Tender For Construction Of Under Ground Reservoir ( Ugr ) In Block-B, Sector-26 At Rohini Phase-Iv.Sh:Sitc Of Clear Water Booster Pump Set And Allied Accessories At Ugr Sector-26 Rohini, rohini-Delhi

Delhi Development Authority-DDA has published Tender For Construction Of Under Ground Reservoir ( Ugr ) In Block-B, Sector-26 At Rohini Phase-Iv.Sh:Sitc Of Clear Water Booster Pump Set And Allied Accessories At Ugr Sector-26 Rohini. Submission Date for this Tender is 03-10-2023. Absorbents Tenders in rohini Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

39832676
Tender For Construction Of Under Ground Reservoir ( Ugr ) In Block-B, Sector-26 At Rohini Phase-Iv.Sh:Sitc Of Clear Water Booster Pump Set And Allied Accessories At Ugr Sector-26 Rohini
Open Tender
Indian
Delhi
rohini
03-10-2023

Tender Details

Construction Of Under Ground Reservoir ( Ugr ) In Block-B, Sector-26 At Rohini Phase-Iv.Sh:Sitc Of Clear Water Booster Pump Set And Allied Accessories At Ugr Sector-26 Rohini ; 1 Supply, Installation, Testing & Commissioning Of Horizontal Split Casing Centrifugal Pump Set With Bronze Impeller Directly Coupled Through Flexible Coupling With Tefc Squirrel Cage Induction Motor Of Suitable Rating For Operation On 415 Volts, 3 Phase, 50 Hz Ac Supply, Mounted On Common M.S Channel Base Frame Complete With Foundation Bolts, Nuts, Washers, Coupling Guard, Pressure Gauge 100Mm Dia With Copper Tubing, Brass Stop Cock, Water Drain Pipe Of Suitable Size And Length, Required Size Of G.I Taper And Anti Vibration Mounting Pads, Rcc Foundation ( 1:2:4 ) Etc. Complete As Per Specifications Attached. The Pump Shall Be Capable To Perform The Following Duties:- A ) Discharge : 118.8 M³ / Hourb ) Head: 26 M C ) Type Of Liquid :Clear Waterd ) R P M : 1450 2 Supplying, Installation, Testing And Commissioning Of Sewage Submersibledrainage Pump Of 300 L / Min Discharge Of Water At 10 M Head Having Solid Handling Capacity Of 35Mm Complete With Base Plate And All Accessoriessuitable For Operation On 220 Volts, Single Phase50hz., A.C. Supply Complete With Starter For Automatic Operation I / C Water Level Sensing Device, Inter Connection, And Submersible Cable Etc. Complete As Reqd. 3 Supplying And Installation Of Following Size M.S Black Pipe Including M.S Flanges Duly Screwed And Welded On Both Ends Of Pipe, Bend, Tee, Nipple Rubber Gasket, G.I Nuts, Bolts And Washers, Support Etc. Complete As Required.A. ) 150 Mm Dia ( Heavy C Class ) Conforming To Is:1239 Part1 ( 2004 ) With Upto Date Amendment. 4 Supplying And Installation Of Following Size M.S Black Pipe Including M.S Flanges Duly Screwed And Welded On Both Ends Of Pipe, Bend, Tee, Nipple Rubber Gasket, G.I Nuts, Bolts And Washers, Support Etc. Complete As Required. B. ) 100 Mm Dia ( Heavy C Class ) Conforming To Is:1239 Part1 ( 2004 ) With Upto Date Amendment. 5 Supplying And Installation Of Following Size M.S Black Pipe Including M.S Flanges Duly Screwed And Welded On Both Ends Of Pipe, Bend, Tee, Nipple Rubber Gasket, G.I Nuts, Bolts And Washers, Support Etc. Complete As Required. C. ) 50 Mm Dia ( Medium B Class ) Conforming To Is:1239 Part-1 ( 2004 ) With Upto Date Amendment. 6 Supplying And Fixing Of Cast Iron Double Flanged Sluice Valve Pn-16 Conforming To Is:14846, Rising Spindle Type Of Following Size: Complete With Nuts, Bolts, Washers, Rubber Insertions, Necessary Support, Hand Wheel Including Painting And Testing Etc Completerequired As Per Technical Specification Attached. A. ) 100 Mm Dia 7 Supplying And Fixing Of Cast Iron Double Flanged Sluice Valve Pn-16 Conforming To Is:14846, Rising Spindle Type Of Following Size: Complete With Nuts, Bolts, Washers, Rubber Insertions, Necessary Support, Hand Wheel Including Painting And Testing Etc Completerequired As Per Technical Specification Attached.B. ) 150 Mm Dia 8 Supplying And Fixing Of Cast Iron Double Flanged Non Return Valve Pn-16 Confirming To Is: 5312 Without By Pass Arrangement Of Following Size Complete With Nuts, Bolts, Washers, Rubber Insertions Necessary Support, Including Painting And Testing Etc, As Required. A. ) 100 Mm Dia 9 Supplying And Fixing Of Cast Iron Flanged Foot Valve Confirming To Is: 4038 Of Following Size Complete With Nuts, Bolts, Washers, Rubber Insertions Including Painting And Testing Etc, As Required. A. ) 200 Mm Dia 10 Supply, Installation, Testing And Commissioning Of Mild Steel Double Flanged Dismantling Joints Of Pressure Rating Pn16 Of The Following Sizes Complete Withginuts, Bolts, Washers, Rubber Insertions, Painting & Testing Etc. As Required.A. ) 100 Mm Dia 11 Supply, Installation, Testing And Commissioning Of Mild Steel Double Flanged Dismantling Joints Of Pressure Rating Pn16 Of The Following Sizes Complete Withginuts, Bolts, Washers, Rubber Insertions, Painting & Testing Etc. As Required.B. ) 150 Mm Dia 12 Supplying And Fixing Of Bronze Globe Valve Of 50 Mm Dia In The Existing Pipe Complete With Rubber Insertions, Teflon Tape Accessories Including Painting And Testing Etc, As Required. 13 Sitc Of Floor Mounted Free Standing Type L.T. Cubical Main Feeder Pillar Duly Compartmentalized ( Outdoor Type ) Made Out Of 2 Mm Thick Ms Crca Sheet, 7 Tank Process Powder Coated, With 4 Nos. X 600 Mm Long Legs Made Of M.S Angle Iron Of Size 40 Mm X 40 Mm X 5 Mm Thick Along With Frame & Legs Suitably Grouted In Foundation I / C Connection Inter Connection Of The Accessories Mounted There On With Suitable Size Of Copper Wire / Strip With Thimble / Lugs, Earthing The Body Of The Feeder Pillar Suitable For Operation On 415V, 3 Phase, 50Hz Ac I / C Supply & Fixing Of The Following Items And As Per Technical Specification Enclosed. A ) 250 A, 50Ka, Fpmccb ( Ics= Icu ) - 1 No ( Incomer ) B ) 63 Amp Tp Mccb, 25 Ka Breaking Capacity= 5 Nos. ( 4 Nos. For Pump Set+1 No. For Iei ) - Outgoingc ) 32 Amp Dp Mcb C Series-4 No.D ) Volt Meter ( 0-500V ) 96 Sq.Mm With Selector Switch – 1 Sete ) Amp-Meter ( 0-100A ) 96Sq.Mm With Selector Switch & 100 / 5 Amp Ratio Cts – 1 Setf ) Led Type Ryb Phase Indicating Lamps, On, Off, Trip Indicating Lampsh ) 6 Amp Sp Mcb – 1 No.I ) 3 Phase 440 Volts Power Shunt Capacitor 7 Kvar ( With 63 Amps Tp Mcb ) Including All Accessory Complete - 4 Setsj ) Single Phase Preventerk ) Star Delta Starter Suitable For Item No.1 Load- 4 Set.L ) 400 Amp, 4 Strip Sleeved Aluminium Busbar – 1 Setm ) Danger Notice Plate – 1 No.N ) 6 Pin 15 A Switch / Socket Outlet - 1 Seto ) Lighting Inside The Feeder Pillarfor All Mccb ( Ics= Icu ) . Outgoing Mccb Of Motor Shall Be Of Motor Grade.Note: Foundation Height Of 750 Mm Duly Plastered & Finishedhaving Top Outer Edges 30 Cm Beyond All Round The Edges Of 40X5 Angle Iron Frame Shall Be Made As Per Site Requirementfor Which Nothing Extra Shall Be Paid. 14 Supplyingof The Following Sizes Of Xlpe Insulatedaluminium Conductor Armoured Cable Of 1.1 Kv Grade Confirming To Is: 7098 Part-1 With Upto Date Amendment. A. ) 3.5 C X95 Mm² 15 Supplyingof The Following Sizes Of Xlpe Insulatedaluminium Conductor Unarmoured Power Cable Of 1.1 Kv Grade Confirming To Is: 7098 Part-1 With Upto Date Amendment.A. ) 3 C X50 Mm² 16 Supplyingof The Following Sizes Of Xlpe Insulatedaluminium Conductor Unarmoured Power Cable Of 1.1 Kv Grade Confirming To Is: 7098 Part-1 With Upto Date Amendment. B. ) 4 C X16 Mm² 17 Supplyingof The Following Sizes Of Xlpe Insulatedaluminium Conductor Unarmoured Power Cable Of 1.1 Kv Grade Confirming To Is: 7098 Part-1 With Upto Date Amendment. C. ) 3 C X4 Mm²flat Cable 18 Supplyingof The Following Sizes Of Xlpe Insulatedaluminium Conductor Unarmoured Power Cable Of 1.1 Kv Grade Confirming To Is: 7098 Part-1 With Upto Date Amendment. D. ) 3 C X4 Mm² 19 Supplying And Installing Following Size Of Perforated Pre-Painted M.S. Cable Trays With Perforation Not More Than 17.5%, In Convenient Sections, Joined With Connectors, Suspended From The Ceiling With M.S. Suspenders Including Bolts & Nuts, Paintingsuspenders Etc As Required.A. ) 300 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 20 Supplying And Installing Following Size Of Perforated Pre-Painted M.S. Cable Trays With Perforation Not More Than 17.5%, In Convenient Sections, Joined With Connectors, Suspended From The Ceiling With M.S. Suspenders Including Bolts & Nuts, Paintingsuspenders Etc As Required.B. ) 100 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 21 Supplying And Installing Following Size Of Perforated Painted With Powder Coating M.S. Cable Trays Bends With Perforation Not More Than 17.5%, , Joined With Connectors, Suspended From The Ceiling With M.S. Suspenders Including Bolts & Nuts, Painting Suspenders Etc As Required.A. ) 300 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 22 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Steel Conduit, With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. Group-B 23 Wiring For Light / Power Plug With 2X4 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Steel Conduit Alongwith 1 No. 4 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable For Loop Earthing As Required. 24 Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required.A. ) 6 Pin 15 / 16 A Socket Outlet 25 Wiring For Circuit / Submain Wiring Alongwith Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Steel Conduit As Required. A. ) 2 X 1.5 Sq. Mm + 1 X 1.5 Sq. Mm Earth Wire 26 Supplying And Fixing Of 90 Watt Led Street Light Luminaire Made Up Of Pressure Die Cast Aluminium Alloy Housing Withip 66, Ik07 Protection, System Efficacy>110 Lm / W Lumens, Integral Electronic Driver With Apfc, Thd<10%, Output Short / Open Circuit Protection, Surge Protection Upto 10 Kv ( With External Spd ) Phase To Phase ( 440 V ) / Over Voltage Protection & Other Safety Test As Per Is 15885 Part-2 / Sec 13. Cri>70, Cct 5700 K Suitable To Operate On 240 V, 50 Hz, A.C Supply. Installation On Bracket Of 1 Mtr Lengthmade Of Suitable Dia Gi Pipe On Surface / In Recess With All Required Accessories Including Connections, Testing Etc. Complete As Required With Minimum 5 Years Guarantee / Warranty 27 Supplying, Installation, Testing And Commissioning Of 24 Watt Prewired Led Batten With Aluminium Housing And Integrated Electronic Driver Efficiency>88%, Inbuilt Surge Protection Of 2.5 Kv, Cri>80, Cct 6500 K, Thd<20, Lumen Output > 100 Lm / Wattcomplete With All Accessories Directly On Ceiling / Wall Suitable For Operation On 230V, 50 Hz Ac Supply Including Connection With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor , Single Core Cable And Earthing Etc. As Required With Minimum 2 Years Guarantee / Warranty. 28 Supply Of Celling Fan Of 1200 Mm Sweep Sizes With Minimum 226 M3 / Hr. Air Delivery Operating On Single Phase 50 Hz, 230V, Ac Supply, Complete Etc. As Required. 29 Supplying And Fixing Extra Conduit Down Rod Of 20 Cm Length G.I. Pipe 15 Mm Dia, Heavy Gauge Including Painting Etc. As Required. ( Note : More Than 5 Cm Length Shall Be Rounded To The Nearest 10 Cm And 5 Cm Or Less Shall Be Ignored ) 30 Supplying And Fixing Two Module Stepped Type Electronic Fan Regulator On The Existing Modular Plate Switch Box Including Connections But Excluding Modular Plate Etc. As Required. 31 Supply Of Exhaust Fan Operating On Single Phase50 Hz230 Volt Ac Supply Of 300 Mm Sweep Size Min 1600 M3 / Hr. Air Delivery At Rated Speed 1380 Rpm In Metal Body, Bird Guard To Protect The Fan In Running Condition, Guarantee / Warranty Of 2 Years With Complete Kit & Required Accessories For Installation Etc As Required 32 Installation Of Exhaust Fan In The Existing Opening, Including Making Good The Damage, Connection, Testing, Commissioning Etc. As Required. Up To 450 Mm Sweep. 33 Extra For Fixing The Louvers / Shutters Complete With Frame For Exhaust Fan Of All Sizes 34 Numbering Of Ceiling Fan / Exhaust Fan / Fluorescent Fittings / Led Fitting / Led Street Light Fitting Etc As Required. 35 Supplying And Fixing Following Way, Single Pole And Neutral, Sheet Steel, Mcb Distribution Board, 240 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator ) . A. ) 12 Way , Double Door 36 Supplying And Fixing 5 A To 32 A Rating, 240 / 415 V, 10 Ka, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. A. ) Single Pole 37 Supplying And Fixing 5 A To 32 A Rating, 240 / 415 V, 10 Ka, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.B. ) Double Pole 38 Earthing With G.I. Earth Plate 600 Mm X 600 Mm X 6 Mm Thick Including Accessories, And Providing Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Of 2.7 Metre Long Etc. With Charcoal / Coke And Salt As Required. 39 Supplying And Laying 25 Mm X 5 Mm G.I Strip At 0.50 Metre Below Ground As Strip Earth Electrode, Including Connection / Terminating With G.I. Nut, Bolt, Spring, Washer Etc. As Required. ( Jointing Shall Be Done By Overlapping And With 2 Sets Of G.I. Nut Bolt & Spring Washer Spaced At 50Mm ) 40 Providing And Fixing 25 Mm X 5 Mm G.I. Strip On Surface Or In Recess For Connections Etc. As Required. 41 Providing And Fixing 6 Swg Dia G.I. Wire On Surface Or In Recess For Loop Earthing As Required. 42 Supplying And Replacement Of Insulation Mat For Electric Purpose Confirming To Is 15652 / 2006, Duly Isi Marked With Anti-Skid Abrasion Size 1 Mtr.X 2 Mtr., B-Class, Thickness 2.5 Mm For 11 Kv Working Voltage. 43 Sitc Of Is: 15683 Marked Powder Stored Pressure Type Portable Fire Extinguisher With Is: 14609 Marked Abc Powder ( M.A.P 90% ) Capacity 6 Kg Complete With Squeeze Grip Release Valve Discharge Pipe Locking Arrangement Pressure Gauge Operation Manual Bracket With Two Screws & Sleeves Etc. Complete As Required 44 Sitc Of Co2 ( Carbon Dioxide ) Fire Extinguisher Isi Marked Confirming To Is: 15683. Capacity 4.5 Kg Complete With Delivery Hose Horn, Locking Arrangement, Operation Manual, Bracket With Two Screw And Sleeve Etc. Complete As Reqd.

Key Value

Document Fees
Refer document
EMD
INR 51020.0 /-
Tender Value
INR 25.50 Lakhs /-

BOQ Items

Name of Work: C/o Under Ground Reservoir (UGR) in block-B, Sector-26 at Rohini Phase-IV. SH:SITC of Clear Water Booster Pump set and allied accessories at UGR Sector-26 Rohini
Sl. No. Item Description
1Supply, Installation, Testing & commissioning of horizontal split casing centrifugal pump set with bronze impeller directly coupled through flexible coupling with TEFC squirrel cage induction motor of suitable rating for operation on 415 volts, 3 phase, 50 HZ AC supply, mounted on common M.S channel base frame complete with foundation bolts, nuts, washers, coupling guard, pressure gauge 100mm dia with copper tubing, brass stop cock, water drain pipe of suitable size and length, required size of G.I taper and anti vibration mounting pads, RCC foundation (1:2:4) etc. complete as per specifications attached. The pump shall be capable to perform the following duties:- a) Discharge : 118.8 m³/hourb) Head: 26 m c) Type of liquid :Clear waterd) R P M : 1450
2Supplying, installation, testing and commissioning of Sewage SubmersibleDrainage Pump of 300 L/min discharge of water at 10 m head having solid handling capacity of 35mm complete with base plate and all accessoriessuitable for operation on 220 Volts, Single phase50Hz., A.C. supply complete with starter for automatic operation i/c water level sensing device, inter connection, and submersible cable etc. complete as reqd.
3Supplying and installation of following size M.S Black Pipe including M.S flanges duly screwed and welded on both ends of pipe, bend, tee, nipple rubber gasket, G.I nuts, bolts and washers, support etc. complete as required.a.) 150 mm dia (Heavy C class) conforming to IS:1239 Part1(2004) with upto date amendment.
4Supplying and installation of following size M.S Black Pipe including M.S flanges duly screwed and welded on both ends of pipe, bend, tee, nipple rubber gasket, G.I nuts, bolts and washers, support etc. complete as required. b.)100 mm dia (Heavy C class) conforming to IS:1239 Part1(2004) with upto date amendment.
5Supplying and installation of following size M.S Black Pipe including M.S flanges duly screwed and welded on both ends of pipe, bend, tee, nipple rubber gasket, G.I nuts, bolts and washers, support etc. complete as required. c.) 50 mm Dia (Medium B Class) conforming to IS:1239 part-1(2004) with upto date amendment.
6Supplying and fixing of cast iron double flanged sluice valve PN-16 conforming to IS:14846, rising spindle type of following size: complete with nuts, bolts, washers, rubber insertions, necessary support, hand wheel including painting and testing etc completerequired as per technical specification attached. a.)100 mm dia
7Supplying and fixing of cast iron double flanged sluice valve PN-16 conforming to IS:14846, rising spindle type of following size: complete with nuts, bolts, washers, rubber insertions, necessary support, hand wheel including painting and testing etc completerequired as per technical specification attached.b.)150 mm dia
8Supplying and fixing of cast iron double flanged non return valve PN-16 confirming to IS: 5312 without by pass arrangement of following size complete with nuts, bolts, washers, rubber insertions necessary support, including painting and testing etc, as required. a.) 100 mm dia
9Supplying and fixing of cast iron flanged foot valve confirming to IS: 4038 of following size complete with nuts, bolts, washers, rubber insertions including painting and testing etc, as required. a.) 200 mm dia
10Supply, installation, testing and commissioning of Mild Steel double flanged Dismantling joints of Pressure Rating PN16 of the following sizes complete withGInuts, bolts, washers, rubber insertions, painting & testing etc. as required.a.) 100 mm dia
11Supply, installation, testing and commissioning of Mild Steel double flanged Dismantling joints of Pressure Rating PN16 of the following sizes complete withGInuts, bolts, washers, rubber insertions, painting & testing etc. as required.b.) 150 mm dia
12Supplying and fixing of bronze globe valve of 50 mm dia in the existing pipe complete with rubber insertions,teflon tape accessories including painting and testing etc, as required.
13SITC of floor mounted free standing type L.T. cubical main feeder pillar duly compartmentalized (outdoor type) made out of 2 mm thick MS CRCA sheet, 7 tank process powder coated, with 4 nos. x 600 mm long legs made of M.S angle iron of size 40 mm x 40 mm x 5 mm thick along with frame & legs suitably grouted in foundation i/c connection inter connection of the accessories mounted there on with suitable size of copper wire/strip with thimble/lugs, earthing the body of the feeder pillar suitable for operation on 415V, 3 phase, 50Hz Ac i/c supply & fixing of the following items and as per technical specification enclosed. a) 250 A,50KA,FPMCCB (Ics= Icu) - 1 No (Incomer)b) 63 Amp TP MCCB, 25 KA breaking capacity= 5 Nos. (4 nos. for pump set+1 no. for IEI)- Outgoingc) 32 Amp DP MCB "C" Series-4 No.d) Volt meter (0-500V) 96 Sq.mm with selector switch – 1 Sete) Amp-meter (0-100A) 96Sq.mm with selector switch & 100/5 Amp ratio CTS – 1 Setf) LED type RYB phase indicating lamps, ON, OFF, trip indicating lampsh) 6 amp SP MCB – 1 No.i) 3 Phase 440 Volts power shunt capacitor 7 KVAR (with 63 Amps TP MCB) including all accessory complete - 4 Setsj) Single phase preventerk) Star delta starter suitable for Item No.1 load- 4 set.l) 400 amp, 4 strip sleeved aluminium busbar – 1 Setm) Danger Notice plate – 1 No.n) 6 Pin 15 A Switch / Socket outlet - 1 Seto) Lighting inside the feeder pillarFor all MCCB(Ics= Icu). Outgoing MCCB of motor shall be of motor grade.Note: Foundation height of 750 mm duly plastered & finishedhaving top outer edges 30 cm beyond all round the edges of 40x5 angle iron frame shall be made as per site requirementfor which nothing extra shall be paid.
14Supplyingof the following sizes of XLPE insulatedaluminium conductor armoured cable of 1.1 KV grade confirming to IS: 7098 part-1 with upto date amendment. a.) 3.5 C x95 mm²
15Supplyingof the following sizes of XLPE insulatedaluminium conductor unarmoured power cable of 1.1 KV grade confirming to IS: 7098 part-1 with upto date amendment.a.) 3 C x50 mm²
16Supplyingof the following sizes of XLPE insulatedaluminium conductor unarmoured power cable of 1.1 KV grade confirming to IS: 7098 part-1 with upto date amendment. b.) 4 C x16 mm²
17Supplyingof the following sizes of XLPE insulatedaluminium conductor unarmoured power cable of 1.1 KV grade confirming to IS: 7098 part-1 with upto date amendment. c.)3 C x4 mm²flat cable
18Supplyingof the following sizes of XLPE insulatedaluminium conductor unarmoured power cable of 1.1 KV grade confirming to IS: 7098 part-1 with upto date amendment. d.)3 C x4 mm²
19Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required.a.) 300 mm width X 50 mm depth X 1.6 mm thickness
20Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required.b.) 100 mm width X 50 mm depth X 1.6 mm thickness
21Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.a.) 300 mm width X 50 mm depth X 1.6 mm thickness
22Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group-B
23Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
24Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.a.) 6 pin 15/16 A socket outlet
25Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. a.) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
26Supplying and fixing of 90 watt LED street light luminaire made up of pressure die cast Aluminium alloy housing withIP 66, IK07 protection,System efficacy>110 lm/w lumens, integral electronic driver with APFC,THD<10%, Output Short/Open Circuit Protection, Surge Protection upto 10 kV ( with external SPD) phase to phase (440 V) / Over Voltage Protection & other safety test as per IS 15885 Part-2/Sec 13. CRI>70, CCT 5700 K suitable to operate on 240 V, 50 Hz, A.C supply. Installation on bracket of 1 mtr lengthmade of suitable dia GI pipe on surface / in recess with all required accessories including connections, testing etc. complete as required with minimum 5 years Guarantee/warranty
27Supplying, installation, testing and commissioning of 24 watt Prewired LED batten with aluminium housing and integrated electronic driver efficiency>88%, inbuilt surge protection of 2.5 kv, CRI>80, CCT 6500 K, THD<20, Lumen output > 100 lm/wattcomplete with all accessories directly on ceiling / wall suitable for operation on 230V, 50 Hz AC supply including connection with 1.5 sq.mm FRLS PVC insulated copper conductor , single core cable and earthing etc. as required with minimum 2 years Guarantee/warranty.
28Supply of celling fan of 1200 mm sweep sizes with minimum 226 m3/Hr. Air delivery operating on Single Phase 50 Hz, 230V, AC supply,complete etc. as required.
29Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
30Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
31Supply of exhaust fan operating on single phase50 Hz230 volt AC supply of 300 mm sweep size min 1600 m3/Hr. air delivery at rated speed 1380 RPM in metal body, bird guard to protect the fan in running condition, guarantee/warranty of 2 years with complete kit & required accessories for installation etc as required
32Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Up to 450 mm sweep.
33Extra for fixing the louvers/ shutters complete with frame for exhaust fan of all sizes
34Numbering of ceiling fan/ exhaust fan/ fluorescent fittings/LED fitting/LED street light fitting etc as required.
35Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). a.) 12 way , Double door
36Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a.) Single pole
37Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.b.) Double pole
38Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
39Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
40Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
41Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
42Supplying and replacement of Insulation mat for Electric Purpose confirming to IS 15652/2006, duly ISI Marked with anti-Skid abrasion size 1 Mtr.X 2 Mtr., B-Class, Thickness 2.5 mm for 11 KV Working voltage.
43SITC of IS: 15683 marked Powder Stored Pressure type Portable Fire Extinguisher with IS: 14609 marked ABC powder (M.A.P 90%) Capacity 6 Kg complete with squeeze grip release valve discharge pipe locking arrangement pressure gauge operation manual bracket with two screws & sleeves etc. complete as required
44SITC of Co2 (Carbon Dioxide) Fire Extinguisher ISI marked confirming to IS: 15683. Capacity 4.5 Kg complete with delivery hose horn, locking arrangement, operation manual, bracket with two screw and sleeve etc. complete as reqd.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail