Jammu And Kashmir Power Development Department-PDDJK has published Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Kastigarh Including 33 Kv Line (From Receiving Station Ganika To Kastigarh) And Singlebus -Out At Receiving Sta. Submission Date for this Tender is 09-10-2023. Wall Construction Tenders in doda Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 05-Oct-2023 | EXTENSION OF DATES | Date | 09-10-2023 |
Sl. No. | Item Description |
1 | A-SUPPLY PART |
2 | SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY |
3 | 33 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
4 | 33 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) |
5 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
6 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
7 | 33 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
8 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
9 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
10 | STEEL STRUCTURES |
11 | Pipe Nominal bore 200, 5.9 mm thick |
12 | Galvanised steel structures |
13 | Galvanized nuts and bolts |
14 | CONTROL CABLES |
15 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
16 | 8 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
17 | 2 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
18 | Lugs & Ferrules etc. |
19 | CONDUCTOR AND HARDWARE |
20 | ACSR Conductor Panther |
21 | T-Clamp |
22 | Single Tension fitting |
23 | PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN |
24 | Earth Wire 7/4 sqmm |
25 | G.I Flat 50*6 mm |
26 | 33/11 KV, 3.15 MVA Power Transformer |
27 | 33/11KV ONAN,Copper wound,outdoor type,Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections |
28 | 10 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
29 | 6 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
30 | 2 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
31 | Lugs & Ferrules etc. |
32 | Single Bus system 11 KV(Transformer Bay Scheme) |
33 | 11 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector meter-5A,DLMS Compliant with RS-485 Port1 Incoming & 3 outgoings |
34 | 11KV Gapless Surge Arrestor,9KV,10KA LA With polymer HousingStation Type |
35 | 11KV (UE)XLPE Power Cable 3 core armoured |
36 | II. 185mm square three core |
37 | II. 120mm square three core |
38 | 11KVHeat shrink termination Cable Kits (Indoor) 185 mm square (3-core) |
39 | 11KV Heat shrink termination Cable Kits (Outdoor)185 mm square (3-core) |
40 | 11KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core) |
41 | 11KV Heat shrink terminationCable Kits (Outdoor) 120 mm square (one spare)(3-core) |
42 | 11 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch |
43 | 11KV Link Set (Go Set), AB switch 3 phase, 3 pole, 400 Amps. |
44 | 100 KVA, 11/.433 KV,Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound. |
45 | St Poles 9 mtrs long |
46 | Galvanised iron of sorts |
47 | 120 mm2 PVC 4 core cable,Armoured FRLS |
48 | MCCB 200 Amp |
49 | Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole |
50 | Earthing of 100 KVA Sub structure As per Standard |
51 | Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long |
52 | COMMON MISCELLANEOUS EQUIPMENTS |
53 | a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand |
54 | b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply. |
55 | Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supplywith 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories |
56 | Distribution panel (415 V, AC)made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories. |
57 | Telecommunication facilities |
58 | Civil Works |
59 | Compound walling of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height |
60 | Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height. |
61 | Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (3000 ltr) and fixing of water lifting motor (1HP) |
62 | 33/11kv power Transformer Foundation |
63 | 33kv Equipment Foundation and gantry foundatyion |
64 | Earthing Mat complete job GI flat 50x8 mm |
65 | Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips |
66 | 33kv Yard Concreting / Metalling |
67 | Water tank 1000 Ltrs.( overhead) |
68 | Control room Building including with internal wiring complete job |
69 | Shift Quarters for Je and SBA including internal wiring complete job |
70 | Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing |
71 | Development of land (2 Kannal 10 Marla) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain. Including Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates) |
72 | Yard Lighting ( 4 Nos yard and 02 Nos CR back side) |
73 | SINGLE BUS OUT AT R/STN GANIKA |
74 | 33 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
75 | 33 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) |
76 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
77 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
78 | 33 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
79 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
80 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
81 | STEEL STRUCTURES |
82 | Pipe Nominal bore 200, 5.9 mm thick |
83 | Galvanised steel structures |
84 | Galvanized nuts and bolts |
85 | CONTROL CABLES |
86 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
87 | 8 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
88 | 2 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
89 | Lugs & Ferrules etc. |
90 | CONDUCTOR AND HARDWARE |
91 | ACSR Conductor Panther |
92 | T-Clamp |
93 | Single Tension fitting |
94 | PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN |
95 | Earth Wire 7/4 sqmm |
96 | G.I Flat 50*06 mm |
97 | ERECTION OF 33 KV LINE FROM RECEIVING STATION GANIKA |
98 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
99 | GI Channel X-arm including clamps and braces |
100 | 100 mm² ACSRDogConductor |
101 | PG Clamps for 100 mm² ACSR Conductor |
102 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
103 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
104 | Galvinized Nuts and Bolts. |
105 | Danger Plates with Clamps |
106 | Anti-Climbing Device with Clamps |
107 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
108 | Red Oxide |
109 | Aluminium Paint |
110 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
111 | Stone Pad (300 mm x 300 mmx 75 mm) |
112 | Aluminium Jointing Sleeves |
113 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
114 | Guard netting |
115 | SAFETY ITEMS |
116 | Rubber Mat 1m*2m (19mm thick) |
117 | Fire Extinguisher CO2 type of 4.5 Kg capacity for control room |
118 | 3-Sand Bucket Fire Extinguisher |
119 | Helmet |
120 | Rubber Gloves for 33 KV Level |
121 | Rubber Gloves for 11 KV Level |
122 | SafetyBelt |
123 | Safety Shoes |
124 | Earthing rod (set of 3 rods) |
125 | HV Detector all Voltages |
126 | B- ERECTION PART |
127 | SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY |
128 | 33 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
129 | 33 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) |
130 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
131 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
132 | 33 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
133 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
134 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
135 | STEEL STRUCTURES |
136 | Pipe Nominal bore 200, 5.9 mm thick |
137 | Galvanised steel structures |
138 | Galvanized nuts and bolts |
139 | CONTROL CABLES |
140 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
141 | 8 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
142 | 2 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
143 | Lugs & Ferrules etc. |
144 | CONDUCTOR AND HARDWARE |
145 | ACSR Conductor Panther |
146 | T-Clamp |
147 | Single Tension fitting |
148 | PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN |
149 | Earth Wire 7/4 sqmm |
150 | G.I Flat 50*60 mm |
151 | 33/11 KV, 3.15 MVA Power Transformer |
152 | 33/11KV ONAN,Copper wound,outdoor type,Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections |
153 | 10 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
154 | 6 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
155 | 2 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
156 | Lugs & Ferrules etc. |
157 | Single Bus system 11 KV(Transformer Bay Scheme) |
158 | 11 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector meter-5A,DLMS Compliant with RS-485 Port1 Incoming & 3 outgoings |
159 | 11KV Gapless Surge Arrestor,9KV,10KA LA With polymer HousingStation Type |
160 | 11KV (UE)XLPE Power Cable 3 core armoured |
161 | II. 185mm square three core |
162 | II. 120mm square three core |
163 | 11KVHeat shrink termination Cable Kits (Indoor) 185 mm square (3-core) |
164 | 11KV Heat shrink termination Cable Kits (Outdoor)185 mm square (3-core) |
165 | 11KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core) |
166 | 11KV Heat shrink terminationCable Kits (Outdoor) 120 mm square (one spare)(3-core) |
167 | 11 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch |
168 | 11KV Link Set (Go Set), AB switch 3 phase, 3 pole, 400 Amps. |
169 | 100 KVA, 11/.433 KV,Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound. |
170 | St Poles 9 mtrs long |
171 | Galvanised iron of sorts |
172 | 120 mm2 PVC 4 core cable,Armoured FRLS |
173 | MCCB 200 Amp |
174 | Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole |
175 | Earthing of 100 KVA Sub structure As per Standard |
176 | Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long |
177 | COMMON MISCELLANEOUS EQUIPMENTS |
178 | a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand |
179 | b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply. |
180 | Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supplywith 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories |
181 | Distribution panel (415 V, AC)made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories. |
182 | Telecommunication facilities |
183 | Civil Works |
184 | Compound walling of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height |
185 | Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height. |
186 | Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (3000 ltr) and fixing of water lifting motor (1HP) |
187 | 33/11kv power Transformer Foundation |
188 | 33kv Equipment Foundation and gantry foundatyion |
189 | Earthing Mat complete job GI flat 50x8 mm |
190 | Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips |
191 | 33kv Yard Concreting / Metalling |
192 | Water tank 1000 Ltrs.( overhead) |
193 | Control room Building including with internal wiring complete job |
194 | Shift Quarters for Je and SBA including internal wiring complete job |
195 | Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing |
196 | Development of land by removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain |
197 | Yard Lighting ( 4 Nos yard and 02 Nos CR back side) |
198 | SINGLE BUS OUT AT R/STN GANIKA |
199 | 33 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
200 | 33 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) |
201 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
202 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
203 | 33 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
204 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
205 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
206 | STEEL STRUCTURES |
207 | Pipe Nominal bore 200, 5.9 mm thick |
208 | Galvanised steel structures |
209 | Galvanized nuts and bolts |
210 | CONTROL CABLES |
211 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
212 | 8 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
213 | 2 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
214 | Lugs & Ferrules etc. |
215 | CONDUCTOR AND HARDWARE |
216 | ACSR Conductor Panther |
217 | T-Clamp |
218 | Single Tension fitting |
219 | PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN |
220 | Earth Wire 7/4 sqmm |
221 | G.I Flat 50*60 mm |
222 | ERECTION OF 33 KV LINE FROM RECEIVING STATION GANIKA |
223 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
224 | GI Channel X-arm including clamps and braces |
225 | 100 mm² ACSRDogConductor |
226 | PG Clamps for 100 mm² ACSR Conductor |
227 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
228 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
229 | Galvinized Nuts and Bolts. |
230 | Danger Plates with Clamps |
231 | Anti-Climbing Device with Clamps |
232 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
233 | Red Oxide |
234 | Aluminium Paint |
235 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
236 | Stone Pad (300 mm x 300 mmx 75 mm) |
237 | Aluminium Jointing Sleeves |
238 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
239 | Guard netting |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy