive wall mounted type suitable for mirror fittings, all accessories pre wired including up with twin core flat flexible copper conductor cable of suitable size complete all as specified and as directed.
72S&F LED Bed side reading stainless steel wall light fitting 3/5 Watts,230 volt,AC, rectangular/round, flexible neck/Gooreneck, cool day light complete with all accessories including connection complete all as specified & directed
73S&F in repairs surface/ceiling mounted LED panel type of size 2ft x 2ft, 36W, 230V, 5700K complete with driver full window glare free opal diffuser LED panel with CRCA powder coated white housing complete with all accessories required for connection and making good the disturbed ceiling complete all as specified & directed
74S&F in repairs of LED linear surface/ suspended fittings, extruded aluminium body with opal polycarbonate diffuser, 38 watt, 4 ft long, CCT 6000 Kincluding connection complete all as specified & directed
75S&F in repairs LED energy efficientflood lightof 30 watt, 230 volt,anti glare diffuser, IP-65 including connection complete all as specified & directed complete all as specified & directed .
76S&F in repairsexhaust fan 300 mm sweep, 230V, AC, steel body with louver shutter etc complete and connection from ceiling rose to fan terminal including cutting of hole at wall for required size and making good disturbed surface and depositing old fan to store yard complete all as specified & directed
77S&F in repairs wall mounting fan 400 mm sweep, adjustable, plastic blade grill for protection, pull cord control for speed and oscillation on-off, ABS body including connection and depositing old fan to store yard complete all as specified & directed
78S&F in repairs PVC flexible twin twisted copper conductor cable multi strand of size 0.5 sqmm nominal cross section complete all as specified & directed
79S&F electronic energy meter, current rating 10-60 amps, 240 Volt, AC, single phase, 2 Wire, accuracy Class 1.0, with LCD display including/ fitted with temper proof meter box, weather proof, transparent, made out of FR polycarbonate, dust proof, good mechanical strength conforming to IS: 14772/2000, IP-65, size not less than 260mm x 190mm x 120mm including connection and depositing old meter to MES store complete all as specified & directed
80M&L for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer ofcharcoal dust and common salt filling in alternate layers and electrode connections by using GI wire of size 4mm dia as earthing lead(upto the body ofthe equipment) by means of GI bolts, nuts, check nuts and washers and thimbles and protected by light grade 40mm diaGI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC (1:3:6)type C-2 using 40mm graded crushed stone aggregate, including excavation and earth work in any type ofsoil, returning, filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 ofSSR 2009 (Part-I) complete all as specified & directed
81Taking down carefully electric geyser of any type and capacity bydisconnecting electric and water supply connection, opening nut, bolt, washer and reassembling after cleaning and replacing defective parts and re-installing the same in original position and making necessary electric and water supply connection and testing complete all as specified and directed. Note:- Spare parts shall be measured and paid seperately
82Supply only geyser inner water tank 35/50Ltrs capacity steel body as per sample, duly tested complete all as specified and directed.
83All as per the description of srl item No 63 above item but 25 Ltrs capacity
84Supply only heating element capacity 1.5 KW (Round/Triangular) ISI marked suitable for geyser (as per sample) complete all as specified & directed (Make : as per sample/ make as per existing geyser)
85All as per the description of srl item No 65above itembut capacity 2 KW
86Supply onlythermostat suitable for 50/35/25 ltrs capacity geysers (Make :- as per sample/ make of existing geyser)
87Supply onlyHeavy duty hot water connection, SS rope threaded type with brassunions at both ends, 45cm long 15mm bore complete all as specified & directed
88Supply onlyindicator lamp, Red/Green suitable for geyser of any type/capacity (Make as per sample)
89Supply onlygeyser base plate assembly of any type(having 6 or 9 hole) any model all as specified and directed complete all as specified & directed (Make as per sample)
90Supply onlyin replacement of outer cover MS sheet/ABS body of geysers 25 to 50 Ltrs capacity complete all as specified & directed
91Supply onlyPlug top, 3 pin, 05 amps, 230 volt complete all as specified & directed .
92Supply onlyPlug top, 3 pin, 15 amps, 230 volt complete all as specified & directed.
93S&F in repairs PVC insulated and sheathed flexible cable 3 core Multi-stranded copper conductor size 2.5 Sqmm 1100 volt grade after taking out old unserviceable one including electric connection complete all as specified and directed.
94S&F in repairs of precast RCC earthing pit with CI cover ISI marked including angle iron frame made out of 35mm x 35mm x 4mm thick for supporting the edges of pit cover as dimension shown inElectrical plate No-2 of SSR part-I 2009complete all as specified & directed
95M&L for dismantling of unserviceable ceiling fan of any make/model/sweep, cutting and removing the old defective/burnt winding, cleaning the core of fan motor and rewinding the fan motor with super enamelled copper winding wire of same gauge with insulating material and varnishing the core assembly, drying the moisture content to get appropricate speed and re-assemble the same complete all as directed Note :- The cost of copper winding wire is deemed to be included in the quoted rate against this item.
96All as per the description of srl item No 76 above but for exhaust fan upto 300mm sweep size
97All as per the description of srl item No 76 above but for exhaust fan of 380/450mm sweep size
98S&F in repairs capacitor 2.5/3.15 MFD suitable for C/fan including connection complete all as specified & directed
99S&F in repairs pedestal fan 500 mm sweep with strong copper wound motor for better air delievery, smooth oscillation, superior low voltage performance, heavy base for stability, 3 speed control regulator, speed not less than 1400 RPM and old to be deposited in store yard complete all as specified & directed
100M&L in repairs ball bearing suitable for any type/size/make of fan complete all as specified & directed (Make : NBC/SKF)
101S&F in repairs factory made metallic louver shutter duly painted complete all as specified and as directed for following size of exhaust fan :
102300 mm sweep
103450 mm sweep
104S&F in repair factory made ceiling fan down rod made out of heavy duty MS conduit pipe of 15mm dia duly with powder coat painted hole at both ends for passing cable/nut and cut at one end for fixing of fan shaft including nut bolt complete all as specified for the following sizes :-
10530 cm
10660 cm
10790 cm
108120 cm
109Excavation in trenches not exc 1.5 Mtr wide and n.exc 1.5 mtr in depth, getting out for electric cable complete in soft soil complete all as specified & directed
110Removing surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level n. exc 1.5 mtr above starting point complete all as specified & directed
111Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified & directed
112Sub class ‘B bricks, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick, complete all as specified and as directed
113Sand cushioning to under ground cable with a layer of sand 8 cm before laying the cable and 15cm after laying the cable (10 cm punned thickness above the top of the upper most cable, total 18 cm), complete all as specified and directed.
114Checking & locating of fault in underground HT/LT cable of any size by cable fault locator machine complete all as specified & directed
115M&L (in replacement) for GI tubing light grade with all necessary fittings laid in trenches/under road crossing/under floor including suitable mild steel FI clamps of required size complete for following sizes:-
11640 mm bore
11750 mm bore
11880 mm bore
119Supply and laying in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following size complete all as specified & directed. Note :- Excavation & earth work, sand cushioning, bricks protection & GIpipe where required shall be measured & paid seperately :-
12010 Sqmm, 2 core
12116 Sqmm, 4 core
12225 Sqmm, 3.5 core
12335 Sqmm, 3.5 core
12450 sqmm, 3.5 core
12595 sqmm, 3.5 core
126120 sqmm, 3.5 core
127185 sqmm, 3.5 core
128400 sqmm, 3.5 core
129Making hole below the road by drilling machine or hand drill without damaging road for inserting pipe upto 80mm dia complete all as specified and directed Note:- GI pipe shall be measured & paid separately
130Dismantling & taking out defective LT PVC/ XLPE cable from trenches including excavation and earth work, cutting and removing defective parts and supply and fixing straight through joint heat shrink kit complete including jointing material and making connection of LT cables for the following sizes :-
13125 sqmm 3.5 core to 50 sqmm, 3.5 core
13270 sqmm 3.5 core to 120 sqmm, 3.5 core
133150 sqmm 3.5 core to 400 sqmm 3.5 core
134S&F in repairs of 1100 volt grade, heavy duty cable PVC insulated aluminium conductor, unarmoured, multistranded, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended complete all as directed
13516 Sqmm, twin core
13610 Sqmm, twin core
137Checking all incoming & outgoing connections and Mechanism, cleaning, servicing, overhauling, testing it for proper tripping system complete of 11 KV VCB of Make Crompton Greaves/AREVA/Siemens, installed at sub-station bldg, inspecting, servicingand testing all the connections of control wiring availability of proper DC supply and AC supply, cleaning of contacts, & terminals, using the blower for dusting, servicing of gears, including replacement of faulty control fuses, faulty wiring & faulty indication lamp, checking & closing of tripping system, taking out relay (over current relay and earth fault relay) from the 11 KV VCB and calibrating the relay and proper setting of relay and refixing back in existing position & testing for proper tripping/functioning system complete all as specified & directed Note :- (i) Necessary certificate for calibration of relay with setting detail shall be submitted by the contractor. (ii) Spare parts will be measured and paid separately
138S&F in repairs Charging Motor assembly set in existing VCB panel of existing make including all connections & fixing arrangement and testing complete all as specified & directed
139S&F in repairs Spring charginggear assembly (big size)for VCB upto 630 Amp as per existing make of VCB complete all as specified & directed
140S&F in repairs Spring charginggear assembly (small size)for VCB upto 630 Amp as per existing make of VCB complete all as specified & directed
141S&F in repairs power pack unit suitable for 220 volts AC input & 110 volts DC output complete with 12 volts, 7 AH sealed lead acid batteries and suitable voltmeter etc suitable for operation of HT Panel complete all as specified and directed
142S&F in repairs Tripping coil assembly 24 V DC for VCB 11 KV as per existing make of VCB complete all as specified & directed
143S&F in repairs Closing coil assembly 24 V DC for VCB 11 KV as per existing make complete all as specified & directed
144S&F in repairs TNC switch (Trip Neutral Close), with 2 NO + 2 NC suitable LT/HT Panel any type/size as per existing complete all as specified & directed. (Make- As per sample of make Vaishno/Kaycee/AE/Siemens/Schneider/Rishabh)
145S&F in repairs heater, 230 Volt, as per existing wattage suitable for 11 KV HT VCB panel including electric connection complete all as specified & directed (Make - As per sample)
146Disconnection of all electric connection & taking out old/defective Current Transformer (CT) from 11 KV VCB panel and Supply, fixing, installation & testing of Current transformer, indoor, single phase resin cast CTs of 100-50/5+5 amps ratio, Class 5P-10 with suitable VA burden and accuracy suitable for protection & metering including making suitable arrangement for fixing in existing VCB panel and connection including disconnection & taking out old/faulty current transformers (CTs) from 11 KV VCB panel complete all as specified & directed Make-ABB/Crompton/Schneider/Siemens/Pactil/AE Note:- for item No. 95 to 104 :- (i) All the instruments and T&P required for the above jobs shall be arranged by the contractor at site and cost of the deemed to be included in the above rates. (ii) The all above checking, inspection, installation & testing work shall be performed by HT expert/ engineer.
147M&L for online Dehydration of HV/ EHV grade transformer oil including filteration using automatic centrifuging machine minimum three cycles to achieve dielectric strength 50 to 60 KV breaking capacity by absorbing and abolishing all sludge particles as per BS-66-1963 including topping up with new transformer oil as required complete all as directed. Note: - (i)Centrifuging Machine with all T&P & testing machine of oil required for dehydration shall be arranged by the contractor. (ii) Oil required for topping up the transformer will be measured & paid separately.
148M&L (in replacement) of Silica Gel (Blue colour) in breather of transformer after cleaning of breather.
149M&L (in replacement) of breather of transformer of any make/capacity upto 630 KVA with exising size
150M&L (in repairs) cable jointing kit for 11 KV cable for end termination cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size:-
151Size 70 sqmm to 185 sqmm, Indoor type
152Size 70 sqmm to 185 sqmm, outdoor type
153M&L (in repairs) cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & directed for size 70 sqmm to 185 sqmm
154Supply & laying in trenches/through pipes/ducts or on poles XLPE armoured cable of following sizes with aluminum conductor, 11 KV `E’ complete all as specified & directed of follwing sizes Note :-Excavation & earth work, sand cushioning, bricks protection & GIpipe where required shall be measured & paid seperately:-
15595 Sqmm 3 core
156120 Sqmm 3 core
157M&L for chequered plate 5/6mm thick of required size for cable duct cover as required at site including cutting & weldingincluding painting with two coats of synthetic enamel paint over acoat of red oxide primer complete all as specified & directed
158M&L for painting ofsteel tubular poles 9 mtr to 11 mtr length with applying two coats of aluminium paint including cross arms and clamps except embedded portion of pole in ground and concrete after removing old painted surfaces by scraping of poles complete and two coat for making colour band/strip 30 CM with synthetic enamel paint of approved/yellow & black colour up to 1.2 mtr from coping level including numbering of poles complete all as specified & directed
159M&L for spray painting of old/existing LT/HT panel/feeder piller box any size/type with powder coated paint withsmoke grey paint in outer/inner side of complete panel after cleaning and preparing surface complete all as specified & directed
160M&L for replacement of lock assembly with key of old/ existing LT panel board any type/size complete all as specified & directed
161Servicing & overhauling of Air Circuit Breaker (ACB) of any capacity by taking out from existing LT panel, cleaning all parts internally and externally, checking of the proper tension of the springs mechanical mechanism, tightening of connection of moving, fixing contact, floating contacts, servicing of motor & charging system including replacement of faulty parts/spares and re-fixing it on its original position and testing complete all as specified & directed. Note :- Spare parts will be measured and paid separately under respective item
162Supply only following item/spares for Air Circuit Breaker (ACB) :-
163Closing release of air circuit breaker
164Shunt release of air circuit breaker
165Under voltage release with time relay
166S&F in repair 3 pole Power Contactor, MNX type ofrating 32/40 amp AC3, closing coil 220 volt with auxiliary block (1 NO + 1 NC ) including electric connection in existing panel complete (Make- Hager/L&T /Siemens/Havell/Schneider)
167M&L (in replacement) danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size for LT/HT 20 x 15 cm size complete all as directed
168S&F (in replacement) following items in the existing panel / location and connection with using aluminum lugs including making necessary alteration in panel/door as required for proper fixing & connection complete all as specified and directed :-
169MCCB 4 Pole 630 amps, 50 KA breaking capacity, 415 Volt
170MCCB 4 Pole 200 amps, 25 KA breaking capacity, 415 Volt
171MCCB 4 Pole 250 amps, 35 KA breaking capacity, 415 Volt
172Volt meter (0 to 500 volts) digital type, three phase of size 96mm x 96mm
173Amp meter (0 to 300 amps) digital type, three phase of size 96mm x 96mm with suitable CTs
174Indicator lamp, LED type
175Multifunction Meter, digital type, three phase, size 80mm x 80mm, accuracy class 1.0 for monitoring of various electric parameters such as voltage, current, wattage, frequency, power factor etc. Make : Schneider model No EM 6436H or equivalent in L&T/Siemens Note :- (i) MCCB should be properly fited in existing compartmentand operating handle of MCCB should be proper in opening existing cover/door of compartment of LT panel board. (ii) Make of MCCB/MCB/Contactor - Schneider/ABB/L&T/Legrand
176S&F steel tubular electric pole, swaged, type 410 SP-31 (9 metre long) complete with CIbaseplate, bolts, nuts & screws including 06 Nos hole on top edge for holding of D-clamp & insulators complete all as specified including the following:-
177Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole infoundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 metres.
178M&L for Providing PCC 1:4:8, type D2 (using 40mm graded crushed stone aggregate) in foundation 600mm x 600mm x 1500mm (planting depth) for concrete encasing the pole upto GL
179M&L for Providing PCC 1:3:6, type C2 (using 40mm graded crushed stone aggregate) for plinth block /Collar aboveGL, 300mm high and 450mm dia
180M&L for painting of pole externally with one coatsof blackbituminouspaint (upto planting depth) and above plinth block/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands/strip 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above coping level
181Dismantling and taking out unsv / damaged PCC pole any size/type complete
182Dismantling & taking down defective stay asembly and S&F stay assembly compring of 7/10 SWG galvanised stay stranded wire of reqd length fixed to pole with and including flat iron clamp, bolts, nuts and washers, galvanised 14mm dia, 400mm long stay bow with 16mm dia 180 cms, long stay rod with threded ends, GI nut & washers GI stay plate 230 x 230 x 6mm thick plate 2 Nos thimble, MS clamp made out of 50 x 6mm flat iron loop insulator 90mm x 140mm dia, hole 25mm porcelain complete all as specified and shown in electrical plate No 1 of SSR Part I .
183M&L in repairs for loop junction box, outdoor type, size 30cm x 20cm x 15cm, made out of engineering plastic one piece moulding type, bus bar rating 63 amps 4 strips aluminium with bus bar mounting colour R, Y, B, N on DMC unbreakable insulator with cable entry main supply from bottom side and pole light connection from back side, simens grey colout, shock proof, rust proof, fire retardant, having front opening and locking arrangementwith MCB SP 10 amps - 01 No, box duly fixedon the pole with flat iron clamp of size 25mm x 3mm with nuts & bolts complete all as specified and directed. Note:- Cost of incoming & outgoing cable lugs & glands of suitable size deemed to be included in the quoted rate) Make : Unilac / Universal Switch Gear Control/Sintex/Tricolite
184M&L (in replacement) for LED street/security light fittings 60 watt, made up of of pressure die cast aluminium housing with toughned glass and individual high power LEDs with secondary optics, IP 66 protection, clamp type suitable for 32-50mm dia bracket pipe, to be mounted on existing/ new GI bracket and connecting the street light fitting using 1.5 Sqmm PVC insulated copper cable complete all as directed. Note: - New GI bracket with clamp shall be measured & paid seperately
185M&L for LED Flood Light luminaire, energy saving & enviornmental friendly, long lifediecast aluminium, IP65, with high power LED as light source including necessary fixing arrangement with clamps of suitable size and connectionusing 1.5 Sqmm PVC insulated copper cable complete all as directed for following wattage.
18670 Watt
187100 Watt
188M&L for replacment of double compression stainless steel gland for power cable including electric connection complete with new lugs/thimble complete all as directed (Make- Jainson/Dowell/Action/3M) of following sizes :-
189Size 22.9 mm dia suitable for 16 sqmm 4 core LT cable
190Size 28.9 mm dia suitable for 25 Sqmm 3.5/4 core LT cable
191Size 32.1 mm dia suitable for 35 to 50 sqmm 3.5/4 core LT cable
192Size 37.7 mm dia suitable for 70 sqmm 3.5/4 core LT cable
193Size 41.7 mm dia suitable for 95 sqmm 3.5/4 core LT cable
194Size 47.1 mm dia suitable for 120 sqmm 3.5/4 core LT cable
195Size 51.4 mm dia suitable for 150 sqmm 3.5/4 core LT cable
196Size 56.6 mm dia suitable for 185 sqmm 3.5/4 core LT cable
197M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick directly buried in ground (earth pit not less than 2.25m deep below ground level) with top edge of earth plate not less than 1.5m below the ground level connected to GI strip 32 x 6mm by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 40mm bore light grade for protection of earthing wire PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, watering pipe 20mm bore light grade,funnel with wire mesh, 50mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm MS bars at 150mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No. 3 of MES SSR part-I and including excavation & earth work & connecting the earthing point/equipment and testing complete all as specified & directed.
198M&L for earthing complete with galvanised mild steel earth plate electrode 60cm x 60cm x 6mm thick buried vertically in ground (earth pit not less than 2.25meter deep below ground level) with top edge of the plate not less than 1.5meter below normal ground level steel earth plate connected with GI wire 04mm dia by means oflug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150mm thick around GI earth plate, GI pipemedium grade 20mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6mm dia at the rate of 75mm center to center both way with 12mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40mm x 40mm x 3mm frame for pit cover including testing on completion complete. Note: On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
199M&L for fabrication of sign board made out of heavy duty MS square pipe 40mm x 40 mm for legs, MS angle iron 40mm x 40mm x 5mm thick for frame and MS sheet 3mm thick and legs of sign board embedded in PCC 1:2:4 in 20mm graded crushed stone aggregate upto 45cm including painting with one coat of red oxide paint and two coat of synthetic enamelled paint complete all as specified & directed.
200M&L for writing letters or figures (Block, Roman, italic or indian) n exc. 30 cm hight complete all as specified & directed
201S&F in repairtime switch, digital type having suitable rating street light timer panel including connection complete all as specified & directed
202S&F in repair PVC insulated and sheathed flexible cable 3 core Multi-stranded copper conductor size 2.5 Sqmm 1100 volt grade after taking out old unserviceable one including electric connection complete all as specified and directed
203M&L for Servicing of DG set, 3 phase, 30 KVA capacity, 415 volt, 50 Hz of Make-Ashok leyland with replacing the air filter, diesel filter, super by pass filter, lubricating filter, heavy duty coolant,15W40 lubricating oil (Make-HP /castrol /Valvoline /CAT), fuel pipe with bengo bolt, hose pipe complete set and vent housing with clamp including servicing and cleaning ofradiator & alternator assembly & diesel tank as per manufacturer instructions including testing after repair & servicing all as specified and directed Note:- Servicing of DG set shall be valid for 6 months or 250 Hrs which is earlier
204All as per the description of srl item No 133 above but of DG set, 3 phase, 160 KVA capacity, 415 volt, 50 Hz of Make- Greaves Cotton
205S&F maintenance free lead acid battery,12 volt of following capacity :-
206150 AH, 23 plates
207180 AH, 25 plates
208S&F (in replacement) Digital Over Current Relay, single phase, 50 Hz suitable for 11 KV VCB panel, including connection with proper setting and testing complete all as specified and directed Make :- Crompton Greaves model No CGI 14N or equivalent in L&T / Siemens
209S&F (in replacement) bracket for street light made out of 40 mm bore GI pipe medium grade not less than 1.2 mtr length bent to shape fixed on pole/wall with and including50x6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
210S&F repair automatic transfer switch 4 pole, 630 Amps, 415 volts, closing current 8A/230 V AC and tripping current 0.8 A/230 V AC with wiring/electric connection complete all as specified and directed. Make:- Havells/ABB or equialent as approved.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy