Tender For Provision Of Automatic Power Control Unit Panel At Af Stn Abohar Under Ge Af Bhisiana, bhisiana-Punjab

Military Engineer Services-MES has published Tender For Provision Of Automatic Power Control Unit Panel At Af Stn Abohar Under Ge Af Bhisiana. Submission Date for this Tender is 04-11-2023. Electrification Work Tenders in bhisiana Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

40036225
Corrigendum : Tender For Provision Of Automatic Power Control Unit Panel At Af Stn Abohar Under Ge Af Bhisiana
Open Tender
Indian
Punjab
bhisiana
04-11-2023

Tender Details

Provision Of Automatic Power Control Unit Panel At Af Stn Abohar Under Ge Af Bhisiana As Per Boq / Price Schedule; 1 Supply, Installing, Testing And Commissioning Factory Made And Cpri Type Tested 100 Kvar Apfc Panel ( 50+25+15+5+5 ) Indoor Type Platform Mounted, Suitable For 415 Volts 3 Phase 4 Wire 50 Hz Ac Supply Copper Having Bus Bar Of Rating 1.5 Times That Of Incoming Mccb Installed.The Panel Shall Be Dust And Vermai Proof Ip-54 Class Protection And Made Of 3.15 Mm Crca Ms Sheet And 50 X 50 X 6Mm Thick Angle Iron Frame Work; Front Opening Type With Double Door Shutter And Locking Arrangement With 2 Keys ) , Powder Coated Finish ( Over A Coat Of Red Oxide ) , Primer On Outside And Two Coats Of Red Oxide Primer On Inside Surface.The Panel Is Including Platform With Pcc 1:4:8 Type D-2 With 40Mm Crushed Stone Aggregate 20Cm In Thick In Foundation And Of Height Upto 3 Mtr Above The Nearest Road Level All As Directed By Engr-In-Charge.All Interconnection Between The Main Bus Bar As Well As Outgoind Feeders Shall Be Carried Out With Tp Copper Bus Bar Of Rating Not Less Than 1.5 Time Rated Capacity Of Individual Outgoing Feeders And Should Be Insulated With Colour Coded Shrinkable Pvc Sleeves.The Mccb Should Be Adjustable Type.The Body Of The Panel Shall Be Powder Coated .Provision Of Threaded Earthing Stud At Bottom & Lifting Lugs Of Suitable Size At Top To Lift Panel Safely Shall Be Made.The Incommer Mccb As Well As Outgoings Shall Have Copper Tpn Extension Links ( Not Less Than 300 Mm Long ) Of Current Carrying Capacity Not Less Than 1.5 Times The Rated Capacity Of Individual Feeders And Should Be Insulated With Heat Shrinkable Pvc Sleeves.All Control Wires Shall Be Of 2.5 Sqmm Multi Stranded Copper Conductor ( Fr ) And Shall Be Properly Bunched, Tied, Ferruled For Proper Identification And Crimped With Adequate Size Of Lugs.A Detachable Predrilled Powder Coated Gland Plate Of Thickness 3.15 Mm Should Be Used At The Bottom.The Scope Of Work Includes Provision Of Following :- ( I ) Mccb Tp 3 Pole 315 Amps 25 Ka Thermal Setting 80-100%, O / C, S / C Release-01 No ( Incoming ) ( Ii ) Mcb Tp, C-Curve, 3 Pole 10 Ka 63 Amp With Thermal Setting 80-100%-01 Nos ( Outgoing ) Make : ( Iii ) Mcb Tp, C-Curve, 3 Pole 10 Kva 32 Amp With Thermal Setting 80-100%-01 Nos ( Outgoing ) ( Iv ) Mcb Tp 3 Pole 10 Ka 16 Amp With Thermal Setting 80-100%-01 Nos ( Outgoing ) 2 ( V ) Apfc Relay 5 Stage With Inbuit P.F Meter -02 No. ( Vi ) Aux. Contactor, 230 V Ac, 4 Nc 02 Nos ( Vii ) Aux Contactor 230V Ac, 4 No - 02 Nos ( Viii ) Heavy Duty Capacitor Bank, 440 V, 5 Kvar - 02 Nos ( Ix ) Heavy Duty Capacitor Bank, 440V, 15 Kvar - 01 Nos ( X ) Heavy Duty Capacitor Bank, 440V, 25 Kvar - 01 Nos ( Xi ) Heavy Duty Capacitor Bank, 440V, 50 Kvar - 01 Nos ( Xii ) Heavy Duty Capacitor Bank, 440V, 25 Kvar - 02 Nos ( Xiii ) Capacitor Duty Contactor With 1 No Aux Contact, 230V Coil Voltage, 5 Kvar - 02Nos ( Xiv ) Capacitor Duty Contactor With 1 No Aux Contact, 230V Coil Voltage, 15 Kvar-01 No ( Xv ) Capacitor Duty Contactor With 1 No Aux Contact, 230V Coil Voltage 25 Kvar-01 No ( Xvi ) Capacitor Duty Contactor With 1 No Aux Contact, 230 V Coil Voltage 50 Kvar-01 Nos ( Xvii ) 6 Exhaust Fan - 01 No ( Xviii ) On Delay Timer ( 0-60 Secs ) 230 V Ac - 01 No ( Xix ) Sfu With Link 200 A Tpn - 01 No ( Xv ) Auto / Manual Selector Switch, 6 Amps, 1 Pole, 2 Way+Off-01 No ( Xxi ) Digital Voltmeter With Built In Selector Switch, 415 V Ac, 96 Sqmm - 01 No ( Xxii ) Current Transformer, Ctr-150 / 5A - 03 Nos ( Xxiii ) Led Type Indiacting Lamp, R-Y-B Phase ( 22.5Mm Dia ) 230 V Ac - 01 Set ( Xxiv ) Push Button , Green 230 V Ac, 1 No - 05 Nos ( Xxv ) Push Button , Red 230 V Ac, 2 Nc - 05 Nos ( Xxvi ) Thermostate ( 30-80 Degree ) , 230 V Ac - 01 No. ( Xxvii ) Control Fuse, 2 Amps - 05 Nos ( Xxviii ) Hrc Fuse With Base 16 A - 02 Nos ( Xxix ) Hrc Fuse With Base, 25A - 01 Nos ( Xxx ) Hrc Fuse With Base, 40 A - 01 Nos ( Xxxi ) Hrc Fuse With Base, 63 A - 01 Nos 3 Note:- ( A ) The Quoted Unit Cost Shallinclude Dismantling Of Existing Lt Cable From Lt Side Of The Transformer And Cutting The Deterorating Cable Up To 02 Mtr Length And Supply And Fix New Cable Of Existing Size Lt Cable 02 Mtr Length. ( B ) The Quoted Unit Cost Shall Include Earth Work Such As Excavation , Returning & Fillingfrom The Existing Loop , Supply And Fix On New Thimbles With Aluminium Including . M&L For Dead Ending Cable Joint Of Existing Size Cable ( 02 Nos End Joint 01 Is Towards Transformer And Other Is Lt Panel Side. ( C ) Connection Of Apfc Panel With Bus Bar Of Main Lt Panel Including Supply And Fixing New Thimbles Of Lt Panel Cables Of Both Side With Lt Cables End Dead Joint Box-02 Nos . With Matching With Existing Cable 02 Nos ( 01 Towards Bus Bar Of Main Lt Panel And 2Nd Is Towards On Connection Of Apfc Panel. ( D ) Ge Shallapprovesample For Afc Panel And Individual Accessories As Per Approved Make Before Incorporation Of Works. 4 Supply, Installing, Testing And Commissioning Factory Made And Cpri Type Tested 35 Kvar Apfc Panel ( 25+15+5 ) Indoor Type Platform Mounted, Suitable For 415 Volts 3 Phase 4 Wire 50 Hz Ac Supply Copper Having Bus Bar Of Rating 1.5 Times That Of Incoming Mccb Installed.The Panel Shall Be Dust And Vermai Proof Ip-54 Class Protection And Made Of 3.15 Mm Crca Ms Sheet And 50 X 50 X 6Mm Thick Angle Iron Frame Work; Front Opening Type With Double Door Shutter And Locking Arrangement With 2 Keys ) , Powder Coated Finish ( Over A Coat Of Red Oxide ) , Primer On Outside And Two Coats Of Red Oxide Primer On Inside Surface.The Panel Is Including Platform With Pcc 1:4:8 Type D-2 With 40Mm Crushed Stone Aggregate 20Cm In Thick In Foundation And Of Height Upto 3 Mtr Above The Nearest Road Level All As Directed By Engr-In-Charge.All Interconnection Between The Main Bus Bar As Well As Outgoind Feeders Shall Be Carried Out With Tp Copper Bus Bar Of Rating Not Less Than 1.5 Time Rated Capacity Of Individual Outgoing Feeders And Should Be Insulated With Colour Coded Shrinkable Pvc Sleeves.The Mccb Should Be Adjustable Type.The Body Of The Panel Shall Be Powder Coated .Provision Of Threaded Earthing Stud At Bottom & Lifting Lugs Of Suitable Size At Top To Lift Panel Safely Shall Be Made.The Incommer Mccb As Well As Outgoings Shall Have Copper Tpn Extension Links ( Not Less Than 300 Mm Long ) Of Current Carrying Capacity Not Less Than 1.5 Times The Rated Capacity Of Individual Feeders And Should Be Insulated With Heat Shrinkable Pvc Sleeves.All Control Wires Shall Be Of 2.5 Sqmm Multi Stranded Copper Conductor ( Fr ) And Shall Be Properly Bunched, Tied, Ferruled For Proper Identification And Crimped With Adequate Size Of Lugs.A Detachable Predrilled Powder Coated Gland Plate Of Thickness 3.15 Mm Should Be Used At The Bottom.The Scope Of Work Includes Provision Of Following :- ( I ) Mccb Tp 3 Pole 125 Amps 25 Ka Thermal Setting 80-100%, O / C, S / C Release-01 No ( Incoming ) ( Ii ) Mcb Tp, C-Curve, 3 Pole 10 Ka 63 Amp With Thermal Setting 80-100%-01 Nos ( Outgoing ) ( Iii ) Mcb Tp, C-Curve, 3 Pole 10 Kva 32 Amp With Thermal Setting 80-100%-01 Nos ( Outgoing ) ( Iv ) Mcb Tp 3 Pole 10 Ka 16 Amp With Thermal Setting 80-100%-02 Nos ( Outgoing ) ( V ) Apfc Relay 03 Stage With Inbuit P.F Meter -02 No. 5 ( Vi ) Aux. Contactor, 230 V Ac, 4 Nc 02 Nos ( Vii ) Aux Contactor 230V Ac, 4 No - 02 Nos ( Viii ) Heavy Duty Capacitor Bank, 440 V, 5 Kvar - 01 Nos ( Ix ) Heavy Duty Capacitor Bank, 440V, 15 Kvar - 01 Nos ( X ) Heavy Duty Capacitor Bank, 440V, 25 Kvar - 01 Nos ( Xi ) Heavy Duty Capacitor Bank, 440V, 50 Kvar - 01 Nos ( Xii ) Capacitor Duty Contactor With 1 No Aux Contact, 230V Coil Voltage, 5 Kvar - 01 ( Xiii ) Capacitor Duty Contactor With 1 No Aux Contact, 230V Coil Voltage, 15 Kvar-01 ( Xiv ) Capacitor Duty Contactor With 1 No Aux Contact, 230V Coil Voltage 25 Kvar-01 Xvii ) On Delay Timer ( 0-60 Secs ) 230 V Ac - 01 No ( Xviii ) Sfu With Link 200 A Tpn - 01 No ( Xix ) Auto / Manual Selector Switch, 6 Amps, 1 Pole, 2 Way+Off-01 No ( Xxi ) Digital Voltmeter With Built In Selector Switch, 415 V Ac, 96 Sqmm - 01 No ( Xxii ) Current Transformer, Ctr-150 / 5A - 03 Nos ( Xxiii ) Led Type Indiacting Lamp, R-Y-B Phase ( 22.5Mm Dia ) 230 V Ac - 01 Set ( Xxiv ) Push Button , Green 230 V Ac, 1 No - 03 Nos ( Xxv ) Push Button , Red 230 V Ac, 2 Nc - 05 Nos Xxvi ) Thermostate ( 30-80 Degree ) , 230 V Ac - 01 No. ( Xxvii ) Control Fuse, 2 Amps - 03 Nos Xxviii ) Hrc Fuse With Base 16 A - 01 Nos ( Xxix ) Hrc Fuse With Base, 25A - 01 Nos ( Xxx ) Hrc Fuse With Base, 40 A - 01 Nos 6 Note: ( A ) The Quoted Unit Cost Shallinclude Dismantling Of Existing Lt Cable From Lt Side Of The Transformer And Cutting The Deterorating Cable Up To 02 Mtr Length And Supply And Fix New Same Size Lt Cable 02 Mtr Length. ( B ) The Quoted Unit Cost Also Including Its Excavation , Returning & Fillingfrom The Existing Loop , Supply And Fix On New Thimbles With Aluminium Including . M&L For Dead Ending Cable Joint Of Existing Size Cable ( 02 Nos End Joint 01 Is Towards Transformer And Other Is Lt Panel Side. ( C ) Connection Of Apfc Panel With Bus Bar Of Main Lt Panel Including Supply And Fixing New Thimbles Of Lt Panel Cables Of Both Side With Lt Cables End Dead Joint Box-02 Nos . With Matching With Existing Cable 02 Nos ( 01 Towards Bus Bar Of Main Lt Panel And 2Nd Is Towards On Connection Of Apfc Panel. ( D ) Ge Shall Approvesample For Afc Panel And Individual Accessories As Per Approved Make Before Incorporation Of Works. 7 S&F Mccb 4 Pole 500 Amp Breaking Capacity 36 Ka 415 Volt 50 Hz Including Necessary Incoming And Outgoing Electric Connection With Suitable Size Of Copper Lugs Complete All As Specified And As Directed By Engineer In Charge. 8 Supply, Installation , Testing And Commissioningbattery Bank 24 V Dc 100 Ah With Maintenance Free Battries Type Vrla , Nos Of Cells 12, Including Full Sine Wavehalf Controlled Float Cum Boost Charger 3 Phase 4 Wire Suitbale For Acinput 415 V ( + - ) 10% , Includinganalog Type Meter Of Size 96Mmx96mm 90 Degree Deflection For Measuring The Parameter Such As Ac Voltmeter With Selector Switch , Ac Ameterwith Selector Switch , Dc Voltmeter With Selector Switch And Dc Ammeter With Selector Switch , Including Neon Lamps For The Indication Of Mains On Adn Led Ijndicators For Charger On / Boost On / Dc Over Voltage / Dc Under Voltage / Ac Supplyfail / Rectifierfusefail / Battery Earth Fault, Including Protections Such As Ac Input Circuit Breaker , Fast Acting Semiconductor Fuse For Charger Bridge , Dc Over Voltage Cutback , Dc Overload Protection Battery Input Fuses, Dc Circuit Breaker And Blocking Diodewith And Including Float Voltage Adjust Potentiometer , Boost Voltage Adjust Potentiometer , Auto , Manual Float / Boost Mode Select Switch , Ac Input Circuit Breaker And Dc Voltmeter Selector Switch Including Special Features Such As Soft Start On Dc Side , Class -F Insulation For All Magnetics , Automatic Voltage Regulation Using Digital Controlled Closed Loop System, Filter Circuit To Limit Ripple , Automatic Float / Boost Changeover Based On Current Drawn By Battery , Built In Auto Phase Reversal Operation , All The Accessories Fitted In Free Standing Cabinet, Floor Mounting Type, Steel Construction, Made Out Of Crca Sheet 2. Mm Thick For Frame And Front Door Adn Rest 1.6 Mm Thick , Duly Seven Tank Processed And Painted With Ral 7032 , Protection Class Ip-42Easy Access For I&C And Operation & Maintenance Including Connection With H1 & H2 Circuit Of Vcb With Suitable Size And Length Ofinclusing Copper Lugs Adn Cable Copper Cable As Required Length At Site , Cable Entry At Bottom Complete All As Specified And As Directed By Engineer In Charge.Note: ( A ) All The Cable Entries Should Be Metalic Gland Only For Battery Details ( B ) The Batteries Shall Have Following Specifications ( I ) 02 Volt 100 Ah , No Of Cell -12, Total Volt 12X2 24 Volt, , Total Ah 12X10= 1200 Ah 9 Supply And Laying , Lt Ug Xlpe Insulated 1100 Volt Grade Heavy Duty Electric Cables With Aluminium Conductor , Cross Sectional Area 240 Sqmm 3.5 Core All As Specified And Directed Tfr To Proposed Panel 160 Kva-02 Nos ) , Complete All As Specified And Directed By Engineer In Charge. 10 Supply And Laying , Lt Ug Xlpe Insulated 1100 Volt Grade Heavy Duty Electric Cables With Aluminium Conductor , Cross Sectional Area 70 Sqmm 3.5 Core All As Specified And Directed ( Tfr To Proposed Panel 63 Kva ) , Complete All As Specified And Directed By Engineer In Charge. 11 Supply Anfd Fix Cable Jointing Kit For 11 Kv ( Earthed ) Grade Cable For Indoor Termination Cold Shrink Type Joint Complete With Jointing Material And Accessories Suitable For 3 Core Xlpearmoured Aluminium Conductor Cable Of Cable Endjoint Kit Size 120 Sqmm To 185 Sqmm, Complete All As Specified And Directed By Engineer In Charge. 12 Supply And Fix Cable Jointing Kit For 1.1 Kv Grade Cable For Straight Through Joint Complete With Jointing Material Heat Shrink Type And Accessories Suitable For 3 ½ / 4 Core Xlpe, Armoured, Al Conductor Cable Of Size 185 To 240 Sqmm, Indoor / Outdoor Type, Complete All As Specified And Directed By Engineer In Charge. 13 Supply And Fix Cable Jointing Kit For 1.1 Kv Grade Cable For Straight Through Joint Complete With Jointing Material Heat Shrink Type And Accessories Suitable For 3 ½ / 4 Core Xlpe, Armoured, Al Conductor Cable Of Size 70 Sqmm, Indoor / Outdoor Type, Complete All As Specified And Directed By Engineer In Charge. 14 Excavation In Trenches Not Exceeding 1.5 Mtr Wide And Not Exceeding 1.5 Mtr In Deep For Foundation Of Poles / Stays / Cables / Pipe Lines Etc And Getting Out In Soft / Loose Soil, Complete All As Specified And Directed By Engineer In Charge. 15 Returning, Filling In Including Spreading, Leveling, Watering And Well Ramming In Layers Each Not Exceeding 25 Cm Thickness, Complete All As Specified And Directed By Engineer In Charge. 16 Removing Surplus Soil To A Distance Not Exceeding 50M And Depositing Where Directed At A Level Not Exceeding 1.5 M Above The Starting Point, Complete All As Specified And Directed By Engineer In Charge. 17 Material And Labour For Sand Cushioning With A Layer Of Sand 8 Cm Thick Before Laying Of Cable And 15 Cm Thick After Laying Of Cable In Trenches, Complete All As Specified And Directed By Engineer In Charge. 18 Supplying & Laying Old Size Sub Calss B Bricks Laid Flat In Trenches Over The Cable With Length Of Bricks Perpendicular To The Direction Of Cable, Adjacent / Abutting Each Other, Complete All As Specified And Directed By Engineer In Charge. 19 Supply And Fixing Of Earthing Complete With Galvanised Steel Steel Earth Plate Electrode 600X600x6mm Thick Burried Directly In Ground ( Earth Pit Not Less Than 2.25 Mtrs Deep Below Nominal Ground Level ) With Top Edge Of The Plate Not Less Than 1.5 Mtrs Below Nominal Ground Level Connected To Galvanised Strip 25X4 Mm By Means Of Bolts, Nuts, Check Nuts And Washers Of Gi All As Shown In Electrical Plate No 3 Of Ssr Part I Connected To Earthing Test Point And Testing On Completion. All As Specified And As Directed. Note:- The Cast Of Excavation And Earth Work Pcc Pit And Pcc Cover With Handle, Funnel & Watering Pipe, Wiremesh, Charcoal Dust And Common Salt And Earth Strip Up To 7.5 Mtrs Long Shall Be Deemed Included In The Unit Rate For Earthing, Complete All As Specified And Directed By Engineer In Charge. 20 Material And Labour For Pcc 1:3:6, Type C-1, Using 20Mm Graded Stone Aggregate For Road Cutting / Making Plith For Transformer Where Required And Fair Finishing To Exposed Surfaces Without Using Extra Cement Including Necessary Form Work Complete All As Specified And Directed By Engineer In Charge. 21 Supply And Fixing Of Gi Tubing Light Grade Of 100 Mm Dia For Cable Protection On Pole / Wall / Floor Or In Trenches And Drain Etc Complete With Necessary Clamp, Nut, Bolts And Washers And Socket And Making Good The Disturbed Surface Of Wall, Complete All As Specified And Directed By Engineer In Charge. 22 Supply And Fixing Of Synthetic Insulating Mat For Electrical Instrument Of Size 2.5Mx1mx12mm, Complete All As Specified And Directed By Engineer In Charge. 23 M&L For Concealed Point Wiring Complete With 4 Sqmm Single Core Multistranded Copper Conductor Pvc Insulated And Unsheathedcable 1100 Volts Grade Drawn Through And Including Non Metallic Rigid Pvc Conduit, Medium Grade Minimum 25Mm Dia Isi Marked And Conduit Accessories Fixed Concealed In Wall / Ceiling / Roof Etc With Sunken Type Pressed Steel / Welded Ms Terminal Boxes Made Out Of 4 Mm Ms Sheet, 3Mm Thick Laminated Sheath Top Cover For Mounting Of Fittings, Switches, Sockets Outlets, Regulators Etc Complete Including Provisining Of 4 Sqmm Pvc Insulatedunsheathedcable 1100 Volt Grade With Multi Stranded Copper Conductor To Common Earth And Connected To Earth Dolly For Tone 3 Pin Socket Outlet. 15 Amps, Independent, With Cables 4 Sq.Mm Size, Complete All As Specified And Directed By Engineer In Charge. 24 Supply And Laying , Pvc Insulated And Fr Pvc Round Sheathed, Copper Conductorconforming To Is: 694 Pvc Nsulated 1100 Volt Grade Heavy Duty Electric Cables With Copper Conductor , Cross Sectional Area 4 Sqmm 2 Corecomplete All As Specified And Directed By Engineer In Charge. 25 Supply And Laying , Pvc Insulated And Fr Pvc Round Sheathed, Copper Conductorconforming To Is: 694 Pvc Nsulated 1100 Volt Grade Heavy Duty Electric Cables With Copper Conductor , Cross Sectional Area 16 Sqmm 4 Corecomplete All As Specified And Directed By Engineer In Charge. 26 Supply And Laying , Control Copper Wiring Cablepvc Insulated And Fr Pvc Round Sheathed, Copper Conductorconforming To Is: 694 Pvc Nsulated 1100 Volt Grade Heavy Duty Electric Cables With Copper Conductor , Cross Sectional Area 2.5 Sqmm 01 Corecomplete All As Specified And Directed By Engineer In Charge.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 28-Oct-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 04-11-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 40430.0 /-
Tender Value
INR 20.23 Lakhs /-

BOQ Items

NAME OFWORK : PROVISION OF AUTOMATIC POWERCONTROL UNIT PANEL AT AF STN ABOHAR UNDER UNDER GE(AF) BHISIANA
Sl. No. Item Description
1Supply,installing,testing and commissioning factory made and CPRI type tested 100 KVAR APFC panel(50+25+15+5+5) Indoor type platform mounted, suitable for 415 volts 3 phase 4 wire 50 Hz AC Supply copper having bus bar of rating 1.5 times that of incoming MCCB installed.The panel shall be dust and vermai proof IP-54 class protection and made of 3.15 mm CRCA MS sheet and 50 x 50 x 6mm thick angle iron frame work; front opening type with double door shutter and locking arrangement with 2 keys), powder coated finish (over a coat of red oxide), primer on outside and two coats of red oxide primer on inside surface.The panel is including platform with PCC 1:4:8 type D-2 with 40mm crushed stone aggregate 20cm in thick in foundation and of height upto 3 mtr above the nearest road level all as directed by Engr-in-Charge. All interconnection between the main bus bar as well as outgoind feeders shall be carried out with TP copper bus bar of rating not less than 1.5 time rated capacity of individual outgoing feeders and should be insulated with colour coded shrinkable PVC sleeves.The MCCB should be adjustable type.The body of the panel shall be powder coated .Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift panel safely shall be made.The incommer MCCB as well as outgoings shall have copper TPN extension links (not less than 300 mm long) of current carrying capacity not less than 1.5 times the rated capacity of individual feeders and should be insulated with heat shrinkable PVC sleeves.All control wires shall be of 2.5 sqmm multi stranded copper conductor (FR) and shall be properly bunched, tied,ferruled for proper identification and crimped with adequate size of lugs. A detachable predrilled powder coated gland plate of thickness 3.15 mm should be used at the bottom.The scope of work includes provision of following :- (i)MCCB TP 3 pole 315 Amps 25 KA thermal setting 80-100%, O/C, S/C release-01 No (INCOMING) (ii)MCB TP, C-curve, 3 pole 10 KA 63 Amp with thermal setting 80-100%-01 Nos (OUTGOING) Make : (iii)MCB TP, C-curve, 3 pole 10 KVA 32 Amp with thermal setting 80-100%-01 Nos (OUTGOING) (iv)MCB TP 3 pole 10 KA 16 Amp with thermal setting 80-100%-01 Nos (OUTGOING)
2(v)APFC relay 5 stage with inbuit P.F meter -02 No. (vi) Aux. contactor, 230 V AC, 4 NC 02 Nos (vii)Aux contactor 230V AC, 4 NO - 02 Nos (viii)Heavy duty capacitor Bank, 440 V, 5 KVAR - 02 Nos (ix)Heavy duty capacitor Bank, 440V, 15 KVAR - 01 Nos (x)Heavy duty capacitor Bank, 440V, 25 KVAR - 01 Nos (xi)Heavy duty capacitor Bank, 440V, 50 KVAR - 01 Nos (xii) Heavy duty capacitor Bank, 440V, 25 KVAR - 02 Nos (xiii)Capacitor duty contactor with 1 NO aux contact, 230V coil voltage, 5 KVAR - 02Nos (xiv)Capacitor duty contactor with 1 NO aux contact, 230V coil voltage, 15 KVAR-01 No(xv)Capacitor duty contactor with 1 NO aux contact, 230V coil voltage 25 KVAR-01 No (xvi)Capacitor duty contactor with 1 NO aux contact, 230 V coil voltage 50 KVAR-01 Nos (xvii)6" Exhaust FAN - 01 No (xviii)ON delay timer (0-60 secs) 230 V AC - 01 No (xix)SFU with link 200 A TPN - 01 No (xv)AUTO/MANUAL Selector switch, 6 Amps, 1 POLE, 2 way+OFF-01 No (xxi)Digital Voltmeter with built in selector switch, 415 V AC, 96 sqmm - 01 No (xxii)Current transformer, CTR-150/5A - 03 Nos (xxiii)LED type indiacting lamp, R-Y-B phase (22.5mm dia) 230 V AC - 01 Set (xxiv)Push button , GREEN 230 V AC, 1 NO - 05 Nos (xxv)Push button , RED 230 V AC, 2 NC - 05 Nos (xxvi) Thermostate (30-80 degree), 230 V AC - 01 No. (xxvii)Control fuse, 2 Amps - 05 Nos (xxviii)HRC fuse with base 16 A - 02 Nos (xxix)HRC fuse with base, 25A - 01 Nos (xxx)HRC fuse with base, 40 A - 01 Nos (xxxi)HRC fuse with base, 63 A - 01 Nos
3Note:- (a) The quoted unit cost shallinclude dismantling of existing LT Cable from LT side of the Transformer and cutting the deterorating cable up to 02 mtr length and supply and fix new cable of existing size LT Cable 02 mtr length. (b) The quoted unit cost shall include earth work such as excavation , Returning & Fillingfrom the existing loop ,Supply and fix on new thimbles with aluminium including . M&L for dead ending cable joint of existing size cable (02 Nos end Joint 01 is towards Transformer and other is LT Panel side. (c) Connection of APFC panel with bus bar of Main LT Panel including supply and fixing new thimbles of LT panel cables of both side with LT cables end dead joint Box-02 Nos . with matching with existing cable 02 Nos (01 Towards bus bar of Main LT Panel and 2nd is towards on connection of APFC panel. (d) GE shallapprovesample for AFC Panel and Individual accessories as per approved make before incorporation of works.
4Supply,installing,testing and commissioning factory made and CPRI type tested 35 KVAR APFC panel(25+15+5) Indoor type platform mounted, suitable for 415 volts 3 phase 4 wire 50 Hz AC Supply copper having bus bar of rating 1.5 times that of incoming MCCB installed.The panel shall be dust and vermai proof IP-54 class protection and made of 3.15 mm CRCA MS sheet and 50 x 50 x 6mm thick angle iron frame work; front opening type with double door shutter and locking arrangement with 2 keys), powder coated finish (over a coat of red oxide), primer on outside and two coats of red oxide primer on inside surface.The panel is including platform with PCC 1:4:8 type D-2 with 40mm crushed stone aggregate 20cm in thick in foundation and of height upto 3 mtr above the nearest road level all as directed by Engr-in-Charge.All interconnection between the main bus bar as well as outgoind feeders shall be carried out with TP copper bus bar of rating not less than 1.5 time rated capacity of individual outgoing feeders and should be insulated with colour coded shrinkable PVC sleeves.The MCCB should be adjustable type.The body of the panel shall be powder coated .Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift panel safely shall be made.The incommer MCCB as well as outgoings shall have copper TPN extension links (not less than 300 mm long) of current carrying capacity not less than 1.5 times the rated capacity of individual feeders and should be insulated with heat shrinkable PVC sleeves.All control wires shall be of 2.5 sqmm multi stranded copper conductor (FR) and shall be properly bunched, tied,ferruled for proper identification and crimped with adequate size of lugs. A detachable predrilled powder coated gland plate of thickness 3.15 mm should be used at the bottom.The scope of work includes provision of following :- (i)MCCB TP 3 pole 125 Amps 25 KA thermal setting 80-100%, O/C, S/C release-01 No (INCOMING) (ii)MCB TP, C-curve, 3 pole 10 KA 63 Amp with thermal setting 80-100%-01 Nos (OUTGOING) (iii)MCB TP, C-curve, 3 pole 10 KVA 32 Amp with thermal setting 80-100%-01 Nos (OUTGOING) (iv)MCB TP 3 pole 10 KA 16 Amp with thermal setting 80-100%-02 Nos (OUTGOING) (v)APFC relay 03 stage with inbuit P.F meter -02 No.
5(vi) Aux. contactor, 230 V AC, 4 NC 02 Nos (vii)Aux contactor 230V AC, 4 NO - 02 Nos (viii)Heavy duty capacitor Bank, 440 V, 5 KVAR - 01 Nos (ix)Heavy duty capacitor Bank, 440V, 15 KVAR - 01 Nos (x)Heavy duty capacitor Bank, 440V, 25 KVAR - 01 Nos (xi)Heavy duty capacitor Bank, 440V, 50 KVAR - 01 Nos (xii)Capacitor duty contactor with 1 NO aux contact, 230V coil voltage, 5 KVAR - 01 (xiii)Capacitor duty contactor with 1 NO aux contact, 230V coil voltage, 15 KVAR-01 (xiv)Capacitor duty contactor with 1 NO aux contact, 230V coil voltage 25 KVAR-01 xvii)ON delay timer (0-60 secs) 230 V AC - 01 No (xviii)SFU with link 200 A TPN - 01 No (xix)AUTO/MANUAL Selector switch, 6 Amps, 1 POLE, 2 way+OFF-01 No (xxi)Digital Voltmeter with built in selector switch, 415 V AC, 96 sqmm - 01 No (xxii)Current transformer, CTR-150/5A - 03 Nos (xxiii)LED type indiacting lamp, R-Y-B phase (22.5mm dia) 230 V AC - 01 Set (xxiv)Push button , GREEN 230 V AC, 1 NO - 03 Nos (xxv)Push button , RED 230 V AC, 2 NC - 05 Nos xxvi) Thermostate (30-80 degree), 230 V AC - 01 No. (xxvii)Control fuse, 2 Amps - 03 Nos xxviii)HRC fuse with base 16 A - 01 Nos (xxix)HRC fuse with base, 25A - 01 Nos (xxx)HRC fuse with base, 40 A - 01 Nos
6Note: (a) The quoted unit cost shallinclude dismantling of existing LT Cable from LT side of the Transformer and cutting the deterorating cable up to 02 mtr length and supply and fix new same size LT Cable 02 mtr length. (b) The quoted unit cost also including its excavation , Returning & Fillingfrom the existing loop , Supply and fix on new thimbles with aluminium including . M&L for dead ending cable joint of existing size cable (02 Nos end Joint 01 is towards Transformer and other is LT Panel side. (c) Connection of APFC panel with bus bar of Main LT Panel including supply and fixing new thimbles of LT panel cables of both side with LT cables end dead joint Box-02 Nos . with matching with existing cable 02 Nos (01 Towards bus bar of Main LT Panel and 2nd is towards on connection of APFC panel. (d) GE shall approvesample for AFC Panel and Individual accessories as per approved make before incorporation of works.
7S&F MCCB 4 Pole 500 AMP breaking capacity 36 KA 415 Volt 50 HZ including necessary incoming and outgoing electric connection with suitable size of copper Lugs complete all as specified and as directed by Engineer in Charge.
8Supply, installation , testing and commissioningbattery bank 24 V DC 100 AH with maintenance free battries type VRLA , Nos of cells 12, including full sine wavehalf controlled float cum boost charger 3 phase 4 wire suitbale for ACinput 415 v( + -)10% , includinganalog type meter of size 96mmX96mm 90 degree deflection for measuring the parameter such as AC voltmeter with selector switch , Ac ameterwith selector switch , DC voltmeter with selector switch and DC ammeter with selector switch , including Neon lamps for the indication of Mains on adn LED ijndicators for charger ON/ Boost ON/DC over voltage /DC under voltage/AC supplyfail /RectifierFusefail/ Battery Earth fault, including protections such as AC input circuit breaker , Fast acting semiconductor fuse for charger bridge , DC Over voltage cutback , DC overload protection battery input fuses, DC Circuit breaker and blocking diodewith and including float voltage adjust potentiometer , boost voltage adjust potentiometer , auto , manual float/boost mode select switch , AC input circuit breaker and DC voltmeter selector switch including special features such as soft start on DC side , class -F insulation for all magnetics , automatic voltage regulation using digital controlled closed loop system, filter circuit to limit ripple , automatic float /boost changeover based on current drawn by battery , built in auto phase reversal operation , all the accessories fitted in free standing cabinet, floor mounting type, steel construction, made out of CRCA sheet 2. mm thick for frame and front door adn rest 1.6 mm thick , duly seven tank processed and painted with RAL 7032 , protection class IP-42easy access for I&C and operation & maintenance including connection with H1 & H2 circuit of VCB with suitable size and length ofinclusing copper lugs adn cable copper cable as required length at site , cable entry at bottom complete all as specified and as directed by Engineer in Charge. Note: (a) All the cable entries should be metalic gland only for Battery details (b)The batteries shall have following specifications (i) 02 Volt 100 AH , No of cell -12, Total volt 12x2 24 Volt, , Total AH 12x10= 1200 AH
9Supply and Laying , LT UG XLPE insulated 1100 volt grade heavy duty electric cables with aluminium conductor , cross sectional area 240 sqmm 3.5 core all as specified and directed TFR to proposed panel 160 KVA-02 NOS), complete all as specified and directed by Engineer in Charge.
10Supply and Laying , LT UG XLPE insulated 1100 volt grade heavy duty electric cables with aluminium conductor , cross sectional area 70 sqmm 3.5 core all as specified and directed (TFR to proposed panel 63 kva), complete all as specified and directed by Engineer in Charge.
11Supply anfd fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPEarmoured aluminium conductor cable of cable endjoint kit size 120 sqmm to 185 Sqmm, complete all as specified and directed by Engineer in Charge.
12Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 185 to 240 sqmm,Indoor/Outdoor type, complete all as specified and directed by Engineer in Charge.
13Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70 sqmm,Indoor/Outdoor type, complete all as specified and directed by Engineer in Charge.
14Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in deep for foundation of poles/stays/cables/Pipe lines etc and getting out in soft/loose soil, complete all as specified and directed by Engineer in Charge.
15Returning, filling in including spreading, leveling, watering and well ramming in layers each not exceeding 25 cm thickness, complete all as specified and directed by Engineer in Charge.
16Removing surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by Engineer in Charge.
17Material and labour for sand cushioning with a layer of sand 8 cm thick before laying of cable and 15 cm thick after laying of cable in trenches, complete all as specified and directed by Engineer in Charge.
18Supplying & laying old size sub calss "B" bricks laid flat in trenches over the cable with length of bricks perpendicular to the direction of cable, adjacent/abutting each other, complete all as specified and directed by Engineer in Charge.
19Supply and fixing of earthing complete with galvanised steel steel earth plate electrode 600x600x6mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below nominal ground level) with top edge of the plate not less than 1.5 mtrs below nominal ground level connected to galvanised strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI all as shown in electrical plate No 3 of SSR Part I connected to earthing test point and testing on completion. all as specified and as directed. Note:- the cast of excavation and earth work PCC pit and PCC cover with handle, funnel & watering pipe, wiremesh,charcoal dust and common salt and earth strip up to 7.5 mtrs long shall be deemed included in the unit rate for earthing, complete all as specified and directed by Engineer in Charge.
20Material and labour for PCC 1:3:6, type C-1, using 20mm graded stone aggregate for road cutting / making plith for transformer where required and fair finishing to exposed surfaces without using extra cement including necessary form work complete all as specified and directed by Engineer in Charge.
21Supply and fixing of GI tubing light grade of 100 mm dia for cable protection on pole/wall/floor or in trenches and drain etc complete with necessary clamp, nut, bolts and washers and socket and making good the disturbed surface of wall,complete all as specified and directed by Engineer in Charge.
22Supply and fixing of Synthetic Insulating Mat for Electrical Instrument of size 2.5mx1mx12mm,complete all as specified and directed by Engineer in Charge.
23M&L for Concealed Point wiring complete with 4 Sqmm single core multistranded copper conductor PVC insulated and unsheathedcable 1100 volts grade drawn through and including non metallic rigid PVC conduit,medium grade minimum 25mm dia ISI marked and conduit accessories fixed concealed in wall/ceiling/roof etc with sunken type pressed steel/welded MS terminal boxes made out of 4 mm MS sheet, 3mm thick laminated sheath top cover for mounting of fittings,switches,sockets outlets,regulators etc complete including provisining of 4 sqmm PVC insulatedunsheathedcable 1100 volt grade with multi stranded copper conductor to common earth and connected to earth dolly for tOne 3 pin socket outlet. 15 amps,independent,with cables 4 sq.mm size,complete all as specified and directed by Engineer in Charge.
24Supply and Laying ,PVC insulated and FR PVC Round Sheathed, Copper Conductorconforming to IS: 694 PVC nsulated 1100 volt grade heavy duty electric cables with copper conductor , cross sectional area 4 sqmm 2 corecomplete all as specified and directed by Engineer in Charge.
25Supply and Laying ,PVC insulated and FR PVC Round Sheathed, Copper Conductorconforming to IS: 694 PVC nsulated 1100 volt grade heavy duty electric cables with copper conductor , cross sectional area 16 sqmm 4 corecomplete all as specified and directed by Engineer in Charge.
26Supply and Laying , control copper wiring cablePVC insulated and FR PVC Round Sheathed, Copper Conductorconforming to IS: 694 PVC nsulated 1100 volt grade heavy duty electric cables with copper conductor , cross sectional area 2.5 sqmm 01 corecomplete all as specified and directed by Engineer in Charge.