Tender For Supply, Installation, Testing And Commissioning Of Cold Room At Ktdc-Hotel Samudra, Kovalam, Thiruvananthapuram-Kerala

Kerala Tourism Development Corporation-KTDC has published Tender For Supply, Installation, Testing And Commissioning Of Cold Room At Ktdc-Hotel Samudra, Kovalam. Submission Date for this Tender is 26-09-2023. Cold Storage Tenders in Thiruvananthapuram Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

39709631
Tender For Supply, Installation, Testing And Commissioning Of Cold Room At Ktdc-Hotel Samudra, Kovalam
Open Tender
Indian
Kerala
Thiruvananthapuram
26-09-2023

Tender Details

Supply, Installation, Testing And Commissioning Of Cold Room At Ktdc-Hotel Samudra, Kovalam

Key Value

Document Fees
INR 2950 /-
EMD
INR 37500.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:Supply, installation, testing and commissioning of coldroom at KTDC- Samudra, Kovalam
Sl. No. Item Description
1Cold room works
2Supply of Condensing & evaporating units suitable for the walk in cold room consisting of freezer room of size (2m x 4m x 2.4m) for the storage of meat at temperature of –20 to –18 deg C and chiller room of size (2m x 4m x 2.4m) for the of vegetables at temp of +2 to +8 degree C .The condensing unit is made up of self supporting steel frame with semi hermetic compressor and air cooled compressor coil, fan motor, electrical and microprocessor controls etc and complete mounted at suitable position including refrigerant piping and all connections as required of minimum 6 meters.The Housing of the evaporator unit is made up of high quality 304a stainless steel specially designed copper coil, filter, expansion device self lubricated axial fans and consist with all safety controls and power saving flow controls with automatic and electrical de frost controls.
3Machine for Freezer room (2m x 4m x 2.40m) of refrigeration capacity 10000 BTU/hr
4Machine for Chiller room (2m x 4m x 2.40m) of refrigeration capacity 10000 BTU/hr
5The Supplier should provide a centralized pre wired electrical control panel for feeding electrical supply to the compressors having individual suitable rating contactor with overload and short circuit protection, single phasing preventer, LED indicators. The panel should have necessary cable entry/ leaving provisions, necessary isolation TP/SP MCBs and ISOLATORS etc complete as required for prevailing standards. KTDC will provide three phase/single supply with in 3m of each cold room and necessary cabling to panel to cold rooms must done by the supplier.The unit is fitted with a micro-processor based digital electronic temperature controller cum indicator for easy readability along with audio-visual alarm system. The controller should have the facility to set temperature and humidity value and also the safety limits for temperature and humidity. An audible alarm should be provided in the event of actual values exceeding the set limits,In the event of failure of the main mechanical refrigeration system or dehumidification device, the switch over to standby system should be automatic with indication of failure of main system.In the event of power failure,module should have delayed start in a sequesnce so that power lines are not loaded.
6The supplier should do the necessary internal electrical wiring confirming to relavant standards as required at site including providing vapour proof type light fittings suiting to all temperature ranges with in the cold room with control on outside.
7Supply of pre fabricated modular 100 mm PUF insulated sand witched (SS304 on both side) panels for freezer room with corner panels and cam lock. The SS sheet shall have o.5mm thickness
8Supply of pre fabricated modular 60 mm PUF insulated sand witched (SS304 on both side) panels for chillerroom with corner panels and cam lock. The SS sheet shall have 0.5mm thickness.
9Supply of 50mm thick PUF slab with bitumen sheet as vapour barrier for floor insulation for chiller room
10Supply of 100mm thick PUF slab with bitumen sheet as vapor barrier for floor insulation for freezer room
11Supply of flush type self closing swing 100 mm PUF insulated door (900 x 2000 mm) including door frame of 60 mm thick with SS laminations on bothsides with anti condensation door heater, pad lock, posi seal closure, human safety release knob and etc complete as required at site
12Supply of flush type self closing swing 60 mm PUF insulated door (900 x 2000 mm) including door frame of 60 mm thick with SS laminations on bothside with anti condensation door heater, pad lock, posi seal closure, human safety release knob and etc complete as required at site.
13Installation testing and commissioning of the cold room including panel erection, flooring, flashings, mounting of indoor & outdoor units, Cu piping, wiring, drain piping, pressure testing, vaccumising, gas charging, testing & commissioning and other electrical hook up, plumbing and drain hook up connection etc. complete in all respect with all required materials etc complete as required at site.
14Supply and providing additional Copper Refrigerant piping ( for freezer room) and fitting using brazed joints, complete with required thickness tubular elastomeric nitrile rubber EPDM insulation and finished with glass cloth (microban) . The refrigerant piping shall be adequately sized to take care of the length of piping. Complete piping workmanship to be carried out as per recommended practice. The piping to be vacuum tested and leaktested. Scope includes all refrigerant pipes shall be properly supported and anchored to the building structure using steel hangers, anchors, brackets and supports etc which shall be fixed to the building structure by means of inserts or expansion shields of adequate size and number.
15Supply and providing additional Copper Refrigerant piping (For chiller room)and fitting using brazed joints, complete with 19 mm thick tubular elastomeric nitrile rubber EPDM insulation and finished with glass cloth (microban) . The refrigerant piping shall be adequately sized to take care of the length of piping. Complete piping workmanship to be carried out as per recommended practice. The piping to be vacuum tested and leaktested. Scope includes all refrigerant pipes shall be properly supported and anchored to the building structure using steel hangers, anchors, brackets and supports etc which shall be fixed to the building structure by means of inserts or expansion shields of adequate size and number.
16Supply and providing hooter and alarm for freezer room for the safety purpose
17Supply and providing PVC strip curtain freezer garde for freezer room .
18Supply of Storage racks suitable for the cold room for storing Vegetables/ Meat as required as per standards made out of food grade stainless steel (SS304) sheets angles , channels and perforated plates of 1.25 mm thickness.
19Electrical works
20Supply and providing 25 A DP MCB isolator of good quality and reputed make in an enclosure
21Supply and providing 32 A Four pole MCB isolator of good quality and reputed make in a suitable enclosure.
22Civil works
23Kota stone slab flooring over 20 mm ( average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1:4 (1 cement : 4 coarse sand)25 mm thick
24Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 )1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)