Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Works Required For Installation Of One Number Set Of Sas System And Sas Based 132 Kv And 33 Kv Control And Relay Panel For Up Gradation Of 132 Kv Substation Sector-62 Noida Under Etd-Ii Noida. Submission Date for this Tender is 18-09-2023. Electrical Panel Tenders in noida Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Dismantling of old 132/33KV Transformer C&R Panel , Transformer Protection Panel, Double feeder control Panel,LineProtection Panel and 33KV Tripple feederC&R Panel by opening its electrical connection, earthing,and all associated work and alsoshifting to store at 132 KV S/S Sec-62Noidaincluding cost of allrequireed man powerand T & Pto complete the work satisfactory. |
2 | Providing and fixing of different make 132KV isolator mechanism boxes at 132KV S/S Sec-62 Noida of size 500X400x330mm made of 18 guage SWG MS including 01 no. front door and no side door with locking arrangement , bottom side mounting the 02 no. chanel for mounting the box and top side mounting a plate in round shape of 165mm with 08 no., 16 mm dia hole matching with horizontal operating pipe plate . this plate connecting 33/28mm pipe rod sand shift along with bush /bearing inside the box straight Hypoid BEVEL and meter gear assembly connected with removal handle to operate the isolator blades fixing and mounting auxiliary contacts with 06 NO+06 NC and 16 nos 20-32 amp TB upon chanel internal connecting the wire with 2.5 mm copper cablebottomside mounting a plate of 150x150mm with 12 no. of cable glands. the box should be duly painted with first coat of primer and double coat of enamel epoxy smoke grey paint , works also includes old and damaged operating boxes and shifting from site to store . after installation of isolator box the operation of isolator should be healthy in all respect ( Mechanically as well as electrically ) the works also include disconnecting and reconnecting of all electrical circuits in isolator and proper status should be communicatedin control bus bar panel |
3 | Providing and fixing of different make isolator operating box of 33KV isolator of size 250X250X150mm made of 18 no. SWG iron in place of damaged and defective (250x250x150mm) isolator box t having 3NO + 3NC Contacts switch and fixed 01 no. bush for vertical operating rod , at the bottom of box fixing a plate of 150x150mm with 4 no. of cable glands. the box should be duly painted with first coat of primer and double coat of enamel epoxy paint as per technical specifications. as per sample including dismentaling and connecting earthing properly.no. |
4 | Laying and termination of control cable from differentequipment installed in switchyard to related panel installed in control room |
5 | Loading, unloading and safe transportation of 132KV Line protection panel /33KV Tripple feeder panelfrom UPPTCL substation as per direction of supervising engineer. Work associated with cost of all men &T&P |