Tender For Repair And Maintenance Oftransformers, Vcb, Ocb, Rmu, Battery Charger, Relay And Connected Items At 4 No. P/F, Station Road, Maude Road, Church Road, Cassel Road, Manekshaw Enclave, Manekshaw Centre, Mall Road, Polo Road, Tigris Road, Mandir Ma, New Delhi-Delhi

Military Engineer Services-MES has published Tender For Repair And Maintenance Oftransformers, Vcb, Ocb, Rmu, Battery Charger, Relay And Connected Items At 4 No. P/F, Station Road, Maude Road, Church Road, Cassel Road, Manekshaw Enclave, Manekshaw Centre, Mall Road, Polo Road, Tigris Road, Mandir Ma. Submission Date for this Tender is 16-10-2023. Battery Chargers Tenders in New Delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

39844909
Corrigendum : Tender For Repair And Maintenance Oftransformers, Vcb, Ocb, Rmu, Battery Charger, Relay And Connected Items At 4 No. P/F, Station Road, Maude Road, Church Road, Cassel Road, Manekshaw Enclave, Manekshaw Centre, Mall Road, Polo Road, Tigris Road, Mandir Ma
Open Tender
Indian
Delhi
New Delhi
16-10-2023

Tender Details

Repair And Maintenance Oftransformers, Vcb, Ocb, Rmu, Battery Charger, Relay And Connected Items At 4 No. P / F, Station Road, Maude Road, Church Road, Cassel Road, Manekshaw Enclave, Manekshaw Centre, Mall Road, Polo Road, Tigris Road, Mandir Marg, Harbaksh Stadium, Parade Road, Parade Camp, Dgncc And Adjoining Area Of Age Sldc Electric Supply Under Ge ( U ) Elect Supply Delhi Cantt-10

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Oct-2023 Revised Tender Pages Other 16-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 40 Lakhs /-

BOQ Items

Name of Work :REPAIR AND MAINTENANCE OFTRANSFORMERS, VCB, OCB, RMU, BATTERY CHARGER, RELAY AND CONNECTED ITEMS AT 4 NO. P/F, STATION ROAD, MAUDE ROAD, CHURCH ROAD, CASSEL ROAD, MANEKSHAW ENCLAVE, MANEKSHAW CENTRE, MALL ROAD, POLO ROAD, TIGRIS ROAD, MANDIR MARG, HARBAKSH STADIUM, PARADE ROAD, PARADE CAMP, DGNCC AND ADJOINING AREA OF AGE SLDC ELECTRIC SUPPLY UNDER GE (U) ELECT SUPPLY DELHI CANTT-10
Sl. No. Item Description
1Disconnecting electrically and mechanically outdoor transformers upto 630 KVA capacity, lowering down from 4/6 pole structure carefully for major/minor repairs complete all as specified and directed.
2Disconnecting electrically and mechanically indoor/outdoortransformersinside the substation or outdoor type onoutside plinth upto 630 KVA capacity, carefully for major/minor repairs complete all as specified and directed.
3M&Llifting of core assembly by opening of top cover and other items for checking of faults/repair and lowering / refixing the same in its original position after inspection to make it ready for transportation to carry out rewinding work in workshop including transportation of unservicieable transformer upto 630 KVA capacity to workshop ( rate is deemed to be inclusive of transportation , T&P and men power ) complete all as specified and directed.
4M&L for transportation of transformer of capacity upto 400 KVA from MES Yard to site location using Hydra/Crane and truck as per requirement to replace defective transformer including installation, testing and connecting at site and to deposit the same to MES Yard after receipt and installation of repaired transformer at site complete all as specified and directed. Note:- Contractor must arrange for transportation and installation for replacement of transformer at site immediately after receipt of verbal/telephonic/written complaint from JE/Engr-in-Charge within 1 day. Any delay beyond 1 day post receipt of complaint shall be penalized @ Rs 2500/- per day and shall be recovered from next due RAR.
5M&L for alternative arrangement by hiring, transportation of transformer of capacity 500 / 630 KVA in place of unserviceable transformer on hire basis for 15 days including, installation, connecting and testing of transformer and return back after installation of repaired transformer complete all as specified and directed. Notes:- (i) Contractor must arrange hired transformer including transportation and installation at site immediately after receipt of verbal/telephonic/written complaint from JE/Engr-in-Charge within 1 day. Any delay beyond 1 day post receipt of complaint shall be penalized @ Rs 3500/- per day and shall be recovered from next due RAR. (ii) Repairing of transformer must be completed within 15 days after receipt of verbal/ telephonic/ written complaint from JE/Engr-in-Charge. In case of any delay, no extra claim will be entertained towards hiring charges beyond 15 days and the contractor shall not be allowed to shift the hired transformer until replaced by repaired transformer.In case of any kind of fault / defect occurred in hired transformer, the contractor shall have to arrange further replacement without any additional cost and shall repair the defect from his own expenses. (iii)Contractor should check the available infrastructure and to be sure regarding safety of hired transformer before installation.The rate quoted is deemed to be including transportation cost, earthing lead etc.
6Takingout the unserviceable copper windingfrom transformer of capacity upto 250 KVA after opening top cover,and carrying out the following workcomplete all as specified and directed :- (a) Dismantling of all attachment viz breather assembly, conservator, oil temperature gauge, HT/LT bushing etc. and keeping aside for reuse.. (b)Taking out the core with winding assembly. (c) Removing of complete winding from core and dismantling the core, cleaning of core laminate sheet and keeping aside for reuse (d) Cleaning of complete transformer tank oil fins, removing of sludge, and making the inside surface of tank dry by blowing of hot air as directed and specified. (e)Painting of outside surfaces of transformer complete by means of spray machine as directed.
7All as per item No 6 here-in -beforebut capacity of transformer 315 to 630 KVA.
8Note for Item No 6 & 7 : - In case the defective transformer not repaired & installed at site within the specified period of 15 days from the date of handing over of defective transformer/complaint to contractor, a penalty recovery @ Rs 2500/- per day will be charged from his dues.
9(a)Repairsto the transformer of capacityupto 250 KVA as follows :- (i) Rewinding of HT/LT leg coil complete using copper wire /strip of appropriate gauge, size and turn as per existing with double paper coated insulation including all requisite insulating materials like packing sleeves, separator, tapes etc. heating, varnishing the core and winding assembly after framing up top and bottom steel structure of transformer all as specified and directed. (ii) Replacement of all insulating materials other than incorporated for rewinding of HT/LT coils as per existing. (iii) Fixing only HT procelain bushing with studs, nuts, washers 3 Nos. and LT procelain bushing with studs, nuts, and washers 4 Nos. and connection with primary and secondary windings and reconnecting with the main terminals as required and directed. (iv) Fixing only breather assembly, conservator, oil temperature gauge after proper cleaning, minor repairs etc. as required and directed. (v) Replacement of all unserviceable gasket from top cover, HT/LT bushing with new one by using rubberised gasket sheet 4.0mm/6.0mm thick duly pasted with suitable adhesive . (vi) Replacement of unserviceable bolts with new one and fixing of existing serviceable bolts, nuts, washers of different sizes and tightening properly. (vii) Repositioning of core and winding assembly inside the tank, assembling complete unit and making the transformer ready for filling oil and subsequent testing as directed. (viii)Filling/topping up of new transformer oil of required quantities .
10(b) M& L fortransportation of repaired transformer to the original position (from where taken-down), disconnecting the alternative transformer, taking down the same, Re-installation of repaired indoor/outdoor transformer on 4/6 pole structure/plinth/inside sub station, connecting electrically and mechanically, testing and commissioning complete all as specified and directed. (c)The following routine test as per IS 1180 (Part I) -2011 shall be carried out at repairing workshop/manufacturer having NABL Lab accredition and valid calibration of test equipments (i)Measurement of winding resistance. (ii)Measurement of voltage ratio and check of voltage vector relationship. (iii)Measurement of impedance voltage/short circuit impedance (principal tapping) and load loss . (iv) Measurement of no load loss and current. (v) Measurement of insulation resistance. (vi)Dielectric tests (d)The contractor shall give written warranty of one year from the date of sucessfull testing and installation of transformer. The contractor shall submit test report from repair workshop/manufacturer for above mentioned test. Note :-HT/LT leg coils copper wire/stripand transformer oilrequiredshall be measured and paid separately under relevant items of this Schedule here-in-after as supply only.
11All as per item No 8 here-in -beforebut capacity of transformer 315 to 630 KVA.
12Supply only HT coils with super enamelled copper wire /DPC of high quality duly matching with the existing guage and impedance.
13Supply only LT coils with super enamelled copper wire strip/DPC of high quality duly matching with the existing guage and impedance.
14M&L for ON load Centrifuging and dehydration includingfilteration and cleaning of transformer oil by dehydration machine of 11/0.433 KV transformer installed at various site on plinth/4/6 pole structure of any capacityand topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed. Note :-Deficient quantity of Transformer oil required for top up shall be measured and paid separately under item No13here-in -after as supply only.
15Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in transformer or for topping up as required and directed
16Supplying and fixing in replacement, Porcelain Transformer bushing on LT (440 Volt) side, including brass stems conical bush and gasketafter disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 160 KVA andre-connecting electrically and mechanically, testingcomplete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil,opening of top cover by unscrewing nut, bolts washers and provision ofpadtype bus bar almuminium of approppiate size /capacities of transformers withnut bolt &washers.
17All as per Serial item No14 here-in-before butcapacity 200 KVA to 315 KVA
18All as per Serial item No 14 here-in-before but capacity 400 KVA to 630 KVA
19Supplying and fixing in replacement, Porcelain Transformer bushing on HT (11 KV) side, including brass stems conical bush and gasketafter disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 160 KVA andconnecting electrically and mechanically, testingcomplete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil,opening of top cover by unscrewing nut, bolts washers andconnections.
20All as per Serial item No 17 here-in-before but200 KVA to 315 KVA
21All as per Serial item No 17 here-in-before but 400 KVA to 630 KVA
22Supplying and fixing in replacement,all unserviceable gasketafter disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 160 KVA andre-connecting electrically and mechanically, testingcomplete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil,opening of top cover by unscrewing nut, bolts washersetc.
23All as per Serial item No 20 here-in-before but200 KVA to 315 KVA
24All as per Serial item No 20 here-in-before but 400 KVA to 630 KVA
25Supplying and fixing in replacement, Silica Gel Breather assembly including vent pipe and Silica Gel for indoor/outdoor transformers,capacityupto 160 KVA complete all as specified and directed.
26All as per Serial item No23 here-in-before butcapacity 200 KVA to 315 KVA
27All as per Serial item No 23 here-in-before but capacity 400 KVA to 630 KVA
28Supply and fixing Thermometer of transformer upto capacity 630 KVA complete all as specified and directed.
29Material & Labour for painting of transformer installed on plinth/4/6 pole structures at various siteof capacity upto 200 KVA with existing colour, with spraying machine, after cleaning, preparation of outer surface of transformer, including writing of SM No, MES and capacity of transformercomplete all as specified and directed.
30Material & Labour for painting of transformer installed on plinth/4/6 pole structures at various siteof capacity 250 to 630 KVAwith existing colour, with spraying machine, after cleaning, preparation of outer surface of transformer, including writing of SM No, MES and capacity of transformercomplete all as specified and directed.
31Earthing complete in replacementwith galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5mbelow normal ground level, connected to galvanized iron strip 32X6 mm by means of electric arc welding of galvanised iron or steel as shown in electricalplate No 3 of SSR Part I, connected to earth test point and the equipment on the other side complete all as specified, including testing and commissioning complete all as directed. Note : - (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe light grade etc. (b)The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI earthing and protection pipe upto 7.5 meter beyond the earth plates electrode.
32Supply and fix in replacement air break switch gang operated tripple pole mechanically operated mechanism, switch air break gang operated mounted on 15 Nos insulator and steel frame with operating rod of 25 mm bore GI Pipe and locking arrangements worked from ground level for current rating 200 Amps, HT 11 KV grade including drop out fuses and necessary silver coper coating jumpers and making all electrical connections complete.
33Material & Labour for replacement of jumper/bus bar made ofACSR conductorof existing sizeon HTFour/Sixpole structurehaving 2/3 incoming/outoing feeder including bus bar with PVC sleeve , lugs , nut bolts and washerscomplete all as directed.
34All as per Serial item No 31 here-in-before but 4/6 incoming/outoing feeder complete all as directed
35M & L for 2 coat ofaluminiumpainting over a coat of red oxide to steel surfacesof HT 4/6 pole sturcture (Angle Iron/MS channel /MS clamp etc)including preparation of oldsurface complete all as specified.
36M & L for cutting and removing grass, vegetation bushes etc from surrounding4 pole/6 pole HT structure , outside area of HT/LT installation and removing all rubbish to a distance not exceeding 50 m as directed.
37Material and labour for sprading of stone aggregate of nominal size not more than 25mm under 4/6 pole structure /surounding area of outdoor transformermanually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick watered and rammed to true surface all as specified and directed.
38Disconnecting electrically& mechanicallyoutdoor transforemrs upto 630 KVA capacity, lowering down/getting out from plinthcarefully for repairing /making of plinthof transformer andre- connecting electrically and mechanically after repairing/making of plinth, testing and commissioning complete all as specified and directed. Note:-(a)Rate is deemed to be inclusive forhydra, men power, and other itemsrequired for temp energization of transformer. (b) M&L usedto repair the Plinthshall be measured and paid separetely under items of sch of work here-in -after.
39S&Fin replacement 100 mm bore GI Pipe light grade with necessary accessories/ fittings for cable protections complete all as directedat site.
40Excavation in trenchesnot exceeding 1.5m wide & not exceeding 1.5m in depth and n.exc10 sqm on plan for foundations , laying of LT under ground cables/ GI pipes and steel tubular poles etc. and getting out as in soft / loose soil complete all as specified and directed.
41Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
42M&L Brick work with sub-class "B" bricks, straight or curved on plan exc 6 m mean radius, built in cement mortar 1:6 complete as specified and directed.
43M&L Rendering 10mm thick on fair faces of brick work or concrete surfaces in cement mortar (1:4) finished fair and even without using extra cement complete as specified and directed.
44M & L for PCC 1:3:6 type C-2 (using 40 mm gradded aggregate) for foundation, filling and mass concrete etc complete all as specified and directed .
45M & L for cement concrete type B-1,1:2:4, 50 mm thick (using 20 mm gradded aggregate) for floors and paving etc complete all as specified and directed.
46S&F in replacement MS angle iron, flat,Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint.
47S&F in replacement 3.15mm dia MS wire75x75mm mesh , made up into mattress or cages appx 2.00 mtr height and fixed with flate iron /angleby welding in position complete all as specified directed .
48M & L for 2 coat of synthetic enamel painting over a coat of red oxide to MS wire fencingincluding preparation ofold surface complete all as specified.
49Supply and fill in replacement silica gel in breather oftransformer complete all as directed
50M&Lin replacement 32x6mm galvanised iron strip for earth continuity conductorfor earthing of transformer , GOD , 4/6 pole , structure etc complete all as directed at site.
51Material and labour for servicing /testing ofbreaker/control panelincludingCT, PT and relays in control panelof VCB of capacity 1250 /800/630 Amps and rating 11 KVcomplete as details mentioned as under:- (a) Details of servicing of breaker :- (i) Adjustment of mechanism if required. (ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth. (iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts. (iv) Check for rust and wear. (v) Check Spring Tension and pitting of the Cluster Contacts. (vi) Visual check for rust and deformation. (vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc. (viii) Check for loosened connections, rust, damaged lead wires. (ix) Check whether the contacts are damaged by arcing. (x) Checking of control circuit & tighten the connections if any. (xi) Check close & trip coil. (xii) Checking of Jaw Contacts Conditions and repair/adjust. (xiii) Replace the jaw contacts,If required. (xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish. (xv) Replacement of Dashpot/shock absorbers . (xvi) Replacement ofcarbon brush of spring charging motor
52(b) The following test shall be carried out:- (i) Primary Injection Test of CT / PT (ii) Closing & Opening Timing Test for all three poles. (iii) IR Test with megger in open and closed condition. (iv) Contact resistance test for all three poles (v) Closing coil resistance (vi) Tripping coil resistance. (c) Testing of following relays of control panelwith Secondary Injection Kit ,checking andprogramming of relay:- (i) Over current and earth fault relay (d) Testing of followig Aux relay (i) DC Supply supervision relay. (ii) Master trip relay
53Supplying ,fixing &testing in replacement master trip relay , 50/24 Volt DC in control panel including wiringcomplete as directed at site
54Supplying ,fixing &testing in replacement Trip circuit supervision relay, 50/24 Volt DC in control panel including wiringcomplete as directed at site
55Supplying ,fixing &testing in replacementDC supervision relay relay, 50/24 Volt DC in control panel including wiringcomplete as directed at site
56Supplying ,fixing , testing ofSF 6 gas pressure supervisionrelay, 50/24 Volt DC in control panel including wiringcomplete as directed at site
57Supply, installation and testing in replacementNumerical Relay draw out type in HT 11 KV VCB Panel comprising of new and modern numerical scheme for detecting, indicating and tripping the breaker on faults over-current and earth-fault in any of the three phases, Trip circuit supervision relay, 5% pick up for OC and 5% for EF. The relay shall also have the following features as minimum; (i) Programmable rated current 1A & 5A, (ii) Last 8 fault record & 200 event record with time stamping, (iii) 4 analog CT & 3 PT input, 8DI &8DO, (iv) Communicable on IEC61850 protocol, (v) Disturbance recording upto 300 cycles, (vi) Self supervision function. The relay shall be fully integrated with the feeder, internally capturing feeder statuses if available including Breaker On, Off, Spring Chrgd, Test, Service, AC-Fail,Trip circuit healthy relay, PT supervision, inter panel tripping, Master trip relay, local remote and display the same locally on a built-in LCD screen and suitably labeled status LEDs. Relay shall have facility to locally Trip/Close the breaker as a backup to TNC switch provided separately on the panel. The relay shall be fixed on new 2mm CRCA sheet of matching existing VCB panel color and suitable size covering all blank space formed by removing old mechanical type IDMT relay complete includingassociated wiring and integration with existing HT VCB panel complete all as specified and directed.,
58Material and labour in replacement Retro Reflective installation sign boards of size 5 feet x 4 feet fabricated out of 16 gauge MS sheet frame duly welded/riveted with MS square pipe of size 25mm x25mm at height 2.00 meter above ground level on stainless steel heavy dutypipe of size 50mmbore embaded 60 CM in PCC 1:2:4 type B 1 block of size 45cmx45cmx60cm including necessary excavation and earth work.The steel portion of the board shall be painted in stove enameled paint and the front & back of the frame shall be overall sheathed with blue colour base painter adhesive tape.The wiriting matter will be in English language on both sides with reflective adhesive painter tapesas directed by Engineer -in-charge.
59Supply installation & commissioning in replacement of 24V/40A Float Cum Boost Battery Charger unit includingbattery bank comprising 02 Nos of 12 Volts-100 AH sealed maintenance free battery.The CCCV battery charger consisting ofcopper wound,air cooled transformer, 01 Set single phase full wave bridge rectifier consisting ofdiodes andSCRs, liberally rated mounted on heat sink andcomplete with resistor/condenser network for surge supperssion .During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller , DCdigital ammeter,DC digitalvoltmeter, Potentiometer , DC, MCB for reverse battery protection . The charger should have alarm annunciation with visual and audible alarm with manual reset facility forfuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness , louvers for ventilation , gland plate will be provided for cable entry from bottom .The battery charger shall be divided into two compartments.The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:-
60(a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1 (c) On load input power factor- > 0.8 (d) On load unit watt efficiencies-> 80% (e) No load losses of complete charge-< 10% (f)Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell . (j)Float charging -2.15 V/Cell (k)Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode. (l)Reverse polarity -No damage will caused .A visual indication for reverse polarity will appear with an audio alarm. (m)Short circuit-MCB protecton provided.
61Material and labour for Preparation of old painted surfaces of steel by brushing/cleaning stain, greasy spots with thinner, applying two coats of synthetic enamel paint by spray machine on all sides of 11 KV VCB panelincluding writing of MES /SM No and details of feeder as directedby Engr-in-charge on graphic plastic sheetcomplete all asdirected .
62Supplying ,fixing &testing in replacement PT fuse failure relay, 50/24 Volt DC in control panel including wiringcomplete as directed at site
63Disconnecting HT supply from11 KV ,630AmpsRMU, 5/4wayand servicing and overhauling of RMU , checking of tripping mechanism , greasing of moving contacts , cleaning of carbon from main contacts , checking of spring tension ,Checking of loosened bolts and nuts, checking of loosened connections, rust, damaged lead wires, checking of spring charging motor , Improvement of resistance of CTs , PT,epoxy insulator and epoxy body by applying post heated varnish completeall as directed and testing on load
64Material and labour for checking the existing pressure of SF6 Gas in Gas Chamber of11 KV ,630AmpsRMU, 5/4waybefore fillingand topping up the SF6 gas in the chamber of RMU including supervision of gas filling/topping up process and checking the pressure of gas after filling complete all as directed at site.
65Supplyingand fixing in replacement operating mechanism(2PA Mechanism W/O hex Rod) for11 KV ,630AmpsRMU, 5/4way complete all as directed at site by Engr-in -charge
66Supply and fixing in replacementcable Boots 11 KV , in630AmpsRMU, 5/4way complete all as directed at site by Engr-in -charge
67Supplying and fixing in replacementassociated ring-core cast-resin insulated CTs 100/50/1 -1 Amp , 2.5 VA, 10P10for protectionin11 KV, 630 AmpsRMU complete all as directed by Engr -in -charge
68Supplying and fixing in replacementassociated ring-core cast-resin insulated CTs 60/30/1-1Amp , 2.5 VA, 10P10for protection in11 KV, 630 AmpsRMU complete all as directed by Engr -in -charge
69Supplying and fixing in replacement 1-Ph (11kV/rt3):110 VAC, 50VA Potentialtransformer in11 KV, 630 AmpsRMU (Ring main unit)complete all as directed by Engr -in -charge
70Supplying and fixing in replacement 1-Ph (11kV/rt3):110VAC, 500VA Auxiliary transformer in11 KV, 630 AmpsRMU (Ring main unit) complete all as directed by Engr -in -charge
71Suplying and laying as replacement in sub station fixing 3.3 to 11 KV electrical insulation mat of size 5 mtr x 1 mtr x 2.5 mm thick specification as per IS 15652 2006
72Supply andfix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable offollowing size :-
7395 Sqmm 3 core.
74120 Sqmm to 185 Sqmm, 3 core.
75240 Sqmm to 300 Sqmm, 3 core.
76Supply andfixCable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable offollowing size :-
7795 Sqmm 3 core.
78120 Sqmm to 185 Sqmm, 3 core.
79Supplying, installation, commissioning and testingof 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type,of 13.1 KA/Sec having ratio 400/200/5-5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VAfor metering andassociated wiringincluding taking down old UNSV CTs complete all as specified and directed.
80All as per item No 70 here-in-beforebut having ratio 200/100/5-5 complete all as directed
81All as per item No 70 here-in-beforebut having ratio 150/75/5-5 complete all as directed
82All as per item No 70 here-in-beforebut having ratio 100/50/5-5 complete all as directed
83All as per item No 70 here-in-beforebut having ratio 60/30/5-5 complete all as directed
84All as per item No 70 here-in-beforebut having ratio 50/25/5-5 complete all as directed
85Supplying and fixingPotential Transformers, Draw-out type in existing HV panel for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolationincluding taking down old UNSVPTs complete all as specified and directed
86Supplying, installation, commissioning and testing ofPT unit three phase, three limbs, upto 11 KV draw-out type, resin cast dry type, single ratio having primary voltage 11 KV & secondary voltage 110 volts, 50 VA class-1 including necessary bus bar connections & wiring for meteringincluding taking down old UNSV PTs complete all as specified and directed
87S&F LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etcfor 11 KV control paneland associated wiring, if reqd,including taking down old UNSV LED indication complete all as specified and directed
88Supply and installation Anti-condensation space-heater withThermostatic control in cable andcircuit breaker compartments ofHT switchgears including taking down old UNSV heater complete all as specified and directed
89S&Fof vacuum interrupter suitable for400/630/800 amps, 11 KV HT VCB including taking down old UNSV vacuum interrupter complete all as specified and directed
90S&Fof isolating contact assembly suitable for400/630/800 amps, 11 KV HT VCB including taking down old UNSV contact assemblycomplete all as specified and directed
91S&Fof fixed contact block complete suitable for400/630/800 amps, 11 KV HT VCB including taking down old UNSV contact block complete all as specified and directed
92S&F of moving contact block complete suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV moving contact block complete all as specified and directed
93S&Fof motor & gear assembly 230V AC suitable for 400/630/800 amps, 11 KV HT VCB, testing & puting on load including taking down old UNSV motoer gear assembly complete all as specified and directed
94S&Fof spring gear suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSVspring bearing gear complete all as specified and directed
95S&Fof closing coilassembly 24 volts DC suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV closing coil complete all as specified and directed
96S&F of tripping coilassembly 24 volts DC suitable for 400/630/800 amps, 11 KV HT VCBincluding taking down old UNSV tripping coil complete all as specified and directed
97Supply and fix close/trip coil 24V DC for 11 KV HT VCB of capacity 400/630/800 Amps capacity including taking down old UNSV close/trip coilcomplete all as specified and directed
98S&F of panel door locksuitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV panel ddor lock complete all as specified and directed.
99Supplying & Fixingauxillary switch (7 No + 7NC) suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV auxillary contactcomplete all as specified and directed
100Supply and fixT&C Switch for Breaker ON/OFF purpose in HT 11 KV VCB panel including associated wiring, if reqd, for proper functioning of switch including taking down old UNSV T& C switch complete all as specified and directed
101Supplying & Fixingsupport rod with screwssuitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSVsupport road with screw complete all as specified and directed
102Supplying & Fixing support insulatorsuitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV support insulator complete all as specified and directed
103Supplying & Fixingupper connector suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV upper connector complete all as specified and directed
104Supplying & Fixinglowerconnectorsuitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV lower connector complete all as specified and directed
105Supply & fix ofset of 6 Nos fixed arcing contacts suitable for 400/630/800 amps, 11 KV HT VCBincluding taking down old UNSVfixed arching contact complete all as specified and directed
106S&F Caution plate “CAUTION MEN AT WORK of size 40cmx15cmmade out of white acrylicsheet withRed coloured glow tape including taking down old UNSV caution plate complete all as specified and directed
107S&Fof HRC fuse of capacity 20 Amps for VCB including taking down old UNSV PTs including taking down old UNSV HRC fusecomplete all as specified and directed
108S&F ofMCB20 to 32 Amps DP including taking down old UNSV MCBscomplete all as specified and directed
109S&FofDigital Ampmeter (CT secondary site selectable 5A) for 11 KV VCB Control Panel including taking down old UNSV meter complete all as specified and directed.
110S&F ofDigital Voltmeter Secondary voltage 110 V for 11 KV VCB Control Panel including taking down old UNSV meter complete all as specified and directed.
111S&F andinstallation battery 12 volts,100 AH, dry type in replacement of old unserviceable battery in battery charger with suitable size of new copper battery terminal and lugs and initialy charging, commissioning and testing complete including taking down old UNSV battery complete all as specified and directed.
112Supply and fixing in replacement of feeder Protection relay for overcurrent and earth fault relay of 11 KV VCB HT Panel complete all as specified and directed.Make C&S /Schneider
113Supply and fixi ng in replacement ofElectronic Trivector meter,3 phase 4 wiresuitable for 11 KV VCB HT Panel compllete all as specified and directed.Make : L&T /Secure or equivalent
114Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work orderand shall be verified by the Eng-in-charge