Tender For Items Of Work A) LIFT & ESCALATOR SITC of Electric Traction Passenger cum Stretcher Lift with · Doors type :- COPO/TOPO Doors with frame made from SS 441 grade solid (non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory).· Lift car enclosure made from SS 441 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge.· COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. · LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings. Lift controller of simplex full collective based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. ,various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information for minimum 30 latest faults, with real-time clock management and handheld keypad with LCD screen for view and setting of parameters, The control panel duly wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. · ARD complete with necessary SMF VRLA batteries.· Fireman controller having fireman switch at fire Landing. · CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min. 20 FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge.· Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength.· Other mechanical parts such as T section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.· Minor civil work such as alteration work if any necessary for erection of landing door frames and its accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.· General: - Job includes entire procedure of obtaining all necessary erection permissions & License to Work the Lift from Electrical Inspector(Lifts) with submission to the Engineer In Charge.· The above rate includes Fully Comprehensive AMC for one year from the date of commissioning. SITC of Electric Traction Passenger cum Stretcher Lift with · Rated capacity :- 13 Passenger/ 884Kg · Floors :- B+G+21 floor (23 Stops/23 Landings) · Travel :- 84.5mtrs · Location of Lift Machine:- MR/MRL· Rated speed :- 2.5 mps VS· Car/Landing door clear opening of 1100/1200 mm wide x 2000 mm high· Clear Car size of 2200mm wide x 2500mm deep x 2250mm high · Lift shaft available having clear size of 2675 mm wide x 1725 mm deep, ......mm Pit depth - 4950 mm Overhead. Job b) SITC of Electric Traction Passenger cum Stretcher Lift with · Rated capacity :- 13 Passenger/ 884Kg · Floors :- B+G+16 floor (18 Stops/18 Landings) · Travel :- 76.5mtrs · Location of Lift Machine:- MR/MRL· Rated speed :- 2.5mps VS· Car/Landing door clear opening of 1100/1200 mm wide x 2000 mm high· Clear Car size of 2200mm wide x 2500mm deep x 2250mm high · Lift shaft available having clear size of 2625 mm wide x 1725 m deep, 4950 mm Pit depth, 4950 mm Overhead. Job c) SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with · Rated capacity :- 13 Passenger/ 884Kg · Floors :- B+G+1 floor (4 Stops/4 Landings) · Travel :- 9.5mtrs · Location of Lift Machine:- MR/MRL· Rated speed :- 1.5mps VS· Car/Landing door clear opening of 1100/1200 mm wide x 2000 mm high· Clear Car size of 2200mm wide x 2500mm deep x 2250mm high · Lift shaft available having clear size of 2500 mm wide x 1700 mm deep, 4550 mm Pit depth, ………mm Overhead. Job 2 Supply, Installation, Testing & Commissioning of Escalator 6.5 m rise fully SS finish with inclination 30/ 35 degrees, step width of 600 to 1000 mm, and speed of 0.5 to 0.65 m/s, self-supporting handrails centred on glass panels. Only government officers will be allowed for material inspection prior to approval. Test report for inspected material will be provided. One-year product warranty can be extended as per requirement. Public flow of 6000 to 8000 passengers per hour. 18KN/Step load carrying capacity. B) MECHANICAL STACK PARKING 1 Supply, Installation, Testing & Commissioning of 2 wheeler stack parkingOperation : Hold to Run Spring Operated Key Switch OperationSafety: Electromagnetic Locks, Emergency Stop Switch1. Hydraulic Stack Park 2. Independent Single Stack Park 1. Lockers on Both the sides in a descending direction2. Emergency Stop Switch.3. Hold to Run Spring Operated Key Switch4. Centre support holding the side columns and side beams with 3U combination.5. IP-55 Protection for Electrical Material.6. Drive through protection cover over Hydraulic Pipe and Electrical Cables.7. Non Return Valve8. Galvanised Protection Cover for Balancing Chain and Electro Magnet.9. Special profile for entry Plate for better grip of tyres while driving over the platform.10. Power Pack with Submerged Motor and self-company make control panel.11. Hydraulic cylinder – Two Stage single acting, single stroke cylinder12.safty device- Solenoid Operated Mechanical Lock Arrangement13.Maximum load capacity of the system – 500 Kg14. Connect Power for power pack in Amps - 1.1 KW Each 2 Supply, Installation, Testing & Commissioning Of 4 Wheeler Stack ParkingOperation: Hold To Run Spring Operated Key Switch OperationSafety: Lockers On Every 100 Mm, Emergency Stop Switch1. Lockers On Both The Sides In A Descending Direction2. Emergency Stop Switch.3. Hold To Run Spring Operated Key Switch4. Centre Support Holding The Side Columns And Side Beams With 3U Combination.5. Ip-55 Protection For Electrical Material.6. Drive Through Protection Cover Over Hydraulic Pipe And Electrical Cables.7. Non-Return Valve8. Galvanised Protection Cover For Balancing Chain And Electro Magnet.9. Special Profile For Entry Plate For Better Grip Of Tyres While Driving Over The Platform.10. Power Pack With Submerged Motor. 11.Model - Hydraulic Stack 210 12. Quantity 1 System – 2/3 Car13. Length 5000 Mm 14. Standard Width 2000 Mm & Standard Height 2000 Mm 15. Standard Weight 2000 Kg 16. Vertical Drive Unit Type Hydraulic Cylinder & Chain Type Motor 3 Hp / 2.2 Kw, 415Vac, 50Hz Speed 4 M/ Min Drive Hydraulic Cylinder & Chain Type 17. Power Source Main Ac 415V, 3 Ph, 50 Hz Lighting Ac 220V, 1 Ph, 50 Hz 18. Operating Box 3 Way Encloser Box With Up, Down & Key Switch19. Control Relay Logic20. Safety Devices Key Selector Switch To Stop The System Mechanical Locking Arrangment21. Finishing Powder Coated C) SWIMMING POOL 1 SITC of Magiline Swimming Pool - Liner Filter Job16.15m x 6.65m x 1.8m (depth)for this swimming pool filter Specification as bellow-- Pipless filtration unit NFX 30, Discharge 30 Cum/Hr, Boosting for automatic cleaning robot at 2 Cum/Hr & Suction 32 Cum/Hr.- 30,000 lit per Hour Capacity- Avg time of running 2.5 to 3 Hours- Motor Capacity 2 HPPool Materials, included:- PVC Liner – Plain Blue (tiles not required)- Filtration Units- Pool Wall Lights- Programming Electric Box- Maintenance Accessories Kit- Start-up Chemical Products- 3 Steps SS Ladder D) FIRE FIGHTING 1 Supplying, installation, testing and commissioning of main fire pump (MFP/EP) suitable for water discharge of 2850 LPM at 110 m Head and 165 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 112 kW or of suitable kW capacity for manual/automatic operation and consisting of following:(a) Horizontal type, single/multi stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/MSC/EP. Rate shall include DLP of 2 years against Commissioning of the project. Each 2 Supplying, installation, testing and commissioning of Jockey fire pump (JP) suitable for water discharge of 180 LPM at 110 m Head and 165 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 15 kW or of suitable kW capacity for manual/automatic operation and consisting of following :(a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520.(b) Suitable kW Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, conforming to IS-325.(c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003)complete, as per specification no. FF-MFP/JP. Rate shall include DLP of 2 years against Commissioning of the project. Each 3 Supply, Installation , testing & commissioning of Diesel engine driven main pump of horizontal centrifugal Multi stage pump suitable for water discharge of 2850 LPM at 110 m Head and 165 m head confirming to IS 5120-1977. The pump shall be coupled to suitable HP diesel engine heat Exchanger type with speed of 1800 /1500 RPM and complete set shall be mounted on commom base frame . Batteries & battery leads with stand, diesel tank 500 ltr with stand & HE piping, fuel piping with valves. coupling guard, silencer, 24 V starting arrangement, oil level indicator & oil coolant and other standard accessories, and foundation bolts , etc. complete. The heat insulation with al cladding for silencer line up to 60 mtr included in the installation The pump shall be capable of giving not less than 150% discharge at a head not less than 65% of the rated head. The Shut off head should not be more than 120% of rated head. Rate shall include DLP of 2 years against Commissioning of the project. Each 4 Supplying and erecting G.I. pipe ‘C’ class ERW 250 mm dia with necessary fittings complete as per specification no. FF-PP Mtr 5 Supplying and erecting G.I. pipe ‘C’ class ERW 300 mm dia with necessary fittings complete as per specification no. FF-PP Mtr 6 Supplying and erecting 250 mm dia. cast iron double flange rising stem sluice valve complete with PN25 pressure rating, as per specification no. FF-VL/SV Nos 7 Supplying and erecting 300 mm dia. cast iron double flange rising stem sluice valve complete with PN25 pressure rating, as per specification no. FF-VL/SV 8 SITC of ABC Type extinguisher 6Kgs. IS 15683 Each 9 SITC at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold. Cost shall be inclusive of providing MS stand duly painted over a coat of primer. Bucket shall be fabricated with stand to install 4 nos of buckets. SET 10 Providing and fixing forged brass ball valve with SS ball suitable for test pressure of not less than 30 kg / sq.cm of the following size : 25 NB Each 11 Providing & Fixing of Installation Control Valve with turbine type automatic Alarm Gong to be connected with control valve, drain & test valve and all other necessary components as per manufacturers specifications complete as required. (Consider 2 nos . isolation valve for each alarm gong) 150 NB size Each 12 Supply and installation of Flexible braided hose pipe of 25mm dia with both end socket for fixing the sprinkler to ranger.Consider length of flexible piece as per below. Flexible connectors should be supported with separate expansion bolts & not on the False ceiling frame work. The pressure carrying capacity of hose shall be 12 bar. The supporting arrangement to get approved from Ceiling Vendor prior to execution. - 1500 mm long Each 13 Supply, installation, testing & commissioning of EN-54 Certified Digital EVAC PA controller with built in audio message generator (multi message), capable of adding 12 zones in the system and expandable upto 400 zones with 14x 4 Audio matrix withAudio matrix with full DSP functionality. 8 audio inputs, 4 audio outputs, 4 channel output matrix. amplifier redundany, 4 x 100V audio inputs and built in 8 zone speaker line outputs. 8000 fault, warning and event conditions log. Built in message manager for 100 emergency/business calls up to 85 minutes. Should be able to send 2 different pre-recorded messages simultaneously (message should be in 2 languages English & Hindi). Shall be able to handle up to 2000Watt load, 10 routers, 6 call stations, 128 speaker zones. The controller should integrates multiple functions such as audio storage, playback, zone control, audio monitoring, scheduled broadcast and fault diagnosis, audio playing, zone control, fault monitoring, log recording, volume control and amplifier switchover etc. complete with cords, connectors, power supply & required accessories. Note- System should operates in two channel operation & fulfill the FAS cause & effect matrix requirements. Each 14 Supplying, erecting, testing and commissioning 1000 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF-PA/AFR Each 15 NOVEC 1230 TUBE BASED GAS SUPPRESSION SYSTEM - MAIN ELECTRICAL PANELSSITC of FK 5-1-12 (Fluoroketone) Clean Agent Direct Low Pressure (DLP) Pre-Engineered Panel Gas Suppression System, Gas shall be Zero ODP and GWP less than 1., Agent shall be UL Listed, the system shall be designed accordance to NFPA 2001 (Latest Edition), The Clean Agent is stored PESO approved Cylinder as compressed liquid, super-pressurized with Dry Nitrogen to 13.5 bar to 16 bar. Cylinder shall be equipped with DLP Valve, Pressure Switch(CE/UL marked) and Pressure Gauge need to be integrated on DLP Valve itself to monitor the Cylinder Pressure. UL Listed Detection Tube shall be manufactured from specially processed polymer material to achieve the desired heat detection and delivery characteristics., and shall cover and routed to each compartment of panel, End Line Adapter to be placed at the termination point of detection tube for charging the Nitrogen., Pressure Switch should be integrated with Master Control Unit for Audio Visual Alarm in the even of Fire & System Discharge. Master Control Unit should have provision to Interface system with main control fire alarm system and BMS. CLEAN AGENT TOTAL FLOODING SYSTEM - SERVER ROOMS1. SITC of Clean Agent Novec Gas /NAF 227 Gas Suppression System consisting of seamless cylinders of 80,120 & 140 litre each and each filled with Clean Agent Novec Gas / NAF 227 Gas pressurised to 25 bar pressure complete with common pipe manifold of seamless pipe, pilot cyinder, Electric Actuator, Relief Valve, Pressure Guages, high pressure rubber hose, high velocity nozzles, brackets, floor mounting assembly consisting of MS angle boxing. Contractor to provide all necessary certificates of approval of cylinder from CCE, and certificate of filling to required pressure and weight.2. SITC of complete with socketweld fittings and supports ASTM Schedule 80 seamless pipes.3. SITC Addressable Fire Alarm cum Gas Release panel complete with cross zoning and 4 zone Gas discharge cards with complete with Power Card, 15 Ah SMF Battery, digital ammeter, each gas zone complete with Isolate, Abort switch, Discharge switch, Timer Knob, Evacuation alert, gas discharge and complete with relay for actuation of gas solenoid valve. Job 17 CLEAN AGENT SUPPRESSION SYSTEM - KITCHEN AREA1. SITC, of Commercial Kitchen System - Light Weight Stainless Steel Body F/K Agent (Wetchemical) required Capacity, Filled with F/K Agent, Electrical Actuated Valve assembly And Necessary Fitting, Cylinder Brackets with Screw & Cabinet, Stainless Steel Fitting Joints, Elbow, reducers etc, SS Piping and Fiting, nozzles with required velocity, sensor cable, Manual Release, Kitchen Suppression Panel, 2 Zone, Hooter Cum Strobe, Abort Switch, Gas Shut Off Valve (Size 1), with fitings all pipe etc, cables and accessories include all other requuired accessories E ELECTRICAL HT ITEMS 1 SITC of 22KV GIS Breaker at 220/22KV Hinjewadi Ph-1 S/S as per MSETCL specification Rated voltage 24Kv, Rated power frequency withstand voltage 50Hz, Rated lightning impulse withstand voltage 125KV, Rated busbar current 1600Amp, Rated peak withstand current 124 kA, Rated short-time current 3 Sec, Internal Arc Classification 40kA 1Sec. Nos 2 SITC of 22 KV Heat shrink Indoor Touch Proof Termination (AJ)kit for XLPE 3 C X 400 sq.mm. Kit 3 SITC of 22KV Heat shrink Straight Through Joint, (AJ) kit for XLPE 3 C x 400 sq.mm. Kit 4 SITC of XLPE 22KV HT, 3C,XLPE Cable 400 sq.mm.cable (Round Armourd) with cable Route marker, cable laid over RCC Cable Trench / Directly Buried / Cable Tray or as per MSEDCL approved Cable Laying arrangement From 220/22KV EHV sub-station. Hinjewadi, Two Feeders with three run cable Mtr 5 SITC of Advance Maintenance Free Earthing System consisting of 80 mm Diameter X 3 Meter Long, made from low carbon steel pipe, galvanised with 2 Nos of stainless steel Nut & Bolt, Suitable for Lug size 50 mm X 6 mm X 100 mm, and cross-section area 616 mm2, along with 50 Kgs. of Premium Ground Improving compound duly modified premium quality for excellent electrical conductivity of approved make. During Earth pit Boring/drilling, If the water logging or water seepage in the earth pit (due to high Ground water level). However, the earth pit gets moist / Sludgy. In such cases, Use Carbon-based Chemical Compounds. Nos 6 Excavation Permission Charges for 22KV HT, 3C,XLPE Cable 400 sq.mm.cable (Round Armourd) with cable Route marker, From 220/22KV EHV sub-station. Hinjewadi, Two Feeders with three run cable Including obtaining necessary road cutting permission from PCMC/ PMRDA / MIDC Mtr 7 SITC of 22kV Indoor VCB panel with incomer feeder for 22 kv 1600 amps 25kA/1 SEC Vaccum circuit breker with C& R panel with O/C + E/F realy, spring charging motor 230V AC, Draw OUT & isolation horizontal, CT Ratio 400/5Amp, Protection relay triple pole IDMLT relay with RS-485COMM. PORT with trip circuit supervision 3 O / C + 1 E / F with high set O / C setting : - 20 % - 200 % OF 5A., E / F setting: - 10 % - 40% OF 5A, with high set for both O/C & E/F AUX. Vtg -110V DC, TYPE :- REJ601/P154 or as per MSEDCL/MSETCL approval spec. Nos 8 SITC of 22kV Indoor VCB panel Bus-Coupler for 22 kv 1600 amps 25kA/1 SEC Vaccum circuit breker with C& R panel with O/C + E/F realy, spring charging motor 230V AC, Draw OUT & isolation horizontal, CT Ratio 400/5Amp, Protection relay triple pole IDMLT relay with RS-485COMM. PORT with trip circuit supervision 3 O / C + 1 E / F with high set O / C setting : - 20 % - 200 % OF 5A., E / F setting: - 10 % - 40% OF 5A, with high set for both O/C & E/F AUX. Vtg -110V DC, TYPE :- REJ601/P154 or as per MSEDCL /MSETCL approval spec. Nos 9 SITC of Outgoing feeder with differential protection relay with indoor Panel 22kV I,1250Amp, 26.3 KA, Vaccume circuit breaker with C & R Panel with differential protection relay,tripping & closing coil 110V DC, spring charging motor 230V AC.draw OUT & Isolation horizontal Aux contact 4 NO + 4 NC, Protection relay triple pole IDMLT relay with RS-485COMM. PORT with trip circuit supervision 3 O / C + 1 E / F with high set O / C setting : - 20 % - 200 % OF 5A., E / F setting: - 10 % - 40% OF 5A, with high set for both O/C & E/F AUX. Vtg -110V DC, TYPE :- REJ601/P154 or as per MSEDCL/MSETCL approval spec. Nos 10 SITC of 22 KV Heat shrink Indoor Touch Proof Termination (AJ)kit for XLPE 3 C X 300 sq.mm. Kit 11 SITC of 22/0.433Kv 160 Amp Switch Fuse Unit (SFU) of the following rating including necessary accessories like Enclosure, Fuse base ,Fuse links etc. and requirement of the item with the Supply Authority (MSEDCL) For station transformer protection 12 SITC of 22 KV H.T. metering cubical (Compact Outdoor Type) Licensee approved fabricated with 2mm.(14 SWG) M.S.sheets with supporting angle and channel, painted with powder coating or epoxy paint shade light grey, copper bus bar electronic security lock and mechanical lock, with counter meter for measuring no of times the opening of doors, top side cover ( C.T.P.T COVER) interlock with meter doors, epoxy coated 3 nos C.T having required ratio between 5/5A to 300/5A burden 10 VA class 0.2 epoxy terminal block suitable for provided tri vector meter, and provision for incoming and outgoing cables etc complete duly tested by Licensee and with necessary Test Certificates and erected on the provided plinth. (Ref SLD A+B Metering kiosk section) Nos 13 SITC of Outgoing feeder with differential protection relay with INDOOR Panel 22kV I,1250Amp, 26.3 KA, Vaccume circuit breaker with C & R Panel with differential protection relay as per MSEDCL/MSETCL Approved specs( 1 IN 1OUT) Nos 14 SITC of Outgoing feeder with differential protection relay with INDOOR Panel 22kV I,1250Amp, 26.3 KA, Vaccume circuit breaker with C & R Panel with differential protection relay as per MSEDCL/MSETCL Approved specs( 1 IN 5OUT) F) TRANSFORMER 1 SITC of 3 phase, 22/0.433 kV, 50 Hz., 2500 kVA, 22/0.415 KV Oil( Easter) Type Transformer with Nitrogen filled and naturally cooled outdoor type, Copper wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45℃ by thermometer in oil and 50℃ by the resistance method in winding at full load rating, using type A winding insulation (kraft paper), with HV tapping (with on load tap changer) on load +5 to -15 in steps of 2.5%, with standard accessories complete with test certificate with losses below 2930 Watts at 50% load, 8085 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL. As per MSEDCL Approval G) ELECTRICAL LT/HT PANELS & SYSTEM 1 SITC of PCC panel (Refer SLD Dwg Main PCC Panel Block A+B ) Busbar: 6300A, 4 pole, 50KA Aluminium bus bars with colour coded heat shrinkable insulating sleeves. Incomer: 2500A, 4 Pole MCCB, 50KA - 10 Nos. protection and measurement as per specification.Metering :One set of incomer Phase indicating lights, shall be protected by 2 amps MCB’s. 1 Nos. with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) Nos 2 SITC of Floor meter panel with 630A ATS , Duel source meter & 630Amp MCCB R458T Compatible to BMS at Electrical shaft (Refer SLD Floor meter panel)with Ethernet module with RS485 for ATyS(MODBUS gateway compatible for BMS System) (RS485 Msdbus communication for ATyS p) Nos 3 Supplying, erecting, testing and commissioning Isolator panel with 4000Amp FP ACB fabricated with 2mm.(14 SWG) M.S.sheets with supporting angle and channel, painted with powder coating or epoxy paint shade light grey, Alu bus bar size in electrical shaft (Refer SLD End feed boxl)with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) Nos 4 SITC of 200 KVAR RTPFC panel with INCOMER:500A,TP MCCB 36 KA WITH SPREADER, EX ROH, AND AUXILIARY BLOCK WITH LSIG , INDICATION LAMP R,YB ,ON, CURRENT TRANSFORMER 1600/5A , 12TAGE APFC RELAY 230V, 15 KVAR X 2 , 10 KVAR X 1 ,5 KVAR X 2 , 25 KVAR X 1 FIXED TYPE ,AL BUSBAR 60 X = 1500Amp, with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) Nos 5 SITC of 100 KVAR RTPFC panel with INCOMER:250A,TP MCCB 36 KA WITH SPREADER, EX ROH, AND AUXILIARY BLOCK WITH LSIG , INDICATION LAMP R,YB ,ON, CURRENT TRANSFORMER 1600/5A , 10TAGE APFC RELAY 230V, 25 KVAR X 2 ,15 KVAR X 1, 10 KVAR X 2 ,5 KVAR X 2,AL BUSBAR 60 X = 1500Amp, with Ethernet module with RS485 for ATyS (MODBUS gateway ) Nos 6 SITC of 22kV Indoor VCB panel with incomer feeder for 22 kv 1600 amps 26.3 KA Vaccum circuit breker with C& R panel with O/C + E/F realy as per MSEDCL approval spec. ( 1 IN 2OUT) Nos 7 SITC of Outgoing feeder with differential protection relay with INDOOR Panel 22kV I,1250Amp, 26.3 KA, Vaccume circuit breaker with C & R Panel with differential protection relay as per MSEDCL Approved specs( 1 IN 2OUT) Nos 8 SITC of PCC Panel for PMPML (Ref SLD PCC Panel for PMPL) Panel shall be Powder Coated Fabrication, BODY 2 MM ,DOOR & load bearing 2MM with BASE MOUNTING.INDOOR TYPE .COLOUR SIMENS GREY RL7032 . 7 TANK PROCESS .INCOMING ACB 4000 A 4P 50 KA WITH MICROPROCESSOR RELEASE LSIG WITH BODBUS COMMUNICATION MCCB 125A TPP 36KA FOR SPD AL BUSBAR 2500 160 X 12 = CURRENT DENSITY with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) Nos 9 SITC of Battery charging Distribution Panel unit (Ref SLD PMPL battery charging Distribution Panel 1-2) Busbar: 4000A, 4 pole, 50KA Aluminium bus bars with colour-coded heat shrinkable insulating sleeves. Incomer: 4000A, 4 Pole ACB, Outgoing: 400A MCCB 14 Nos &630A MCCB with ATS-1 Nos. protection and measurement as per specification.Metering:One set of incomer Phase indicating lights, shall be protected by 2 amps MCB’s. 1 Nos with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) Nos 10 SITC of single phase, 240V, Common Service panel up to the max load of 140kW, powder coated CRCA 14 SWG sheet, outdoor type, having IP54,IK10 protection, With incomer 320Amp 4FPMCCB, outgoing - 63Amp 4 pole MCB with MFM, indicator lamps, control wiring, metering device, etc. for automatic operation & overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) 11 SITC of single phase, 240V, Common Service panel up to the max load of 378kW, powder coated CRCA 14 SWG sheet, outdoor type, having IP54,IK10 protection, With incomer 800Amp 4FPMCCB, outgoing - 63Amp 4 pole MCB with MFM, indicator lamps, control wiring, metering device, etc. for automatic operation & overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) H) DG SET, SYNCHRONISING PANEL & ETC. 1 1600 KW / 2000 KVA, Diesel Generating Set Prime rated comprising of: “Cummins” Model QSK60-G4, Radiator Cooled, Diesel engine developing 2319 BHP at 1500 RPM, complete with standard accessories. coupled to “Stamford” Alternator rated at 1600 KW / 2000 KVA at 415V, mounted on Channel Iron Base Frame complete and 02 no 12 V Batteries.controller PC3.3 With Fuel Tank 990 Ltrs capacity (supplied loose, located outside canopy)Standard Alternator is Class H to temp rise limited to H @40Deg C ambient.Factory testing as per PL std QAP for 3Hrs.With Acoustic Enclosure With Alternator mounted Isolator Panel with Manually fix type ACB as per Powerica standard design.(Breaker make – L&T/ Schneider/Reputed) with Including DG Fuel System ,DG Exhaust System including with all necessary Stack, heat insulation with required density and alu cladding as per norms approx 90mtr,Piping etc. required accessories Job 2 SITC of AMF cum Synchronising Panel for 5x2000KVA DG Set as per Powerica standard design as per IS8623. Incomer ACB 3200A, 3P, 50KA, O/L, S/C Release – 5Nos KWH Meter -5Nos EF Relay -5Nos Load Manager Conserv EM6400-5Nos Battery Charger SMPS based ENKO make -5Nos Buscoupler ACB 6300A, 3P, 50KA, O/L, S/C Release – 1No PLC for LDSS Allenbradly make -1no Indoor type Panel IP52 Busbar Aluminium 6000A TPN 50KA Breaker Make-Schneider NW /L&T U Power Protection & safties in DG controller shall not be duplicated in Panel. Common outgoing breaker not offered/ not under Powerica scope.with Ethernet module with RS485 for ATyS (MODBUS gateway compatible for BMS System) Nos 3 SITC of HSD Transfer Gear Pumps capable of delivering 250LPH diesel at a head of 15m. Pump is coupled with 3 HP, 3 phase, 415V 50Hz flame proof motor. Pump motor set mounted on common base frame. Including M.S. class ‘B’ (heavy duty) pipes, including fittings like bends and required all necessary accessories ( FOR SUPPLY LINE) Nos 4 SITC of HSD Transfer Gear Pumps capable of delivering 110LPH diesel at a head of 10m. Pump is coupled with 1.5 HP, 3 phase, 415V 50Hz flame proof motor. Pump motor set mounted on common base frame.including fittings like bends and required all necessary accessories ( This is to transfer overflowed diesel back to underground tank.) Nos 5 PESO Approval for 30 KL UG Tank which includes, obtaining required local NOCs, approvals from all local statutory bodies to receive FINAL PESO approval. ( Statutory fees to be borned by customer, also the required documents to be submit by customer as and when required to obtained the PESO Aprroval I) BUSTRUNKING & ACCESSORIES 1 Providing & erecting hot dipped galvanised for Ladder type Cable tray with cover manufactured from 14 SWG (2 mm thick) GI sheet of 1500 mm width & 75 mm height complete with necessary hardware Mtr 2 Supply of make 4000A,(SBA 230N2) 4P, 415V Sandwich Aluminium Bustrunking with Suitable external Alu earthing Straight Length – Indoor ( IP 55 ) Mtr 3 Supply of 3200A,(SBA 175N2) 4P, 415V Sandwich Aluminium Bustrunking with 2 runs of Suitable external Alu earthing Indoor (IP 55 ) Mtr 4 Supply of 2000A,(SBA 175N2) 4P, 415V Sandwich Aluminium Bustrunking with 2 runs of Suitable external Alu earthing Indoor (IP 55 ) Mtr 5 Supply of 4000A,(SBA 230N2) 4P, 415V Sandwich Aluminium Bustrunking with Suitable external Alu earthing Straight Length – Indoor ( IP 66 ) Mtr 6 Supply & Installation of Adaptor Box for Trasformer/ Panel end for Aluminium bustrunking Nos 7 Supply & Installation of 3200A Phase Crossover for Aluminium bustrunking Nos 8 Supply & Installation of 4000A,(SBA 175N2) 4P, 415V Flanged End for Aluminium bustrunking Nos 9 Supply & Installation of 3200A,(SBA 175N2) 4P, 415V Flanged End for Aluminium bustrunking Nos 10 Supply & Installation of 2000A,(SBA 175N2) 4P, 415V Flanged End for Aluminium bustrunking Nos 11 Supply & Installation of Rubber Bellow for Aluminium bustrunking Nos 12 Supply & Installation of Flexible link for Aluminium bustrunking Nos 13 Supply & Installation of 4000A Vertical Elbow for Aluminium bustrunking Nos 14 Supply & Installation of 3200A Vertical Elbow for Aluminium bustrunking Nos 15 Supply & Installation of 2000A Vertical Elbow for Aluminium bustrunking Nos 16 Supply & Installation of End cover for Aluminium bustrunking Nos 17 Supply & Installation of End Feed Box with isolator MCCB for Aluminium bustrunking Nos 18 Supply & Installation of 630Amp Tap Off Box for Aluminium bustrunking J) EV CHARGING 1 SITC of 25 nos. 160 KW DC EV chargers (50 nos. PMPML buses. ) Double gun charger - (Rated Power:- 160kW/ Input voltage:- 415V AC/ Electrical Protection:- O/C, S/C, SPD, Isolation, EF, /User Authorization:- QR Code/ Communication Protocol:- OCPP v1.6 J.) Nos 2 SITC of 600 nos. 3.3 KW AC 2-wheeler charging points charger (Rated Output Current:- 16Amp, Input voltage:-220V, Electrical Protection:- Over Current, Short Circuit, Isolation, User Authorization:- QR Code, Network Connectivity:- GSM/ GPRS, Place of Installation:- Indoor and Outdoor, Installation:- Wall Mounted.) Nos 3 SITC of 175 nos. 7.4 KW AC 4-wheeler charging points charger (Rated Output Current:- 32A, Input voltage:- 220V, Electrical Protection:- Over Current, Over/Under Voltage, Surge Protection, Short Circuit Protection, Earth-Leakage, Ground Fault, User Authorization:- QR Code, Network Connectivity:- GSM/ GPRS, Place of Installation:- Indoor and Outdoor, Ingress Protection:- IP-55, Charging Mode Standard:- IEC 61851-1 Charging Mode-3. K) FAÇADE LIGHTHING 1 SITC of LED RGB/RGBW floodlighting luminaire for facade lighting with Die-cast aluminium housing, powder-coated finish . The beam angle of the fitting shall be narrow, medium, wide or asymmetric as per the requirement. Luminaire shall be complete with a driver and capable of operating at line voltage without any separate power supply from 100-270 V AC, 50 Hz with power factor > 0.9. The fixture shall be suitable to operate at an ambient temperature range of - 10°C to +50°C and shall be IP 65 and IK 06 rated.Lifetime shall be at least L70:50000 burning hours at 50°C. Luminaire shall conform to BIS (IS 10322) and shall be complete with all necessary accessories required for the proper working of the fixture including weatherproof connection cables, waterproof connectors etc. as required. Make- Phillips, Lighting Technology, Wipro, Syska, Jaguar, Crompton, Wipro, Bajaj, Havells, OSRAM, Orient.Facade Area - 14500 Sq.Mt, Perimeter of Building - 320 Mtr, Height of the Building - 88.50 Mtr. L) PUMPING SYSTEM 1 SITC of SS vertical inline pump with Positive suction. Each pump shall have three phase electric motor of S1 duty. The pump shall have cast iron head, base plate SS Shaft / Impeller / Intermediate chamber along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, stainer (with by-pass) at suction. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia), flexible mettalic pump collector of stainless steel corrugated tubing with Stainless steel overbraid and carbon steel flanges. The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. The flexible connectors shall be installed on both suction and delivery side of suitable size and standard length including Electrical Control Panel with 1 VFD for Operation & Control of pump-sets including provision of Pressure Vessel and capacity not less than 2 times the total suction volume of the pump to be provided as per directions of engineer in charge as per manufacturers standard. Domestic Pumps UGWT to OHWT (Pump Discharge = 240 LPM. Head = 115m) (3 W + 1 S) set 2 SITC of SS vertical inline pump with Positive suction. Each pump shall have three phase electric motor of S1 duty. The pump shall have cast iron head, base plate SS Shaft / Impeller / Intermediate chamber along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, stainer (with by-pass) at suction. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia), flexible mettalic pump collector of stainless steel corrugated tubing with Stainless steel overbraid and carbon steel flanges. The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. The flexible connectors shall be installed on both suction and delivery side of suitable size and standard length including Electrical Control Panel with 1 VFD for Operation & Control of pump-sets including provision of Pressure Vessel and capacity not less than 2 times the total suction volume of the pump to be provided as per directions of engineer in charge as per manufacturers standard. Drinking Pumps UGWT to OHWT (Pump Discharge = 100 LPM, Head = 115m) (2 W + 1 S) set 3 SITC of SS vertical inline pump with Positive suction. Each pump shall have three phase electric motor of S1 duty. The pump shall have cast iron head, base plate SS Shaft / Impeller / Intermediate chamber along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, stainer (with by-pass) at suction. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia), flexible mettalic pump collector of stainless steel corrugated tubing with Stainless steel overbraid and carbon steel flanges. The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. The flexible connectors shall be installed on both suction and delivery side of suitable size and standard length including Electrical Control Panel with 1 VFD for Operation & Control of pump-sets including provision of Pressure Vessel and capacity not less than 2 times the total suction volume of the pump to be provided as per directions of engineer in charge as per manufacturers standard. Flushing Pumps STP to OHWT (Pump Discharge = 250 LPM, Head = 125 m) (3 W + 1 S) 4 SITC of Stainless Steel Vertical In-line Pump Sets consisting of 1 Working & 1 Standby pump having Built-in Overload Protection, Motor Housing, Suction Plate, Bottom Screen & all Screws to be of stainless steel, Motor Cover & Pump Housing to be of corrosion proof Cast Iron, Pump to have Stainless Steel Impeller & Double Mechanical seals in oil chambers, including necessary supports/ foundations, Main Suction Header & Delivery Header along with Y Strainers,Isolation and N.R valve, Pressure Guages & Pressure Switches, all necessary fittings,and Cable from Panels to the individual pumps etc including Electrical Control Panel with 1 VFD for Operation & Control of pump-sets including provision of Pressure Vessel. complete as per directions of engineer in charge (TERRACE -Top 3 floor). 1 pump to run on VFD and the VFD shall be transferrable to any of the pumps. Domestic Terrace Booster Pump (Pump Discharge = 150 LPM, Head =25m) (1 W + 1 S) Set 5 SITC of Vertical Monoblock Sewage/ Mud Pump With 1500 LPM @ 8 MWC , 5.5 KW (7.5 HP) (1W+1S) M) LV SYSTEM & MISC. 1 SITC of Electric 360° Occupancy Slim PIR - Presenting Room Ceiling Mount - 230V Energy Saving Motion Sensor, White CSS54E_WE by making necessary arrangement/recess in wall to make it flush with surface. Nos 2 Video Wall Displays- VHR-R, VHT-E, VMT-E, VMT-U seriesPanel- Size/Class 54.6, Type IPS Resolution - 1920 * 1080, Pixel Pitch(mm) -0.63mm(H) * 0.63mm(V), Active Display Area(mm) -1209.6mm * 680.4mm, Brightness Max 700cd/m2, Contrast Ratio- 1200:1Viewing Angle(H/V)- 178/178, Response Time(G-to-G) - 8ms, Display Colors 8 bit - 16.7MColor Gamut-72%, Operation Hour -24/7, Haze -28%, Dynamic C/R 500,000:1, H-Scanning Frequency- 57.3kHz ~ 70kHz, V-Scanning Frequency -48Hz ~ 75Hz, Maximum Pixel Frequency 77MHz, INPUT-RGB DVI-D, Display Port 1.2, INPUT VIDEO HDMI 2.0, INPUT HDCP 2.2, INPUT AUDIO Stereo mini Jack USB Only F/W upgrade, OUTPUT-RGB DP1.2(Loop-out), OUTPUT AUDIO Stereo mini Jack, EXTERNAL SENSOR Detachable type(IR), Power- Supply AC - 240 V, 50/60 Hz, Power Consumption- 242WTypical-[W/h] 136W, Sleep Mode less than 0.5W MechanicalNSpec Dimension(mm) Set 1211.0 x 681.7 x 70 Weight (kg) Set 19.4 Kg Bezel Width (mm) 0.9mm JOB 3 SITC for ACCESS CONTROL(Human Face: PIN Card ( EM Prox - ) Bluetooth Supported Device User Profiles 50,000 FaceLogs 500,000 ,Recognition * 3.5 IPS LCD (Touch Screen ) , IP65 ,WiFi , POE , Access Control Feature ( Door Lock ) ,Reports,Integration with MS SQL, MY SQL, ORACLE,,POSTGRE, DB2*Web APIs for Integration with Third,Party Application Email,Notification,Enterprise Structure and Report,Schedular,Import User Master Data and Export 500,000 Events Storage)Metal Electro Magnetic Lock ( EM Lock Single )Exit Push Button L Bracket Installation Implementation Training And One Year Support. JOB 4 SITC of INTERCOM IP PHONE EPABX SYSTEM 1. SPARK200 Matrix Pure IP Hardware Platfrom for Unified Communication Server Pre-loaded with 1 VOCODER. On-Board CPU and AC Power Supply in 1U Enclosure. Max. IP Trunks: 99 (license-free) Max. IP Users: 2100. Max. VOCODER Channels: 248 Max. VMS Channels: 64. PRASAR UCS ENT license built-in2. SPARSH VP510E Proprietary IP Phone with PoE -(VoIP Protocol: Proprietary • Ethernet Ports: 2 (PC andLAN) • Display: 240 x 64 Pixels Graphical LCD with Backlit • Color: Black • Programmable Keys: 4 Context Sensitive Keys, 16 DSS Keys. Power Supply: PoE BMS System Software : Web Based Graphical Software meeting the requirements in the Given I/O Summary & technical specifications including configuration and facility to create / provide the graphic mapping for all I/O Summary points, animate the Graphics, Navigation between pages, display of logs, changing the time zones, popup alarms, configurable password protection for Building Mgmt System as per Specifications. Software shall be able to communicate with Lon works, Bacnet, Modbus devices simultaneously, with unlimited user license capacity.UL listed, BTL certified, Hardware Interface/Soft integrators with inbuilt webbrowser for third party equipment, Open Protocol Software Integration. These integrators shall be of same make as DDCs and shall contain all necessary ports for software intgeration of below mentioed equipment.DDC Controller with I/O module, expandable to meet the IO summary listed, The controllers shall be minimum 32 bit Double microprocessor based standalone working on TCP/IP on Bacnet IP with integral web browser, calender fundtion complete with day, month, week, year etc, real time clock & 1 second scan time. DDC working on 230V AC are preferred. The DDCs shall be capable of peer to peer communication without help of communication controller / router / system interface controller / PC and shall communicate with the building LAN directly. These shall come with lockable mounting cabinets duly powder coated connector strip, internal wiring and space to house controller & relays, connector strip step down transformer, MCB, internal wiring. (Contractor shall confirm his I/O provision w.r.t requirement on basis of data point) on AHRAE approved Bacnet protocol only. DDCs shall work on either 230V power supply or shall contain UL listed SMPS in the panel Job 6 Supply Installation testing, programming & and commissioning work for a Music System including 2c x 1.5 Sq.mm, twin parallel multi-stranded copper Armoured/Unmanoured cable in 20 /25 mm diameter PVC conduit. with Full range, a 6.5-inch woofer and a 1.25-inch coaxial tweeter mounted within the Dispersion Alignment system, delivering a frequency range of 59 Hz – 20 kHz. Public address amplifier 1200W 120V /MK2 version Should have required signal-to-noise ratio, wireless handheld microphone, 9U 19 Rack for mounting of all Amplifire and Player, Portable Bluetooth PA System, Wireless Option and USB ., One year on-site support. One-time user training. System configuration, tuning. Documentation. with all required accessories including all support work. Job 7 Supply Installation testing & and commissioning work for projector installation with Projection Screen Image brightness -6000 ANSI lumens 7,150 ISO lumens ,contrast ratio • Full On/Off 1300:1 • 3,000,000:1 technology type-native resolution 1-chip 0.67DMD S600HB1920 x 1200 WUXGA 16:10 aspect ratio Illumination type- High-efficiency blue laser phosphorperformance - 20,000 hrs to 50% brightnessInputs - HDMI (1.4a) • HDMI 2.0 • HDBaseT • 3D Sync In (BNC) • VGA • Audio In (3.5mm phone jack) • USB-A • IR RecieverOutputs - 3D Sync Out (BNC) • HDMI • Audio Out (3.5mm phone jack),Warping and blending standardTAA compliant- Yes Speakers 2 x 10WLens type • 1.25-2.0:1 (1.6x throw ratio) motorized lens - powered zoom, focus and offset • 0.65-0.75:1 (1.1x zoom) motorized lens - powered zoom, focus and offset lens offset • Vertical +/- 110% • Horizontal +/- 50% • Vertical +/- 100%• Horizontal +/- 30%Displayable scanning frequency scan rates - max pixel clock rates• Horizontal: 15.375-91.146 KHz • Vertical: 24-85 Hz (120Hz for 3D feature) • 594 MHz (4096 x 2160); 162 MHz (1600 x 1200) Accessories standard • Power cable ,IR remote control (batteries included) optional • Dust filter • WiFi dongle • 3.5mm cable for wired remote functionality 8 Power requirements operating voltage • AC 100-240V, 50/60Hz power consumption • 500W • 660W operating current • 5A • 6.5AAudible noise • 25dBA-30dBA depending • 27dBA-34dBA depending • 27dBA-36dBA depending on the mode used on the mode used on the mode used Enviroment temperature • 0-40°Chumidity • 10-85% RH altitude • 0-2,500ft @ 0°C-40° C • 2,500-5,000ft @ 0°C-35°C • 5,000-10,000ft @ 0°C-30°C• conforms to all relevant European directives, standards, safety, health and environmental concerns RoHS, REACH, WEEEWarranty • 3 years parts and labor on the projector • 3 years or 20,000 hours parts and labor on the illumination system• Reference the Christie Standard Limited Warranty document for details• Or contact an authorized Christie representative for full details of our limited warranty N) HVAC SYSTEM 1 SITC of Basement - Ventilation and smoke extraction system comprises of Axial type fans, Jet fans, CO sensors and PLC panel. System will be operational in case of normal mode and fire mode as pe the NBC considering 6 / 12 ACPH. The System also needs to be intergrated with fire panel through a potential free contact. 1. Ceiling Suspended Fresh Air Tube Axial Dual Speed Fan suitable as per specifications, 12000 CFM Vs 20 mm Static (Normal Mode) 24000 CFM Vs 80 mm Static (Fire Mode)2. Ceiling Suspended Exhaust Air Tube Axial Dual Speed Fan, suitable for 250° C for 2 Hrs. and as per specifications 12000 CFM Vs 20 mm Static (Normal Mode) 24000 CFM Vs 80 mm Static (Fire Mode)3. Ceiling Suspended Ductless Centrifugal type Dual Speed Jet Fan suitable for 250° C for 2 Hrs. and as per specifications Ø504 MM : 3275 CFM (Normal Mode) Ø504 MM : 6550 CFM (Fire Mode)4. CO Transmitters, 0-50 PPM5. Microprocessor Panel / Controller with Control Cabling for integration of CO Transmitters and Jet Fans6. Factory Fabricated G.I. Fresh Air Duct with flanges, supports etc.as per approved Shop drawings, Specifications and SMACNA standards - 22 Gauge (0.81 mm Thick) 24 Gauge (0.63 mm Thick)7. Fresh air weather louvers with bird screen8. Distribution Panel with mounting arrangements, Incoming and Outgoing MCCB / MCB, Indication of Voltage, Current & Power, PhaseIndicating Lights, Contactor / Over load Relay with built in Single Phase preventor, Power Factor Improvement (Lagging) close to Unityand Input Signal from Fire Alarm System and suitable for :1No. Fresh Air Fan, 1No. Exhaust Air Fan, 3Nos. Jet Fans, 3Nos. CO Transmitters, Controllers and Spares9. Power Cabling & Earthing as per specifications between Panel andall Equipment with hangers, supports, and trays etc.4 Core 16 sqmm Cu armoured FRLS cable4 Core 10 sqmm Cu armoured FRLS cable4 Core 6 sqmm Cu armoured FRLS cable4 Core 2.5 sqmm Cu armoured FRLS cable4 Core 1 sqmm Cu armoured shielded cable (Area - 3500 Sqm) Job 2 SITC of Staircase & Lobby Pressurisation is proposed for the fire staircase and the respective lobby to allow safe rescue of occupants and access to the firefighters. The pressure levels are to be maintained as per the norms laid by NBC 50 pascals. The system Should contain axial fans, grilles for air distribution, a pressure relief damper and a necessary electrical panel. This system will be operational only in case of fire thus the system should be looped with a fire fighting system through a potential free contact. (4 Staircases & 2 Lift Lobbies) (42,000 cfm) Job 3 SITC of liftwell Pressurisation.This system is proposed to provide smoke-free lift access for fire fighters for quick access to floors . Axial fans and electrical panel considered with necessary accessories. This system will be operational only in case of fire thus the system should be looped with fire fighting system through a potential free contact (27,500 cfm for one liftwell) Nos 4 SITC of the system which is an essential component in helping to maintain indoor air quality and improve comfort for occupants. The System requires a proper selection of fans with the necessary static pressure for all toilets with properly sized GI ducting and other Air distribution products. The foul air will be pushed to the ambient through GI ducting installed in the plumbing shaft. The system will be efficiently designed to keep the toilets smell free (20,000 cfm , 1 working & 1 standby) For ducting length approx 60 meter. Job 5 Air ConditioningSITC of VRV System with Modulating Outdoor Units, with R410 A Refrigerant, Multi Scroll Compressors (all Variable), Special Precoated Fins, Panel, Corrosion resistant(suitable for seaside installation) coated Condenser, Inverter basedCondenser Fan, M.S. Hot Dip Galvanised stands / supports,Electrical & Microprocessor Panel, Isolating Valves and all the necessary accessories for proper functioning of the Units, andcompatible to operate in Cooling mode at 42 deg C ambient conditions,with following minimum Cooling capacities. with all necessary Accesories & properly sized GI ducting, other Air distribution products for uniform distrution of air and maintain a temperature of 24 degC in the premises. a Entrance lobby 50TR b Food court 190 TR Per TR c Lift lobby 100 TR Per TR d Banquet Hall 110 TR Per TR e GYM 30TR Per TR 6 Supply, Installation, Testing and Commissioning of Modulating Outdoor Units, with R410 A Refrigerant, Multi Scroll Compressors (all Variable), Special Precoated Fins, Panel, Corrosion resistant(suitable for seaside installation) coated Condenser, Inverter basedCondenser Fan, M.S. Hot Dip Galvanised stands / supports, Electrical & Microprocessor Panel, Isolating Valves and all the necessary accessories for proper functioning of the Units, andcompatible to operate in Cooling mode at 42 deg C ambient conditions,with following minimum Cooling capacities. All Refrigerant (Cu) Piping along with fittings, hangers, trays and supports etc. between Indoor & Outdoor Units duly Class O insulatedfinished with glass cloth and lag coating as per specifications.Gas Piping with 19 mm Nitrile Rubber InsulationLiquid Piping with 13 mm Nitrile Rubber InsulationCommunication Cabling between Outdoor Units and Indoor Units inFRLS PVC ConduitMS stands for ODU UnitsPower Cabling & Earthing as per specifications between Panel and all Equipment with hangers, supports, and trays etc.14G perforated Cable tray with cover 600mm x 100mm.(120 TR) Per TR 7 SITC of the system is designed to remove smoke, heat, grease, and cooking odours generated during the cooking process in a kitchen. These systems are essential for maintaining a healthy and comfortable indoor environment with SISW exhaust fan with dry scrubber (Optional), electrical panel, and also necessary ducting suitable to release the exhaust air outside the building on the same floor approx length 60 mtr. (10,000 cfm )