Increasing Capacity Of 33 / 11Kv Sub Station Bilsanda From 3X5 Mva To 2X10+5 Mva In District Pilibhit, pilibhit-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Increasing Capacity Of 33 / 11Kv Sub Station Bilsanda From 3X5 Mva To 2X10+5 Mva In District Pilibhit. Submission Date for this Tender is 20-09-2023. Substation Tenders in pilibhit Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

39616540
Increasing Capacity Of 33 / 11Kv Sub Station Bilsanda From 3X5 Mva To 2X10+5 Mva In District Pilibhit
Open Tender
Indian
Uttar Pradesh
pilibhit
20-09-2023

Tender Details

Increasing Capacity Of 33 / 11Kv Sub Station Bilsanda From 3X5 Mva To 2X10+5 Mva In District Pilibhit- 1 Loading, Unloading And Safe Carriage Of The Following Materials From Any Electy. Store Center Of Electricity Store Division Of Bareilly Zone. 2 M.S. Channel 125X65mm 3 M.S.Angle 75X75x8mm 4 33 Kv Lightening Arrestor 5 33 Kv Line Isolator 6 33 Kv Vcb 800A 750 Mva 7 10 Mva 33 / 11Kv Transformer 8 33 Kv O / D Ct Ctr 200 / 100 / 1 9 11 Kv 3X300 Mm2 Xlpe Cable 10 11 Kv Cable Jointing Kit 3X300 Mm2 I / D 11 11 Kv Cable Jointing Kit 3X300 Mm2 O / D 12 Cost Of Acsr Dog Conductor 13 Earthing Of Indoor & Outdoor Equipments Of Sub-Station After Proper Welding Of Joints And Painting Of Earth Strip Above Soil With Proper Clamp Etc. As Per Respo Approved Drawing & Resistance Of Earthing Should Be Not More Than 2O As Per Details Given Below. 14 Making Of Triangular Bridge By Using Ms Electrode, Gi Strip 50X6mm And Gi Pipe 40 Mm Dia With Providing Of Well Type Pipe Earthing Upto 15 Mtr. Depth Below Ground Level Including Welding Etc. By Boaring Process At T / F Neutral, La And Newly Erected Structure Including Cost Of Gi Pipe Of Size 40 Mm Dia 15 Mtr. Long Of Isi Mark. ( All The Required Material Will Be Supllied By The Contractor ) . 15 Supply Of Gi Strip Of Size 50X6mm For Earthing Of All Newly Erected Structures And Equipments In Switchyard Including Cutting, Fixing & Proper Welding With Equipments. All La Will Be Seprately Earth Also As Per Respo Norms. ( All The Required Materials Will Be Provided By Firm. ) 16 Construction Of New Transformer Plinth Of Size 4.5X3.5 Mtr. For Upto 10 Mva Transfomer Having Depth 0.5 Mtr. Below Ground Level & 0.5 Mtr. Above Ground Level. Existing Plinth Is In Very Damage Condition And Its Height Is Below Ground Level. The Work Including Excavation Of Foundation. Base & Concreting Of Foundation Base Of Cc 1:6:12 Ratio ( Cement, Fine Sand & Brick Ballast ) First Class Brick Work Of Cement Morter Of Ratio 1:4 For Masonry & Lintring Work Of Transformer Plinth Of Rcc Work Of Ratio 1:2:4 ( Cement, Coarse Sand And Store Grit Of 20Mm Using Ms Bars Of 10Mm Dia ( Tor ) For Reinforcement Of Linter Including Cutting, Bending & Binding Of Ms Bars Of Required Plinth Size & Shape. The Work Also Includes Laying Of 2 Nos. 3.5 Mts. Long Rail Pieces After Cutting In Proper Size & Shape & Fitting Etc. The Plinth Will Be Made As Per Resspo / Approved Drawing Suitable For 10 Mva Transformer & Shall Be Plastered Of Walls Of Ratio 1:4 ( Cement & Fine Sand ) / Finished On Top And Sides Of The Plinth. ( All Material Will Be Provided By Firm ) . 17 Fabrication, Erection And Grouting Of The Following Structures As Per Resspo / Approved Drawing And Its, Plinth 30Cm Above Ground Leval As Directed By The Engineer Incharge ( All Steel Sections Will Be Provided By Deptt ) . 18 Fuse Set Structure 19 Installation Of Followig Equipments On Their Respective Structures Including Mechanical & Electrical Fixing After Proper Adjustment On Their Structure. 20 33 Kv Line Side Isolator 21 Lightening Arrestor 22 33 Kv Vcb Complete 23 33 Kv Ct 24 33 Kv Fuse Set ( Will Be Provided By Firm ) 25 Dismantling Of Existing Following Damage Equipments On Their Structure. 26 33 Kv Line Isolator 27 33 Kv Lightening Arrestor 28 33 Kv Vcb 29 33 Kv Ct 30 Complete Laying And Termination Of Copper Control Cables From 10 Mva Power T / F, 33 Kv Vcb, 33 Kv Ct In The Out Door Switch Yard To The Existing Transformer Relay Control Panel Inside The Control Room Including Cost Of All Materials And Labour Required For Proper Completion Of Works As Per Resspo Drawings, Including Cost Of Testing Of Transformer, Vcb, Ct, Relay Pannel & Proper Relay Settings As Per Requirement Etc. 31 Laying Of Dog Conductor Alongwith Cost Of All Required Calmps And Connectors Etc. As Per Resspo Approved Drawing Of Bus Bar L.A., C.T., V.C.B., Bus Isolator Etc. 32 Laying Of 11Kv Cable Of Different Size From Power T / F To Control Room I / C . 11 Kv Cable Will Be Layed In Brick Trench Constructed Below 750Mm To The Ground Level Over The Ganga Sand. Brick Trench Will Be Constructed By Ist Class Bricks Covering Three Sides Of Cable, After Laying 11 Kv Cable Brick Trench Will Be Filed By Ganga Sand & Then Will Be Covered By Bricks & Backfill Of Soil Over Cable Trench As Per Respo Norms. 33 Termination Of 33 Kv 3X300sqmm Size Xlpe Cable By Filling 33 Kv Heat Shrinkable Type Cable Boxes Including Hoisting Of Cable And Proper Connection Withbus Bar Gantry And Bus Isolatorby Providing Suitable Connectors. 34 Painting Of The Fabicated Structures With One Coat Of Red Oxide Primer And Two Coats Of Synthetic Enamel Alumm. Paint / Green Paint Of Isi Mark Alongwith Earthing Strip Above Ground Level. 35 Safely Shifting And Dragging Of 33 / 11 Kv 5 Mva Transformer From Its Plinth To Safe Site At Sub-Station. 36 Carriage Of Old Scrap Material From Site To Store Center Pilibhit. 37 Complete Repairnig Of Swichyard Fencing.

Key Value

Document Fees
INR 1180 /-
EMD
INR 7850.0 /-
Tender Value
INR 7.85 Lakhs /-

BOQ Items

Name of Work : INCREASING CAPACITY OF 33/11KV S/S BILSANDA FROM 3X5 MVA TO 2x10+5 MVA IN DISTRICT PILIBHIT.
Sl. No. Item Description
1Loading, unloading and safe carriage of the following materials from any Electy. Store Center of Electricity store division of Bareilly zone.
2M.S. Channel 125x65mm
3M.S.Angle 75x75x8mm
433 KV Lightening Arrestor
533 KV Line Isolator
633 KV VCB 800A 750 MVA
710 MVA 33/11KV Transformer
833 kv O/D CT CTR 200/100/1
911 KV 3x300 mm2 XLPE Cable
1011 KV Cable jointing Kit 3x300 mm2 I/D
1111 KV Cable jointing Kit 3x300 mm2 O/D
12Cost of ACSR Dog conductor
13Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2O as per details given below.
14Making of triangular bridge by using MS electrode, GI strip 50x6mm and GI Pipe 40 mm dia with providing of well type pipe earthing upto 15 Mtr. depth below ground level including welding etc. by boaring process at T/F neutral, LA and newly erected structure including cost of GI pipe of size 40 mm dia 15 mtr. long of ISI mark.(all the required material will be supllied by the contractor).
15Supply of GI strip of size 50x6mm for earthing of all newly erected structures and equipments in switchyard including cutting, fixing & proper welding with equipments. All LA will be seprately earth also as per RESPO norms. (All the required materials will be provided by firm.)
16Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above ground level. Existing plinth is in very damage condition and its height is below ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth.(all material will be provided by firm).
17Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing and its, plinth 30cm above ground leval as directed by the Engineer Incharge (All steel sections will be provided by Deptt).
18Fuse Set Structure
19Installation of followig equipments on their respective structures including mechanical & electrical fixing after proper adjustment on their structure.
2033 KV Line side isolator
21Lightening Arrestor
2233 KV VCB complete
2333 KV CT
2433 KV Fuse Set (will be provided by firm)
25Dismantling of existing following damage equipments on their structure.
2633 KV Line Isolator
2733 KV Lightening Arrestor
2833 KV VCB
2933 KV CT
30Complete laying and termination of copper control cables from 10 MVA power T/F, 33 KV VCB, 33 KV CT in the out door switch yard to the existing transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings, including cost of testing of transformer, VCB, CT, relay pannel & proper relay settings as per requirement etc.
31Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing of Bus bar L.A., C.T., V.C.B., Bus Isolator etc.
32Laying of 11KV cable of different size from power T/F to control room I/C . 11 KV Cable will be layed in brick trench constructed below 750mm to the ground level over the ganga sand. brick trench will be constructed by Ist class bricks covering three sides of cable, after laying 11 KV Cable brick trench will be filed by Ganga sand & then will be covered by bricks & backfill of soil over cable trench as per RESPO norms.
33Termination of 33 KV 3x300sqmm size XLPE cable by filling 33 KV heat shrinkable type cable boxes including hoisting of cable and proper connection withbus bar gantry and bus isolatorby providing suitable connectors.
34Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
35Safely shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site at Sub-station.
36Carriage of old scrap material from site to store center Pilibhit.
37Complete repairnig of swichyard fencing.
Disclaimer :