Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Kastigarh Including 33 Kv Line (From Receiving Station Ganika To Kastigarh) And Singlebus -Out At Receiving Sta, doda-Jammu And Kashmir

Jammu And Kashmir Power Development Department-PDDJK has published Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Kastigarh Including 33 Kv Line (From Receiving Station Ganika To Kastigarh) And Singlebus -Out At Receiving Sta. Submission Date for this Tender is 09-10-2023. Wall Construction Tenders in doda Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

39870673
Corrigendum : Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Kastigarh Including 33 Kv Line (From Receiving Station Ganika To Kastigarh) And Singlebus -Out At Receiving Sta
Open Tender
Indian
Jammu And Kashmir
doda
09-10-2023

Tender Details

Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33 / 11Kv Receiving Station At Kastigarh Including 33 Kv Line ( From Receiving Station Ganika To Kastigarh ) And Singlebus -Out At Receiving Station Ganika , In District Doda Under The Jurisdiction Of Sub Transmission Division Doda , Jpdcl , Jammu- 1 A-Supply Part 2 Sub-Station Main Equipment Transformer Bay 3 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 4 33 Kv Isolatorwithout Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 5 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 6 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 7 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 8 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 9 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 10 Steel Structures 11 Pipe Nominal Bore 200, 5.9 Mm Thick 12 Galvanised Steel Structures 13 Galvanized Nuts And Bolts 14 Control Cables 15 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 16 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 17 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 18 Lugs & Ferrules Etc. 19 Conductor And Hardware 20 Acsr Conductor Panther 21 T-Clamp 22 Single Tension Fitting 23 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 24 Earth Wire 7 / 4 Sqmm 25 G.I Flat 50*6 Mm 26 33 / 11 Kv, 3.15 Mva Power Transformer 27 33 / 11Kv Onan, Copper Wound, Outdoor Type, Conventional Power Transformer, Oil Filled With Oltc And All Accessories Including Ht And Lt Terminal Connections 28 10 / 12 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 29 6 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 30 2 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 31 Lugs & Ferrules Etc. 32 Single Bus System 11 Kv ( Transformer Bay Scheme ) 33 11 Kv Vcb Panel Board ( 12Kv, 1250A, 25Ka, Outdoor ) With Over Current, Earth Fault Relays ( Iec 61850 ) , Mimic Diagram, Voltmeter, Ammeter, Annuniaciation Windows With Annunciation Relays, 3-Phase Tri Vector Meter-5A, Dlms Compliant With Rs-485 Port1 Incoming & 3 Outgoings 34 11Kv Gapless Surge Arrestor, 9Kv, 10Ka La With Polymer Housingstation Type 35 11Kv ( Ue ) Xlpe Power Cable 3 Core Armoured 36 Ii. 185Mm Square Three Core 37 Ii. 120Mm Square Three Core 38 11Kvheat Shrink Termination Cable Kits ( Indoor ) 185 Mm Square ( 3-Core ) 39 11Kv Heat Shrink Termination Cable Kits ( Outdoor ) 185 Mm Square ( 3-Core ) 40 11Kv Heat Shrink Termination Cable Kits ( Indoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 41 11Kv Heat Shrink Terminationcable Kits ( Outdoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 42 11 Kv Isolator, Double Break, 3 Pole, 600 Amp. Horizental Mounting Type With Earth Switch 43 11Kv Link Set ( Go Set ) , Ab Switch 3 Phase, 3 Pole, 400 Amps. 44 100 Kva, 11 / .433 Kv, Auxiliary Transformer, 3 Phase Distribution Transformer With Bimetallic Terminal Connectors , Energy Level -2, Al Wound. 45 St Poles 9 Mtrs Long 46 Galvanised Iron Of Sorts 47 120 Mm2 Pvc 4 Core Cable, Armoured Frls 48 Mccb 200 Amp 49 Cement Bottomng 1:2:4 Mix As Per Rec Standards 0.5Cum Per Pole 50 Earthing Of 100 Kva Sub Structure As Per Standard 51 Earthing Complete Gi Pipe 400 Mm Or Gi Rod 20Mm 2.5 Mtr Long 52 Common Miscellaneous Equipments 53 A ) Battery Bank 30 V, 100 Ah, Of 15 No. Cells Of 2 V Each, Sealed Maintenance Free Vrla Type, High Impact Polyprophelene Copolymer Container, Flame Retardant With Stand 54 B ) 30 V, 100 Ah, Float-Cum-Boost Charger With Full Wave Rectification For 220 V, 1 Phase, 50 Hz Ac Input Supply. 55 Distribution Panel ( 30V, Dc ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 For Two Number Battery Incoming Supplywith 2No. 63 Amp. Dp Mcb For Incoming Supplydouble Bus Bar Of Adequate Size, Twelve Number Dp Dc Mcb ( 0-32A ) Including Indication Lamp And Cables And Other Accessories 56 Distribution Panel ( 415 V, Ac ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 200A Switch Fuse Disconnector For Incoming Supply And Five Numbers Tpn Mcbs ( 16-125A ) And Five Number Dp Mcb ( 0-32A ) , Rectangular Bus Bar Suitable For 200 A Continous Supply Including Indication Lamp Cables And Other Accessories. 57 Telecommunication Facilities 58 Civil Works 59 Compound Walling Of Identified Land By Way Of Mass Concrete In Foundation And 228Mm Bricks Of 2M Height 60 Chain-Link Fencing Of 33Kv Yard Of Substation By Way Of Mass Concrete In Foundations And Chain-Link Fencing Of 6 Ft Height. 61 Provision For Water Supply By Way Of Laying Of Service Line From The Nearest Source , Construction Of Underground Tank ( 3000 Ltr ) And Fixing Of Water Lifting Motor ( 1Hp ) 62 33 / 11Kv Power Transformer Foundation 63 33Kv Equipment Foundation And Gantry Foundatyion 64 Earthing Mat Complete Job Gi Flat 50X8 Mm 65 Earthing Electrode ( 3 Meters Long, 40 Mm Dia Gi Pipe ) Through Gi Strips 66 33Kv Yard Concreting / Metalling 67 Water Tank 1000 Ltrs. ( Overhead ) 68 Control Room Building Including With Internal Wiring Complete Job 69 Shift Quarters For Je And Sba Including Internal Wiring Complete Job 70 Truss For Control Room Building 1.3Xplinth Area .Providing And Fixing Of Steel Truss Including Provision For Colur Coated Roofing 71 Development Of Land ( 2 Kannal 10 Marla ) By Way Of Removing Weeds, Wild Grass And Undulation If Any, Ornamental Land Scraping And Growing Of Ornamental Trees In Un Built Areas And Road Sides And Development Of Road Along With Surface Drain. Including Construction Of Protection Walls ( R / B Walls ) As Per Site Requirement. ( The Participating Bidders Must Visit The Site Before Quoting The Rates ) 72 Yard Lighting ( 4 Nos Yard And 02 Nos Cr Back Side ) 73 Single Bus Out At R / Stn Ganika 74 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 75 33 Kv Isolatorwith Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 76 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 77 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 78 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 79 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 80 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 81 Steel Structures 82 Pipe Nominal Bore 200, 5.9 Mm Thick 83 Galvanised Steel Structures 84 Galvanized Nuts And Bolts 85 Control Cables 86 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 87 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 88 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 89 Lugs & Ferrules Etc. 90 Conductor And Hardware 91 Acsr Conductor Panther 92 T-Clamp 93 Single Tension Fitting 94 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 95 Earth Wire 7 / 4 Sqmm 96 G.I Flat 50*06 Mm 97 Erection Of 33 Kv Line From Receiving Station Ganika 98 11 Mtr. Long St Pole ( For New Line ) St-410 Sp56 99 Gi Channel X-Arm Including Clamps And Braces 100 100 Mm² Acsrdogconductor 101 Pg Clamps For 100 Mm² Acsr Conductor 102 33Kv Polymeric Composite Pin Insulator 36Kv, 10Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 103 33Kv Polymeric Composite Disc Insulator 36Kv, Min Failing Load 70Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 104 Galvinized Nuts And Bolts. 105 Danger Plates With Clamps 106 Anti-Climbing Device With Clamps 107 Earthing Complete By Gi Pipe 40 Mm Or Gi Rod 20Mm 2.5 Mtr Long Through Gi Strip. 108 Red Oxide 109 Aluminium Paint 110 Cement Bottoming 1:2:4 Mix As Per Rec Standards .6Cum / Pole 111 Stone Pad ( 300 Mm X 300 Mmx 75 Mm ) 112 Aluminium Jointing Sleeves 113 Galvanised Stay Set With 50 X 8 Mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 300X 300 X 8 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 20 Mm Diameter Solid Gs Stay Rod & 7 / 4.00 Mm Dia Gi Stranded Wire Complete 114 Guard Netting 115 Safety Items 116 Rubber Mat 1M*2M ( 19Mm Thick ) 117 Fire Extinguisher Co2 Type Of 4.5 Kg Capacity For Control Room 118 3-Sand Bucket Fire Extinguisher 119 Helmet 120 Rubber Gloves For 33 Kv Level 121 Rubber Gloves For 11 Kv Level 122 Safetybelt 123 Safety Shoes 124 Earthing Rod ( Set Of 3 Rods ) 125 Hv Detector All Voltages 126 B- Erection Part 127 Sub-Station Main Equipment Transformer Bay 128 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 129 33 Kv Isolatorwithout Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 130 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 131 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 132 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 133 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 134 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 135 Steel Structures 136 Pipe Nominal Bore 200, 5.9 Mm Thick 137 Galvanised Steel Structures 138 Galvanized Nuts And Bolts 139 Control Cables 140 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 141 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 142 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 143 Lugs & Ferrules Etc. 144 Conductor And Hardware 145 Acsr Conductor Panther 146 T-Clamp 147 Single Tension Fitting 148 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 149 Earth Wire 7 / 4 Sqmm 150 G.I Flat 50*60 Mm 151 33 / 11 Kv, 3.15 Mva Power Transformer 152 33 / 11Kv Onan, Copper Wound, Outdoor Type, Conventional Power Transformer, Oil Filled With Oltc And All Accessories Including Ht And Lt Terminal Connections 153 10 / 12 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 154 6 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 155 2 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 156 Lugs & Ferrules Etc. 157 Single Bus System 11 Kv ( Transformer Bay Scheme ) 158 11 Kv Vcb Panel Board ( 12Kv, 1250A, 25Ka, Outdoor ) With Over Current, Earth Fault Relays ( Iec 61850 ) , Mimic Diagram, Voltmeter, Ammeter, Annuniaciation Windows With Annunciation Relays, 3-Phase Tri Vector Meter-5A, Dlms Compliant With Rs-485 Port1 Incoming & 3 Outgoings 159 11Kv Gapless Surge Arrestor, 9Kv, 10Ka La With Polymer Housingstation Type 160 11Kv ( Ue ) Xlpe Power Cable 3 Core Armoured 161 Ii. 185Mm Square Three Core 162 Ii. 120Mm Square Three Core 163 11Kvheat Shrink Termination Cable Kits ( Indoor ) 185 Mm Square ( 3-Core ) 164 11Kv Heat Shrink Termination Cable Kits ( Outdoor ) 185 Mm Square ( 3-Core ) 165 11Kv Heat Shrink Termination Cable Kits ( Indoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 166 11Kv Heat Shrink Terminationcable Kits ( Outdoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 167 11 Kv Isolator, Double Break, 3 Pole, 600 Amp. Horizental Mounting Type With Earth Switch 168 11Kv Link Set ( Go Set ) , Ab Switch 3 Phase, 3 Pole, 400 Amps. 169 100 Kva, 11 / .433 Kv, Auxiliary Transformer, 3 Phase Distribution Transformer With Bimetallic Terminal Connectors , Energy Level -2, Al Wound. 170 St Poles 9 Mtrs Long 171 Galvanised Iron Of Sorts 172 120 Mm2 Pvc 4 Core Cable, Armoured Frls 173 Mccb 200 Amp 174 Cement Bottomng 1:2:4 Mix As Per Rec Standards 0.5Cum Per Pole 175 Earthing Of 100 Kva Sub Structure As Per Standard 176 Earthing Complete Gi Pipe 400 Mm Or Gi Rod 20Mm 2.5 Mtr Long 177 Common Miscellaneous Equipments 178 A ) Battery Bank 30 V, 100 Ah, Of 15 No. Cells Of 2 V Each, Sealed Maintenance Free Vrla Type, High Impact Polyprophelene Copolymer Container, Flame Retardant With Stand 179 B ) 30 V, 100 Ah, Float-Cum-Boost Charger With Full Wave Rectification For 220 V, 1 Phase, 50 Hz Ac Input Supply. 180 Distribution Panel ( 30V, Dc ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 For Two Number Battery Incoming Supplywith 2No. 63 Amp. Dp Mcb For Incoming Supplydouble Bus Bar Of Adequate Size, Twelve Number Dp Dc Mcb ( 0-32A ) Including Indication Lamp And Cables And Other Accessories 181 Distribution Panel ( 415 V, Ac ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 200A Switch Fuse Disconnector For Incoming Supply And Five Numbers Tpn Mcbs ( 16-125A ) And Five Number Dp Mcb ( 0-32A ) , Rectangular Bus Bar Suitable For 200 A Continous Supply Including Indication Lamp Cables And Other Accessories. 182 Telecommunication Facilities 183 Civil Works 184 Compound Walling Of Identified Land By Way Of Mass Concrete In Foundation And 228Mm Bricks Of 2M Height 185 Chain-Link Fencing Of 33Kv Yard Of Substation By Way Of Mass Concrete In Foundations And Chain-Link Fencing Of 6 Ft Height. 186 Provision For Water Supply By Way Of Laying Of Service Line From The Nearest Source , Construction Of Underground Tank ( 3000 Ltr ) And Fixing Of Water Lifting Motor ( 1Hp ) 187 33 / 11Kv Power Transformer Foundation 188 33Kv Equipment Foundation And Gantry Foundatyion 189 Earthing Mat Complete Job Gi Flat 50X8 Mm 190 Earthing Electrode ( 3 Meters Long, 40 Mm Dia Gi Pipe ) Through Gi Strips 191 33Kv Yard Concreting / Metalling 192 Water Tank 1000 Ltrs. ( Overhead ) 193 Control Room Building Including With Internal Wiring Complete Job 194 Shift Quarters For Je And Sba Including Internal Wiring Complete Job 195 Truss For Control Room Building 1.3Xplinth Area .Providing And Fixing Of Steel Truss Including Provision For Colur Coated Roofing 196 Development Of Land By Removing Weeds, Wild Grass And Undulation If Any, Ornamental Land Scraping And Growing Of Ornamental Trees In Un Built Areas And Road Sides And Development Of Road Along With Surface Drain 197 Yard Lighting ( 4 Nos Yard And 02 Nos Cr Back Side ) 198 Single Bus Out At R / Stn Ganika 199 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 200 33 Kv Isolatorwith Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 201 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 202 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 203 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 204 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 205 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 206 Steel Structures 207 Pipe Nominal Bore 200, 5.9 Mm Thick 208 Galvanised Steel Structures 209 Galvanized Nuts And Bolts 210 Control Cables 211 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 212 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 213 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 214 Lugs & Ferrules Etc. 215 Conductor And Hardware 216 Acsr Conductor Panther 217 T-Clamp 218 Single Tension Fitting 219 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 220 Earth Wire 7 / 4 Sqmm 221 G.I Flat 50*60 Mm 222 Erection Of 33 Kv Line From Receiving Station Ganika 223 11 Mtr. Long St Pole ( For New Line ) St-410 Sp56 224 Gi Channel X-Arm Including Clamps And Braces 225 100 Mm² Acsrdogconductor 226 Pg Clamps For 100 Mm² Acsr Conductor 227 33Kv Polymeric Composite Pin Insulator 36Kv, 10Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 228 33Kv Polymeric Composite Disc Insulator 36Kv, Min Failing Load 70Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 229 Galvinized Nuts And Bolts. 230 Danger Plates With Clamps 231 Anti-Climbing Device With Clamps 232 Earthing Complete By Gi Pipe 40 Mm Or Gi Rod 20Mm 2.5 Mtr Long Through Gi Strip. 233 Red Oxide 234 Aluminium Paint 235 Cement Bottoming 1:2:4 Mix As Per Rec Standards .6Cum / Pole 236 Stone Pad ( 300 Mm X 300 Mmx 75 Mm ) 237 Aluminium Jointing Sleeves 238 Galvanised Stay Set With 50 X 8 Mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 300X 300 X 8 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 20 Mm Diameter Solid Gs Stay Rod & 7 / 4.00 Mm Dia Gi Stranded Wire Complete 239 Guard Netting

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Oct-2023 EXTENSION OF DATES Date 09-10-2023

Key Value

Document Fees
INR 4000 /-
EMD
INR 640000.0 /-
Tender Value
INR 3.20 Crore /-

BOQ Items

Name of Work: <“Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning of 1x3.15 MVA, 33/11KV Receiving Station at Kastigarh including 33 KV Line (from receiving station Ganika to Kastigarh) and SingleBus -out at Receiving Station Ganika , in District Doda under the jurisdiction of Sub Transmission Division Doda ,JPDCL ,Jammu.” .>
Sl. No. Item Description
1A-SUPPLY PART
2SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY
333 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
433 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
533 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
630 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
733 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
833 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
933 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
10STEEL STRUCTURES
11Pipe Nominal bore 200, 5.9 mm thick
12Galvanised steel structures
13Galvanized nuts and bolts
14CONTROL CABLES
1510 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
168 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
172 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
18Lugs & Ferrules etc.
19CONDUCTOR AND HARDWARE
20ACSR Conductor Panther
21T-Clamp
22Single Tension fitting
23PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
24Earth Wire 7/4 sqmm
25G.I Flat 50*6 mm
2633/11 KV, 3.15 MVA Power Transformer
2733/11KV ONAN,Copper wound,outdoor type,Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections
2810 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
296 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
302 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
31Lugs & Ferrules etc.
32Single Bus system 11 KV(Transformer Bay Scheme)
3311 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector meter-5A,DLMS Compliant with RS-485 Port1 Incoming & 3 outgoings
3411KV Gapless Surge Arrestor,9KV,10KA LA With polymer HousingStation Type
3511KV (UE)XLPE Power Cable 3 core armoured
36II.  185mm square three core
37II.  120mm square three core
3811KVHeat shrink termination Cable Kits (Indoor) 185 mm square (3-core)
3911KV Heat shrink termination Cable Kits (Outdoor)185 mm square (3-core)
4011KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core)
4111KV Heat shrink terminationCable Kits (Outdoor) 120 mm square (one spare)(3-core)
4211 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch
4311KV Link Set (Go Set), AB switch 3 phase, 3 pole, 400 Amps.
44100 KVA, 11/.433 KV,Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound.
45St Poles 9 mtrs long
46Galvanised iron of sorts
47120 mm2 PVC 4 core cable,Armoured FRLS
48MCCB 200 Amp
49Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole
50Earthing of 100 KVA Sub structure As per Standard
51Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long
52COMMON MISCELLANEOUS EQUIPMENTS
53a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand
54b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply.
55Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supplywith 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories
56Distribution panel (415 V, AC)made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories.
57Telecommunication facilities
58Civil Works
59Compound walling of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height
60Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height.
61Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (3000 ltr) and fixing of water lifting motor (1HP)
6233/11kv power Transformer Foundation
6333kv Equipment Foundation and gantry foundatyion
64Earthing Mat complete job GI flat 50x8 mm
65Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips
6633kv Yard Concreting / Metalling
67Water tank 1000 Ltrs.( overhead)
68Control room Building including with internal wiring complete job
69Shift Quarters for Je and SBA including internal wiring complete job
70Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing
71Development of land (2 Kannal 10 Marla) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain. Including Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates)
72Yard Lighting ( 4 Nos yard and 02 Nos CR back side)
73SINGLE BUS OUT AT R/STN GANIKA
7433 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
7533 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
7633 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
7730 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
7833 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
7933 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
8033 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
81STEEL STRUCTURES
82Pipe Nominal bore 200, 5.9 mm thick
83Galvanised steel structures
84Galvanized nuts and bolts
85CONTROL CABLES
8610 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
878 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
882 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
89Lugs & Ferrules etc.
90CONDUCTOR AND HARDWARE
91ACSR Conductor Panther
92T-Clamp
93Single Tension fitting
94PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
95Earth Wire 7/4 sqmm
96G.I Flat 50*06 mm
97ERECTION OF 33 KV LINE FROM RECEIVING STATION GANIKA
9811 Mtr. Long ST Pole(For new line) ST-410 SP56
99GI Channel X-arm including clamps and braces
100100 mm² ACSRDogConductor
101PG Clamps for 100 mm² ACSR Conductor
10233kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
10333kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
104Galvinized Nuts and Bolts.
105Danger Plates with Clamps
106Anti-Climbing Device with Clamps
107Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
108Red Oxide
109Aluminium Paint
110Cement bottoming 1:2:4 mix as per REC standards .6cum /pole
111Stone Pad (300 mm x 300 mmx 75 mm)
112Aluminium Jointing Sleeves
113Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
114Guard netting
115SAFETY ITEMS
116Rubber Mat 1m*2m (19mm thick)
117Fire Extinguisher CO2 type of 4.5 Kg capacity for control room
1183-Sand Bucket Fire Extinguisher
119Helmet
120Rubber Gloves for 33 KV Level
121Rubber Gloves for 11 KV Level
122SafetyBelt
123Safety Shoes
124Earthing rod (set of 3 rods)
125HV Detector all Voltages
126B- ERECTION PART
127SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY
12833 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
12933 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
13033 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
13130 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
13233 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
13333 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
13433 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
135STEEL STRUCTURES
136Pipe Nominal bore 200, 5.9 mm thick
137Galvanised steel structures
138Galvanized nuts and bolts
139CONTROL CABLES
14010 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
1418 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
1422 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
143Lugs & Ferrules etc.
144CONDUCTOR AND HARDWARE
145ACSR Conductor Panther
146T-Clamp
147Single Tension fitting
148PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
149Earth Wire 7/4 sqmm
150G.I Flat 50*60 mm
15133/11 KV, 3.15 MVA Power Transformer
15233/11KV ONAN,Copper wound,outdoor type,Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections
15310 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
1546 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
1552 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
156Lugs & Ferrules etc.
157Single Bus system 11 KV(Transformer Bay Scheme)
15811 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector meter-5A,DLMS Compliant with RS-485 Port1 Incoming & 3 outgoings
15911KV Gapless Surge Arrestor,9KV,10KA LA With polymer HousingStation Type
16011KV (UE)XLPE Power Cable 3 core armoured
161II.  185mm square three core
162II.  120mm square three core
16311KVHeat shrink termination Cable Kits (Indoor) 185 mm square (3-core)
16411KV Heat shrink termination Cable Kits (Outdoor)185 mm square (3-core)
16511KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core)
16611KV Heat shrink terminationCable Kits (Outdoor) 120 mm square (one spare)(3-core)
16711 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch
16811KV Link Set (Go Set), AB switch 3 phase, 3 pole, 400 Amps.
169100 KVA, 11/.433 KV,Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound.
170St Poles 9 mtrs long
171Galvanised iron of sorts
172120 mm2 PVC 4 core cable,Armoured FRLS
173MCCB 200 Amp
174Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole
175Earthing of 100 KVA Sub structure As per Standard
176Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long
177COMMON MISCELLANEOUS EQUIPMENTS
178a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand
179b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply.
180Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supplywith 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories
181Distribution panel (415 V, AC)made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories.
182Telecommunication facilities
183Civil Works
184Compound walling of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height
185Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height.
186Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (3000 ltr) and fixing of water lifting motor (1HP)
18733/11kv power Transformer Foundation
18833kv Equipment Foundation and gantry foundatyion
189Earthing Mat complete job GI flat 50x8 mm
190Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips
19133kv Yard Concreting / Metalling
192Water tank 1000 Ltrs.( overhead)
193Control room Building including with internal wiring complete job
194Shift Quarters for Je and SBA including internal wiring complete job
195Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing
196Development of land by removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain
197Yard Lighting ( 4 Nos yard and 02 Nos CR back side)
198SINGLE BUS OUT AT R/STN GANIKA
19933 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
20033 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
20133 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
20230 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
20333 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
20433 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
20533 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
206STEEL STRUCTURES
207Pipe Nominal bore 200, 5.9 mm thick
208Galvanised steel structures
209Galvanized nuts and bolts
210CONTROL CABLES
21110 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
2128 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
2132 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
214Lugs & Ferrules etc.
215CONDUCTOR AND HARDWARE
216ACSR Conductor Panther
217T-Clamp
218Single Tension fitting
219PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
220Earth Wire 7/4 sqmm
221G.I Flat 50*60 mm
222ERECTION OF 33 KV LINE FROM RECEIVING STATION GANIKA
22311 Mtr. Long ST Pole(For new line) ST-410 SP56
224GI Channel X-arm including clamps and braces
225100 mm² ACSRDogConductor
226PG Clamps for 100 mm² ACSR Conductor
22733kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
22833kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
229Galvinized Nuts and Bolts.
230Danger Plates with Clamps
231Anti-Climbing Device with Clamps
232Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
233Red Oxide
234Aluminium Paint
235Cement bottoming 1:2:4 mix as per REC standards .6cum /pole
236Stone Pad (300 mm x 300 mmx 75 mm)
237Aluminium Jointing Sleeves
238Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
239Guard netting
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail