Tender For Special Repair To Lt Panel Starters And Connected Lt Cable At Sewage Installation And Certain Minor Work Pertaining To Summer Appliances At Ge Utility Ambala Cantt, ambala-Haryana

Military Engineer Services-MES has published Tender For Special Repair To Lt Panel Starters And Connected Lt Cable At Sewage Installation And Certain Minor Work Pertaining To Summer Appliances At Ge Utility Ambala Cantt. Submission Date for this Tender is 09-10-2023. Starter Tenders in ambala Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

39556655
Corrigendum : Tender For Special Repair To Lt Panel Starters And Connected Lt Cable At Sewage Installation And Certain Minor Work Pertaining To Summer Appliances At Ge Utility Ambala Cantt
Open Tender
Indian
Haryana
ambala
09-10-2023

Tender Details

Special Repair To Lt Panel Starters And Connected Lt Cable At Sewage Installation And Certain Minor Work Pertaining To Summer Appliances At Ge Utility Ambala Cantt

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 19-Sep-2023 AMENDMENT BOQ 29-09-2023
2 29-Sep-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-10-2023
3 07-Oct-2023 AMENDMENT Date 09-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 96200.0 /-
Tender Value
INR 48.10 Lakhs /-

BOQ Items

Name of Work : Special Repair to LT Panel, Starters And Connected LT Cable At Sewage Installation And Certain Minor Work Pretaining To Summer Appliances At GE (U) Ambala Cantt.
Sl. No. Item Description
1Supplyand installation of desert coolers having nominal air flow capacity 4000 cum per hour of size 660x660x825 mm made out of PGI sheet not less than 0.90 mm thick for fixed parts and not less than 0.70 mm thick for front grill as approved, the desert coolers having copper wounded fan motor 480 mm sweep, 1350- 1400 RPM, 230 volts, 50 Hz with submersible water pump 18/20 watt for required flow of water including having three speed regulator (high/medium/low) with and including provision of two coats of synthetic enamel anticorrosive oven dried paint over a coat of redoxide primer complete all as specified and as directed.
2M&L for mild steel angle iron frame of any size and shape for provision of desert cooler stand including necessary cutting, welding and grouting in wall. complete all as specified and as directed.
3Material and labour for Point wiring with 2 Run of 2.50 Sqmm single core PVC insulated , unsheathed cable FRLS-H, 1100 volt grade ISI marked with multi stranded copper conductor drawn through and including medium grade, ISI marked,PVC conduit medium grade not less than 15 mm dia with accessories/ casing caping, concealed/surface type on wall/ceilingand including provision of 1.50 Sqmm single core PVC insulated, unsheathed cable FRLS-H, 1100 volt grade with multi stranded copper conductorgreen colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including sunken pressed steel terminal boxes with and includingscrews, modular cover plate over sunken box for housing the switches, socket outletsetc and making goodthe disturbed surfaces as per existingfor:-One light point controlled by one switch Note:-1.Switch, socket to be measured and paid separately.
4S&F switch piano type single pole one way 15 Amp. complete all as specified and as directed.
5Supply and fixing socket outlet 5/15 Amp flush type complete all as specified and as directed.
6Supply and laying GI pipe medium grade ISI markedwith all fittings for 15 mm bore complete all as specified and directed by Engr in charge
7Supply and fixstop valve, screwed, 15 mm (1/2")dia pipe. complete all as specified and as directed.
8Supply and fixing ball brass valves, high pressure with polythene float and flynut complete screwed for iron pipe or brass ferrule and fixed.
9Supply and fixing GI Tee, 15 mm . Complete all as specified and as directed.
10Dismantling andtaking down old unsv LT panel and Supplying, installing, testing & commissioning out door type cubical panel board of size 1.2x0.9x0.5M outer shell made out of3.15 mm thick MS sheet iincluding door frame, Persplex Sheet for front door only 6 mm thick should be properly fixed with minimum 80% coverage in door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :- (a)TPN aluminium bus bar 400Amps insulated with colour coded heatshrinkable sleeve and shall be mounted on suitable size “F”class insulators (b) Incoming MCCB 250 Amp, 4 pole 415 volts 50 Hz 35 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (3-6) In for power distribution- 01 No (c) Outgoing MCCB 160 Amp, 4 pole 415 volts 50 Hz 25 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (6-10) In for power distribution -03 Nos.(01 Spare) d) On Load change over switch four pole 415 Volts, 250 Amps. (e) Digital Ammeter 0-500 Amps of size 96x96 sqmm with selector switch. (f) Digital Voltmeter of size 96x96 sqmm with selector switch 0-500 Volts. g)Indicator lamps LED type RYB with holder -01 Set of three
11Dismantling andtaking down old unsv LT panel and Supplying, installing, testing & commissioning out door type cubical panel board of size 1.2x0.9x0.5M outer shell made out of3.15 mm thick MS sheet iincluding door frame, Persplex Sheet for front door only 6 mm thick should be properly fixed with minimum 80% coverage in door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :- (a)TPN aluminium bus bar 300Amps insulated with colour coded heatshrinkable sleeve and shall be mounted on suitable size “F”class insulators (b) Incoming MCCB 200 Amp, 4 pole 415 volts 50 Hz 35 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (3-6) In for power distribution- 01 No (c) Outgoing MCCB 100 Amp, 4 pole 415 volts 50 Hz 16 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (6-10) In for power distribution -03 Nos.(01 Spare) d) On Load change over switch four pole 415 Volts, 200 Amps. (e) Digital Ammeter 0-500 Amps of size 96x96 sqmm with selector switch. (f) Digital Voltmeter of size 96x96 sqmm with selector switch 0-500 Volts. g)Indicator lamps LED type RYB with holder -01 Set of three
12Dismantling andtaking down old unsv LT panel and Supplying, installing, testing & commissioning out door type cubical panel board of size 1.0x0.8x0.5M outer shell made out of3.15 mm thick MS sheet iincluding door frame, Persplex Sheet for front door only 6 mm thick should be properly fixed with minimum 80% coverage in door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :- (a)TPN aluminium bus bar 300Amps insulated with colour coded heatshrinkable sleeve and shall be mounted on suitable size “F”class insulators (b) Incoming MCCB 200 Amp, 4 pole 415 volts 50 Hz 35 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (3-6) In for power distribution- 01 No (c) Outgoing MCCB 100 Amp, 4 pole 415 volts 50 Hz 16 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (6-10) In for power distribution -02 Nos. d) fully automatic star delta starter suitable upto10 Hp Sewage submersible motor complete with suitable rating size of Contactor ,over load realy ,single phase preventor , on off push button complete with wiring etc.- 02 Nos (e) Digital Ammeter 0-60 Amps of size 96x96 sqmm with selector switch-03 Nos (f) Digital Voltmeter of size 96x96 sqmm with selector switch 0-500 Volts.- 03 Nos (g)Indicator lamps LED type RYB with holder -03 Set of three
13Dismantling andtaking down old unsv LT panel and Supplying, installing, testing & commissioning out door type cubical panel board of size 1.2x0.9x0.5M outer shell made out of3.15 mm thick MS sheet iincluding door frame, Persplex Sheet for front door only 6 mm thick should be properly fixed with minimum 80% coverage in door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :- (a)TPN aluminium bus bar 300Amps insulated with colour coded heatshrinkable sleeve and shall be mounted on suitable size “F”class insulators (b) Incoming MCCB 200 Amp, 4 pole 415 volts 50 Hz 35 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (3-6) In for power distribution- 01 No (c) Outgoing MCCB 100 Amp, 4 pole 415 volts 50 Hz 16 KA AC with adjustable thermal release setting Ics 80-100% of Icu and adjustable short circuit (6-10) In for power distribution -03 Nos.(01 Spare) d) On Load change over switch four pole 415 Volts, 200 Amps. (e) Digital Ammeter 0-500 Amps of size 96x96 sqmm with selector switch. (f) Digital Voltmeter of size 96x96 sqmm with selector switch 0-500 Volts. g)Indicator lamps LED type RYB with holder -01 Set of three
14Supplying, installing, testing & commissioning out door type cubical panel board of size 1.0x0.8x0.5M outer shell made out of3.15 mm thick MS sheet iincluding door frame, Persplex Sheet for front door only 6 mm thick should be properly fixed with minimum 80% coverage in door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :- (a) TPN aluminum bus bar 150 A insulated with colour coded heat shrinkable sleeve and shell be monted of "F" class insulators. (b)MCCB 100 A , 4 pole 415 volts 50 Hz , 25 kA with adjustable thermal release setting (80-100% of ln) and adjustable magnetic (3-6 of In) for power distribution - 01 No(Incomer) (c)MCCB 63 A , 4 pole 415 volts 50 Hz , 16 kA with adjustable thermal release setting (80-100% of ln) and adjustable magneticfor power distribution - 01 No(Outgoing) (d)MCCB 40 A , 4 pole 415 volts 50 Hz , 16 kA with adjustable thermal release setting (80-100% of ln) and adjustable magneticfor power distribution - 02 No(Outgoing).(Note:- one Number MCCB will be kept as spare.)(e) On load changeover switch four pole 100A ,415 volts. (f) Digital Ammeter 0-200 Amps of size 96x96 sqmm with selector switch. (g) Digital Voltmeter 0-500 Amps of size 96x96 sqmm with selector switch. (h) Indicating lamps LED type RYB with holder - 01 set of three.
15Note :- Sr Item No 9 to 13 (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves,link spreader provision of extra holes in bus bar etc. (ii)All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694. (iii) Panel drawing shall be got approved from Engr-in-Charge/GE before placing of order. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (vi) The Panel shall be surrounded with 9 inch brick wall upto 0.5 mtr height all around the panel and blank portion between panel and wall shall be filled with PCC 1:2:4incl masonary work leaving ducts for cables complete all as directed.
16Supply, laying, jointing and testing in replacement XLPE PVC insulated armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 120 sqmm, 3.5 core complete all as specified by Engr-in -charge.
17All as per Item Ser No 14 here in before but cross sectional area 95 Sqmm, 3.5 Core.
18All as per Item Ser No 14 here in before but cross sectional area 70 Sqmm, 3.5 Core.
19All as per Item Ser No 14 here in before but cross sectional area 35 Sqmm, 3.5 Core.
20Note for Srl item No. 14 to 17 : (i) Earth work, sand , bricks shall be measured andpaid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii)All equiments, machinery or tool if required for laying electrical cable through new pipes are provided by the contractor without any extra cost.
21Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locatingfault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and as directed.
22Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
23Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
24M&L for sand cushioning for cable with river washed sand with a layer of 8 cm before laying the cable and 15 cm deep after laying the cable. (Punned down to 18 cm after laying and streaching of cable). Complete all as specified and directed by Engr-In-Charge. Note: Punned thickness of sand layer shall be 18 cm and same will be considered for payment to contractor.
25Supply and laying bricks, common burnt clay, sub class "B", old size, laid in vertical direction to cable as cable protection.Complete all as specified and as directe by Engr-In-Charge.
26Supply ,Install Testing & Commissioning in replacement Submersible Fully Automatic Star-Delta pump Starterin steel sheet enclosure, for max. motor of50 HPRating 415V, 50 Hz, 3 Phase completeall as specified and directed by Engr in charge.
27Supply ,Install Testing & Commissioning in replacement Submersible Fully Automatic Star-Delta pump Starterin steel sheet enclosure, for max. motor of30 HPRating 415V, 50 Hz, 3 Phase completeall as specified and directed by Engr in charge.
28Supply ,Install Testing & Commissioning in replacement Submersible Fully Automatic Star-Delta pump Starterin steel sheet enclosure, for max. motor of20 HPRating 415V, 50 Hz, 3 Phase. Completeall as specified and directed by Engr in charge.
29Supply ,Install Testing & Commissioning in replacement Submersible Fully Automatic Star-Delta pump Starterin steel sheet enclosure, for max. motor of10 HPRating 415V, 50 Hz, 3 Phase. Complete all as specified and directed by Engr in charge.
30Material & LabourPVC insulated armoured heavy duty electrical flat submersible cable with copper conductor, 1100 volts grade, cross sectional area 25 sq.mm 3 core in replacement complete all as specified & directed by Engineer-in-Charge.
31Material & LabourPVC insulated armoured heavy duty electricalflat submersible cable with copper conductor, 1100 volts grade, cross sectional area 16 sq.mm 3 core in replacement complete all as specified & directed by Engineer-in-Charge.
32Material & LabourPVC insulated armoured heavy duty electricalflat submersible cable with copper conductor, 1100 volts grade, cross sectional area 10 sq.mm 3 core in replacement complete all as specified & directed by Engineer-in-Charge.
33Material & LabourPVC insulated armoured heavy duty electricalflat submersible cable with copper conductor, 1100 volts grade, cross sectional area 6 sq.mm 3 core in replacement complete all as specified & directed by Engineer-in-Charge.
34Dismantling andtaking down old u/s earthing andMaterial and labour for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire with GI strip of 32x6 mm by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn and including 40 mm dia GI pipe for protection including20mm bore GI pipe medium grade for watering GI funnel PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part - I including testing complete all as specified and as directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC. (iii) On testing after completion if the desired earth resistance ismore than 2? the earthing will be redone at no extra cost
35Supply and fix in electronic over current relay BOCR 3EZ ( 05 to 960 Ampere Cat No- MP363EZ800 of BCH (over current, under current, phase lose, phase unbalance, phase reversal, locketd rotor, ground fault) suitable for motors 7.5 HP to 40 HPRating 415V, 50 Hz, 3 Phase completeall as specified and directed by Engr in charge.
36Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality with 5 star rating and EER 3.2 of capacity 1.5 TR.
37Supply and fix automatic voltage stabilizer, single phase wall mounted copper wound air cooled digital display and designed for input variation between 140V to 280V with output voltage stabilized at 230V with accuracy of + 2.5% and of capacity 5.0 KVA, Make : Vguard/Volina/Microtech or make given in Appx "B".
38Wiring for circuit/submain wiring alongwith earth wire with the 2x4.0 sq. mm + 1x2.5 sq. mm earth wire of FR is PVC insulated copper conductor, single core cable in surface/ recessed as required.
39M&L for single pole and neutral enclosure with a 2 pin and earth plug and socket complete with one single pole MCB 20 Amps ISI mark.
40M&L for wall stand suitable outer unit 1.5 TR.
41Note:-Amount of credit ofRs 70900.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender.