National Institute Of Science Education And Research has published Tender For Provision For Additional Power Point Fixing, Cable Laying For The Instruments Installations And Ups Installation In The Lab No 206B Of Scs Building. Submission Date for this Tender is 26-09-2023. UPS Tenders in bhubaneswar Odisha. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door VTPN DB Make- Schnieder/Legrand/Hager/Havells |
2 | Supplying and fixing 63 A rating, 415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required in the existing DB. Make-Legrand/Hager/Schnieder/Havells |
3 | Supplying and fixing 32 A rating, 240/415 V, 10 kA, "C" curve, TP MCB (miniature circuit breaker) suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as requiredin the existing DB. Make-Legrand/Hager/Schnieder/Havells |
4 | Supplying and fixing 20 A to 32 A rating, 240/415 V, 10 kA, "C" curve, SP MCB (miniature circuit breaker) suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as requiredin the existing DB. Make-Legrand/Hager/Schnieder/Havells |
5 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door Make-Legrand/Hager/Schnieder/Havells |
6 | Supplying and fixing 40A rating, 240/415 V, 10 kA, "C" curve, Four Pole MCB (miniature circuit breaker) suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as requiredin the existing DB. Make-Legrand/Hager/Schnieder/Havells |
7 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 AMp RCCB Make-Legrand/Hager/Schnieder/Havells |
8 | Supply and Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. 3.5Cx25 Sq MM AL Armoured XLPE Cable Make: Polycab/Finolex/RR Kabel |
9 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5Cx25 sqmm AL XLPE Armoured Cable |
10 | Supplying and fixing 32 A, 415 V, TPN Steel Enclosure, with 4 pole and earth, metal enclosed plug top alongwith 32 A "C" curve, TPNMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. Make-Legrand/Hager/Schnieder/Havells |
11 | Supplying and fixing of 6 Module Modular PVC Surface Flush Box with base and cover plate with 2 nos. of6/16A socket outlet with 2 nos. of Modular switch including installation, fixing of switch and socket and connection.) in the surface. 2 socket and 2nos. Of Switch each for Instrument and System Make: Legrand (Mylinc/Myrius) |
12 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire Make: Polycab/Universal/Finolex/RR |
13 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 4 sq. mm + 1 X 4 sq. mm earth wire Make: Polycab/Universal/Finolex/RR |