Tender For Repair/Maintenance Of Lt Panel Including Lt Switch Gear, Earthing, Timer Panel, Lt Pole, Pole Box, Street Lights, Fiood Lights, Area Lights Lt Distribution Network And Connected Items At Otm/Md Accn Of Skp, Lbs Marg, Usman Road, Surya Canteen, , lucknow-Uttar Pradesh

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Lt Panel Including Lt Switch Gear, Earthing, Timer Panel, Lt Pole, Pole Box, Street Lights, Fiood Lights, Area Lights Lt Distribution Network And Connected Items At Otm/Md Accn Of Skp, Lbs Marg, Usman Road, Surya Canteen, . Submission Date for this Tender is 16-10-2023. Electrification Work Tenders in lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

39742117
Corrigendum : Tender For Repair/Maintenance Of Lt Panel Including Lt Switch Gear, Earthing, Timer Panel, Lt Pole, Pole Box, Street Lights, Fiood Lights, Area Lights Lt Distribution Network And Connected Items At Otm/Md Accn Of Skp, Lbs Marg, Usman Road, Surya Canteen,
Open Tender
Indian
Uttar Pradesh
lucknow
16-10-2023

Tender Details

Repair / Maintenance Of Lt Panel Including Lt Switch Gear, Earthing, Timer Panel, Lt Pole, Pole Box, Street Lights, Fiood Lights, Area Lights Lt Distribution Network And Connected Items At Otm / Md Accn Of Skp, Lbs Marg, Usman Road, Surya Canteen, Ccsr, 11 Grrc, Otm / Md Accn West Of Mg Road And Adjoining Area Of Age E / M Ext ( Elect ) Under Ge E / M Lucknow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Sep-2023 Corrigendum1 Other 09-10-2023
2 29-Sep-2023 Corrigendum2 Other 09-10-2023
3 09-Oct-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 82000.0 /-
Tender Value
INR 41 Lakhs /-

BOQ Items

Name of Work: REPAIR/MAINTENANCE OF LT PANEL INCLUDING LT SWITCH GEAR, EARTHING, TIMER PANEL, LT POLE, POLE BOX, STREET LIGHTS, FIOOD LIGHTS, AREA LIGHTS LT DISTRIBUTION NETWORK AND CONNECTED ITEMS AT OTM/MD ACCN OF SKP, LBS MARG, USMAN ROAD, SURYA CANTEEN, CCSR, 11 GRRC, OTM/MD ACCN WEST OF MG ROAD AND ADJOINING AREA OF AGE E/M EXT (ELECT) UNDER GE E/M LUCKNOW
Sl. No. Item Description
1Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
2Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm using excavated suitable soil complete all as specified.
3Removing excavated soil from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
4M&L for providing dry river sand as in sand cushioning to under ground cable of any descreption including punning down of sand in layer all as specified and directed by Engg-in-Charge. Note: for measurement purpose any punned thickness of sand will be considered.)
5M&L for laying well burnt old sizebricks, sub class "B" bricks, laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge.
6M&L for cutting of road / path / hardstading / concrete in floor, etc for laying of cable complete all as directed at site by Engr-in-charge
7M&L for cement concrete type C2 1:3:6 (40mm graded stone aggregate) as in foundation / filling of cutting of roads / path / hardstanding and mass concrete all as specified by Engr-in-charge.
8Material and labour for PCC1:2:4 type B-1 using 20 mm graded stone aggregates for coping of pole etcincluding necessary form work and demolition of old coping complete all as specified and as directed by Engineer-in-Charge.
9Deployment of manpowe / tools for Boring / drilling (Horizontly) manually / mechanically under existing road max 10 M in width) suitable for passing tubing 40 to 100 mm bore complete all as specified and directed by Engineer in Charge
10S&F 40 mm dia bore mild steel galvanized iron tubes, "light grade" with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable including taking down old pipe complete all as directed
11S&F 50 mm dia bore mild steel galvanized iron tubes, "light grade" with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable including taking down old pipe complete all as directed
12S&F 80 mm dia bore mild steel galvanized iron tubes, "light grade" with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable including taking down old pipe complete all as directed
13Material & Laying, jointing and testing in replacement of LT under ground electric power cablecrossed linked polyethylene ( XLPE)insulated, galvanised steel strip or wire armoured,ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including taking out old LT UG cable complete all as specified and directed. Note :-Excavation, earth work, sand cushioning, protection bricks/ tiles/ block andpipe shall be measured and paid separately under appropriate items.
14All as per item No 13 above butof size 16 Sqmm 4 core
15All as per item No 13 above butof size 25 Sqmm 4 core
16All as per item No 13 above butof size 35 Sqmm 3.5 core
17All as per item No 13 abovebutof size 50 Sqmm 3.5 core
18All as per item No 13 above butof size 95 Sqmm 3.5 core
19All as per item No 13 above butof size 120 Sqmm 3.5 core
20All as per item No 13 above butof size 240 Sqmm 3.5 core
21M&L Earthing in replacementcomplete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased inand including 40 mm dia GI "lightgrade" pipe from upper end of earth plate upto equipments,20 dia bore GI pipe "light grade" as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate of SSR Part I completeall as specified and directed and testing on completion.
22Earthing in replacement complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including PCC cover and frame, PCC (1:3:6) type C-2 as in earthing pit, MS funnel with wire mesh GI pipe 20 mm dia light grade for watering and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 5 SSR Part-I.PCC chamber shall be constructed at least one metre away from the earth pit and GI pipe fittings for watering shall be provided up to chamber and cost of the same is deemed to be included in the rate of earthing.
23M&L for disconnecting the existing cable from Panel / Pole, preparing the end for jointing Supply and fix cable end termination heat shrinkable joint including sleeves suitable for LT XLPE cable of size 3.5 / 4 core 10 to 16 Sqmm
24All as per item No 23 abovebut size 25 to 50 Sqmm
25All as per item No 23 abovebut size 70 to 120 Sqmm
26All as per item No 23 abovebut size 150 to 185 Sqmm
27All as per item No 23 above but size 240 to 300 sqmm
28Supply & Fix in replacement twin core, 6 sqmm nominal cross sectional area multistrandedaluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy dutycable PVC insulatedand PVC sheathed complete all as specified.
29Supply & Fix in replacement twin core, 10 sqmm nominal cross sectional area multistrandedaluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy dutycable PVC insulatedand PVC sheathed complete all as specified.
30Supply & Fix connecting andtesting in replacementMCCB 63 Amp 4 pole 25 KA 415 volts 50 Hzthermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
31Supply & fix connecting andtestingin replacement MCCB 100 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
32Supply & fix connecting andtestingin replacement MCCB 125 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
33Supply & fix connecting andtestingin replacement MCCB 160 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
34Supply & fix connecting andtestingin replacement MCCB 200 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
35Supply & fix connecting andtestingin replacement MCCB 250 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
36Supply & fix connecting andtestingin replacement MCCB 400 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
37Supply & fix connecting andtestingin replacement MCCB 630 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceableMCCB complete all as directed.
38Supply and fix in replacement MCCB 125 Amp 4 pole 25 KA 415 volts 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed. Note : The cost of suitable size fastner / Nut bolts required at site for fixing of cubical is deemed to beincluded in the quoted rate by the contractor.
39Supply and fix in replacement MCB 20 Amp 2 pole 10 KA, 250 volts 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed. Note : The cost of suitable size fastner / Nut bolts required at site for fixing of cubical is deemed to beincluded in the quoted rate by the contractor.
40Supply drawing, connecting and testing in replacement3 core, 1.5 Sqmm PVC insulated and PVC round sheathed` copper conductor (flexibleindusturial cable, 1100 Volts conforming to IS 694 in steel tubular poles from Junction box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge.
41S&F in replacementwheather proof pole mountingPVC junction box, base and door of junction boxmade out of SMC having outside dimention333 x 233 x 120 mm, inside dimention300 x 200 x 105 mm, single door front openable provided withhinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelin insulatorincluding M&L for MCB SP10 Amp -1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable size FI clamp nut bolts and washer including embossing / painting of danger notice of size not less than 10 cm x 7.5 cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body Complete all as directed by Engr-in-Charge.
42Supply & fix in replacement GI brackets made of 40 mm nominal bore GI pipemedium grade of required length not less than 1.5 M long, mounting brackets made out of Mild steel FI 40 x 6 mm of required shape ( two Nos) duly fitted with Mild steel nuts, bolts and washers and painting with two coats of synthetic enamelled paint over one coat of red oxide primer and fixed to pole / walls etc complete all as specified & directed by Engr-in-Charge.
43M&L for 3.15 mm thick CRCA sheet cut to size bend to shape for replacement of door / side / compartment of LT panel of any descreption, including all fixing arramgement i.e. suitable size of hinge, nuts, bolts, washers, cutting and welding works etc, overall powder coated finish complete all as directed by Engr -in-charge.
44M&L for Preparation of old painted surfaces of LT steel tubular pole 9 mtrs long and applying one coat aluminium paint from bottom to top and painting up to 1.5 mtr height from top of PCC coping with synthetic enamel paint one coat in black and Yellow / white alternate strip including re writing pole numbering in 8 cm height with one coat synthetic enamel paint complete all as specified & directed byEngineer –in-Charge.
45M&L for Preparation of old painted surfaces of LT panel by scrapping, making good distrubed surfaces by applying putties on uneven surface to make it even and spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour complete all as specified and directed.
46Supply, installing, testing and commissioning in replacementfactory made , tested , CPRI approvedpowder coatedLT Panel board(Dimention of Cubical/enclosure not less than 1700mmx1200mmx500mm) ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HzAC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proofIP-54 class protection and outer shell made of of 3.15 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 50x50x6mm thick MS angle iron frame work, the cubical have bottom channel of size 75x40mm duly coated with zink metal coating,front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked,1100 volts grade of appropriate size ( but not less than 2.5 Sqmm)and comprising of the following:-
47(a) Incoming :- (i)MCCB 4 pole , 630Amps,50 Hz,415 Volts, 36 KA, with microprocessorrelease - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTsratio 800/5 A ,class 1, ISI marked -01 sets of three (iv)Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 1200 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators.
48(b) Outgoing (i)MCCB 4 pole ,200Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 05 Nos (ii) MCCB 4 pole ,100Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 02 Nos
49(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class "B", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
50All as per item No - 46above but comprising with following:- (a) Incoming :- (i)MCCB 4 pole , 200Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii)Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTsratio 200/5 A ,class 1, ISI marked -01 sets of three (iv)Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 400 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i)MCCB 4 pole , 63Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 06 Nos
51All as per item No46 above but comprising with following:- Size - 900x600x450 mm (a) Incoming :- (i)MCCB 4 pole , 250Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii)Change over switch - 200 Amps -01 Nos (ii)Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTsratio 200/5 A ,class 1, ISI marked -01 sets of three (iv)Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 100Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 03 Nos
52All as per item No46 above but comprising with following:- Size - 1200x800x500 mm (a) Incoming :- (i)MCCB 4 pole , 630Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii)Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTsratio 200/5 A ,class 1, ISI marked -01 sets of three (iv)Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 1200 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 250Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 03 Nos (ii) MCCB 4 pole , 100Amps,50 Hz,415 Volts, 25 KA thermal magnetic release- 01 Nos
53Supply and installed steel tubular swaged pole type 410 SP - 31 (9 mtr long) complete with MS base plate of size 300 x 300 x 6mm thick at bottom, welded at the centre with through hole of 14mm dia at a height of 300 mm above the coping finial cap and painted with two coats of aluminium paint over a coat of red oxide primer with writing number including excavation upto required depth and PCC type C-2 1:3:6 (using 40mm graded) at bottom and PCC type B-1 1:2:4 (20mm graded) for mass filling and pole coping (60x60x30cm) and rendering of coping with 5 mm thick in 1:3 cement mortar complete all as specified and directed.
54M&L out door type busbar panel board (Dimention of Cubical/enclosure not less than 600mmx450mmx450mm) made out of3.15 mm thick MS sheet and MS angle section 50x50x6 mm factory made suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- (a)FP, Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Incoming MCCB 400 Amps 36 KA, 415 Vots, 50 Hz, FP.– 1 No (c)LED Indicator lamp RYB - 01 set of three. (d) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class "B", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be such that it is of a height 45 cm above the nearest road level.
55Trimming and cutting of tree branches coming across 1100 Volt LT over head line clearing the line around 2 m single / both sides andand disposal of branchesfrom siteexeeding 50 m and not exceeding 250 m from site complete allas directed by Engr-in-Charge. Note : - (i)Length of span is approx 35 to 45 RM. (ii) Due care is to be given while trimming / cutting the tree branches that there should no damage to over head line conductor / pole.In case due to any negligence, damage is caused to be make good / renewal by the contractor from his own resources and nothing extra is admissible. (iii)All Safetytolabourer must be adhered by the contractor during trimming and cutting of tree branches.
56Dismetling and taking down old / unsv ACSR conductor any size from pole complete all as specified and directed.
57S&F ACSR conductor incl jointing with existing conductor and straining on LT pole and proper fastening to pin / shackle insulators with aluminium binding wires and required jumpering connection all as dercted. Note :- Size of aluminium conductor as per site requirement will be directed by Engineer-in-Charge.
58Dimentling and taking down old / unsv insulator of any type any size from pole / stay complete all as specified and directed.
59S&F pin type, porcelain, vitreous, brown, including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 100 mm height and 65 mm dia for 1100 volts grade all as specified and directed.
60S&F shackle type, porcelian vitreouswhite, brown or green insulator including galvanised mild steel straps, washers, insulators bolts ,washer and nuts of size 100 mm heightand 115 mm dia for 1100 Volts grade complete all as specified and directed.
61S&F Loop type insulator, porcelian vitreousbrown of size 65 x 90 mm and clearence hole 16 mm all as specified and directed.
62Restraining of overhead ACSR conductor of any size of 5 conductor on pole after disconnecting all jumpering connection & binding of insulators and redoing all jumpering connection and insulator binding with aluminium conductor providing required T&P all as specified and directed. Note:- 5 Run conductoe per sapn will be measured as Each span.
63Restraining of ACSR conductor of any size of 2 conductor on pole after disconnecting all jumpering connection & binding of insulators and redoing all jumpering connection and insulator binding with aluminium conductor providing required T&P all as specified and directed. Note:- 2 Run conductoe per sapn will be measured as Each span.
64S&F rigid PVC line spacer, suitable for 5 wire, made from high grade PVC material, distance between phase to phase 300 mm, suitable for use with 1100 volts grade including taking down unsv one all as specified and directed.
65Taking down old LT steel swage pole 9 mere long and shifting of LT pole 9 mtrfrom one place to another places of entier Cantt area, fixed the pole in location, including necessary excavation and earth work , PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C2 around poles and PCC 1:3:6 type C1 as in plinth block , disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting steel tubular poles exposed surafces with one coat Aluminium paint and painting 300 mm wide bands (3 bands/ straps with one coat synthetic enamel paint and 2 bands with Black bituminous paint) 30 cm interval and numbering of poles, painting embedded portion of poles with one coat of bituminous paint complete all as specified and as directed by Engineer-in-Charge.
66Supply & fix in repair Aluminium bus bars of 400 Amp capacity cut to size and fixed in existing panel, including drilling hole and all fixing arrangement and all connection.
67Dismantling of existing old damage PCC pole/ steel poleof any description complete all as specified and as directed by Engineer-in-Charge.
68Taking outLT UG aluminium conductor cable of size 16 Sqmm to 35 Sqmm 4/3.5 core 1100 Volt grade for fault checking and relaying same cable in same trenches including excavation, returning filling, taking out brick cable cover & sand cushning, relaying same cable cover and sand cushion complete all as specified & directed.( Straight through joint will be measured & paid seperatly.
69Taking outLT UG aluminium conductor cable of size 50 Sqmm to 70 Sqmm 3.5 core 1100 Volt grade for fault checking and relaying same cable in same trenches including excavation, returning filling, taking out brick cable cover & sand cushning, relaying same cable cover and sand cushion complete all as specified & directed.( Straight through joint will be measured & paid seperatly.
70S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 core 16 Sqmm XLPE armoured aluminium conductor cable.
71S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 core 25 to 50 Sqmm XLPE armoured aluminium conductor cable.
72S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 core 70 Sqmm XLPE armoured aluminium conductor cable.
73Supply and fix in repair Isolator 100 Amps 4 pole fixied in position all as specified & directed.
74Supply and fix in repair 10-12 LED bollard light fitting 60 cm long, having epoxy powder coated pressure die cast aluminium housing Light optic, high impact polycarbonate diffuser, colour temprature 5700K, CRi>70, THD<10% PF >.90surge protection 4 KV inbuilt, rated voltage and frequency 240 Volt, 50 Hz,aesthetic innovative design with uniformly lit diffuser at the upper portion acts a beacon of path guidance in a landsscape IP 65 environmental with PCC 1:3:6 as in foundation work nut, bolt and washer etc complete all as specified and directed by Engr in Charge.
75Supply and fix in repair 18-20 LED bollard light fitting 60 cm long, having epoxy powder coated pressure die cast aluminium housing Light optic, high impact polycarbonate diffuser, colour temprature 5700K, CRi>70, THD<10% PF >.90surge protection 4 KV inbuilt, rated voltage and frequency 240 Volt, 50 Hz,aesthetic innovative design with uniformly lit diffuser at the upper portion acts a beacon of path guidance in a landsscape IP 65 environmental with PCC 1:3:6 as in foundation work nut, bolt and washer etc complete all as specified and directed by Engr in Charge.
76Supply and fix in replacement of 45 W LED Street light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant, lens for better distribution and toughened glass fixed to housing withscrews, street lightshould haveIP 66 protectionand impact resistance ofIK 07, system lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at full load CRI> 70%, street light should have built in potted driver, THD, open circuit protection, over voltage protection, surge voltage protection, 10 KV surge protection divice, andprovided with company LOGO ingraved on housing of the Streetlight including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge. Note :-The contractor should take approval of techincal specification ofluminaries and driver from department before procurement .
77Supply and fix in replacement of 60 W LED Street light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant, lens for better distribution and toughened glass fixed to housing withscrews, street lightshould haveIP 66 protectionand impact resistance ofIK 07, system lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at full load CRI> 70%, street light should have built in potted driver, THD, open circuit protection, over voltage protection, surge voltage protection, 10 KV surge protection divice, andprovided with company LOGO ingraved on housing of the Streetlight including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge. Note :-The contractor should take approval of techincal specification ofluminaries and driver from department before procurement .
78Supply and fix in replacement of 90 W LED Street light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant, lens for better distribution and toughened glass fixed to housing withscrews, street lightshould haveIP 66 protectionand impact resistance ofIK 07, system lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at full load CRI> 70%, street light should have built in potted driver, THD, open circuit protection, over voltage protection, surge voltage protection, 10 KV surge protection divice, andprovided with company LOGO ingraved on housing of the Streetlight including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge. Note :-The contractor should take approval of techincal specification ofluminaries and driver from department before procurement .
79Supply and fixing in replacement of 120 W LED Flood light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant.IP lens for better distribution and toughened glass fixed to housing withscrews, street lightshould haveIP 66 protectionand impact resistance ofIK 07 , Lumen efficiency of LED not less than 110>_ lumen per wattsystem efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,Street light should have built in potted Driver THD, open circuit protection , over voltage protection , surge voltage protection 5KV in built & 10KV SPD ,andprovided with company LOGO ingraved on housing of the Streetlightcomplete including taking down of oldUNSV fittings all as specified and directed by Engr -in-Charge. Note :-The contractor should take approval of techincal specification ofluminaries and driver from department before procurement . .
80S&F in repair 40 watt LED Post top light fitting, energy saving, 240V, 50Hz AC, environmental friendly, aesthetically designed electronic constant current, IK07, having epoxy powder coated pressure die cast aluminium housing top cover spun aluminium sheet powder coated, front cover clear acrylic diffuser with indirect symmetrical light distributio, IP-65 luminaire with high power LED as light source, 5700K, PF >0.9, THD<10% and light efficiency 85> , CRI > 70, Surge protection 5KV, fixed over existing post, all as specified and directed.
81M&L for 15mm dia galvanised iron, light grade, ISI marked, complete with all fittings fixed to pole with fixing arrangement including clamps, nut and bolts of suitable size complete all as specified and directed
82Supply and errection inof 05 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987, Poles shall be provided with base plate of size 225 x 225 x 12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendationand one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps, Cat NO: HM-1107 P for pole and HM-SA 1 M for bracket. A triangular flat MS plat of 6 mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket, welding work shall be done 250 mm on bracket and 150 mm on pole"s cap including foundation in RCC work type (1:2:4) type B-1 as per pole manufacturer"s drawing and earth work all as per requirement complete all as
83Supply and errection inof 07 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987, poles shall be provided with base plate of size 225 x 225 x 12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendationand one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps, Cat NO: HM-1107 P for pole and HM-SA 1 M for bracket. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole"s cap including foundation in RCC work type (1:2:4) type B-1 as per pole manufacturer"s drawing and earth work all as per requirement complete all as
84S&F LED lamp 10 watt, CDL, B-22 cap, (Pin type), 230V, PF-0.95 (min) incl dismentling taking out unsv CFL.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail