| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable inPVC casing caping with modular switch, modular plates,suitable size modular surface box of specified Category and earthing the point with 1.5 sq.mm FR PVC insulated copper conductor single core cable etc. as required. |
| 2 | \"(f) Group C-- with Cat B Modular Accessories |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor single core cable in the independentPVC casing capping of appropriate size as required. |
| 4 | (b) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earthwire (20mm casing ) |
| 5 | (c) 2 x 4 sq.mm + 1 x 4 sq.mm earthwire(20mm casing ) |
| 6 | Supplying and fixing suitable size modular PVC box with modular plate and coverin front on surface or in recess including providing and fixing 1 no 6 pin 15/16 A modular socket outlet and 1 no 15/16 Amodular switch connection painting etc. as required. (for work stations) Cat B |
| 7 | Supplying and fixing suitable size modular PVC box with modular plate and coverin front on surface or in recess including providing and fixing 1 no 3 pin 5/6 A modular socket outlet and 1 no 5/6 Amodular switch connection painting etc. as required. The scope of work includes altrnate arrangement, if required as per site conditions, to provide switches and socket seperately, above and below the table respectively (for work stations)Cat B |
| 8 | Supplying and fixing brass batten/ angle holderincluding connections etc as required. |
| 9 | Supplying and fixing stepped type electronic fan regulator on the existing modularplate switch box including connections but excluding modular plate etc.as required. Cat B |
| 10 | Supply and erecting of 48 inch ( 1200mm sweep) ceiling fan, double ball bearing type, complete with all accessories. |
| 11 | (b) Cat B |
| 12 | Installation,earthing, testing and commissioning of ceiling fan including wiring the down rodof standard length ( upto 30 cm) with 1.5 sq .mm FRFRLS PVC insulated copper conductor single core cable etc. as required. |
| 13 | Supply and erectingS type Stainless Steel fanhook fabricated out of10 mm round bar complete as required. |
| 14 | Chasing the ceiling to erect a fanhookincluding making good the plaster, neeru and paint complete as required( hook not included). |
| 15 | Supplying and fixing 6 A to 32 A,C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required. |
| 16 | (f) SP, Cat B |
| 17 | Supplying and fixing 40 A,C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required. |
| 18 | 40 A, TP Cat B |
| 19 | Supplying installation testing and commissioning of surface/ recess mounting vertical type 415 V TPN,double door MCB DB of sheet steel dust protected duly phosphatised and powder painted inclusive of 200 A tinned copper busbar common neutral link earth bar din bar for mounting MCBs detachable gland knock out plate and with 250 A 10 KA MCCB as incomer interconnection between incomer MCCB and busbars of following ways (but without MCCB/MCBs as required) |
| 20 | 8 way with 250A MCCB as Incomer double doorCat A |
| 21 | Providing and fixing following rating and breaking capacity fixed type/adjustible 3 pole MCCB inside the existing cubicle panel board including drilling holes in cubicle panel making connections etc as required. |
| 22 | (i) 200 A Adjustible 35/40 KA, CAT A |
| 23 | Supply and erecting of 18 inch (450 mm sweep) exhaust fan with double ball bearings, 1400 rpm,heavy duty, complete with all accessories. |
| 24 | Cat A |
| 25 | Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosure with CI/RCC cover having locking/lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation ofpit of size 1.0x1.0x 3.0 mtrs(min) and disposal of excavated soil. c)Watering GI pipe, 20 mm Class B,with funnel as per specs. d)Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs(min) with soft blackagriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation, cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. g)watering arrangement(plumbing will be paid seperately). |
| 26 | (b) In rocky strata |
| 27 | Extra for using salt and charcoal for GI or copper plate earth electrode as required |
| 28 | Supplying and laying 25 mm x 5 mm copperstripin 40 mm dia GI pipefromearth electrode as required |
| 29 | Providing and fixing 25 mm x 5 mm GI strip on surface or in recess for coneections etc. as required |
| 30 | Supply, installation testing and commissioning of450 mm Thunderstorm Wall Fan Parrot Green make Orientor Equivalent in Havells / Crompton / Bajaj / Almonard, etc . Complete as required.(Equivalent to be approved by Engineer incharge ) |
| 31 | Supply, installation testing and commissioning ofLED 22 W,Luminaire make Havells, ( Cat no. LUMINEBS22WLED865SPCWH)or Equivalent in Crompton / Bajaj / Phillips / Legero . Complete as required. (Equivalent to be approved by Engineer incharge ) |
| 32 | Supply and erectingof120 W LEDStreet light of make Havells Endura Omniplus (Cat no. ENDURAOMNIPLUSSL120WLED757 SASYTOPC )or Equivalent in Crompton / Bajaj / Phillips / Legero, etc . Complete as required.(Equivalent to be approved by Engineer incharge ) |