Tender For Repair / Replacement And Day To Day Maintenance Of Lt Distribution System Lt Panel / Apfc Panel / Lt Poles At Makarpura At Afs Baroda, baroda-Gujarat

Military Engineer Services-MES has published Tender For Repair / Replacement And Day To Day Maintenance Of Lt Distribution System Lt Panel / Apfc Panel / Lt Poles At Makarpura At Afs Baroda. Submission Date for this Tender is 06-10-2023. Electrical Panel Tenders in baroda Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

39560295
Corrigendum : Tender For Repair / Replacement And Day To Day Maintenance Of Lt Distribution System Lt Panel / Apfc Panel / Lt Poles At Makarpura At Afs Baroda
Open Tender
Indian
Gujarat
baroda
06-10-2023

Tender Details

Repair / Replacement And Day To Day Maintenance Of Lt Distribution System Lt Panel / Apfc Panel / Lt Poles At Makarpura At Afs Baroda

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 29-Sep-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 50000.0 /-
Tender Value
INR 25 Lakhs /-

BOQ Items

Name of Work : REPAIR / REPLACEMENT AND DAY TO DAY MAINTENANCE OF LT DISTRIBUTION SYSTEM LT PANEL / APFC PANEL / LT POLES AT MAKARPURA AT AFS BARODA
Sl. No. Item Description
1M&L for dismantling of existing panel including disconnecting cables, etc. and design, supplying, installing, testing and commissioning of factory made LT cubical double door panel with roof canopy, outdoor type, made out of CRCA sheet 3.15mm thick duly powder coated with Seimens grey shade RAL 7032,totally enclosed, dust and vermin proof outer cubicle. Inner cubicle should be made out of 2 MM thick CRCA sheet with working voltage of 415V, 50 Hz, 3 phase 4 wire fully compartmentalised design with single door system for each compartment for each control gear with provn of side cable alley for outgoing cables. Outer cubicle must be extendable in both ends having both sides door openable and shall be provided with suitable louvers for ventilation. The Bus bar rating shall be aluminium -4Nos and each have 1.5 time of incommer MCCB i.e. 1000Amp. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
2The bus bar connections and their insulated supports shall be mechanically strong and shall with stand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes.The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring shall be done with 2.5 sqmm multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel shall contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The cubicle incomer MCCB as well as outgoings shall have TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The cubicle shall be inclusive of following :
3LOCATION -(Main panel AIR MEN Sub STN) 1. INCOMING - (a). MCCB TPN, 50 kA, 630 Amps with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In with Spreader Terminals and rotery handle - 01 No. Make: L&T/Havells/Siemens/ABB 2. OUTGOING - (a) MCCB TP, 36kA, 320 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In with Spreader Terminals and rotery handle Make L&T-CAT NO-CM94005OOR1OG or equivalent in ABB/Siemens/Havells - 01 No. (b). MCCB TP, 36kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In with Spreader Terminals and rotery handleMAKE- L&T-CAT NO-CM94005OOQ1OG or equivalent in ABB/Siemens/Havells - 02 Nos.
4(c). MCCB TP, 36kA,125 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In including rotary handle with spreader terminal.- 03 Nos. (d). LED INDICATORS RIBBED LENS WITH TRIMMED COLLAR - Red, Yellow and Blue - 3 Each, L&T Make - CAT NO - HB07E or equivalent to ABB/Siemens/Havells (e). Digital Ammeter 630 Amp alternating current range selector switch suitable for line currents including3 Nos CT of ratio630 A/5A . -1Nos (f). Digital Voltmeter alternating current voltage range : Range 0-500 V selector switches suitable for Voltage between Phases with OFF -1Nos (g). Aluminium bus bar1000 AMPS ratingfor R-Y-B phases andNeutral - Sets (h). Base frame for cubical for mounting made out of 40x40x6mm equal angle iron duly painted. (j). Foundation for the panel shall provided with PCC 1:2:4 at a depth of 150 MM below G.L. and 500 MM above the G.L. with slot openings for I/C and O/G cables.
5M&L for dismantling of existing panel including disconnecting cables, etc. and design, supplying, installing, testing and commissioning of factory made LT cubical double door panel with roof canopy, outdoor type, made out of CRCA sheet 3.15mm thick duly powder coated with Seimens grey shade RAL 7032,totally enclosed, dust and vermin proof outer cubicle. Inner cubicle should be made out of 2 MM thick CRCA sheet with working voltage of 415V, 50 Hz, 3 phase 4 wire fully compartmentalised design with single door system for each compartment for each control gear with provn of side cable alley for outgoing cables. Outer cubicle must be extendable in both ends having both sides door openable and shall be provided with suitable louvers for ventilation. The Bus bar rating shall be aluminium -4Nos and each have 1.5 time of incommer MCCB i.e. 500Amp. Bus bars provided shall be adequately supported on insulators to with stand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
6The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring shall be done with 2.5 sqmm multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel shall contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The cubicle incomer MCCB as well as outgoings shall have TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The cubicle shall be inclusive of following :
7LOCATION - NEAR SNCO"s Billet 1. INCOMING - (a). MCCB Four Pole 36kA, 315 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In withSpreader Terminals and Extended Rotary Handle - 01 No. MAKE- L&T-CAT NO-CM94006OOT1OG or equivalent in ABB/Siemens/Havells 2. OUTGOING - (a) MCCB Four pole, 36kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x InwithSpreader Terminals and Extended Rotary Handle- 01 No. MAKE- L&T-CAT NO-CM94005OOR1OG or equivalent in ABB/Siemens/Havells
8(b). MCCB TP, 36kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x InwithSpreader Terminals and Extended Rotary Handle- 02 Nos. MAKE- L&T-CAT NO-CM94005OOQ1OG or equivalent in ABB/Siemens/Havells (c) MCCB TP, 36kA,125 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In including rotary handle with spreader terminal- 03 Nos. MAKE- L&T/ ABB/Siemens/Havells (d). LED INDICATORS RIBBED LENS WITH TRIMMED COLLAR - Red, Yellow and Blue - 3 Each, L&T Make (e). Aluminium bus bar500 AMPS rating of size 50X10 MM for R-Y-B phases andfor Neutral. (f). Foundation for the panel shall provided with PCC 1:2:4 at a depth of 150 MM below G.L. and 500 MM above the G.L. with slot openings for I/C and O/G cables.
9Repairing/overhauling of LT panel any size by welding of door replacement ofhinges wherever required and re-arrange the internal fitting/fixtureincluding replacing of nut bolt and locking arrangement,replace of doorsheet thickness 3.15mm size, bottom plate including cable gland upto size 150mm cable (1+4) one incomming and four outgoing cables and disconnection of unserviceable internal cables of any size rewiring/reconnection by suitable size of wire/cable including fixing of panel in PCC 1:2:4 type B-2 using20 mm graded stone aggregate complete including one coat of red oxide primer and one coat smoke gray colour paint complete all as specified and directed
10S&F in repairs Glow sign board of size 1.5 m x 0.9 m x 0.20 m made out of 1.0 mmthick tin sheet all side except front side aluminium beading "L" shape at all border exterier and interier side, front shall be acrylic cover 2.0 mm thick of blue colour including writing the subject matter as given by the Engr-in-charge in english capital letter in white colour with twin LED tubelight fitting 1x22 watt (2 nos) including all electrical connection with surface conduit wiring 1.5 Sqmm ((length not exceeding 8 meter) copper wire with drilling and necessary required arrangement for fixing of board including testing complete all as specified and directed
11M & L for making foundation of LT Distribution panels with rectangular boundary of specified size made of bricks in cement mortar 1:4 covering the area all around the panel upto 0.5 m distance and the inner area filled with loose filling aggregates of size upto 80 mm, bricks along the boundary should be painted in white and blue colours alternately complete all as specified and directed
12Earthing complete in repairs with galvanised steel earthelectrode 60 cm x 60 cm x 6 mm burried directly in ground vertically to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level connected to and including galvanised earth leadas GI strip of 32X6mm dia by means of bolts,nuts, check nuts and washer etc made of galvanised iron and connected to earthing test point all as shown in electrical plate No.3 of SSR Part I 2009 and as specified or indicated and testing on completion including excavation/earth work in any type of strata, PCC (1:3:6) type C1 earthing chamber, precast RCC slab 50 mm thick in reinforced cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric (XPM jali weight not less than 4 Kg/Sqm), cast iron frame, funnel with wire mesh, 40 mm bore medium grade GI watering pipe, lugs, 15 mm bore medium grade GI protection pipe, test point etc. complete all as specified and directed. Note: (i)Item includes the cost of 7.5 metre GI pipe for protection of earth lead. Any addition in length shall be adjusted through deviation order.
13Repair & maintenance of ACB cleaning, tighting of nut bolt and greasing of machenism complete all as specified and directed.
14S& F in replacement of old unserviceable lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugsincluding crimping with crimping tools in the existing LT cable size up to 240 sqmm including necessary connection complete all as specified and directed. Note: Aluminium Lugs shall be measured and paid separately.
15Supply only Aluminium cable lugs ( lugs are made from 99.5% pure aluminium) as per IS of following size complete all as specified and directed:-
16185 Sqmm
17120 Sqmm
1895 Sqmm
1970 sqmm
2050 sqmm
2135 sqmm
2225 Sqmm
23M&L for straight through joint outdoor type for LT UG cable including jointing kits heat srinkable typecomplete suitable for aluminium conductor cables complete all as specified and directed for the following size. Make : Denson, M-Seal or equivalent make approved by GE.
2425 to 50 sqmm3.5 core
2570 to 95 sqmm3.5 core
26120 to 185 sqmm3.5 core
27Supply and fix AVF meter(amper,Volt and Frequency meter ) digital type accuracy Class 1.0, ,Flush mounting 96 x 96 mm, Inbuilt selector switch for 3 phase meters complete all as specified and directed. Make .L&T, AE, HPL
28Supply and fixSelector switch for voltmeter/ ammeter complete all as specified and directed.Make . L&T, AE, HPL
29Supply and fixPhase indicator lamp neon type complete with holder assy RYB. complete all as specified and directed Make .L&T, AE, HPL
30Supply and fixCT coils of range. 200/5 Amp complete all as specified and directed
31Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 125 KVARs and up 8/10 stages installed atvarious locations at AFS MakarpuraBaroda area including carrying out complete maintenance/repairs as required of all the sub systems viz. basedcontrol panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT,MCBs/MCCBs for isolation (with all the accessoires) anybreakdownmaintenance and replacement of unserviceable parts, refixingof old serviceable parts/new parts if anyproject completionand trouble shooting responsibility also lies with contractor including following provisions complete all as specified and directed.
32Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring, small part such as Push button, lugs any auxilary contatct,auto selctor switch etcand necessary servicing repair by expert technician and register will be maintaned for the same. (ii)The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii) Measure components such ascapacitors bank, APFC relay, power contactor, control CT, MCBs/MCCBshall be measured and paid saperatly
33Supply only powerfactor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
34Description all as per item No 16.00 here-in-before but 10 KVAR Capactor Bank
35Description all as per item No 16.00 here-in-before but 15 KVAR Capactor Bank
36S&F APFC relay eta CON L series with auto-set function 3-8 stage, Model etaCON L3 including taking down old unserviceable one complete all as specified and directed. Make:- L&T or equivalent make in Schneider/HPL/Indo Asian.
37S&F in repairs, capacitor duty contactor, type MOC built in auxillary contact blocks, 8.5 KVAR, 415 volts, 3 phase, 50 Hz, type MO C8.5 complete all as specified and directed.
38Description all as per item No 20.00 here-in-before but capacitor duty contactor, type MO C12.5 complete all as specified and directed.
39Description all as per item No 20.00 here-in-before but capacitor duty contactor, type MO C15 complete all as specified and directed.
40S&F ON Load change over switch open execution type, 4 Pole, 250 Amps rating of L&T make, CAT No. - CO32500OOOO including operating handle - CAT No. - CX40001OOOO or equivalent in complete all as specified and directed.
41S&F MCCB TP, 36KA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In of L&T Make, CAT No. - CM92009OOP1OG including spreader Terminals (CAT No. - ST98053OOOO - Set of Six) and extended Rotary Handle (CAT No. - CM99860OOOO) complete all as specified and directed.
42S&F MCCB TP, 36kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In of L&T Make, CAT No. - CM92009OOP1OG including spreader Terminals (CAT No. - ST98053OOOO - Set of Six) and extended Rotary Handle (CAT No. - CM99860OOOO) complete all as specified and directed.
43S&F MCCB TP, 36kA, 125 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 - 1.0 x In, Adjustable Short Circuit setting: 6 - 10 x In of L&T Make, CAT No. - CM92008OOL1OG including spreader Terminals (CAT No. - CM97785OOOO - Set of Six) and extended Rotary Handle (CAT No. - CM99860OOOO) complete all as specified and directed.
44Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth, for foundation etc. or for shafts, welles cesspitsm, manholes, pier holes, etc. n exc 10 sqm on plan and n exc 1.5m in depth in hard/dense soil and getting out , complete all as specified and directed.
45Add to item 27.00 here-in-before for each additional 1.5m or part thereof in depth beyond the first 1.5 m complete all as specified and directed.
46Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the stratingpoint, complete all as specified and as directed.
47Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25m, complete all as specified and directed.
48M&L for Sand cushioning to underground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Par-I, complete all as specified and as directed.
49Supply and laying factory made, machine pressed, unreinforced, pre-cast concrete cable cover class LV type-I flat size 250 x 150x40mm , complete all as specified and directed
50Taking down / dismantling of unsv LT cable complete all as specified and directed
51Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 3.5 core complete all as specified and directed.
52Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core complete all as specified and directed.
53Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core complete all as specified and directed.
54Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core complete all as specified and directed.
55Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sqmm 3.5 core complete all as specified and directed.
56Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed.
57Supply, laying and testing in repair to replacement cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed.
58Taking down dismantling of unsv rusted LT pole with all fitting complete all as specifed and directed
59Supply and installation of steel tubular swaged pole complete with cast iron base plate, finial Taper plug, bolts, nuts, and screws as specified type confirming to IS 2713 complete including 2 coats of aluminium paint over one coat of red oxide primer on external exposed surfaces and 2 coats of black bituminous paint on portion embedded in concret in internal surfaces of pole as in repairs, complete all as specified and directed as in repairs for 410 SP-31 (9 mtr long)
60S&F new generation energy saving and environmental friendly long life varsatile pressure die cast aluminium IP66 road way light fitting with high power LED as light source of capacity 72 watts with suitable drivers etc and connecting with 4.0 sqmm aluminium conductor PVCinsulatedtwin core weather proof cable etc, fixing to wall / pole with and, fixed to Pole/Wall in any position with flat iron clamps of size 30 x 4mm including taking down old unserviceable street light fitting of any type and capacity complete all as specified and directed. Make:-Havells or equivalent model of Philips/Bajaj/orient.
61M&L modular enclosure cable junction box IP 65, weather proof with hinged door and locking arrangement of size 240mm x 320mm x 135mm internal comprising of one No MCB SP 6 Amps and epoxy porcealin terminal blcok 6 way suitable for three incoming cable and for outgoing and single phase connection for light fitting with provision of cable entry through gland and fixed to the existing/new PCC/Steel pole with suitable clamps made out of MS flat iron 25 x 4mm thick with nuts, bolts and washer complete all as specified and directed. Make:-NEPTUNE Cat Part No 6320 or equivalent model of HENSEL/ABB/Schneider.
62M&L for preparation of external surfaces of steel tubular poles / rail / garden poles of any height by rubbing sand paper and cleaning,applying two coats of aluminium paint complete all as specified and directed.
63M&L for PCC type C2, 1:3:6 using 40 mm gradded stone aggregate in foundations complete all as specified & directed.
64M&L for PCCtype B-1, 1:2:4 using 20 mm gradded stone aggregate for coping, including form work complete all as specified & directed.
65Surface excavation n.exc30 cm deep and averaging 15cm deep and getting outcomplete all as specified and directed.
66Supply and spread and leveling Graded coarseAggregate in loose filling over dress earth surfaceof guage 40mm nominal size in the installation yard complete all as specified and directed.
67Trimming/prunning and removing of tree branches or any other foreign objects from HT/LT over head conductor and clearing the OH Line of any type and size for one span of any length in 2 way /4 way/6 way conductor system complete all as specified and directed. Notes: (i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P and safety equipments to complete the job. (iii) Quoted rate is deemed to inclusive of Replacement of Insulators, Joining the ACSR Conductor, Jumpering and stringing the ACSR conductor etc.
68Findout Faultin existing U/GLT/ cables laidbelow earth surface in any location of AFS MakarpuraAreabythe expert engineers team of state electricity boardusing and hiring ofLT fault loactorcomplete all as specified and directed. Note : LT Straight through Joint kitwill bepaid and measured seperatly in relevent item of BOQ.
69M&L for boring under road with trench less tecnology including DWC HDPE pipe of required dia complete for protection of HT cable complete all as specified and directed.
70Supply & lay G I tubinglight grade in protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc all as specified anddirected for following sizes :-
7140 mm dia bore
7250 mm dia bore
7380mm dia bore
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail