| 1 | Mandar R/L |
| 2 | Earth work in hard soil for excavation of foundation including dressing and levlling the bed and depositing the soil within 50 mtr. initial lead and 1.5 mtr. initial lift as per direction of Engineer-in-charge. |
| 3 | Filling in foundation and plinth with sand wellwatered and rammed including cost of sand as per direction of Engineer-in-charge. |
| 4 | C.C(1:4:8) with 4 Cm. size H.B.G metal laying and hoistingetc. complete with curing as per direction of Engineer-in-charge |
| 5 | Brick work with Fly ash bricks of(23cm x 11 cm x 8 cm )in cement mortar (1:6) in foundation and plinth with curingetc.complete as per direction of Engineer-in-charge. |
| 6 | Cement concrete (1:2:4) for R.C.C. works with 12mm size h.g.b. chips including hoisting and laying etc. complete with curing as per direction of Engineer-in-charge |
| 7 | Providing & supplyingof M.S.Rod forfor M.S. Reinforcement for R.C.C work including cutting, bending, binding & tying the grills & placing in position including cost of binding wire etc.complete as per direction of Engineer-in-charge |
| 8 | Rigidsmooth centering and shuttering for R.C.C. works including false work and dismentling them after casting including cost of materials complete etc. completeforColumn baseetc |
| 9 | Rigidsmooth centering and shuttering for R.C.C. works including false work and dismentling them after casting including cost of materials complete etc. completefor Slab,Column,Beam etc. |
| 10 | Rigidsmooth centering and shuttering for R.C.C. works including false work and dismentling them after casting including cost of materials complete etc. completefor Lintel |
| 11 | Cement concrete (1:2:4) with 12mm size h.g.b. chips including hoisting and laying etc. complete with curing as per direction of Engineer-in-charge |
| 12 | 12 mm thick cement plastering with cement mortar(1:6)over brick work with curing etc.complete.as per direction of Engineer-in-charge. |
| 13 | Filling F & P with excavated materials, earth, moorum including watering and ramming as directed by the Engineer-in-charge. |
| 14 | Labour charges for conveyance of 200mmdiaPVC pipes from stack yardto work siteandLaying & fittingof the sameas per direction ofsite Engineer in charge. |
| 15 | Labour charges for conveyance of 160mmdiaPVC pipes from stack yardto work siteandLaying & fittingof the sameas per direction ofsite Engineer in charge. |
| 16 | Brick work with Fly ash bricks of size (23cm x 11 cm x 8 cm ) having crushing strength not less than 75kg./cm2 with dimensional tolerance+ 8% in cement mortar (1:6)inSuperstructurewith curingetc.complete as per direction of Engineer-in-charge. |
| 17 | 2.5 cm artificial stone flooring with cement concrete (1:2:4) including punning using 12mm size hard broken granite chips etc. complete with curing as per direction of Engineer-in-charge |
| 18 | Finishing walls with water proofing cement paint of approved shade on new work two coatsover 2 coats of White washing to give an even shape including cost of paint etc.complete as per direction of Engineer-in-Charge. |
| 19 | Painting two coats with any approved paint over a coat of primer on new M.S Shutter including cost of paint ,primer and labour charges and all taxes etc..complete as per direction of Engineer-in-Charge. |
| 20 | Providing electrificaton to the Pump chamber by wiring the room with required item of materials including cost ofmaterial,labour,T& P etc. complete as per direction of Engineer-in-charge. |
| 21 | Construction of Display Board with 45mm dia steel pipes 2nos with a height of 1.50mtr over the ground level having couping depth of 0.60mtrwith a width of 1mtr jointed with MS plate of size 1.00mtrx0.75mtr and painting,lettering the detail salient featuresof project over the plate having radium back ground etc. complete as per direction of Engineer-in-Charge |
| 22 | Installation ofMono Block Pump Set,on fixed foundation ,fitting of 100 mm dia G.I.Pipe in Suction side & delivery side with required G.I.Flange, Bend, socket, primary unit, foot valve,N.R.Valve, nut bolt, rubber packing etc., cutting ,threading & welding of G.I.Pipe connecting the same with Z type to main pressure P.V.C. pipe line including cost of white lead paint ,cotton tape,M seal ,hickaw blade and other unforseen items as required for fitting works ,earch cutting of river bank , river belt, making Sump pit for dipping of foot valve at required depth for smooth running of Pump set including all transportation of materials etc.& Electrical Installation completeas per direction of the site Engineer-in-charge |
| 23 | Supplythe hard copy & soft copy of 3 stage Photographs of the projectandpreparation of Handing over Documents of Panipanchayat etc.completeas perdirection of site Engineer in charge. |
| 24 | Providing ,fitting & fixingofM.S.shutter confirming to IS No.6248/7 of size (0.76x0.90) sq.mtrhaving32mmx32mm angle iron framed chowkhat and shutter plate with 18SWG MS Sheet includingall costs,taxes etccomplete with priming & paintingas per satisfaction of Engineer-in-Charge. |
| 25 | Providing ,fitting & fixingofM.S. WINDOWconfirming to IS No.6248/7 of size (0.76x1.00) sq.mtrhaving32mmx32mm angle iron framed chowkhat and shutter plate with 18SWG MS Sheet includingall costs,taxes etccomplete with priming & paintingas per satisfaction of Engineer-in-Charge. |
| 26 | 10 HP/7.50 KW Energy efficiency Monoblock pump set of total head 18 mtrs having discharge 1700 LPM withsquirrel cage induction motor fitted with bronze impeller TB-2 of IS 318/1981, companion flanges & Class \"F\"insulation suitable for operation 415 volt +6%-15% 3 phase, 50Hz AC poweer supply suction/deliveery= 100mmx100mm with BEE 3 Star rated energy efficiency Pump & as per IS-9079/2002 with overall efficiency 62 to 65% of reputed brand having wide dealership net work for easy availability of spares confirming to IS specification (a) Casing: FC 200 as per IS 210/1978 (b) Impeller: Bronze grade LTB-2 of IS 318/1981 including all cost, conveyance, cess etc complete but excluding cost of GST |
| 27 | Automatic Star Delta starter sheet steel enclosure suitable for operation of squirrel cage Induction motor upto 15HP (8-13) with 16. Amp (AC-3) contactor at 415 volt +6%-15%, 3 phase, 50 Hz, AC supply with suitable overload relay & No volt coil with electric pnemutic timer suitable for operation at voltage range of 300-440 volt having dependable protection against overload and single phasing & should be of reputed brand of ISI specifications having wide dealership network for easy availability of spares including all cost, conveyance, cess etc complete but excluding cost of GST |
| 28 | 63 AMP Triple Pole Mainswith confirming to IS No.4064(Part I & II) with ISI marking of reputed company having utilisation capacity cagegory AC- 22 reputed brand of ISI specification including all cost, conveyance, cess etc complete but excluding cost of GST |
| 29 | Motor hood size (0.45mx0.45mx0.60m) made with 18 SWG (cold rolled M.S.Sheet with one coat of red axide primer and two coats of powder coated paint of approved quality on both side (inside & outside) suitable to cover centrifugal monoblock Pump Set from 10 HP to 15 HP and having provision for attachement with the groves on rear side of the pannel board of approved brand including all cost, conveyance, cess etc complete as per the direction of the Engineer-In-Charge but excluding cost of GST |
| 30 | 3x10 sqmm PVC insulated (HD) tropoder armoured Electric Cable with alluminum conductor for use in 3 phase power system of working voltage upto & including 1100 volts at 50Hz confirming to IS 7098 (Pt-II) of approved brand ofISI marked including all cost, conveyance, cess etc complete but excluding cost of GST |
| 31 | 4KVAR Power ShuntCapacitor with ISI mark of of reputed approved brand ofISI marked including all cost, conveyance, cess etc complete but excluding cost of GST |
| 32 | 100mm dia nominal bore G.I.pipe having wall thickness 4.5mm electrical resistance welded of medium class confirming to IS- 1239(part-1/2004) with latest ammendments, screwed at both ends as per IS-554 with socketed at one end and the other end protected with plastic threaded protector including its transportation and unloading at L.I.P. site. The socket confirming to ISI 1239(part II/1992) with latest ammendments in random length of 4 to 7 mtr.Each pipe should bear IS certification and manufacturers name/trade mark. |
| 33 | 100mm dia C.I. Screw boss Foot Valve of swing type friction less with single disc conforming to IS-4038/1979 of reputed brand with ISI mark of reputed company having wide dealership network including all cost, conveyance, cess etc complete but excluding cost of GST |
| 34 | 100mm dia C.I.Double Flanged Non Return Valve swing type PN-1.0 (IS-5312(Part-I-2004) with bypass arrangement with ISI mark of reputed brand including all cost, conveyance, cess etc complete but excluding cost of GST |
| 35 | 100mm dia G.I.Bend( Medium Duty) conforming to IS No-1239 (part II/1992) with ISI mark of reputed brand including all cost, conveyance, cess etc complete but excluding cost of GST |
| 36 | 100mm dia G.I.Flange(Medium Duty) conforming to IS No-6392/1971 with ISI mark of reputed brand including all cost, conveyance, cess etc complete but excluding cost of GST |
| 37 | 100X100X75mm dia G.I.Tee with ISI mark of reputed brand having priming arrangement by locking system including all cost, conveyance, cess etc complete but excluding cost of GST |
| 38 | Cost, supplying of 50mm diaC.I double Air Release Valve with saddle and Raiser pipe conforming to IS 14845 (SI) with ISI mark |
| 39 | Rigid UPVC pipe of 200 mm diaIvory grey in colour having specific gravity of 1.4 to 1.46 Gm / CC ofstraightlength of 6 M for portable water supplies confirming to IS 4985 / 2000 of BIS - Amendment - 2 Read with Table - I , of IS specification bearing ISI Mark for working presure of 4Kgf/Cm2 as per latest amendment of ISI 4985 including cost of coupler for plain ended pipes or one end plain & other bell ended. The pipe should be tested by CIPET & each pipe should be clearly & indebile marked ink or Stenciled conforming to IS 4985/2000including transportationand laying at site all complete. (The Rate inclusive of CIPET Testing Charges) |
| 40 | 200 mmX110mm dia PVC Reducing Socket (6Kgf/Cm2) |
| 41 | 200 mmX160mm dia PVC Reducing Socket (6Kgf/Cm2) |
| 42 | 200 mm dia PVC End Cap(6Kgf/Cm2) |
| 43 | 200 mm dia PVC Equal Tee(6Kgf/Cm2) |
| 44 | Rigid UPVC pipe of 160 mm diaIvory grey in colour having specific gravity of 1.4 to 1.46 Gm / CC ofstraightlength of 6 M for portable water supplies confirming to IS 4985 / 2000 of BIS - Amendment - 2 Read with Table - I , of IS specification bearing ISI Mark for working presure of 2.5 Kgf/Cm2 as per latest amendment of ISI 4985 including cost of coupler for plain ended pipes or one end plain & other bell ended. The pipe should be tested by CIPET & each pipe should be clearly & indebile marked ink or Stenciled conforming to IS 4985/2000including transportationand laying at site all complete. (The Rate inclusive of CIPET Testing Charges) |
| 45 | 160 mm dia PVC End Cap(6Kgf/Cm2) |
| 46 | 160 mm dia PVC Equal Tee(6Kgf/Cm2) |
| 47 | 200mmx200mmx160 mm dia PVCTee(6Kgf/Cm2) |
| 48 | Cost, supplying of 160mmx160mmx110mm dia Weldless G.I.Tee (3.6mm thickness) with bend, closing and opening arrangement of reputed brand including all cost, conveyance, cess etc complete but excluding cost of GST |
| 49 | Construction of 3 phase 11 KV line as per REC standard confirming to IE Rules 1956 with 300 kg 9Mtrlong PSC Pole(IS: 1678-1998) with 55mm² AAA Conductor,11 KV \"V\" Cross arm(10.2 k.g. each), with required No.of 11 KV T & C Disc. Insulators 70KN in tension point &11 KV Pin insulators, Couping & Padding of Poles. Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & double stay at end point with 18 mm G.I.H.T.Stay, concreting of Stay with Anchor plate, guarding at Road crossings etc.with a cut point including cost of all materials, labour transportation,inspection & commissioning etc. complete. |
| 50 | Construction anderection of 11 /0.4 KV ,25 KVA Double Pole mounted Substationwith BIS Energy Level-II transformer confirming to RE Rules 1956, mounted on 2.44 Mtr. Long structure, supported in 300 kg 9 mtr long PSC pole,transformer hard channel & top channel made of 2.8 M long 100 X 50 X 6 mm M.S.Channel (9.2 kg/mtr), Transformer belting on 2.80 M long 50 X 50 X 5 mm M.S.Angle(4.5 kg/mtr),, (all REC SPN Std.F-3) with all accessories like 3 pole 11 KV HG Fuse(F-5)& A.B.Switches(F-9) both mounted on 2.8 M long 75 X 40 X 6 mm M.S.Channel and supported by 1.0 M long 50 X 50 X 6 mm M.S.Angle, with 3 No. 11 KV Lightening Arrestors & Distribution box for25KVA S/S, G.I.pipe earthingwith 25X5mm G.I.Flatsincluding cost of 25 KVA 11/0.4 K.V. 3 star rated Transformer , 35 Sqmm 3 ½ Core PVC Cable - 40 mtr, couping & padding of Poles, Danger board at each Pole, Anti climbing Devices & all other necessary fittings i.e required size Nuts & Bolts, Brackets, Cable, Cable Sockets etc., including cost of all materials, labour , transportation complete with liasioning for testing inspection & commissioning. |
| 51 | Construction of 3 phase 4 wire Line using 8mtr long 200 kgPSC Poles with LT XLPE AB Cable of (3X35 mmSq.+ 1X25mm sq.) along with all required materials and concreting of stay/poles LT Dead end clamp, suspension clamp with I - hook, stay accessories such as Wire Insulators, clamp etc.to completepower supply as per the field condition (40m Span length) |
| 52 | Construction ofBoundary wallof (3.70mx 2.5 )Sq.mtr having total inside lenth of 11.20mtr around the sub station by providing10no of 23cmx23cm pillarsand restwalling withbrick masonary having proper foundation as per the drawingincluding Sand filling and metal spreading inside the boundary , Fixing of MSgrill gate of size 1.5mx1.5mwith 35x35x6mm angles and 25x6mm flatsetc. as per direction of Engineer-in-charge. |
| 53 | Earthing installation with required earthing materials like charcoal, common salt, conduit pipe, soft solder alcaps ,nuts & bolts, cable socket etc. including excavationof earth pits2 Nos of size 1200mm X1200mm X 3000mm for fixing of earthing pipe2 Nos of size 30mm dia X 3000 mm length with required slotting in pipes & fittings with 30 mm dia G.I.Flange etc. includidng excavation of earthing trench for laying of earthing G.I.Wire & filling the Trench Pits after fixing of pipes on completion on earthing work and pannel wiring with required4mm2/2.5mm2PVC coper wire including supply & transportation of materials to work site as per the direction of site Engineer in-charge. |